Technical guide P122/EN IC/B11

MiCOM P122C

Information and Control Tables


Technical guide P122/EN IC/B11
Information and control tables
MiCOM P122C Page 1/8

CONTENTS

1. INFORMATION AND CONTROL TABLES 3


1.1 Menu OP PARAMETERS 3
1.2 Menu MEASUREMENTS 4
1.3 Menu EVENT COUNTERS 5
1.4 Menu CONTROL/TESTING 5
1.5 Menu RECORD 6
1.5.1 Submenu FAULT RECORD 6

1.5.2 Submenu STARTING RECORD 6

1.5.3 Submenu CB MONITORING 6

1.6 ALARMS 7
1.7 Material alarms issued by internal monitoring 8
P122/EN IC/B11 Technical guide
Information and control tables
Page 2/8 MiCOM P122C

BLANK PAGE
Technical guide P122/EN IC/B11
Information and control tables
MiCOM P122C Page 3/8

1. INFORMATION AND CONTROL TABLES


1.1 Menu OP PARAMETERS
Signal Default Values range
Device Type P122C P122C
Software version 2. 2.A...2.Z
Active Group - 1/2
Input Status - 0 / 1 (low / high)
Relay Status - 0 / 1 (inactive / active)
P122/EN IC/B11 Technical guide
Information and control tables
Page 4/8 MiCOM P122C

1.2 Menu MEASUREMENTS


Measured data Default Values range
IA Rms - 0.00...400000.00 A
IB Rms - 0.00...400000.00 A
IC Rms - 0.00...400000.00 A
IN Rms - 0.00...120000.00 A (high range)
0.00...24000.00 A (normal range)
0.00...2400.00 A (sensitive range)
IA Rms Sec - 0.000...40.000 In
IB Rms Sec - 0.000...40.000 In
IC Rms Sec - 0.000...40.000 In
IN Rms Sec - 0...40.000 A (high range)
0...8.000 A (normal range)
0...0.800 A (sensitive range)
I1 Positive - 0.00...400000.00 A
I1 Positive Sec - 0.000...40.000 In
I2 Negative - 0.00...400000.00 A
I2 Negative Sec - 0.000...40.000 In
I2/I1 Ratio - 0...9999 %
I0 Zero - 0.00...40000.00 A (high range)
0.00...8000.00 A (normal range)
0.00...800.00 A (sensitive range)
I0 Zero Sec - 0.00...13.33 INn (high range)
0.00...2.66 INn (normal range)
0.000...0.266 INn (sensitive range)
Frequency - 45.00...65.00 Hz
Max Ph Current - 0.00...400000.00 A (clear with reset key !)
IN - fn - 0.00...120000.00 A (high range)
0.00...24000.00 A (normal range)
0.00...2400.00 A (sensitive range)
(Clear/trigger with reset key !)
Thermal State - 0...65535 % (clear with reset key !)
Rst.Max&Average - (Clear/trigger with reset key !)
Max. IA Rms - 0.00...400000.00 A
Max. IB Rms - 0.00...400000.00 A
Max. IC Rms - 0.00...400000.00 A
Average IA Rms - 0.00...400000.00 A
Average IB Rms - 0.00...400000.00 A
Average IC Rms - 0.00...400000.00 A
Rst.MaxSubperiod - Clear max. sub-period values with reset key !
Max. Subperiod IA Rms - 0.00...400000.00 A
Max. Subperiod IB Rms - 0.00...400000.00 A
Max. Subperiod IC Rms - 0.00...400000.00 A
Rst.Roll.Average - Clear rolling average values with reset key !
Rolling Average IA Rms - 0.00...400000.00 A
Rolling Average IB Rms - 0.00...400000.00 A
Rolling Average IC Rms - 0.00...400000.00 A

NOTE: Various designation texts may be selected from the local control
panel to display the phase currents (e.g. phase A current: IA, I1,
IL1 or IR) or the residual current (see submenu LOCAL
INDICATION). It is therefore possible that the text displayed on
the local control panel LCD in the menu MEASUREMENTS
differs from the text as described in this Operation guide.
Technical guide P122/EN IC/B11
Information and control tables
MiCOM P122C Page 5/8

1.3 Menu EVENT COUNTERS


Counter/Command Default Values range
Reset Counters - Clear event counters with reset key !
General Start NB - 0...65535
Total Trip NB - 0...65535
tExt 1;2 Trip NB - 0...65535
tI>;>>;>>> Trip NB - 0...65535
tIN>;>>;>>>Trip NB - 0...65535
tI2>;tI2>> Trip NB - 0...65535
tI< Trip NB - 0...65535
Therm Trip NB - 0...65535
CB Fail Trip NB - 0...65535
Trip onto fault NB - 0...65535

1.4 Menu CONTROL/TESTING


Command Default Values range
General Reset not execute not execute or execute
Open Order not execute not execute or execute
Close Order not execute not execute or execute
Disturb Trigger not execute not execute or execute
Maintenance mode No Yes or No
Block. CB-Meas. No Yes or No
P122/EN IC/B11 Technical guide
Information and control tables
Page 6/8 MiCOM P122C

1.5 Menu RECORD


1.5.1 Submenu FAULT RECORD
Parameter Default Values range
Record Number 5 1...5
Fault Time - 00:00:00:00...23:59:59:99
Fault Date - 00/00/00...31/12/99
Active Set Group - 1/2
Faulted Phase - ABC
Trip by - See selection Trip command
Magnitude - Depending on the fault
IA Magnitude - 0.00...400000.00 A
IB Magnitude - 0.00...400000.00 A
IC Magnitude - 0.00...400000.00 A
IN Magnitude - 0.00...120000.00 A (high range)
0.00...24000.00 A (normal range)
0.00...2400.00 A (sensitive range)

1.5.2 Submenu STARTING RECORD


Parameter Default Values range
Number 5 1...5
Hour - 00:00:00:00...23:59:59:99
Date - 00/00/00...31/12/99
Origin - I>, I>>, I>>>, IN>, IN>>, IN>>>, I2>, I2>>
Start.duration - 0.00...99999.99 s
Dur.t elapsed - 0.00...99999.99 s
Trip - Yes or No

1.5.3 Submenu CB MONITORING


Measured
Default Values range
data/Command
CB Open Time - 0.05...10.00 s
CB Close Time - 0.05...10.00 s
CB Open NB - 0..50000 (clear with reset key !)
Reset Sum A n - Clear Sum An with reset key !
Sum A n IA - 0...4000 E06 An
Sum A n IB - 0...4000 E06 An
Sum A n IC - 0...4000 E06 An
Technical guide P122/EN IC/B11
Information and control tables
MiCOM P122C Page 7/8

1.6 ALARMS
Signals Default Signalling behaviour
Phase A Start. - self updating or stored 1)
Phase B Start. - self updating or stored 1)
Phase C Start. - self updating or stored 1)
Starting GF - self updating or stored 1)
General Start. - self updating or stored 1)
tGS - stored 1)
Starting I> - self updating or stored 1)
tI> Phase … - stored 1)
Starting I>> - self updating or stored 1)
tI>> Phase … - stored 1)
Starting I>>> - self updating or stored 1)
tI>>> Phase … - stored 1)
Starting IN> - self updating or stored 1)
tIN> - stored 1)
tIN> int. - stored 1)
Starting IN>> - self updating or stored 1)
tIN>> - stored 1)
Starting IN>>> - self updating or stored 1)
tIN>>> - stored 1)
Starting I2> - self updating or stored 1)
tI2> - stored 1)
Starting I2>> - self updating or stored 1)
tI2>> - stored 1)
tI< Phase … - stored 1)
Thermal Alarm - self updating
Therm Overload - stored 1)
Therm. Block. - self updating
tExt1 - stored 1)
tExt2 - stored 1)
CB Failure - stored 1)
Trip by CB Failure - stored 1)
Trip by SOTF - stored 1)
Trip Circ Fail - stored 2)
CB Open Time - stored 2)
CB Close Time - stored 2)
CB Opening NB - stored 2)
Sum A n - stored 2)
CT Fail - stored 2)
Maintenance Mode - self updating
Latch Relay - self updating
Latch Relay Trip - self updating
1) The selected operating modes must be considered
2) Can only be cleared manually

Command Default Values range


Clear LED Alarms - Clear signals with reset key !
Clear All Alarms - Clear signals and latched relays with reset key !
P122/EN IC/B11 Technical guide
Information and control tables
Page 8/8 MiCOM P122C

1.7 Material alarms issued by internal monitoring


Signals Default Designation
CLOCK ERROR - minor material alarm
RAM ERROR - minor material alarm
BATTERY FAIL - minor material alarm
EEPROM ERROR DATA - major material alarm
DEFAULT SETTINGS - major material alarm
EEPROM ERROR CALIBR. - major material alarm
ANA ERROR - major material alarm
RELAYS ERROR - major material alarm