208_21_2_prn

Trip Log - 000507 / 4/ 4/2019


SIMATIC 2:53:00.972 AM - New Dipalpur / FINAL / 04.04.19 07:20:10

New Dipalpur / FINAL / 220KV / KIOSK-4 / 208_21.2

MLFB: 7SA52216AB904QJ4----0S----------
Parameter set version: V04.70.07
Device path: C:\Siemens\Digsi4\D4proj\FINAL DIGSI DIPALPUR_23112016
\FINAL DIGSI DIPALPUR 21112012\New_Dipa\P7DI\GV\SD\00000034
Author:
Creation date: 21.12.11 12:32:59
Last modified: 04.04.19 07:19:39
Operating mode: Online
Comment:
Setting values in: Secondary value description

PRINT-CONTENTS
1 Indications ..................................................................................................................................................................... 2
1.1 Trip Log - 000507 / 4/ 4/2019 2:53:00.972 AM - New Dipalpur / FINAL / 220KV / KIOSK- ...................................... 2
4 / 208_21.2/7SA522 V04.70.07

Page 1 of 2
208_21_2_prn
Indications
Trip Log - 000507 / 4/ 4/2019
SIMATIC 2:53:00.972 AM - New Dipalpur / FINAL / 04.04.19 07:20:10

1 Indications

1.1
Trip Log - 000507 / 4/ 4/2019 2:53:00.972 AM - New Dipalpur / FINAL / 220KV / KIOSK-
4 / 208_21.2/7SA522 V04.70.07
Trip Log - 000507 / 4/ 4/2019 2:53:00.972 AM - New Dipalpur / FINAL / 220KV / KIOSK-4 / 208_21.2/7SA522
V04.70.07
Number Indication Value Date and time Cause State

00301 Power System fault 507 - ON 04.04.2019 02:53:00.972


00302 Fault Event 510 - ON 04.04.2019 02:53:00.972
01358 E/F picked up FORWARD ON 0 ms
01336 E/F phase selector L1 selected ON 0 ms
01357 E/F 3I0p PICKED UP ON 0 ms
03682 Distance Pickup L1E ON 8 ms
03701 Distance Loop L1E selected forward ON 8 ms
01335 Earth fault protection Trip is blocked ON 10 ms
02784 AR: Auto-reclose is not ready ON 206 ms
03805 Distance TRIP command Phases L123 ON 357 ms
00536 Relay Definitive TRIP ON 358 ms
00533 Primary fault current IL1 2.70 kA 362 ms
00534 Primary fault current IL2 0.21 kA 362 ms
00535 Primary fault current IL3 0.19 kA 362 ms
01336 E/F phase selector L1 selected OFF 378 ms
01345 Earth fault protection PICKED UP OFF 378 ms
03671 Distance PICKED UP OFF 418 ms
03701 Distance Loop L1E selected forward OFF 418 ms
03652 Distance is BLOCKED ON 422 ms
03652 Distance is BLOCKED OFF 444 ms
00511 Relay GENERAL TRIP command OFF 456 ms
01123 Fault Locator Loop L1E ON 277 ms
01117 Flt Locator: secondary RESISTANCE 1.39 Ohm 277 ms
01118 Flt Locator: secondary REACTANCE 6.93 Ohm 277 ms
01114 Flt Locator: primary RESISTANCE 3.48 Ohm 277 ms
01115 Flt Locator: primary REACTANCE 17.33 Ohm 277 ms
01119 Flt Locator: Distance to fault 36.2 km 277 ms
01120 Flt Locator: Distance [%] to fault 97.5 % 277 ms

Page 2 of 2