5.1 Introduction
CSC-211 is line protection measurement control equipment that is applicable to neutral indirect ground
system of under 110kV and can be installed inside the switch cabinet on the spot.
b) Three-zone zero-sequence over current protection (EF) with definite-time (via direction lock),
wherein 䊢 can be set as reverse-time zone (Once set as reverse-time, definite-time
zero-sequence over current II and 䊢 exit automatically).
b) Remote control of open and close for small current-grounded detection, remote control of open
and close for normal breaker
c) Remote measurement of Ua, Ub, Uc, Ia, Ic, P, Q, cos M and F analog
13
CSC-200 numerical protection measurement control equipment Manual
e) 32 setting-group
a) MAX ( Ia, Ib, Ic) ! Idzn , Idzn is the current setting of the nth zone;
b) Delay expiration
c) The low-voltage component and the direction component meet the operation conditions
The three-zone over current protection starts up/shuts down via a soft connector, when the rear board
terminal X5.7 is used as the common remote signal. The software and hardware combined connector
mode can be selected. Here, the X5.7 is the hard contact digital input of the three-zone over current
protection. The direction component and low-voltage component can be quit or adopted via the control
word. When the direction or low-voltage lock condition starts up, the protection logic is affected by the VT
disconnection and control word KG1.13; when the direction and low-voltage lock condition do not
operate, the protection logic is not affected by VT disconnection. The following figure shows the A phase
over current protection logic with the direction and low-voltage lock condition.
Ia > Idz1
VT Fail & T
KG1.13=1
OC I
KG1.13=0 ı1
Phase A direction
KG1.0=1
&
Low Voltage
KG1.3=1
The over current 䊢 zone can be set as the reverse-time (here, the over current II and 䊢 zone exit), the
logic figure is shown as follows (taking A phase reverse-time over current as one example):
14
CSC-200 numerical protection measurement control equipment Manual
Phase A INV
KG1.13=0 ı1
Phase A direction
KG1.10=1
The low-voltage component can be quit or adopted via the control word.
b) Delay expiration
The three-zone zero-sequence over current protection starts up/shuts down via a soft connector, and the
zero-sequence direction component can be quit or adopted via the control word. When the direction
component starts up, the protection logic is affected by the VT fail and control word KG1.13,or the
protection logic is not affected by VT fail.
The three-zone zero-sequence over current with definite-time protection logic is shown as follows (taking
zero-sequence over current I zone as one example):
KG1.13=0 ı1
Negative direction
KG1.7=1
15
CSC-200 numerical protection measurement control equipment Manual
The zero-sequence over current 䊢 can be set as the reverse-time (here, the zero-sequence over current
II and 䊢 zone shuts down), and the protection logic is shown as follows:
EF INV
VT Fail &
KG1.13=1
EF ċ
KG1.13=0 ı1
Negative direction
KG1.11=1
90o
I
Action
zone
U
O
-30o
$ 3I 0
The action zone of the zero-sequence direction component is 120 arg 240$ , 3U0 is the
3U 0
self-generation zero-sequence voltage, the external 3I0 terminal wiring is not reverse, and the blurry
angle error of the edge is smaller than r5q(as shown in the figure 5-6).
16
CSC-200 numerical protection measurement control equipment Manual
Action 120o
zone
3U0
3I0 120o
Note: when the onsite test condition is not met, only the analogue phase sequence is validated, and the
direction action zone is not validated.
If there is no main station system, it is judged as the ground line as the 3U0 is higher than 18V upon
close, 3U0 is smaller than 18V after the onsite test trip and open,. The alarm message “local line
ground“ is reported. After trip test, the equipment will automatically reclose.
In addition, the equipment includes the trip test and line selection function. The on-duty person
makes the trip operation at the monitoring main station to identify the ground line. The test trip
provides the automatic reclose function. (When the reclose starts up and the hide trip reclosing
control word starts up)
17
CSC-200 numerical protection measurement control equipment Manual
c) Extreme reverse-time: t 80
Tp
I 2
( ) 1
Ip
Wherein: Tp is the time coefficient, ranges from 0.05 to 1; Ip is the basic current, I is the fault current, and t
is the trip time.
Deducted from above equation, the reverse time limit feature expression of this equipment is written as
the equation 5-1:
Tinv
t (equation 5-1)
I Exp
( ) 1
Ip
The reverse-time index setting is the Exp value of the equation 5-1 in the setting list. The reverse-time
time setting is the Tinv in the equation 5-1. it is the product of the numerator in the above three IEEE
expressions and the unit is second.
18
CSC-200 numerical protection measurement control equipment Manual
The inter-phase current and zero-sequence current of the equipment includes the fixing and reverse time
protection function. The related bits of the control word can be set to select the definite-time or
reverse-time limit. When the reverse time is selected, the definite-time over current II and III zone and
zero-current II and III zone component will automatically shuts down, the function connector of the
inter-phase current III zone and zero-sequence current III zone becomes the connector of the
inter-phase current reverse-time and zero-sequence current reverse-time function.
d) The breaker changes from open to close and closes at the fault.
2.The breaker keeps open means TWJ of the device is close which is the actual location of the
breaker.
b) Delay expiration
The over current acceleration low-voltage lock can operate and exit via the control word. When the
low-voltage lock starts up, the protection logic is affected by VT fail and control word KG1.13,or the
protection logic is not affected by VT fail.
a) The zero-sequence current is higher than the zero-current acceleration current setting;
b) Delay expires
The logic of the manual close over current acceleration protection is shown as follows:
19
CSC-200 numerical protection measurement control equipment Manual
Change to closed
KG1.13=1
PT Fail
KG1.13=0 ı1
Low voltage
KG1.6=1
The logic of the manual close zero current protection is shown as follows:
Change to closed
Charging full
Has current
& T Trip
& ACC
Reclose action KG2.14=0
a) Protection trip
When the breaker closes, the reclosing starts to be charged, the charging duration is 15 s. The green
reclosing indicator will flicker during charging. The green indicator will keep on after the reclosing is
charged fully. When any condition is met, the reclosing starts to discharge.
20
CSC-200 numerical protection measurement control equipment Manual
b) The spring non energy storage terminal is at high level and is discharged after 2 s delay.
d) After permanent trip (such as under-frequency, under-voltage action, and over-load action )
b) Check no voltage
c) Check synchronization
d) If check no voltage fails, the reclosing will automatically enter into the check synchronization.
The reclosing function starts up/shuts down via the soft connector; the reclosing mode and
synchronization phase selection are set via the control word. For check no voltage mode, when the
control word KG2.9=0, and the line extraction voltage is lower than 0.3Un, it is judged as no voltage;
when the control word KG2.9˙1, no bus voltage or no line extraction voltage is met, it is judged as no
voltage.
Note: when the PT is not installed on the line side, the reclosing mode should be non synchronization
mode.
The reclosing mode, synchronization phase selection uses the same control word and setting of
Sync-Check with three phase first reclosing. For “DI4 manual digital input“ is at the high level , check
whether the close condition is met during extension period 9s, if it is met, equipment puts the spare exit 2
out.
When the manual close digital input keeps a high level for 10s, an alarm “manual close digital input
error“ is reported.
Action condition:
b) Delay expiration.
Lock condition:
a) The minimum line voltage is lower than the lock voltage setting;
d) When the load current < Idz(this condition is optional via the control of the control word);
e) VT disconnect;
Idz is the under-frequency current setting, its setting range is from 0 to 10.0In, it is recommend to be over
0.1In.
The under frequency load shedding component starts up/shuts down via a soft connector, the rear
terminal X5.6 is used as the common remote communication. If the software and hardware combined
connector mode be selected, the X5.6 is the hard contact digital input of this component.
Min(Uab,Ubc,Uca)<Block Vdz
& T Trip
Max(Ia,Ib,Ic) <No Idz ı1
KG1.12=1 UF
VT Fail
On unclosed status
Note: the under frequency signal indicator (red indicator) of the panel can be used as the under
voltage action indicator.
Action condition:
b) Delay expiration:
Lock condition:
22
CSC-200 numerical protection measurement control equipment Manual
b) Three-phase current is lower than 0.1In(this condition is optional via the control of the control
word);
f) VT disconnection;
The low-voltage separation protection equipment function starts up/shuts down via the control word.
Note: the under-frequency signal indicator(red indicator) of the panel can be used as the under-voltage
action indicator.
Max(Uab,Ubc,Uca)<Udz
U/t >(du/dt)dz
U2 > 5V
VT Fail
On unclosed status
a) MAX ( Ia, Ib, Ic) ! Idz , Idz is the over-load current setting;
b) Delay expiration;
The over-load function starts up/shuts down via the soft connector and the control word is used to
decide whether to trip.
Note: this equipment considers that generally the over-load time is long delay, and the protection exit
delay is the practical setting time, but the report does not embody it.
Tgj To alarm
23
CSC-200 numerical protection measurement control equipment Manual
Wherein Ttz is the over-load trip time and Tgj is the over load alarm time.
a) If the self-generated 3U0 is smaller than 8V, the three-phase voltage is smaller than 8V, and
the current is over no current threshold (the default is 0.125 A), it is judged as three phase
voltage loss.
b) If the self-generated 3U0 is higher than 8V, and the minimum line voltage is lower than 16V,
it is judged as two-phase failure.
c) If the self-generated 3U0 is higher than 8V and the difference between the maximal line
voltage and minimal line voltage is higher than 16V, it is judged as single phase VT failure.
After the equipment detects VT failure, it can exit the protection with direction component or voltage
component via the control word, or select to shut down the direction components and voltage
components.
If the analog self-check function and reclosing function operate, and the reclosing selects the check
no voltage or check synchronization mode, when the line voltage is lower than 0.3Un and any phase
current is higher than the default 0.125A (no current value can be changed in the factory setting).
The line VT fail is reported after 9-second delay, the alarm signal is given, and the automatic
reclosing is locked. When the line voltage recovers to normal status, the reclosing will automatically
recover to normal status.
VT loop monitoring function starts up/shuts down via the analog self-check control word.
No current
max{UA,UB,Uc}<8V &
Generated 3U0 < 8V
Max{UAB,UBC,UCA}- &
Min{UAB,UBC,UCA}>16V
Relay start up
24
CSC-200 numerical protection measurement control equipment Manual
No current
Ux<0.3Uxn
ARC Sync-Check
& 9S Report“Ux VT Fail”
ı1 KG1.15=1
ARC Check LU
Relay start up
factory setting.
Name Function
OC ĉ OC ĉ ON/OFF
OC Ċ OC Ċ ON/OFF
OC ċ OC ċ ON/OFF
EF ĉ EF ĉ ON/OFF
EF Ċ EF Ċ ON/OFF
25
CSC-200 numerical protection measurement control equipment Manual
Name Function
EF ċ EF ċ ON/OFF
0.25~100(In=5A)
4 OC ĉ I A
0.05~20(In=1A)
5 OC ĉ T 0.0̚32.00 s
0.25~100(In=5A)
6 OC Ċ I A
0.05~20(In=1A)
7 OC Ċ T 0.1̚32.00 s
0.25~100(In=5A)
8 OC ċ I A
0.05~20(In=1A)
9 OC ċ T 0.1̚32.00 s
0.25~100(In=5A)
11 EF ĉ I A
0.05~20(In=1A)
26
CSC-200 numerical protection measurement control equipment Manual
12 EF ĉ T 0.0̚32.00 s
0.25~100(In=5A)
13 EF Ċ I A
0.05~20(In=1A)
14 EF Ċ T 0.1̚32.00 s
0.25~100(In=5A)
15 EF ċ I A
0.05~20(In=1A)
16 EF ċ T 0.1̚32.00 s
OC ACC I
0.25~100(In=5A)
17 A
0.05~20(In=1A)
OC ACC T
18 0.0̚3.00 s
EF ACC I
0.25~100(In=5A)
19 A
0.05~20(In=1A)
EF ACC T
20 0.0̚3.00 s
0.25~100(In=5A)
21 OC INV I A
0.05~20(In=1A)
22 OC INV T 0.005̚250 s
0.25~100(In=5A)
23 EF INV I A
0.05~20(In=1A)
24 EF INV T 0.005̚250 s
0.25~100(In=5A)
26 Overload I A
0.05~20(In=1A)
27
CSC-200 numerical protection measurement control equipment Manual
27 OL Alarm T 6̚6000 s
28 OL Trip T 0.1̚6000 s
30 ARC T 0.2̚32.0 s
31 UF F 45.0̚49.5 Hz
32 UF T 0.0̚32.0 s
0~50(In=5A)
35 BLK UF I A
0~10(In=1A)
37 UV split T 0.1̚32.0 s
14 CT Rated 5A CT Rated 1A
28
CSC-200 numerical protection measurement control equipment Manual
29
CSC-200 numerical protection measurement control equipment Manual
3 Reclosing phase
1
Reclosing mode
0
Note:To separate the reclosing signal node from the protection action signal node, the enhanced
CSC211 terminal X6-19 and X6-20 can be used as the reclosing action signal contact. This contact
can act as the reclosing action signals or spare exit 4 via the control word KG2.10 in the software. If
this node is used as the reclosing action signal contact in the engineering, please set the control
word KG2.10 as the “1”.
1 0 ARC Check LU
0 0 0 /
0 0 1 Syn-Check UA
30
CSC-200 numerical protection measurement control equipment Manual
0 1 0 Syn-Check UB
0 1 1 Syn-Check UC
1 0 0 None
1 0 1 Syn-Check UAB
1 1 0 Syn-Check UBC
1 1 1 Syn-Check UCA
2 EF CT Rated 1A EF CT Rated 5A
b) CT change ratio is special for measurement; it is set via dividing the change ratio by 1000.
c) All protection function can start up/shut down via the soft connector or control word.
31
POWER TRIP LOGIC CPU COM AC2 AC2 AC1
X8 X7 X6 X5 X4 X3 X2 X1
1 DI1 BLK ARC 1 1 Common 1 Rem/Loc 1 Ua 1 1
2 DI2 CB unpower 2 2 Trip1 2 Reset 2 Ub 2 2
3 3 3 Close1 3 Overhaul 3 Uc 3 3
4 4 4 Common 4 4 Un 4 4
5 5 5 Trip2 5 -24V 5 Ux 5 5
6 6 6 Close2 6 UF/P 6 Ux' 6 6
5.4 Terminal figure
7 7 7 Common 7 OC/Q 7 7
8 8 8 Remote trip 8 Common- 8 8
9 9 9 Remote close 9 9 9
10 (-) 10 10 Common 10 10 10
11 11 11 Operation 11 11 11
12 12 12 Alarm 12 12 12 Ib'
13 13 13
Backup1
14 Failure 14 14
15 15 15
Backup2
16 16 16
CSC-200 numerical protection measurement control equipment
17 17 17
Backup3
32
18 18 18
19 19 19
20 20 20
33
CSC-200 numerical protection measurement control equipment Manual
6.1 Introduction
It is applicable to 66kV and lower capacitor protection and measurement and control and can be installed
at the switch cabinet.
d) Over-voltage protection(OV)
e) Under-voltage protection(UV)
d) Over-voltage protection
e) Under-voltage protection
b) Remote control of open and close for small current-grounded detection, remote control of open
and close for normal breaker
c) Remote measurement of Ua, Ub, Uc, Ia, Ib, Ic, P, Q and cos M
d) Forward/reverse re power
c) CB unpower alarm
34
CSC-200 numerical protection measurement control equipment Manual
MAX(I)) > MIN(Id ); Id is n-zone over current setting, I) is phase current (terminal X2-1~6).
Two-zone over current protection starts up/shuts down via the soft connector.
I¶>Idzn Tn Trip
OC
Action condition:
Two-zone zero-sequence over current protection starts up/shuts down via a soft connector.
The zero-sequence rated current is 1A or 5A and can be set via the internal parameters.
35
CSC-200 numerical protection measurement control equipment Manual
b) The three phase current of this line is lower than the setting
c) The line voltage exists for over 2s, namely the voltage reduction edge action
The under-voltage protection starts up and shuts down via a soft connector. When the mode is “soft and
hard combination”, the hard connector (5X-7) should operate.
Uab<Udz
&
Ubc<Udz
Y
Uca<Udz
& UV
I<IYL Td Trip
Y
HWJ
2S
Any Up-p>Udz
Td+2S
b) T > setting;
c) Breaker is closed;
The over-voltage protection starts up/shuts down via the soft connector.
Uab>Udz
ı1
Ubc>Udz OV
H &
Td
Uca>Udz Trip
KG1.5=0
Y
TWJ Td Alarm
KG1.5=1
0.14 13.5 80
t tp t tp t tp
( I I p )0.02 1 (I I p ) 1 ( I I p )2 1
Wherein: tp is the time coefficient, ranges from 0.05 to 1; Ip is the basic current, I is the fault current, and t
is the trip time.
Deducted from above equation, the reverse time limit feature expression of this equipment is written as
Tinv
t
( I I p )Exp 1
the equation.
The reverse-time index setting is the Exp value of the equation. The reverse-time time setting is the Tinv,
it is the product of the numerator in the above three IEEE expressions and the unit is second.
The inter-phase current and zero-sequence current of the equipment includes the fixing and reverse time
protection function. The related bits of the control word can be set to select the definite-time or
reverse-time limit. When the reverse time is selected, the definite-time over current II zone and
zero-current II zone component will automatically shuts down, the function connector of the inter-phase
current II zone and zero-sequence current II zone becomes the connector of the inter-phase current
reverse-time and zero-sequence current reverse-time function.
a) Any one (three phase) of three phase imbalanced input (terminal X1-1 ~ 6) is higher than the
imbalanced setting
b) Breaker is closed
Note: If the imbalanced analog only includes one phase, connect the three phase imbalanced input
terminal to get any phase.
37
CSC-200 numerical protection measurement control equipment Manual
TWJ Td Alarm
KG1.6=1
a) Any one of three line voltages is higher than the automatic switching over-voltage setting;
Uab>Udz
ı1
Ubc>Udz KG1.12=1
H & “1”
Uca>Udz Tzq Remove
Y Autoswitch “0”
TWJ
a) Three line voltage is lower than the automatic switching low-voltage setting and is higher than
64V
38
CSC-200 numerical protection measurement control equipment Manual
64V<Uab<Udz
&
64V<Ubc<Udz KG1.12=1
Y & “1”
64V<Uca<Udz Tzt Start-up
Y Autoswitch “0”
TWJ 5minutes
0
To prevent capacitor from closing upon fault, manual trip, remote trip or protection lock occurs, this
protection automatically shuts down “Autoswitch” soft connector. Therefore, the spare action signal
contact should feed back to connect to lock digital input.
Manual or
remote trip ı1 Remove Auto
15ms switch
H connector
Protection Block automatic
action switch
a) If the three phase voltage is lower than 8V and the current of a phase (a or c phase) is
higher than 0.25A (set), it is judged as the three phase voltage loss.
b) If the sum of the three phase voltage is higher than 8V and the minimal line voltage is lower
than 16V, it is judged as the two-phase VT failure.
c) If the sum of the three phase voltage is higher than 8V and the difference between
maximum and minimum line voltage is higher than 16V, it is judged as the single phase VT
failure.
VT loop monitoring function starts up/shuts down via the self-check control word. When KG1.15
(D15)=1, VT detection function starts up;
39
CSC-200 numerical protection measurement control equipment Manual
Name Function
OC ĉ OC ĉ ON/OFF
OC Ċ OC Ċ ON/OFF
EF ĉ EF ĉ ON/OFF
EF Ċ EF Ċ ON/OFF
OV OV ON/OFF
UV UV ON/OFF
Connector8 Backup
Connector9 Backup
0.25~100(In=5A)
3 OC ĉ I A
0.05~20(In=1A)
4 OC ĉ T 0.0̚32.00 S
0.25~100(In=5A)
5 OC Ċ I A
0.05~20(In=1A)
40
CSC-200 numerical protection measurement control equipment Manual
6 OC Ċ T 0.1̚32.00 S
0.25~100(In=5A)
7 EF ĉ I A
0.05~20(In=1A)
8 EF ĉ T 0.0̚32.00 S
0.25~100(In=5A)
9 EF Ċ I A
0.05~20(In=1A)
10 EF Ċ T 0.1̚32.00 S
0.25~100(In=5A)
11 OC INV I A
0.05~20(In=1A)
12 OC INV T 0.005̚120 S
0.25~100(In=5A)
13 EF INV I A
0.05~20(In=1A)
14 EF INV T 0.005̚120 S
16 Imbalanced 0.25~100(In=5A)
A CSC221B: Imbalanced I
0.05~20(In=1A)
17 Imbalanced T 0.0̚32.0 S
18 OV V 70̚130.0 V Phase-to-phase
19 OV T 0.0̚100.0 S
20 UV V 10̚110.0 V Phase-to-phase
21 UV T 0.0̚100.0 S
41
CSC-200 numerical protection measurement control equipment Manual
0.25~100(In=5A)
22 BLK UV I A
0.05~20(In=1A)
26 Auto On T 0.1̚100.0 S
Mea CT
27 0.001̚7.0 Primary Mea CT/1000
Ratio(kA/A)
Mea VT
28 0.01̚2.0 Primary VT/1000
Ratio(kV/V)
D5 OV Trip OV Alarm
D4 EF Ċ Trip EF Ċ Alarm
D3 EF ĉ Trip EF ĉ Alarm
42
CSC-200 numerical protection measurement control equipment Manual
D0 OV 3X1~4 OV Clearance
2. When the over-voltage is the bus voltage (KG1.0=0), the bus voltage is connected to the terminal
X3-1~4; when the over-voltage is the clearance voltage (KG1.0=1), the clearance voltage is connected to
the terminal X1-3 ~ 6, and any voltage of two channels is higher than the over-voltage setting, action
occurs.
b) CT change ratio is special for measurement, and is set via dividing the change ratio by 1000.
c) All protection equipment function can start up/shut down via the soft connector or control word.
e) The above part lists the standard configuration. If the content is not consistent with the
equipment list, refer to the practical equipment.
43
POWER TRIP LOGIC CPU COM AC2 AC2 AC1
X8 X7 X6 X5 X4 X3 X2 X1
1 DI1 1 1 Common 1 Rem/Loc 1 Ua 1 1
2 DI2 CB unpower 2 2 Trip1 2 Reset 2 Ub 2 2
3 3 3 Close1 3 Overhaul 3 Uc 3 3
4 4 4 Common 4 4 Un 4 4
5 5 5 Trip2 5 -24V 5 5 5
6 6 6 Close2 6 OV/P 6 6 6
7 7 7 Common 7 UV/Q 7 7
6.4 Terminal figure
17 17 17
Backup
18 18 18
44
19 19 19
Backup
20 20 20
Wiring note: if only one imbalanced analog input is provided, the A phase X3-1 and X3-2 of the three
phase imbalance at the X3 terminal is connected. If the automatic voltage switching function of this
equipment is not used, the action signal contact of the X6-19~20 is not connected to the X5-4. Generally
the strong current digital input 1 (X8-1) is used as the remote communication of the entity. After the entity
action is expanded by the external relay, the connection equipment trips and the digital input makes a
remote communication.
45