This document contains settings for a protection relay called MPTTR1 from ABB Ltd. It includes 6 setting groups for parameters like overload factor, alarm thermal value, time constants, and environmental temperature settings. The settings apply to a project called PB ABK A2 that is replacing another project.
This document contains settings for a protection relay called MPTTR1 from ABB Ltd. It includes 6 setting groups for parameters like overload factor, alarm thermal value, time constants, and environmental temperature settings. The settings apply to a project called PB ABK A2 that is replacing another project.
This document contains settings for a protection relay called MPTTR1 from ABB Ltd. It includes 6 setting groups for parameters like overload factor, alarm thermal value, time constants, and environmental temperature settings. The settings apply to a project called PB ABK A2 that is replacing another project.
C02 Rev. Modification Rel. date Created by Based on
Settings
Group / Parameter Name IED Value PC Value Unit Min Max
MPTTR1: 1 3Ith>M Operation on Rated current 0.60 xIn 0.30 2.00 Initial thermal Val 74.0 % 0.0 100.0 Setting Group 1 Overload factor 1.10 1.00 1.20 Alarm thermal value 95.0 % 50.0 100.0 Restart thermal Val 40.0 % 20.0 80.0 Negative Seq factor 6.0 0.0 10.0 Weighting factor p 50.0 % 20.0 100.0 Time constant normal 80 s 80 4000 Time constant start 80 s 80 4000 Time constant stop 80 s 80 8000 Env temperature mode FLC Only Env temperature Set 40.0 °C -20.0 70.0 Setting Group 2 Overload factor 1.05 1.00 1.20 Alarm thermal value 95.0 % 50.0 100.0 Restart thermal Val 40.0 % 20.0 80.0 Negative Seq factor 6.0 0.0 10.0 Weighting factor p 50.0 % 20.0 100.0 Time constant normal 320 s 80 4000 Time constant start 320 s 80 4000 Time constant stop 500 s 80 8000 Env temperature mode FLC Only Env temperature Set 40.0 °C -20.0 70.0 Setting Group 3 Overload factor 1.05 1.00 1.20 Alarm thermal value 95.0 % 50.0 100.0 Restart thermal Val 40.0 % 20.0 80.0 Negative Seq factor 6.0 0.0 10.0 Weighting factor p 50.0 % 20.0 100.0 Time constant normal 320 s 80 4000 Time constant start 320 s 80 4000 Time constant stop 500 s 80 8000 Env temperature mode FLC Only Env temperature Set 40.0 °C -20.0 70.0 Setting Group 4
Project Responsible department
PB ABK A2 ABB Ltd.
Replacing
PB ABK A2.CCMMT-01.4.16 kV.Proteccion M-01
C02 Rev. Modification Rel. date Created by Based on Project Responsible department
PB ABK A2 ABB Ltd.
Replacing
PB ABK A2.CCMMT-01.4.16 kV.Proteccion M-01
C02 Rev. Modification Rel. date Created by Based on
Group / Parameter Name IED Value PC Value Unit Min Max
Overload factor 1.05 1.00 1.20 Alarm thermal value 95.0 % 50.0 100.0 Restart thermal Val 40.0 % 20.0 80.0 Negative Seq factor 6.0 0.0 10.0 Weighting factor p 50.0 % 20.0 100.0 Time constant normal 320 s 80 4000 Time constant start 320 s 80 4000 Time constant stop 500 s 80 8000 Env temperature mode FLC Only Env temperature Set 40.0 °C -20.0 70.0 Setting Group 5 Overload factor 1.05 1.00 1.20 Alarm thermal value 95.0 % 50.0 100.0 Restart thermal Val 40.0 % 20.0 80.0 Negative Seq factor 6.0 0.0 10.0 Weighting factor p 50.0 % 20.0 100.0 Time constant normal 320 s 80 4000 Time constant start 320 s 80 4000 Time constant stop 500 s 80 8000 Env temperature mode FLC Only Env temperature Set 40.0 °C -20.0 70.0 Setting Group 6 Overload factor 1.05 1.00 1.20 Alarm thermal value 95.0 % 50.0 100.0 Restart thermal Val 40.0 % 20.0 80.0 Negative Seq factor 6.0 0.0 10.0 Weighting factor p 50.0 % 20.0 100.0 Time constant normal 320 s 80 4000 Time constant start 320 s 80 4000 Time constant stop 500 s 80 8000 Env temperature mode FLC Only Env temperature Set 40.0 °C -20.0 70.0
Project Responsible department
PB ABK A2 ABB Ltd.
Replacing
PB ABK A2.CCMMT-01.4.16 kV.Proteccion M-01
C02 Rev. Modification Rel. date Created by Based on