Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CHAPTER 5
5.1 INTRODUCTION
complexity and the size of the generators. The important role of generators in
the power system and the high cost of repair in case of damage require a good
protection system against faults. It must be protected against the damage
caused by abnormal conditions in the electrical network or in the generator
itself. Generators are protected against external faults by several circuit
breakers that isolate all faults that occur in the network (i.e. transformers,
buses, lines, etc). At the same time, the generators must be protected against
faults that occur inside the machine. There are several ways to detect these
faults and avoid the damages caused by them. This work focuses on stator
winding ground faults to provide 100% protection in synchronous machines.
A stator winding ground fault is the most common type of fault to which
generators are subjected. Stator ground faults could be caused by the
insulation degradation in the windings as well as environmental influences
such as moisture or oil in combination with dirt which settles on the coil
surfaces and outside the stator slots. This often leads to electrical tracking
discharges in the end winding which eventually punctures the insulation.
First of all, the measuring circuit will be taken out. The injection
transformer and all the elements of the injection circuit (signal controllers, test
circuits, etc) will be substituted for injection impedance (Zinj = Rinj+j·Xinj).
Therefore, the 12.5 Hz voltage source will have to be reflected (E'inj) to the
generator side of the transformer using the turns ratio (rt). The internal
resistance of the subharmonic source will be reflected as well to the generator
side of the transformer and will also be included in the injection impedance
(Zinj).
Finally, the capacitor between the circuit breaker and the step-up
transformer, the bus and the step-up up transformer can be modelled just
taking into account their capacitances to ground. Thus, three capacitors per
phase is placed to model these elements. Figure 5.3 shows the equivalent of
the unit-connected generator with the injection scheme.
Vgenerator _ side 1
rt (5.1)
Vsource _ side 2.5
and the voltage source has a magnitude of 140 V (source side), which means
that the reflected voltage to the generator side is given by
1
Vgen._ side Vsource _ side . 56V (5.2)
2.5
R 36
Zinj 36 j.125 125 (5.3)
L 2..60 0.331H
Thus, it will be assumed that Zinj (impedance of the injection circuit) will be
calculated with R=36 Ω and L=0.331 H. One must realize that depending on
the system frequency this impedance will vary since X=j2πfL.
58
E 'inj
I (5.4)
zinj R n ZC total
As one knows the values of the injection circuit impedance, the grounding
resistor and the total capacitance to ground, it is possible to calculate the non-
fault current.
56
I non _ fault
1
36 j 0.331 2 12.5 1212 j 6
2.035 10 2 12.5
0.0088A78.67
The magnitude of the non-fault current is very small since the impedance of
the capacitances to ground is very large. The angle of the non-fault current is
close 90 º due to the influence of this large capacitance. When the ground
fault occurs, the impedance that limits the subharmonic current changes.
Consequently, the subharmonic current is divided in two currents: one that
flows through the capacitor and the other one through the fault resistance. The
total subharmonic current in a fault scenario is:
E 'inj E 'inj
Ifault IC I Rf (5.5)
Zinj R n ZC total || R f Z R
Zinj R n Ctotal f
ZCtotal R f
56 56
Ifault
j 6257 R f j 6257 R f (R f j 6257)
36 j 26 1212 1248 j 26
j 6257 R f (R f j 6257) (R f j 6257)
56
39150049 R f 6257 R f2
1248 j 26
R 2f 39150049 R f2 39150049
α=0 means that the fault is placed at the neutral since all the
capacitance of the stator winding is placed after the fault
resistance. Figure 5.4 shows the subharmonic protection scheme
with the 50 Hz power generation.
In Figure 5.6, one can see the 12.5 Hz sine wave. Once again, the
amplitude of the non-fault subharmonic current is 8.8 mA.
% of Resistance Resistance
% of Fault
Fault ( in Ohms) ( in Ohms)
1 5.265649 17 0.672677
2 3.047938 18 0.645939
3 2.254692 19 0.621447
4 1.833225 20 0.598896
5 1.566449 21 0.578036
6 1.379858 22 0.558657
7 1.240637 23 0.540585
8 1.131947 24 0.523673
9 1.044203 25 0.507796
10 0.97152 26 0.492846
11 0.910069 27 0.478731
12 0.857247 28 0.46537
13 0.811213 29 0.452693
14 0.770627 30 0.440638
15 0.73449 31 0.429152
16 0.702037 32 0.418186
64
% of Resistance Resistance
% of Fault
Fault ( in Ohms) ( in Ohms)
33 0.407698 67 0.189578
34 0.397649 68 0.185073
35 0.388007 69 0.180607
36 0.378739 70 0.176176
37 0.369819 71 0.171778
38 0.361221 72 0.167407
39 0.352924 73 0.163059
40 0.344905 74 0.158731
41 0.337147 75 0.154418
42 0.329633 76 0.150115
43 0.322346 77 0.145817
44 0.315272 78 0.14152
45 0.308398 79 0.137219
46 0.301712 80 0.132907
47 0.295201 81 0.128578
48 0.288856 82 0.124227
49 0.282667 83 0.119845
50 0.276623 84 0.115423
51 0.270718 85 0.110954
52 0.264942 86 0.106426
53 0.259289 87 0.101825
54 0.25375 88 0.097139
55 0.24832 89 0.092349
56 0.242992 90 0.087434
57 0.23776 91 0.082366
58 0.232618 92 0.077111
59 0.227561 93 0.071624
60 0.222584 94 0.065843
61 0.217682 95 0.059679
62 0.212849 96 0.052992
63 0.208082 97 0.045553
64 0.203376 98 0.036906
65 0.198726 99 0.025877
66 0.194128 100 0.000002
65
For protecting the generator against stator earth fault training data
for ANN, GA-BPN and ANFIS are encoded as specified in Figure 5.9. The
last column of the data is representing the percentage of winding affected by
earth fault which is to be the output of Computational Intelligence
Techniques.
66
Sampling of
Fault current
Check
For
No ¼ cycles
(n = 10)
Yes
I II III IV
In Output
In In In In In In In (%
Level
Level Level Level Level Level Level Level Wdg.
V
V VI VI VII VII VIII VIII Under
Max.
Range Max. Range Max. Range Max. Range Earth
Fault)
For protecting the generator against inter-turn fault training data for
ANN, GA-BPN and ANFIS are encoded as specified in Figure 5.10. The last
column of the data is representing the percentage of winding affected by
Inter-turn fault which is to be the output of Intelligent Computational
Approaches.
Ia Ia Ia Ia Ia Ia Ia Ia Output
Level Level Level Level Level Level Level Level (% Wdg
I I II II III III IV IV inter-turn
Max. Range Max. Range Max. Range Max. Range Fault)
The input vector elements for stator earth fault protection are
shown in the Figure 5.11.
In In In In In In In In
Level Level Level Level Level Level Level Level
V V VI VI VII VII VIII VIII
Max. Range Max. Range Max. Range Max. Range
The input vector elements for Stator Inter-Turn fault protection are
shown in the Figure 5.12.
Ia Ia Ia Ia Ia Ia Ia Ia
Level Level Level Level Level Level Level Level
I I II II III III IV IV
Max. Range Max. Range Max. Range Max. Range
After encoding the data of fault current as per the formats shown
above it is given to the corresponding ANNs or GA-BPNs or ANFISs which
are trained for I, II, III, IV quadrants of faulty currents respectively.
Intelligent Computational approaches are giving decision about the
69
percentage of winding affected by fault. The same flow can be adopted for
other phase windings of synchronous generator. So, the synchronous
generator can be protected completely from faulty condition by identifying
the percentage of winding affected by Inter-Turn and Earth fault on the phase
winding. No fault case is also taken into account for training the ANN, GA-
BPN and ANFIS.
Figure 5.13 Simulation Model of Sample Power System for Stator Inter-
Turn Fault
70
Training data for the ANN, GA-BPN and ANFIS are prepared by
simulating various percentage of winding short circuit faults on the phase
winding. With 95% Inter-Turn fault on phase ‘A’ winding of the generator,
the phase fault current recorded for quarter cycle is shown in Figure 5.14.
Total simulated data are four hundred in number which are shown
in Appendix 2. But ten sample data are given in Table 5.4 (Unnormalized).
Table 5.5 shows corresponding normalized data. System is tested with many
data for different % of Inter-turn fault.
Table 5.4 Simulated Actual Training Data of Sample Power System for
Stator Inter-Turn fault protection
Table 5.5 Simulated Actual Training Data of Sample Power System for
Stator Inter-Turn fault protection (Normalized)
ANFIS used for this purpose uses hybrid method as its optimization
method. The error tolerance is taken as zero.
Error
Epochs
Training data for the ANN, GA-BPN and ANFIS are prepared by
simulating various percentages of stator earth faults on the phase winding.
With 50% stator earth fault on phase ‘A’ winding of the generator, the neutral
subharmonic current recorded for quarter cycle is shown in Figure 5.27.
Figure 5.27 Neutral Subharmonic Current for 50% of ‘A’ winding earth
fault of Synchronous Generator
subharmonic current in neutral when the generator ‘A’ phase winding is under
50% of stator earth fault.
Table 5.6 Simulated Actual Training Data of Sample Power System for
stator earth fault protection
Table 5.7 Simulated Actual Training Data of Sample Power System for
stator earth fault protection (Normalized)
Number of nodes : 36
ANFIS used for this purpose uses hybrid method as its optimization
method. The error tolerance is taken as zero.
Figure 5.36 shows output of ANFIS for 40% of winding earth fault
of the generator with fault resistance equal to 200Ω. Its average testing error
is only 0.0019157 i.e., indicating the percentage of winding affected by earth
fault is 40.
Figure 5.37 shows output of ANFIS for 60% of winding earth fault
of the generator with fault resistance equal to 0 Ω. Its average testing error is
only 0.00084479 i.e., indicating the percentage of winding affected by earth
fault is 60.
The ANN used for this protection scheme is also feed forward
network which follows Levenberg-Marquardt optimization for updating the
weights and bias values of the Neural Network. Figure 5.39 shows the
performance curve of ANN after training the network.
5.9 CONCLUSION
From the above results, it is found that ANFIS is giving lesser MSE
but the time taken for training is more than the other two techniques. Table
5.9 shows the test results at different loading of sample system for Winding
Inter-turn Fault Protection. Table 5.10 shows the test results at different fault
resistance of the sample system for Stator Earth Fault Protection. From the
tables, it is understood that ANFIS is giving better performance than the other
two techniques.
All the proposed schemes are providing 100% stator earth fault
protection that is covering 0-100% of phase winding. Percentage of winding
nearer to the neutral of about 5% can effectively be protected using these
techniques than the conventional protection schemes where they are just
giving 5-100% protection.
The same schemes can be adopted for other two phase windings of
synchronous generator. So, the synchronous generator can be protected from
faulty condition by identifying the percentage of winding affected by the earth
fault and the percentage of winding by the inter-turn fault. No fault case is
also taken into account for training the ANN, GA-BPN and ANFIS.
92