Sei sulla pagina 1di 8

INFORMACION GENERAL

PROPIETARIO:

Representante Legal:
MARTA LINARES DE MARTINELLI
NOTA:

8-239-406 FUE APROBADO POR LAS RESPECTIVAS AUTORIDADES.

TODAS LAS MEDIDAS SON EN METROS.

PROYECTO:
Sistema fotovoltaico conectado a la red
De 574.28 kWp para SUPER 99- LA CHORRERA

ING. GUILLERMO BETHANCOURT El Coco - Corregimiento de Barrio Balboa, Distrito de La

INGENIERO
ING. GUILLERMO BETHANCOURT MUNICIPAL:
FECHA: HOJA:
OCTUBRE, 2017 1/8
PLANTA GENERAL A DETALLE DE ESTRUCTURA Y ANCLAJE (ESTACIONAMIENTOS)
2 ESC: 1:100 ESC: 1:100
ESC: 1:300
NOTA:

EL MEDIO DE CON LA
AN 10206 -ELEC, EN LA QUE SE UTILIZARA
PANELES SOLARES
TABLERO PV1
Canal pluvial EL PROYECTO SE LIMITA AL SISTEMA FOTOVOLTAICO Y SU
CON EL SISTEMA
EXISTENTE, EL CUAL EN SU MOMENTO FUE APROBADO POR
4-Tub. 4" (103mm)PVC LAS RESPECTIVAS AUTORIDADES.
de ancho PV1 hacia IPPD
TECHO NAVE PRINCIPAL
A
2 (INTERRUPTOR PRINCIPAL GFCI)

termopanel V 5 IN
V6
INV
7
INVERSORES
V 4 IN
V 3 IN
2 IN
INV
INV
1
7
PV1
6 INV
5 INV
V
4 IN
3 INV
INV
V2
A/A

1 I N
INV
PV1

PANELES SOLARES

A/A
RIELES

RIELES

B DETALLE DE TECHO EXISTENTE


B 3
2 S/E

V9
8 IN
INV
PV2

Muro de 0.75 m B DETALLE DE INVERSORES (ESTACIONAMIENTOS)


termopanel 2 ESC: 1:75
DETALLE DE MONTAJE DE FILAS (EDIFICIO PRINCIPAL)
ESC: 1:20
NOTA: PIEZA INTERMEDIA PANELES SOLARES PIEZA INTERMEDIA
RIEL

CERO PARA SISTEMA FOTOVOLTAICO. PIEZA FINAL CARRIOLA PIEZA "L" PIEZA "L" PIEZA FINAL
TECHO TIPO TRAPEZOIDAL CARRIOLA TECHO TIPO TRAPEZOIDAL
TECHO ESTACIONAMIENTOS
VISTA LATERAL
PIEZA "L" PIEZA "L" VISTA ISOMETRICO DE RIEL RIEL
9 (76,2mm) (19,05mm)
8 INV (6,35mm)
INV INVERSORES (19,05mm)

PV2 4-Tub. 4" (103mm)PVC (76,2mm)

El sistema solar propuesto se sobre la estructura existente la cual fue aprobada para por las autoridades TABLERO PV2 hacia IPPD (42,86mm)
pertinentes (9,525mm)
(76,2mm)

(6,35mm)
(19,05mm)
(50,8mm) (50,8mm)
Todas las medidas son en metros.

PROYECTO:
Sistema fotovoltaico conectado a la red
De 574.28 kWp para SUPER 99- LA CHORRERA

ING. GUILLERMO BETHANCOURT El Coco - Corregimiento de Barrio Balboa, Distrito de La

INGENIERO
ING. GUILLERMO BETHANCOURT MUNICIPAL:
FECHA: HOJA:
OCTUBRE, 2017 2/8
PLANTA DE ESTRUCTURA ESTRUCTURA (TECHO NAVE PRINCIPAL)
ESC: 1:75 ESC: 1:40
DETALLE DE ESTRUCTURA
ESC: 1:400
TECHO ESTACIONAMIENTOS
(EXISTENTES)

7
6 INV
N V
5 I
4 INV
V
3 IN
INV

TECHO NAVE PRINCIPAL (EXISTENTE)

ESTRUCTURA (TECHO ESTACIONAMIENTOS)


ESC: 1:75

NOTA:

LA RODADURA, ACERA Y ESTRUCTURA DE


ESTACIONAMIENTO Y NAVE PRINCIPAL ES INV
9
EXISTENTE Y APROBADA BAJO LAS V 8
IN 5938
RESPECTIVAS AUTORIDADES EN SU PV2
MOMENTO.

Peso del Sistema Solar por unidad de

El sistema solar propuesto se sobre la


estructura existente la cual fue aprobada para

El peso por unidad de se y

Todas las cotas no especificadas se deben


considerar en metros.
NOTA:

EL MEDIO DE CON LA AN 10206


PANELES FV

ESC: 1:30 200


EL PROYECTO SE LIMITA AL SISTEMA FOTOVOLTAICO Y SU 1143 1143

CON EL SISTEMA EXISTENTE, EL CUAL EN SU PAR DE APRIETE M8 (calidad 70)

17 Nm
PAR DE APRIETE M8 (calidad 70)

17 Nm

MOMENTO FUE APROBADO POR LAS RESPECTIVAS AUTORIDADES. 5938 25 1956


PAR DE APRIETE M8 (calidad 70)

17 Nm
1956 25 5938

25 1956 1956 25

RIEL 1956 1956

FOTOVOLTAICO.
CONTRAPESO
TODA ESTRUCTURA EXISTENTE HACE REFERENCIA A COPIA DE PLANOS
CORRU BRAKET - AU MINI ORIGINALES.

PROYECTO:
Sistema fotovoltaico conectado a la red
De 574.28 kWp para SUPER 99- LA CHORRERA

ING. GUILLERMO BETHANCOURT El Coco - Corregimiento de Barrio Balboa, Distrito de La

INGENIERO
ING. GUILLERMO BETHANCOURT MUNICIPAL:
FECHA: HOJA:
OCTUBRE, 2017 3/8
DETALLE DE PANELES EN ESTACIONAMIENTOS DETALLE DE PANELES EN CUBIERTA DEL SUPER MERCADO
ESC: 1:75 ESC: 1:25 ESC: 1:50 W10X26

4 pernos de 1/2"
Perno de 1/2" Rosca doble Fillet E7018 todo alrededor
Espesor 3/16 Plato de 1/2"
#3@0.2m 400

N.S.N
Rellenar con mortero de 646

alta densidad o similar 350

w 10x28

DETALLE DE ZAPATA DETALLE TIPICO DE TRASLAPE DE VIGA


5250 ESC: 1:50 ESC: 1:50
992 N.S.N WF

600 1000
h/2
h

h
400
300
8.3039 h/2

1x1 1000

6#5 A/D,I

1956

10.4482

ESC: 1:50 W 8 X 21
W 8 X 15
PLATO DE 1/2" Fillet E7018 todo alrededor
Espesor 3/16

50
50
EF018
PLATO DE 1/2"

5938 DETALLE DE ESTRUCTURA


10.0460 ESC: 1:150
W8X15 TENSOR 6.7500 6.7500
DE 5/8"

DETALLE DE ESTRUCTURA DE ESTACIONAMIENTO


W8X21
ESC: 1:75
134
433 433

50
250
400

416
200

168 250 1000

416

W10X26

3.0000

DETALLE DE CUMBRERA
2.3039
ESC: 1:40

200
3.0000 1143 1143
PAR DE APRIETE M8 (calidad 70)

17 Nm

PAR DE APRIETE M8 (calidad 70)

17 Nm

PAR DE APRIETE M8 (calidad 70)

5938 25 1956 17 Nm
1956 25 5938

25 1956 1956 25

1956 1956

5.0000 5.0000

NOTA:

-.-----------------------------------TODAS LAS MEDIDAS SON EN METROS.

PROYECTO:
Sistema fotovoltaico conectado a la red
De 574.28 kWp para SUPER 99- LA CHORRERA

ING. GUILLERMO BETHANCOURT El Coco - Corregimiento de Barrio Balboa, Distrito de La

INGENIERO
ING. GUILLERMO BETHANCOURT MUNICIPAL:
FECHA: HOJA:
OCTUBRE, 2017 4/8
DIAGRAMA UNIFILAR EXISTENTE
S/E

NOTA:

10206 -ELEC, EN LA QUE SE UTILIZARA CONTROL DE

NUMERO DE NIS 6313280.

SE UTILIZARA EL SECCIONADOR DEL TRANSFORMADOR COMO


MEDIO DE MANUAL EN ACUERDO CON LA
DISTRIBUIDORA.

EL PROYECTO SE LIMITA AL SISTEMA FOTOVOLTAICO Y SU

EXISTENTE, EL CUAL EN SU MOMENTO FUE APROBADO POR LAS


RESPECTIVAS AUTORIDADES.

DE PUESTA TIERRA EXISTENTE EN EL PROYECTO.

AISLAMIENTO TIPO RHW-2 Y DE CORRIENTE ALTERNA THHN-2

M MEDIDOR POZO DE

100

VARILLA DE TIERRA
DISPOSITIVO DE

TRANSFERENCIA
AUTOMATICA TRANSFORMADOR

PROYECTO:
Sistema fotovoltaico conectado a la red
De 574.28 kWp para SUPER 99- LA CHORRERA

ING. GUILLERMO BETHANCOURT El Coco - Corregimiento de Barrio Balboa, Distrito de La

INGENIERO
ING. GUILLERMO BETHANCOURT MUNICIPAL:
FECHA: HOJA:
OCTUBRE, 2017 5/8
#2 #4 #5 #7
19 19 19 19 19 19 19 19 19 19 19 19 17 17 17

DIAGRAMA UNIFILAR NUEVO 17 17 17 13 13 13


20
#1
20 20

S/E
19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19
2-1/c PV
Wire #10
20 20 20 20 20 20
2-1/c PV 2-1/c PV 2-1/c PV
Wire #10 Wire #10 Wire #10
2-1/c PV
Wire #10

#1 KACO POWADOR 72 #3 KACO POWADOR 72 KACO POWADOR 72 KACO POWADOR 48

19 19 19 19 4-1/c #2 Cu. THHN-2 + 19 19 19 19 4-1/c #2 Cu. THHN-2 + 4-1/c #2 Cu. THHN-2 +


#6 4-1/c #6 Cu. THHN-2 +
1-1/c # 8 Cu. DESNUDO 1-1/c # 8 Cu. DESNUDO 1-1/c # 8 Cu. DESNUDO 1-1/c # 8 Cu. DESNUDO
1-Tub. 2" (53mm) PVC 1-Tub. 2" (53mm) PVC 1-Tub. 2" (53mm) PVC
15 15 15 1-Tub. 1-1/2" (41mm) PVC #2
KACO POWADOR 72
15 15 15
19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 19 15 15 15 15 15 15
70A/3p 4-1/c #2 Cu. THHN-2 +
100A/3p 1-1/c # 8 Cu. DESNUDO
1-Tub. 2" (53mm) PVC
100A/3p 100A/3p
17 17 17 15 15 15
2-1/c PV 2-1/c PV 2-1/c PV
Wire #10 4-1/c #6 Cu. THHN-2 +
Wire #10 Wire #10 1-1/c # 8 Cu. DESNUDO 100A/3p
4-1/c #2 Cu. THHN-2 + 1-Tub. 1-1/2" (41mm) PVC 2-1/c PV
1-1/c # 8 Cu. DESNUDO Wire #10
4-1/c #2 Cu. THHN-2 + 4-1/c #2 Cu. THHN-2 + 1-Tub. 2" (53mm) PVC
1-1/c # 8 Cu. DESNUDO 1-1/c # 8 Cu. DESNUDO
1-Tub. 2" (53mm) PVC 1-Tub. 2" (53mm) PVC
4-1/c #2 Cu. THHN-2 +
1-1/c # 8 Cu. DESNUDO
KACO POWADOR 72 KACO POWADOR 72
1-Tub. 2" (53mm) PVC
4-1/c #2 Cu. THHN-2 + 4-1/c #2 Cu. THHN-2 +
KACO POWADOR 48
1-1/c # 8 Cu. DESNUDO 1-1/c # 8 Cu. DESNUDO
1-Tub. 2" (53mm) PVC 1-Tub. 2" (53mm) PVC
4-1/c #6 Cu. THHN-2 +
1-1/c # 8 Cu. DESNUDO KACO POWADOR 48
1-Tub. 1-1/2" (41mm) PVC
4-1/c #6 Cu. THHN-2 +
100A/3p 100A/3p 1-1/c # 8 Cu. DESNUDO
1-Tub. 1-1/2" (41mm) PVC
70A/3p

4-1/c #2 Cu. THHN-2 + 4-1/c #2 Cu. THHN-2 +


PV 1 70A/3p
1-1/c # 8 Cu. DESNUDO 1-1/c # 8 Cu. DESNUDO NEMA 3R
1-Tub. 2" (53mm) PVC 1-Tub. 2" (53mm) PVC 4-1/c #6 Cu. THHN-2 +
1-1/c # 8 Cu. DESNUDO
100A/3p 100A/3p 1-Tub. 1-1/2" (41mm) PVC PV 2
4-1/c #6 Cu. THHN-2 +
NEMA 3R 1-1/c # 8 Cu. DESNUDO
100A/3p 70A/3p
1-Tub. 1-1/2" (41mm) PVC

100A/3p 70A/3p 100A/3p 70A/3p

100A/3p 150A/3p 150A/3P

ACOMETIDA DEL SISTEMA 4-1/c #1/0 Cu. THHN-2 + 1-1/c #6 Cu. DESNUDO
1000A/3P 1-Tub.3" (78mm) PVC

PLC
8-1/c #500 MCM Cu. THHN-2 + 1-1/c # 1/0 Cu. DESNUDO
4-Tub.4" (103mm) PVC
DISPOSITIVO DE

8-1/c #500 MCM Cu. THHN-2 + 1-1/c # 1/0 Cu. DESNUDO


4-Tub.4" (103mm) PVC
NOTA:

CONECTADO AL SISTEMA DE PUESTA TIERRA


EXISTENTE EN EL PROYECTO.
TODO EL CABLEADO DE CORRIENTE CONTINUA

CORRIENTE ALTERNA THHN-2

SE UTILIZARA EL SECCIONADOR DEL


TRANSFORMADOR COMO MEDIO DE
MANUAL EN ACUERDO CON LA
DISTRIBUIDORA.

EL PROYECTO SE LIMITA AL SISTEMA


Y SU
CON EL SISTEMA EXISTENTE, EL CUAL
EN SU MOMENTO FUE APROBADO POR LAS
RESPECTIVAS AUTORIDADES.

MEDIDOR 14000795 CON NUMERO DE NIS 6313280.

TRANSFERENCIA
AUTOMATICA
M MEDIDOR

POZO DE
PANEL SOLAR

100
NOTA: VARILLA DE TIERRA
EN CORRIENTE ALTERNA, LA POTENCIA DE PLACA DE
DISPOSITIVO DE
TRANSFORMADOR
LA PERDIDA DE POTENCIA DEBIDO A LA EFICIENCIA DEL

CONTINUA A CORRIENTE ALTERNA.

PROYECTO:
Sistema fotovoltaico conectado a la red
De 574.28 kWp para SUPER 99- LA CHORRERA

ING. GUILLERMO BETHANCOURT El Coco - Corregimiento de Barrio Balboa, Distrito de La

INGENIERO
ING. GUILLERMO BETHANCOURT MUNICIPAL:
FECHA: HOJA:
OCTUBRE, 2017 6/8
NOTA: EL ATERRIZAJE DEL SISTEMA SOLAR
CONECTADO AL SISTEMA DE PUESTA
TIERRA EXISTENTE EN EL PROYECTO.
TODO EL CABLEADO DE CORRIENTE
CONTINUA AISLAMIENTO TIPO
RHW-2 Y PARA CORRIENTE ALTERNA THHN-2.

POWADOR 72.0 TL3 PARK (480V)

MODELO POWADOR 48.0 TL3 PARK (480V)

@ STC - Standard Test Condition


NOTA:
VALOR
325 W
EL ATERRIZAJE DEL SISTEMA SOLAR CONECTADO AL
37.19 Vdc SISTEMA DE PUESTA TIERRA EXISTENTE EN EL PROYECTO.
8.74 Adc TODO EL CABLEADO DE CORRIENTE CONTINUA
Voltaje en circuito abierto (Voc) 45.72 Vdc AISLAMIENTO TIPO RHW-2 Y EL DE CORRIENTE ALTERNA
Corriente en corto circuito (Isc) 9.31 Adc
1000 Vdc

PROYECTO:
Sistema fotovoltaico conectado a la red
De 574.28 kWp para SUPER 99- LA CHORRERA

ING. GUILLERMO BETHANCOURT El Coco - Corregimiento de Barrio Balboa, Distrito de La

INGENIERO
ING. GUILLERMO BETHANCOURT MUNICIPAL:
FECHA: HOJA:
OCTUBRE, 2017 7/8
NOTAS

PROTECCIONES NOTAS GENERALES DE ELECTRICIDAD

1. SE UTILIZARA EL INTERRUPTOR DEL SISTEMA FOTOVOTAICO DE 800 A. PARA EL TABLERO PV1.


EN CUMPLIMIENTO CON EL ARTICULO 690 DEL MISMO, EN CUMPLIMIENTO CON EL 690.5, 690.8, 690.15, 690.14

TODAS ELLAS INCLUIDAS EN EL INVERSOR.

DE LA EMPRESA DISTRIBUIDORA. EL ATERRIZAJE DEL SISTEMA FOTOVOLTAICO ES MEDIANTE EL SISTEMA DE PUESTA A TIERRA EXISTENTE.

PARA EL CABLEADO. CC SE UTILIZARA CABLE DE COBRE DE TIPO FOTOVOLTAICO TIPO USE-2, CON RETARDO
DE FLAMA, VW-1 RESISTENTE A LA HUMEDAD, RoHS, RESISTENTE A LA LUZ DEL SOL

5. LAS CAPACIDADES PERMISIBLES DE CORRIENTE EN CONDUCTORES AISLADOS SE BASAN

6. SOLO SE PERMITE UNIR EL NEUTRAL A TIERRA EN EL INTERRUPTOR PRINCIPAL.


TANTO EN EL LADO DE CORRIENTE CONTINUA COMO EN EL DE CORRIENTE ALTERNA NO HAY ACCESO DIRECTO

ATORNILLADA Y PRENSAESTOPAS EN LA ENTRADA DE CABLES. 8. EL INVERSOR CUMPLE CON LAS SIGUIENTES CERTIFICACIONES: IEC 62109-1:2010,IEC 62109-1:201, EN 61000-6-1:2005, EN 61000-6-3:2007 +
A1:2011, EN 61000-6-4:2007 + A1:2011, EN 61000-3-11:2000 EN 61000-3-12:2011, IEC 62109-1/-2, EN 61000-6-1/-2/-3/-4, EN 61000-3-12/-11

CORRIENTE CONTINUA
EL INVERSOR INCORPORA FUSIBLES DE 15 A EN CADA UNA DE SUS ENTRADAS MPPT, TANTO PARA LAS ENTRADAS NOTAS GENERALES
DE VOLTAJE NEGATIVO COMO EL DE VOLTAJE POSITIVO.

CORRIENTE DIRECTA

EL INVERSOR INCORPORA PROTECCIONES CONTRA CORTOCIRCUITOS BASADA EN LA RUPTURA DE IGBT.


DISPOSITIVOS ENTRE UN GENERADOR Y LAS REDES PUBLICAS BAJO VOLTAJE.
MEDICIONES POR CAMBIOS DE TEMPERATURAS.
EN EL CASO DE QUE EL SISTEMA DE VIGILANCIA DE LA COMPONENTE CONTINUA DETECTE NIVELES

PROTECCION CONTRA INDIRECTOS


LAS INVERSIONES NECESARIAS PARA MANTENER LA CALIDAD DE SERVICIO QUE PRESTA ENSA
EN EL LADO DE CORRIENTE CONTINUA, DETECTOR DE DEFECTOS DE AISLAMIENTO EN EL INVERSOR.
EN EL LADO DE CORRIENTE ALTERNA EL BREAKER Y LA PUESTA A TIERRA.
TOMA A TIERRA
9. EL PROYECTO SE LIMITA AL SISTEMA FOTOVOLTAICO.

NOTA DE ESTRUCTURA:

PARA EVITAR QUE EL INVERSOR FUNCIONE EN MODO ISLA, EL CONTROL DEL INVERSOR VERIFICA EN FORMA

NORMALICEN.

QUE PUEDA CRECER. EL MATERIAL EMPLEADO ES ALUMINIO.