Sei sulla pagina 1di 12

Energy and Buildings 43 (2011) 653–664

Contents lists available at ScienceDirect

Energy and Buildings


journal homepage: www.elsevier.com/locate/enbuild

Passive control methods for a comfortable indoor environment: Comparative


investigation of traditional and modern architecture of Kerala in summer
A.S. Dili a,∗ , M.A. Naseer b , T. Zacharia Varghese c
a
Department of Architecture, TKM College of Engineering, Kollam, Kerala, India
b
Department of Architecture, National Institute of Technology Calicut, Kerala, India
c
Department of Civil Engineering, National Institute of Technology Calicut, Kerala, India

a r t i c l e i n f o a b s t r a c t

Article history: Scientific investigation on traditional architecture of Kerala, that is known for its use of natural and pas-
Received 15 July 2010 sive methods for a comfortable indoor environment, has been revealing remarkable results recently.
Received in revised form Qualitative analysis of the passive methods adopted in traditional buildings and detailed quantitative
19 September 2010
investigation carried out during all seasons to evaluate thermal comfort have already been reported.
Accepted 5 November 2010
As a step ahead, in order to understand the performance of traditional building in comparison with
that of modern building, a field study was conducted simultaneously in a selected traditional and a
Keywords:
modern residential building during the most unpleasant summer period. The study was conducted by
Kerala
Traditional architecture
continuously monitoring the indoor and outdoor conditions of both the buildings using a custom made
Modern building instrument called “Architectural Evaluation System”. The results reveal that an efficient passive and natu-
Indoor environment ral control system exists in Kerala traditional architecture in providing a comfortable indoor environment
Summer irrespective of the outdoor climatic conditions.
© 2010 Elsevier B.V. All rights reserved.

1. Introduction controls are used [12–14]. The building’s characteristics influence


the impact of outdoor climate and play a major role in controlling
The main purpose of a building is to provide an environment the indoor thermal conditions [15]. Studies on passive environ-
that is comfortable, and spoils neither the health nor performance ment control methods of achieving thermal comfort in buildings
of its occupants [1]. A good indoor environment is important to the and studies for extracting methods and techniques from traditional
success of a building, not only because it will make its occupants buildings are in progress in various countries [16–24]. Researches
comfortable, but also because it will decide its energy consumption on the aspect of thermal comfort and energy efficiency of buildings
and thus influence its sustainability in terms of energy [2,3]. are also underway throughout the world [25].
The role of passive controls in reducing the need for high-energy Although, about 48% of the energy consumed in Indian residen-
solutions has become important during today’s energy-economic tial buildings is used for providing thermal comfort indoors [26],
crises [4]. Natural and passive cooling method for buildings, can studies on environment control aspects of traditional architecture
improve indoor environment quality, provide thermal comfort, and have been reported only recently [27–40].
reduce energy consumption in buildings. As a result, the study of Kerala, located in the southwest coast of India, has a charac-
natural and passive methods for controlling indoor environment teristic Warm-Humid climate because of its geographic settings
has gained more and more attention in recent years [5]. [41]. The presence of high amount of moisture in the atmosphere
The energy savings using passive and traditional techniques in for major part of the year causes thermal discomfort as there is
houses for the purpose of maintaining thermal comfort in compari- less evaporation, resulting in sweating. Prolonged exposure to such
son with modern techniques are established in many investigations thermal discomfort conditions can create adverse effects includ-
[6–9]. Moreover, the trend towards more efficient architectural ing extensive loss of efficiency in work along with physical strain
designs is pausing challenges to the engineers to provide healthy [42–44].
low-energy design solutions [10,11]. The authors have conducted an investigation on the passive
The indoor environment in naturally ventilated buildings environment control system of traditional architecture of Kerala. A
greatly depends on the local climate and the way environmental qualitative analysis discussing in detail about the passive concepts
adopted in traditional buildings, a quantitative investigation car-
ried out during all seasons to evaluate thermal comfort and a study
∗ Corresponding author. Tel.: +91 944 7303875; fax: +91 474 2712023. based on questionnaire survey among the occupants of traditional
E-mail addresses: dili as@yahoo.com, dili@nitc.ac.in (A.S. Dili).
and modern buildings on the subjective responses of thermal com-

0378-7788/$ – see front matter © 2010 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2010.11.006
654 A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664

Fig. 1. Plan and section of Puthiya Kovilakam located at Nilambur – selected area is marked in rectangle [36].

fort have been reported [32–40]. However, it is essential to have a doors opening to the courtyard. The average room height of the
comparative study of traditional building vis-à-vis modern building building is 2.1 m. Plan with selected area for the study marked and
to verify the effectiveness of such a passive control system. A field a section of Puthiya Kovilakam located at Nilambur is shown in
study was thus conducted simultaneously in a selected traditional Fig. 1 [36].
and a modern residential building during the most unpleasant sum-
mer period. 2.1.2. Modern building
This paper presents the passive environment control system of In order to have a logical comparative analysis, the modern
Kerala traditional architecture by analyzing various thermal com- building was also selected from the locality of the traditional build-
fort parameters in comparison with that of modern building. ing. The residential building selected for the study is located at the
south-west side of Puthiya Kovilakam at a distance of 50 m. The 26
2. Experimental investigation years old building “Shinnu” has two bedrooms with other activity
spaces arranged as shown in Fig. 2. This building has more or less
2.1. Building description the most common layout that is generally seen in modern houses.
This single storeyed building is constructed with the modern mate-
2.1.1. Traditional building rials i.e., 20 cm thick walls of brick masonry plastered with cement
Since the design of Kerala traditional residential buildings is mortar and roof of reinforced cement concrete (RCC). The roof has
based on a modular concept with four blocks built around an open a slope of 10◦ towards the north and south side for easy drainage
courtyard strictly adhering to the ancient rules pertaining to geo- of the rain water. The average room height of the building is 3.2 m.
metrical grids, proportions and scale, the investigation is confined A bedroom of size 4.2 m × 3.6 m located at its North-West side
to a typical traditional residential building in a selected location. (marked in Fig. 2) is selected for the investigation. The bedroom
The traditional residential building selected for the study is has two windows of size 1.7 m × 1.5 m each, one on the northern
located at Nilambur in the Malappuram district of the northern side and other on the western side as shown in the figure. The
part of Kerala. The building (Puthiya Kovilakam) is nearly 300 years windows are provided with shades projecting 60 cm from the wall
old. It has three rectangular courtyards in which one courtyard is for protection from sun and rain.
surrounded by a double storeyed structure while the other two
courtyards are surrounded by single storeyed structures. The inter- 2.2. Experimental setup
nal space taken for the investigation is around the courtyard of
1.83 m × 3.66 m surrounded by double storeyed structures. The The authors have devised an instrument setup called Architec-
courtyard has an inward looking verandah of 1 m width. Two sides tural Evaluation System (AES) with electronic sensors (to record
of the courtyard are semi open spaces that are used for living. air temperature, mean radiant temperature, relative humidity and
The other two sides are provided with rooms having windows and air movement), data logger, memory module (to record data from
A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664 655

Fig. 2. Plan and section of the modern house taken for investigation.

all sensors) and a computer interface (to view and download data cent to the courtyard. MRT sensors were fixed in the bedroom and
to the computer) to continuously record the comfort parameters semi open space. Sensors were located inside the building to record
over a period of time. The threshold speed of air movement sen- the air movement in the semi open space around the courtyard. RH
sor is 0.39 m/s and is capable of sensing the required indoor air sensors were kept in the courtyard, in the semi open space and
flow suitable for the investigation. A schematic representation of in the bedroom. Simultaneous recording of outside ambient tem-
Architectural Evaluation System (AES) is shown in Fig. 3. perature, RH and air movement were done using sensors suitably
located around the building. A photograph showing the installation
of AES in and around the courtyard of Puthiya Kovilakam is given in
2.3. Field measurements
Fig. 3.
In the modern residential building (Shinnu), the AES sensors for
Continuous data for a period from mid February 2010 to mid
air temperature, MRT, RH and air movement were positioned in the
May 2010 were recorded simultaneously in both traditional and
selected bedroom as shown in Fig. 3. Outdoor ambient temperature
modern buildings. The investigation was carried out keeping the
and wind speed were also recorded simultaneously. The selected
windows open for allowing natural indoor air movement through-
area of the modern house was kept fully in passive mode (no active
out the whole period. This is because natural air flow is an important
systems like A/C, fans, coolers, etc. were operated) during the period
parameter in determining indoor thermal comfort in a passive
of investigation.
system especially in warm-humid climate. Air temperature, mean
radiant temperature (MRT), relative humidity (RH) and air move-
ment were recorded using AES that was set to 15 minutes recording 3. Results
interval. The installation of AES done in the traditional and modern
building is described below. The results obtained from the traditional and modern building
In the traditional residential building (Puthiya Kovilakam), the during the period of investigation, the interpretation of the results,
temperature sensors were fixed at the bottom and top of courtyard, the comparative analysis of the results and the discussion on them
in the semi open space around the courtyard and in a bedroom adja- are described in the following sections.
656 A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664

Fig. 3. Arrangement of AES in the modern and traditional residential buildings.

3.1. Results from traditional building found to be lower than that of semi open space around the court-
yard. There was no time lag observed between outdoor and indoor
It is observed that the outdoor temperature has a diurnal varia- temperature and the decrement factor (ratio of diurnal variations
tion of 13 ◦ C i.e., from 28 ◦ C to 41 ◦ C in the region during summer. in indoor temperature to that of outdoor temperature) is 0.30.
The indoor temperature was varying from 31 ◦ C to 35 ◦ C showing a The variation of air temperature and MRT, recorded in the semi
diurnal variation of 4 ◦ C only (Fig. 4). The lower part of the court yard open space and the bedroom is shown in Fig. 5. While the maxi-
was found to be cooler by about 8 ◦ C from the maximum outdoor mum air temperature of semi open space was slightly more (about
temperature during the day, while the upper part of the courtyard 1 ◦ C) than that of bedroom, the minimum temperature is in syn-
has a temperature 3 ◦ C lower than the maximum outdoor tempera- chronization with that of the bedroom. While the maximum MRT
ture. The minimum temperature of the upper part of the courtyard of the bedroom was about 2 ◦ C lower than the maximum air tem-
was found to be almost the same as that of the bedroom tempera- perature, the maximum MRT of the semi open space was about
ture. The maximum temperature recorded inside the bedroom was 4.5 ◦ C lower than the air temperature. The minimum air temper-

Outside ambient Courtyard Top Courtyard Bottom Semi open Bedroom


43
42
41
40
39
Temperature in Degree C

38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
18 00 06 12 18 00 06 12 18 00 06 12 18 00 06 12 18
Time in Hours

Fig. 4. Air temperature vs. time – traditional building.


A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664 657

Outside Ambient Temp Semi open Temp Bedroom Temp Semi open MRT Bedroom MRT
43
42
41
40
39
Temperature in Degree C
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
18 00 06 12 18 00 06 12 18 00 06 12 18 00 06 12 18
Time in Hours

Fig. 5. Air temperature and MRT vs. time – traditional building.

atures and the minimum MRTs of the corresponding spaces also from this figure that the indoor air flow is continuous and
have the same trend in variation but with a lesser margin as evi- maintained around 0.5 m/s and is not totally dependent on the out-
denced from Fig. 5. It was clear from this figure that the semi open door wind. This is due to the effect of internal courtyard which
space has much low MRT compared to that of the bedroom even also allows a continuous and controlled air flow through the
when the air temperature of the semi open space is higher than building.
that of the bedroom.
The variation of RH of outdoor, courtyard, semi open space and 3.2. Results from modern building
bedroom and the corresponding air temperature of outdoor and
bedroom of the traditional house is shown in Fig. 6. It is clear that A diurnal variation of 12.5 ◦ C (28–40.5 ◦ C) was observed out-
the RH is inversely proportional to the air temperature. While the doors when the bedroom temperature was varying from 31 ◦ C to
outdoor RH was varying from 32% to 95%, the bedroom RH was 37 ◦ C showing a variation of 6 ◦ C (Fig. 8). While the maximum air
varying from 50% to 80%. And, while the courtyard was having more temperature of the bedroom was 37 ◦ C, the corresponding MRT was
fluctuation in RH, the bedroom was having the least fluctuation. It 38 ◦ C. And, while the minimum air temperature of the bedroom was
is evident from Figs. 4 and 6 that the variation of RH is well related 31 ◦ C, the corresponding MRT was 31.5 ◦ C. It is clear from Fig. 8 that
to the variation of temperature of the respective spaces. all MRT readings are higher than the corresponding air temperature
Fig. 7 shows the variation of indoor air movement with respect readings except for some hours during the day. During that period
to the fluctuating outdoor wind speed in the traditional build- (9 am to 12 noon), the MRT was matching with the air temperature,
ing for a continuous period of 19 days in summer. It is evident as evidenced from the figure. A time lag of about 3 h was observed

Outside Ambient Temperature Bedroom Temperature Outside RH


Bedroom RH Courtyard RH Semi open RH
43 100
42
95
41
40 90
39 85
38
Temperature in Degree C

80
Relative Humidity (%)

37
36 75
35
70
34
33 65
32
60
31
30 55
29 50
28
27 45
26 40
25
35
24
23 30
18 00 06 12 18 00 06 12 18 00 06 12 18 00 06 12 18
Time in Hours

Fig. 6. Air temperature and RH vs. time – traditional building.


658 A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664

Outdoor Indoor
3

2.5
Wind velocity in m/s

1.5

0.5

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19
Interval in days

Fig. 7. Wind speed vs. time – traditional building.

between outdoor and indoor air temperature and the decrement higher in the modern bedroom and the increase in MRT is from
factor is 0.48. 1.5 ◦ C to 5.5 ◦ C (Fig. 10).
Fig. 9 shows the variation of indoor air movement with respect The diurnal variations of outdoor and bedroom air tem-
to the fluctuating outdoor wind speed in the modern house for a perature corresponding to traditional and modern houses are
continuous period of 19 days in the peak summer. It is evident from shown in Fig. 11. From this figure, it is clear that in tradi-
this figure that the indoor air movement is not at all continuous and tional building, the rate of increase of indoor diurnal variation
is fluctuating between 0 and 1.5 m/s and is totally dependent on the is less compared to that of outdoor diurnal variation. It can
outdoor wind. also be observed that the indoor diurnal variation is approach-
ing a steady state when the outdoor variation reaches beyond a
3.3. Comparison and analysis of results limit.
On the other hand, in the modern bedroom, the rate of increase
It is observed that, when the minimum temperature recorded in of indoor diurnal variation with respect to that of outdoor is
the bedrooms of both buildings are the same, the maximum tem- very high and it shows an increasing trend (Fig. 11). These
perature of the modern bedroom is higher than traditional by about distinct trends in the indoor diurnal variation of both the build-
2.5 ◦ C. There is a drastic difference between the MRTs recorded in ings reveal the difference in their passive environment control
the bedrooms of the two buildings. The MRT values are always systems.

Outdoor Ambient Temperature Bedroom Temperature Bedroom MRT Bedroom RH


43 100
42
41 95
40 90
39
Temperature in Degree C

38 85
Relative Humidity (%)

37
36 80
35 75
34
33 70
32
31 65
30 60
29
28 55
27
26 50
25 45
24
23 40
18 00 06 12 18 00 06 12 18 00 06 12 18 00 06 12 18
Time in Hours

Fig. 8. Air temperature, MRT and RH vs. time – modern building.


A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664 659

Outdoor Bedroom
3

2.5

2
Wind velocity in m/s

1.5

0.5

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18
Interval in days

Fig. 9. Wind speed vs. time – modern building.

Traditional Building Modern Building


43
42
41
40
39
Temperature in Degree C

38
37
36
35
34
33
32
31
30
29
28
27
26
25
Min Max Min Max Min Max

Outdoor Ambient Bedroom Temperature Berdroom MRT

Fig. 10. Comparison of air temperature and MRT – traditional and modern buildings.

It can be observed that in the traditional building, the indoor ature in the traditional building, a time lag of about 3 h is noticeable
air temperature is kept a little higher than the outdoor mini- in the modern building during the day and about 1 h during the
mum temperature during the night while the same is kept lower night.
than the maximum outdoor temperature during the day main-
taining a range of 31–35 ◦ C. In the modern building on the other 4. Discussion
hand, the minimum temperature indoors is kept either equal
or lower than that of traditional building during the night but Ventilation has an important role in buildings to create
the maximum temperature is much higher than that of tradi- thermally comfortable environment by regulating indoor air
tional building during the day maintaining a range of 31–37 ◦ C parameters, such as air temperature, relative humidity and air
(Fig. 12). speed [45]. Building envelope to control the heat from sun through
The variation of indoor (bedroom) air temperatures of both tra- conduction and radiation along with appropriate ventilation can
ditional and modern buildings with respect to the variation of provide a comfortable indoor environment in warm-humid cli-
outdoor ambient temperature is shown in Fig. 13. Another very mate. Recent studies reported that such a system is embedded
important factor that is evident from this figure is the “time lag”. in traditional architecture of Kerala to control its indoor environ-
While there is no time lag between the outdoor and indoor temper- ment irrespective of the seasonal variations of the climate [35,36].
660 A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664

Traditional Building Modern Building The whole roof system acts as an insulation layer against the
Diurnal Variation - Bedroom Temperature in Degree C

10 conduction of external heat through the roof. The attic air space
is further ventilated with openings (jalli) on both sides to permit
9
maximum cross ventilation in order to remove the hot air and help
8
increasing the insulation. The breathing space between the clay
roofing tiles further helps in ventilating the under side of the roof
7 reducing the conduction of heat. The roof of the modern house is of
RCC and has a thickness of only 10 cm and that is directly exposed
6 to the interior. This allows more heat flow towards the interior
and contributes to increase internal air temperature and thermal
5
discomfort.
4 The time lag between the outdoor and indoor air temperature is
an important factor in determining thermal comfort. As shown in
3 Fig. 13, while the traditional building has no time lag between the
outdoor and indoor temperature, the same of modern building is
2 about 3 hours. The absence of time lag in traditional building can be
attributed to the highly insulative wall preventing conductive heat
1
flow and due to the continuous air flow maintained through the
0 building [35]. On the contrary, the envelope of modern building is
9 10 11 12 13 14 15 16 17 18 19 conductive and the air flow through the modern building is not at
Diurnal Variation - Outdoor Ambient Temperature in Degree C all continuous and is highly fluctuating with the outdoor air flow as
shown in Fig. 9. The concrete roof of the modern building absorbs
Fig. 11. Diurnal variation in air temperature – traditional and modern houses. heat in the day time due to the increase in outdoor temperature
and solar radiation. The heat is transmitted to the interiors through
the roof and the delay in transmitting heat results in time lag.
However a critical comparison of each aspect with that of modern
Mean Radiant Temperature (MRT) has a very important role in
buildings is also essential to make a final conclusion.
providing indoor thermal comfort [7]. The variation of MRT in mod-
ern building is very high compared to that of traditional building
4.1. Discussion on results as shown in Figs. 5, 8 and 10. It is clear that the heat gain through
radiation is also very high in modern building. In the semi open
Figs 4, 8, 11 and 13, show that the traditional building in compar- space of the traditional building, the MRT is lower (about 1 ◦ C) than
ison with the modern building, maintains a low diurnal variation that of the bedroom. This is due to the presence of indoor surfaces
of the indoor temperature. This proves the high thermal insulation that are maintained at a low temperature. Of these surfaces, the
property of the envelope of the traditional building. bottom of the courtyard is the one that is maintained at the lowest
While the thickness of external walls of the traditional building temperature (Fig. 4). Since MRT can be considered as an indicator of
is 75 cm, the same in the modern building is only 20 cm. The exter- thermal comfort in warm-humid climate, one can easily assess that
nal window openings are smaller in size in the traditional building the traditional buildings of Kerala can provide a comfortable indoor
as compared to the modern building (Figs. 1 and 2). The external environment in summer while the modern buildings cannot.
windows of traditional building are covered by wide verandahs, The real reason for thermal discomfort in summer season in Ker-
whereas the same in modern building are protected by a narrow ala is not due to the increase in minimum temperature alone, but
sunshade. is mainly due to the increase in the moisture content in the air
In the case of traditional building, the roof system is a combina- during that period [35]. From Figs. 6 and 8, it is very much evi-
tion of clay tiled roof, wooden ceiling (tattu) and a well ventilated dent that the indoor air temperature in the traditional building
attic space in between as shown in Fig. 1. is maintained between 31 ◦ C and 35 ◦ C during summer with RH

Traditional Building Modern Building Traditional Building Modern Building


32 38
Indoor maximum temperature in Degree C
Indoor minimum temperature in Degree C

31 37

30 36

29 35

28 34

27 33

26 32
22 23 24 25 26 27 28 29 35 36 37 38 39 40 41 42
Outdoor minimum ambient temperature in Degree C Outdoor maximum ambient temperature in Degree C

Fig. 12. Variation of minimum and maximum air temperature – traditional and modern houses.
A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664 661

Fig. 13. Bedroom air temperature vs. time – traditional and modern houses.

values of 79% and 50% while in modern building the indoor tem- and activity. For given clothing values and activity ranges, there
perature is maintained between 31 ◦ C and 37 ◦ C with RH of 76% and are environmental conditions under which most people feel com-
41% respectively. This is when the outdoor temperature is varying fortable [47].
between 28 ◦ C and 41 ◦ C with RH of 92% and 32% respectively. It PMV/PPD analysis based on Fanger’s comfort theory [48–50]
can be concluded from these observations that the variation in RH was performed for both the buildings; the results are illustrated
is dependent on the variation in temperature and the kind of build- in Fig. 15. A normal clothing was assumed for the analysis.
ing envelope or openings have no significant role in controlling RH In traditional building, the PMV values ranges from −1.2 to 1.1
directly. and the corresponding PPD values are 36% and 30%, while in modern
In warm-humid climate, the best way to achieve thermal com- building the PMV values ranges from 0.63 to 3 and the correspond-
fort indoors is to have a control over the air temperature along ing PPD values are 13% and 100%. It can be noted that the PPD value
with a controlled and continuous air movement that can ensure the of 36% (corresponding to PMV value −1.2) can be brought up to
required rate of evaporation from the body of occupants. The tradi- 5% by adjusting the clothing level. The semi open space is found
tional buildings of Kerala are thus the ideal examples for the above to be more cooler compared to the bedroom of traditional building
concept as evidenced from the investigation and earlier reports. except for the over heated period during the day time. This is due
The modern buildings of Kerala on the other hand, lack the above to the effect of lower MRT of semi open space that contribute in the
aspects and are therefore uncomfortable to stay in summer. PMV value in warm-humid climate as explained earlier.
It is evident from Fig. 15 that, traditional buildings of Kerala are
4.2. Thermal comfort analysis cooler most of the time in summer season. At the same time the
modern buildings are either warmer or hotter. It is very clear that
4.2.1. Analysis using Bioclimatic chart the modern building is very uncomfortable to live in especially from
Fig. 6 shows that during summer days when the indoor temper- 9 am till midnight in summer season.
ature of traditional building is high up to 35 ◦ C, the humidity is as On comparing the PMV-PPD analysis and the Bioclimatic chart, it
low as 50%. This falls well within the comfort region of the Biocli- is evident that the most suitable tool to assess the thermal comfort
matic chart and very near to the comfort zone (Fig. 14) [46], since
the air speed maintained inside the building is around 0.5 m/s. Dur-
ing night, since temperature becomes as low as 31 ◦ C, the increase
in humidity (up to 79%) does not really affect the indoor com-
fort condition of traditional building. Thus the continuous air flow
(maintained around 0.5 m/s) inside the building provides thermal
comfort even at a high humidity as per the Bioclimatic chart.
In the modern building, during summer days when the indoor
temperature is high up to 37 ◦ C (Fig. 8), the humidity is 40%. This
does not fall even in the comfort region of the Bioclimatic chart
since the air speed maintained inside the building is negligible
and the temperature is very high. During nights, even though the
temperature is around 31 ◦ C, the absence of air flow results in dis-
comfort as per Bioclimatic chart.

4.2.2. PMV-PPD analysis


The state of comfort depends on a set of factors such as air tem-
perature, radiant temperature, humidity, air movement, clothing Fig. 14. Bioclimatic chart [46].
662 A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664

PMV - Traditional Bedroom PMV - Traditional Semi Open Space PMV - Modern Bedroom
PPD - Traditional Bedroom PPD - Traditional Semi Open Space PPD - Modern Bedroom

a 3 100

2.5 90

Predicted Percentage Dissatisfied (PPD)


2
80
Predicted Mean Vote (PMV)

1.5
70
1

0.5 60

0 50
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
-0.5 40
Time in Hours
-1
30
-1.5
20
-2

-2.5 10

-3 0

Traditional Bedroom Traditional Semi Open Space Modern Bedroom


100
b
Predicted Percentage Dissatisfied (PPD)

90

80

70

60

50

40

30

20

10

0
-3 -2.5 -2 -1.5 -1 -0.5 0 0.5 1 1.5 2 2.5 3
Predicted Mean Vote (PMV)

Fig. 15. PMV-PPD analysis – traditional and modern houses. (a) PMV and PPD vs. time – traditional and modern houses. (b) PMV vs. PPD – traditional and modern houses.

in warm-humid climate is PMV-PPD analysis since MRT is directly helps to maintain the internal court with the lowest temperature
taken as a parameter. However, both the analyses confirm the com- which in turn helps in lowering the MRT as discussed earlier.
fortable indoors of traditional building while revealing the real The control of convective heat flow is an important aspect of
discomfort of the modern building. traditional architecture of Kerala. The effect of air movement on
human thermal comfort becomes critical depending on the air tem-
4.3. The passive control system perature and RH. Air movement is helpful in achieving thermal
comfort when the air is cooler than the skin temperature and the
This investigation on the comparative assessment of traditional difference between skin and air temperature is large. Conversely, if
and modern buildings in terms of indoor thermal comfort reveals the air is only slightly below skin temperature, very large increases
that an effective passive control system is embedded in the tradi- in air speed are needed to achieve an increase in convective cool-
tional architecture of Kerala. The passive system effectively controls ing. The air movement, in combination with air temperature, will
all the three ways of heat flow (conduction, radiation and convec- affect the rate at which warm air or vapour (for example) is taken
tion) towards the interiors. away from the body, thus cooling the body temperature [51,52].
The traditional building system is highly insulative against con- This philosophy is found to be applied in the traditional interiors in
duction. The highly thick double layered external walls largely an effective manner.
protected from direct sun light with the help of external veran- The building system with optimum window openings (size as
dahs provide a good thermal insulation even when there is external well as distribution) protected by verandahs and the presence of
heating of the surfaces. The roof system with a combination of air internal courtyard induces a controlled and continuous air flow
cavities within the clay tiles topping the roof, and the wooden ceil- inside the building. The warm air from outside that is pulled into the
ing with well ventilated attic space insulate the building from the interiors becomes cooler during its gentle flow towards the inte-
conductive and convective heat flow through the roof. rior spaces as it interacts with the cooler internal surfaces and the
It was observed that the central court provides enough of dif- cold air deposition in the courtyard. The total air volume in the
fused light into the interior spaces. The internal verandah around interiors is reduced by providing low room height (210 cm). The
the courtyard protects the court from receiving direct sunlight cold air deposited in the courtyard during night will be sufficient
thereby reducing the heat gain through the solar radiation. This for conditioning the total air in the interior, throughout the day.
A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664 663

Since the indoor air is maintained at a lower temperature, a gentle to improve survivability levels in low-income households, Energy and Buildings
(controlled) air flow is sufficient to provide thermal comfort to the 39 (2007) 859–866.
[9] N.H. Wong, S. Li, A study of the effectiveness of passive climate control in nat-
occupants as explained in the previous paragraph. urally ventilated residential buildings in Singapore, Building and Environment
42 (2007) 1395–1405.
[10] C. Isaksson, F. Karlsson, Indoor climate in low-energy houses – an interdisci-
5. Conclusions plinary investigation, Building and Environment 41 (2006) 1678–1690.
[11] M.J. Holmes, J.N. Hacker, Climate change, thermal comfort and energy: meet-
This investigation has attempted a comparative analysis of the ing the design challenges of the 21st century, Energy and Buildings 39 (2007)
802–814.
thermal performance of traditional and modern buildings of Kerala [12] M. Indraganti, Using the adaptive model of thermal comfort for obtaining
by continuously monitoring the thermal comfort parameters in the indoor neutral temperature: findings from a field study in Hyderabad, India,
buildings and assessing the performance using Bioclimatic chart Building and Environment 45 (2010) 519–536.
[13] M. Indraganti, Adaptive use of natural ventilation for thermal comfort in Indian
and PMV-PPD analysis.
apartments, Building and Environment 45 (2010) 1490–1507.
It was found that the diurnal variation of indoor air temperature [14] M. Indraganti, Behavioural adaptation and the use of environmental controls
is less in traditional building of Kerala as compared to the mod- in summer for thermal comfort in apartments in India, Energy and Buildings
42 (2010) 1019–1025.
ern building. Time lag between outdoor and indoor temperature
[15] I.A. Raja, J.F. Nicol, K.J. McCartney, M.A. Humphreys, Thermal comfort: use
in traditional building is negligible while that in the selected mod- of controls in naturally ventilated buildings, Energy and Buildings 33 (2001)
ern building is about 3 h. This shows the high thermal insulation 235–244.
property and temperature control of the traditional building. [16] K.-H. Lee, D.-W. Han, H.-J. Lim, Passive design principles and techniques for
folk houses in Cheju Island and Ull ng Island of Korea, Energy and Buildings 23
MRT of traditional building is very low compared to that of mod- (1996) 207–216.
ern house. This is due to the presence of cold air deposition and [17] F. Wang, Y. Liu, Thermal environment of the courtyard style cave dwelling in
presence of cooler surfaces in the interiors of traditional building. winter, Energy and Buildings 34 (2002) 985–1001.
[18] R. Ooka, Field study on sustainable indoor climate design of a Japanese tra-
This, low MRT contributes much to the indoor thermal comfort. ditional folk house in cold climate area, Building and Environment 37 (2002)
While air flow in traditional building is controlled and continu- 319–329.
ous, that in modern house is rare and draughty. The characteristics [19] L. Borong, et al., Study on the thermal performance of the Chinese traditional
vernacular dwellings in summer, Energy and Buildings 36 (2004) 73–79.
of air flow in traditional building maintain the air temperature at a [20] D.-K. Kim, The natural environment control system of Korean traditional archi-
lower level while providing evaporative cooling to the occupants. tecture: comparison with Korean contemporary architecture, Building and
Analysis using Bioclimatic chart shows that traditional building Environment 41 (2005) 1905–1912.
[21] M.S. Sozen, G.Z. Gedık, Evaluation of traditional architecture in terms of
is comfortable compared to modern building. PMV-PPD analysis
building physics: old Diyarbakır houses, Building and Environment 42 (2007)
confirms the thermal comfort of traditional building whereas the 1810–1816.
modern building is proved to be very hot and uncomfortable to live [22] Y. Ryu, S. Kim, D. Lee, The influence of wind flows on thermal comfort in the
Daechung of a traditional Korean house, Building and Environment 44 (2009)
in during summer. Of the two, PMV-PPD analysis is comprehensive
18–26.
since the influence of MRT is directly taken into account. [23] T.J. Kim, J.S. Park, Natural ventilation with traditional Korean opening in con-
It can thus be concluded that the traditional architecture of temporary house, Building and Environment 45 (2010) 51–57.
Kerala has an effective passive and natural control system that [24] Z.J. Zhai, J.M. Previtali, Ancient vernacular architecture: characteristics catego-
rization and energy performance evaluation, Energy and Buildings 42 (2010)
is responsible for providing a comfortable thermal environment 357–365.
indoors in summer that is considered to be the most unpleasant [25] E. Arens, M.A. Humphreys, R. de Dear, H. Zhang, Are ‘class A’ temperature
time of the year to live indoors. requirements realistic or desirable? Building and Environment 45 (2010) 4–10.
[26] Energy Conservation Building Code 2007, Bureau of Energy Efficiency (BEE),
May, 2008.
Acknowledgements [27] M.K. Singh, S. Mahapatra, S.K. Atreya, Development of bio-climatic zones in
north-east India, Energy and Buildings 39 (2007) 1250–1257.
The authors would like to dedicate this paper to Dr. Ziaudeen [28] M.K. Singh, S. Mahapatra, S.K. Atreya, Bioclimatism and vernacular architecture
of north-east India, Building and Environment 44 (2009) 878–888.
(Late), former Principal, TKM College of Engineering, Kerala, who
[29] M.K. Singh, S. Mahapatra, S.K. Atreya, Thermal performance study and eval-
provided immense help to initiate this research. uation of comfort temperatures in vernacular buildings of North-East India,
The authors extend sincere gratitude to Mr. Ravi Varma of Building and Environment 45 (2010) 320–329.
[30] M. Indraganti, Understanding the climate sensitive architecture of Marikal, a
Puthiya Kovilakam (Nilambur) and Mr. K. Sasidharan of Shinnu
village in Telangana region in Andhra Pradesh, India, Building and Environment
(Nilambur) for their kind cooperation in the conduct of the investi- 45 (2010) 2709–2722.
gation in their residences. The authors also extend sincere gratitude [31] S. Edward, D. Kurian, Thermal performance of traditional buildings in Kerala,
to Mr. Sreejith T.S., Production Executive of EMCON, Cochin, Kerala, The Journal of the Indian Institute of Architects (2008) 7–8.
[32] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, The passive environment control
for fabrication of the experimental setup. system of Kerala vernacular residential architecture: an experimental investi-
gation on wind flow and thermal comfort, International Journal of Earth Science
References & Engineering 2 (2009) 264–271.
[33] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, Passive environment control system
[1] R. de Dear, Thermal comfort in practice, Indoor Air 14 (7) (2004) 32–39. for a healthy and comfortable indoor environment: a study of Kerala vernacu-
[2] J.F. Nicol, M.A. Humphreys, Adaptive thermal comfort and sustainable thermal lar residential buildings, in: Healthy Buildings 2009 International Conference,
standards for buildings, Energy and Buildings 34 (2002) 563–572. Syracuse, NY, USA, 14th–17th September, 2009 (paper no. 947).
[3] M.A. Humphreys, F. Nicol, Adaptive thermal comfort in buildings, The Kinki [34] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, Investigation on indoor air temper-
Chapter of the Society of Heating, Air-Conditioning and Sanitary Engineers of ature control of vernacular residential buildings of Kerala in summer, Journal
Japan, Kyoto, Japan, SHASE, 17th October, 2008, pp. 1–43. of the Institution of Engineers (India) – AR 91 (2010) 17–19.
[4] N.H. Wong, H. Feriadi, P.Y. Lim, K.W. Tham, C. Sekhar, K.W. Cheong, Thermal [35] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, Passive control methods of Kerala
comfort evaluation of naturally ventilated public housing in Singapore, Building traditional architecture for a comfortable indoor environment: a comparative
and Environment 37 (2002) 1267–1277. investigation during winter and summer, Building and Environment 45 (2010)
[5] Y. Jiang, Q. Chen, Effect of fluctuating wind direction on cross natural ventilation 1134–1143.
in buildings from large eddy simulation, Building and Environment 37 (2002) [36] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, Passive environment control system
379–386. of Kerala vernacular residential architecture for a comfortable indoor environ-
[6] M.-S. Yeo, I.-H. Yang, K.-W. Kim, Historical changes and recent energy sav- ment: a qualitative and quantitative analyses, Energy and Buildings 42 (2010)
ing potential of residential heating in Korea, Energy and Buildings 35 (2003) 917–927.
715–727. [37] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, Passive control methods of Kerala
[7] D.H. Kang, P.H. Mo, D.H. Choi, M.S. Yeo, K.W. Kim, Effect of MRT variation on traditional architecture for a comfortable indoor environment: comparative
the energy consumption in a PMV-controlled office, Building and Environment investigation during various periods of rainy season, Building and Environment
45 (2010) 1914–1922. 45 (2010) 2218–2230.
[8] M. Santamouris, K. Pavlou, A. Synnefa, K. Niachou, D. Kolokotsa, Recent [38] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, Climate responsive design for
progress on passive cooling techniques. Advanced technological developments comfortable living in warm-humid climate: the need for a comprehensive
664 A.S. Dili et al. / Energy and Buildings 43 (2011) 653–664

investigation of Kerala vernacular architecture and its present status, in: Design [45] Q. Chen, Ventilation performance prediction for buildings: a method overview
Conference 2010, Illinois University, Chicago, USA, 13th to 15th February, and recent applications, Building and Environment 44 (2009)848–858.
2010. [46] Koenigsberger, et al., Manual of Tropical Housing and Building – Climatic
[39] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, The influence of internal courtyard Design, Orient Longman Private Limited, 1975.
of Kerala traditional residential buildings in providing a comfortable indoor [47] F.H. Mallick, Thermal comfort and building design in the tropical climates,
environment, International Journal of Earth Sciences and Engineering 3 (2010) Energy and Buildings 23 (1996) 161–167.
1–5. [48] P.O. Fanger, Thermal Comfort – Analysis and Applications in Environmental
[40] A.S. Dili, M.A. Naseer, T. Zacharia Varghese, Thermal comfort study of Kerala Engineering, McGraw-Hill Book Company, 1970.
traditional residential buildings based on questionnaire survey among occu- [49] ANSI/ASHRAE Standard 55-2004, Thermal Environmental Conditions for
pants of traditional and modern buildings, Energy and Buildings 42 (2010) Human Occupancy, American Society of Heating, Refrigerating and Air Con-
2139–2150. ditioning Engineers, Atlanta, 2004.
[41] IS. SP 7: 2005, National Building Code of India 2005, Bureau of Indian Standards, [50] ISO 7730, Ergonomics of the Thermal Environment-Analytical Determination
New Delhi, 2005. and Interpretation of Thermal Comfort using Calculation of the PMV and PPD
[42] J.L. Stoops, Possible connection between thermal comfort and health, Lawrence Indices and Local Thermal Comfort Criteria, International Standards Organiza-
Berkeley National Laboratory, University of California, LBNL Paper LBNL-55134, tion, Geneva, Switzerland, 2005.
2004. [51] S. Heidari, Effect of air movement in buildings, in: International Conference
[43] J.L. Stoops, Indoor thermal comfort, an evolutionary biology perspective, in: “Passive and Low Energy Cooling for the Built Environment”, Santorini, Greece,
Proceedings of the Conference: Comfort and Energy Use in Buildings – Getting May, 2005, pp. 1045–1051.
them Right, Cumberland Lodge (Windsor, UK), 27–30th April, 2006. [52] H.B. Rijal, P. Tuohy, M.A. Humphreys, J.F. Nicol, A. Samuel, J. Clarke, Using
[44] S.P. Corgnati, R. Ansaldi, M. Filippi, Thermal comfort in Italian classrooms under results from field surveys to predict the effect of open windows on ther-
free running conditions during mid seasons: assessment through objective and mal comfort and energy use in buildings, Energy and Buildings 39 (2007)
subjective approaches, Building and Environment 44 (2009) 785–792. 823–836.

Potrebbero piacerti anche