Sei sulla pagina 1di 2

Home | New Search | My Project | My RFI | Help

Back Print

Technical Specification
Single Core Unarmoured Cables - Copper Conductors XLPE Insulated 0.6/1KV

DESCRIPTION
Single Core cables with copper conductors, XLPE insulated and PVC sheathed. Cables are rated 0.6/1KV and conform to IEC:60502 - 1.

APPLICATION
z These cables have been designated for general purpose, including underground use where they are not likely to suffer mechanical damage.

CONSTRUCTION
1. Conductor Plain circular solid or stranded, copper conductors, per IEC:60228 class 1 and 2.
2. Insulation XLPE (cross-linked polyethylene) rated 90°C.
3. Outer Sheath PVC type ST2 to IEC 60502, colour black.
Colours for core
Red (black color on request)
identification

DIMENSION AND WEIGHT


Catalogue
Conductor Insulation Outer Sheath Packaging
No
Cross sectional area Minimum number of Thickness Thickness Overall diameter Net weight Standard
Nominal wires Nominal Nominal Approx Approx package
(mm2) (No.) (mm) (mm) (mm) (kg/km) m±5%
Single Core
ANH1-04A 1.5 1 0.7 1.4 5.8 44 1000
CNH1-04A 1.5 7 0.7 1.4 6.4 45 1000
ANH1-05A 2.5 1 0.7 1.4 6.6 57 1000
CNH1-05A 2.5 7 0.7 1.4 6.8 60 1000
ANH1-06A 4 1 0.7 1.4 7.1 74 1000
CNH1-06A 4 7 0.7 1.4 7.3 78 1000
ANH1-07A 6 1 0.7 1.4 7.6 96 1000
CNH1-07A 6 7 0.7 1.4 7.9 100 1000
ENH1-08A 10 7 0.7 1.4 8.8 146 1000
ENH1-09A 16 7 0.7 1.4 9.8 210 1000
ENH1-10A 25 7 0.9 1.4 11.5 310 1000
ENH1-11A 35 7 0.9 1.4 12.6 405 1000
ENH1-14A 50 7 1.0 1.4 14.3 525 1000
ENH1-16A 70 12 1.1 1.4 16.3 740 1000
ENH1-17A 95 15 1.1 1.5 18.3 1000 1000
ENH1-19A 120 18 1.2 1.5 20.1 1240 1000
ENH1-21A 150 18 1.4 1.6 22.3 1520 1000
ENH1-22A 185 30 1.6 1.6 24.6 1885 1000
ENH1-24A 240 34 1.7 1.7 26.5 2510 500
ENH1-26A 300 34 1.8 1.8 29.2 3120 500
ENH1-27A 400 53 2 1.9 32.5 3960 500
ENH1-28A 500 53 2.2 2.0 36.2 5030 500
ENH1-30A 630 53 2.4 2.2 41.8 6355 500
CURRENT CARRYING CAPACITY
Conductor Conductor resistance Current carrying capacity
Cross Sectional DC at 20°C AC at 90° C in flat AC at 90° C in trefoil
Area Maximum formation Approx formation Approx
mm2 ohm/km ohm/km ohm/km In ground In air
Direct laid Direct laid
In duct Free Free In pipes

Approx Approx Approx Approx Approx Approx


(amps) (amps) amps amps amps amps
1.5 12.1 15.4 15.4 31 30 22 27 22 19
2.5 7.41 9.45 9.45 40 39 29 36 29 24
4 4.61 5.88 5.88 52 50 38 47 38 32
6 3.08 3.93 3.93 65 63 47 60 49 40
10 1.83 2.33 2.33 87 83 63 82 66 54
16 1.15 1.47 1.47 112 107 82 109 88 70
25 0.727 0.927 0.927 144 137 105 145 116 92
35 0.524 0.669 0.668 172 165 127 178 143 112
50 0.387 0.494 0.494 204 195 151 218 175 134
70 0.268 0.342 0.343 251 238 187 277 222 168
95 0.193 0.247 0.248 301 286 225 344 274 205
120 0.153 0.196 0.197 345 327 258 409 326 237
150 0.124 0.159 0.16 385 363 290 461 367 269
185 0.0991 0.128 0.129 436 410 330 534 425 308
240 0.0754 0.098 0.1 507 474 382 638 505 361
300 0.0601 0.079 0.0815 573 532 431 740 583 411
400 0.0470 0.0629 0.0661 654 600 489 865 676 469
500 0.0366 0.0504 0.0543 744 673 550 1009 779 533
630 0.0283 0.0407 0.0453 847 752 615 1184 900 603

Ampacity is based on:


All values are calculated in accordance with
IEC 60287
Ground temperature 35°C
Air ambient temperature 40°C
Depth of burial 0.5m
Thermal resistivity of soil 1.2Km/W
Spacing between cables in flat formation One cable diameter

Back Print

Saudi Cable Company 2004 All Rights Reserved Privacy Policy - Terms & Conditions

Potrebbero piacerti anche