REPORT NO:04 Format No : IC/OC EFR/06-1

Project : 8520000621
Erection & Commissioning Date : 21-11-2018
Supervision
Customer : Hindustan Zinc Ltd Page 1 of 3

TEST REPORT FOR NUMERICAL RELAY

1. Location : CENTRAL MOCHIA 52MRL

2. Feeder No & Name : 4F1-INCOMER

3. Panel No :4

4. Equipment Details
Make : ABB
Type : REJ 601
SR. No : 1VYV91239956
Mfg. Year : 2018
Auxiliary supply : 30V DC

5. Secondary injection test:

I > (Over Current Low Set-1) Curve: IEC-NI

Set T.M.S. Operating time


Preference Curve Current(In) (sec) (sec)
(Is) 2*Is 5*Is 10*Is
IDMT
Rph 0.5 0.5 5.032 2.288 1.598
IEC NI
IDMT
Yph 0.5 0.5 5.066 2.273 1.599
IEC NI
IDMT
Bph 0.5 0.5 5.004 2.278 1.599
IEC NI

I >> (Over Current High Set) Curve: DT

Preference Curve Set Set Operating time


Current(In) Time (sec)
(Sec) 2*Is 5*Is
Rph IEC DMT 1.0 0.5 0.571 0.569
Yph IEC DMT 1.0 0.5 0.582 0.572
Bph IEC DMT 1.0 0.5 0.579 0.558

Test Performed by SP TECH Witnessed by ABB Witnessed by HZL


Name: Mr. PRATYUSH SONI
Name : V. RAJENDRAN Name: Mr. JANARTHANARAO
Designation: COMMISSIONING Designation: ASSOCIATE
Designation : T/C ENGINEER
ENGINEER MANAGER
Signature & Signature & Signature &
Date Date Date
REPORT NO:04 Format No : IC/OC EFR/06-1
Project : 8520000621
Erection & Commissioning Date : 21-11-2018
Supervision
Customer : Hindustan Zinc Ltd Page 2 of 3

TEST REPORT FOR NUMERICAL RELAY


I >>> (Over Current High Set) Curve: DT

Preference Curve Set Set Operating time


Current(In) Time (sec)
(Sec) 2*Is 5*Is
Rph IEC DMT2.0 0.3 0.380 0.378
Yph IEC DMT 2.0 0.3 0.376 0.380
Bph IEC DMT 2.0 0.3 0.379 0.379

Io > (Earth fault Low Set-1) Curve: IEC-NI

Set T.M.S. Operating time


Preference Curve Current(In) (sec) (sec)
(Is)
2*Is 5*Is 10*Is
IDMT
Rph 0.5 0.1 1.058 0.510 0.366
IEC NI
IDMT
Yph 0.5 0.1 1.054 0.517 0.394
IEC NI
IDMT
Bph 0.5 0.1 1.067 0.516 0.389
IEC NI

Io >> (Earth fault High Set) Curve: DT

Preference Curve Set Set Time Operating time


Current(In) (Sec) (sec)
2*Is 5*Is
IEC
Rph 1.0 0.5 0.580 0.570
DMT
IEC
Yph 1.0 0.5 0.579 0.576
DMT
IEC
Bph 1.0 0.5 0.581 0.577
DMT

Test Performed by SP TECH Witnessed by ABB Witnessed by HZL


Name: Mr. PRATYUSH SONI
Name : V. RAJENDRAN Name: Mr. JANARTHANARAO
Designation: COMMISSIONING Designation: ASSOCIATE
Designation : T/C ENGINEER
ENGINEER MANAGER
Signature & Signature & Signature &
Date Date Date
REPORT NO:04 Format No : IC/OC EFR/06-1
Project : 8520000621
Erection & Commissioning Date : 21-11-2018
Supervision
Customer : Hindustan Zinc Ltd Page 3 of 3

TEST REPORT FOR NUMERICAL RELAY


6. Functional checks:

1 Wiring checks OK
2 Correct operation of appropriate indicator / aux. relay OK
3 Correct initiation of alarm contacts OK
4 Correct circuit breaker tripping contacts OK
5 Relay cover properly fixing NA
6 Correct operating reset switch OK
7 Relay Draw out conditions CT shorting link should be short NA

7. Instruments used for testing:

Sr.No Descriptions Make Sr.No Calibration period


1 Relay test kit SUDHARSAN 14/08 29/09/2019

8. Remarks : The Numerical Relay Test Results found Satisfactory.

Test Performed by SP TECH Witnessed by ABB Witnessed by HZL


Name: Mr. PRATYUSH SONI
Name : V. RAJENDRAN Name: Mr. JANARTHANARAO
Designation: COMMISSIONING Designation: ASSOCIATE
Designation : T/C ENGINEER
ENGINEER MANAGER
Signature & Signature & Signature &
Date Date Date