Controller settings:
To establish a communication between a beckhoff plc and a EXTER there are some settings
necessary in the terminal, but also in the plc.
To configure the CX-controller you need a “remote tool” called Cerhost. Start Cerhost and use
the name or the ip-adress of the controller to connect to the system.
Now you have to register all participants the controller should communicate to in the AMS remote
connections. You find this under My device—Hard Disk—System—TC AmsRemoteMgr.
Important!!:
Elektronik-Systeme LAUER GmbH & Co. KG - Kelterstraße 59 - 72669 Unterensingen - Tel.: +49 (0)7022-9660-0
Seite2 31.08.2010
Connection name
AMS Net ID
IP address
Transport
The AMS Net ID of the local computer is the IP address of the controller followed by 1.1
Elektronik-Systeme LAUER GmbH & Co. KG - Kelterstraße 59 - 72669 Unterensingen - Tel.: +49 (0)7022-9660-0
Seite3 31.08.2010
Settings Terminal: