Sei sulla pagina 1di 1

Ginlong Technologies

Final test report


Model:Solis-3P20K-4G Product
Product:PV grid tie inverter Date: 12.10.2018
Standard:IEC61727 S/N:1107E018A120025
Test
Test parts NO Test item Limit Test data result
(P/F)
2120Vdc (PV/Grid) to Ground
1 Hi-pot test NA P
Safety test 4240Vdc(PV/Grid) to RS485
2 Ground resistance 500kΩ NA P
1 Comm. Test 180Vdc/400Vac NA P
2 PV isolation test 180Vdc/400Vac <200kΩ P
3 Start up voltage 180Vdc/400Vac 180V P
4 Standby power 180Vdc/400Vac 5~10 W P
5 Max. output power 600Vdc/24000W /400Vac 22000~22
00~22000W P
6 Max. output current 600Vdc/24000W /400Vac 28.9~33.5
3.5 A P
7 Max. Efficiency 600Vdc/24000W /400Vac 98.7%~98.
%~98.1 % P
8 Max.MPPT Efficiency 600Vdc/24000W/400Vac >99.5%~1
100% P
600Vdc/24000W/400Vac (0.8 P
9 PF leading E0.8
Performan
lagging)
ce and
10 THDi 600Vdc/24000W/400Vac 1.5 % P
protection
11 DCi 600Vdc/24000W/400Vac <0.5%In P
test
600Vdc/24000W
12 UVP <0.2S P
Vac>470V/F=50Hz
600Vdc/24000W
13 OVP <0.2S P
Vac<310V/F=50Hz
600Vdc/24000W
14 UFP <0.2S P
F<51Hz
600Vdc/24000W
15 OFP <0.2S P
F>47Hz
16 Residual current 600Vdc/24000W/400Vac >30mA trigger P
17 Anti-islanding 600Vdc/24000W/400Vac <2S P
1 Sealing test; P
Check
heck the surface
surface—clean and no scratch; check the LCD Board—no
no P
2
scratch;
3 Check and confirm
rm the tightness of screws;
screws P
4 Check and confirm
rm the tightness of AC/DC terminal; P
Inspection 5 Check
heck the silk print—clear,
print in proper place, and with correct color; P
6 Check the inside—
—no foreign material; P
7 Check
heck the package—no
package humidity, subsidence, or smearing; P
8 Check
heck the silk print (on package)
package)—confirm to the design drawing; P
Check
heck the accessories
access are complete, the nameplate is correct, and the P
9
entity is in accordance with the order requirement
requirement.
QC department: Date:12.10.2018