How to Find Capacitor Size in kVAR & F for Pf Improvement https://www.electricaltechnology.org/2013/11/How-to-Calculate-Suitabl...
Motor input = P = 5 kW
Original P.F = Cosθ1 = 0.75
Final P.F = Cosθ2 = 0.90
θ1 = Cos-1 = (0.75) = 41°.41; Tan θ1 = Tan (41°.41) = 0.8819
θ2 = Cos-1 = (0.90) = 25°.84; Tan θ2 = Tan (25°.50) = 0.4843
Required Capacitor kVAR to improve P.F from 0.75 to 0.90
Required Capacitor kVAR = P (Tan θ1 – Tan θ2)
= 5kW (0.8819 – 0.4843)
= 1.99 kVAR
And Rating of Capacitors connected in each Phase
1.99/3 = 0.663 kVAR
2 of 19 6/04/2019, 9:43 pm
How to Find Capacitor Size in kVAR & F for Pf Improvement https://www.electricaltechnology.org/2013/11/How-to-Calculate-Suitabl...
3 of 19 6/04/2019, 9:43 pm
How to Find Capacitor Size in kVAR & F for Pf Improvement https://www.electricaltechnology.org/2013/11/How-to-Calculate-Suitabl...
Example 2:
Supplying kW = 650 kW
From Table 1, Multiplier to improve PF from 0.65 to unity (1) is 1.169
Required Capacitor kVAR to improve P.F from 0.65 to unity (1)
Required Capacitor kVAR = kW x Table 1 Multiplier of 65 and 100
= 650kW x 1.169
= 759.85 kVAR
Supplying kW = 650 kW
Original P.F = Cosθ1 = 0.65
Final P.F = Cosθ2 = 1
θ1 = Cos-1 = (0.65) = 49°.45; Tan θ1 = Tan (41°.24) = 1.169
θ2 = Cos-1 = (1) = 0°; Tan θ2 = Tan (0°) = 0
Required Capacitor kVAR to improve P.F from 0.75 to 0.90
Required Capacitor kVAR = P (Tan θ1 – Tan θ2)
= 650kW (1.169– 0)
= 759.85 kVAR
4 of 19 6/04/2019, 9:43 pm
How to Find Capacitor Size in kVAR & F for Pf Improvement https://www.electricaltechnology.org/2013/11/How-to-Calculate-Suitabl...
How to Calculate the Required Capacitor bank value in both kVAR and
Farads?
(How to Convert Farads into kVAR and Vice Versa)
Example: 3
A Single phase 400V, 50Hz, motor takes a supply current of 50A at a P.F (Power
factor) of 0.6. The motor power factor has to be improved to 0.9 by connecting a
capacitor in parallel with it. Calculate the required capacity of Capacitor in both
kVAR and Farads.
Solution.:
(1) To ;ind the required capacity of Capacitance in kVAR to improve P.F from 0.6 to
0.9 (Two Methods)
(2) To ;ind the required capacity of Capacitance in Faradsto improve P.F from 0.6
to 0.9 (Two Methods)
We have already calculated the required Capacity of Capacitor in kVAR, so we can easily
convert it into Farads by using this simple formula
Required Capacity of Capacitor in Farads/Microfarads
C = kVAR / (2 π f V2) in microfarad
5 of 19 6/04/2019, 9:43 pm
How to Find Capacitor Size in kVAR & F for Pf Improvement https://www.electricaltechnology.org/2013/11/How-to-Calculate-Suitabl...
We know that;
IC = V/ XC
Whereas XC = 1 / 2 π F C
IC = V / (1 / 2 π F C)
IC = V 2 F C
= (400) x 2π x (50) x C
IC = 125663.7 x C
And,
kVAR = (V x IC) / 1000 … [kVAR =( V x I)/ 1000 ]
= 400 x 125663.7 x C
IC = 50265.48 x C … (ii)
50265.48 x C = 10.188C
C = 10.188 / 50265.48
C = 2.0268 x 10-4
C = 202.7 x 10-6
C = 202.7μF
Example 4
What value of Capacitance must be connected in parallel with a load drawing 1kW
at 70% lagging power factor from a 208V, 60Hz Source in order to raise the overall
power factor to 91%.
Solution:
You can use either Table method or Simple Calculation method to Find the required
value of Capacitance in Farads or kVAR to improve Power factor from 0.71 to 0.97. So I
used table method in this case.
P = 1000W
Actual Power factor = Cosθ1 = 0.71
Desired Power factor = Cosθ2 = 0.97
From Table, Multiplier to improve PF from 0.71 to 0.97 is 0.783
Required Capacitor kVAR to improve P.F from 0.71 to 0.97
Required Capacitor kVAR = kW x Table Multiplier of 0.71 and 0.97
= 1kW x 0.783
=783 VAR (required Capacitance Value in kVAR)
Current in the Capacitor =
IC = QC / V
= 783 / 208
= 3.76A
And
XC = V / IC
= 208 / 3.76 = 55.25Ω
C = 1/ (2 π f XC)
C = 1 (2 π x 60 x 55.25)
C = 48 μF (required Capacitance Value in Farads)
Good to Know:
Important formulas which is used for Power factor improvement calculation as
well as used in the above calculation
6 of 19 6/04/2019, 9:43 pm
How to Find Capacitor Size in kVAR & F for Pf Improvement https://www.electricaltechnology.org/2013/11/How-to-Calculate-Suitabl...
Power in Watts
kW = kVA x Cosθ
kW = HP x 0.746 or (HP x 0.746) / EfFiciency … (HP = Motor Power)
kW = √ ( kVA2– kVAR2)
kW = P = VI Cosθ … (Single Phase)
kW = P =√3x V x I Cosθ … (Three Phase)
Apparent Power in VA
kVA= √(kW2+ kVAR2)
kVA = kW/ Cosθ
Reactive Power in VA
kVAR= √(kVA2– kW2)
kVAR = C x (2 π f V2)