Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Volume 2, No 3, 2012
© Copyright 2010 All rights reserved Integrated Publishing services
Research article ISSN 0976 – 4399
ABSTRACT
STAADPro and ETABS are the present day leading design softwares in the market. Many
design companies use these softwares for their project design purposes. So, this project
mainly deals with the comparative analysis of the results obtained from the design of a
regular and a plan irregular (as per IS 1893) multi storey building structure when designed
using STAADPro and ETABS softwares separately. These results will also be compared with
manual calculations of a sample beam and column of the same structure designed as per IS
456.
1. Introduction
STAADPro and ETABS are the present day leading design softwares in the market. Many
design companies use these softwares for their project design purposes. So, this project
mainly deals with the comparative analysis of the results obtained from the design of a multi
storey building structure when designed using STAADPro and ETABS softwares separately.
For first case, a 25mx25m 11 storey structure is modeled using both STAADPro and ETABS
softwares. The height of each storey is taken as 3mts making the total height of the structure
30mts. Analysis and design of the structure is done and then the results generated by these
softwares are compared and a conclusion is drawn from them. For second case, a 25mx25m 5
storey plan irregular structure as per IS 1893 is modeled using both STAADPro and ETABS
softwares. The height of each storey is taken as 3mt making the total height of 15mts. Design
results of both the softwares are compared along with the manual calculations of a sample
beam and column designed using IS 456.
2. Problem Definition
2.1 Case 1
A 25mtx25mt 11 storey multi storey regular structure is considered for the study. Modeling,
analysis and design of the structure is done separately on both STAADPro and ETABS
software. Plan of the building considered is shown in Figure 1.
Loads acting on the structure are dead load (DL), Live Load (IL) and Earthquake Load (EL)
DL: Self weight of the structure, Floor load and Wall loads
• LL: Live load 3KN/sq.m is considered
• SL: Zone: I
• Soil type: II
• Response reduction factor: 5
• Importance factor: 1
• Damping: 5%
• Time period: 0.54 sec (calculated as per IS 1893: 2002)
Results of vertical reactions of a sample node for different loads have been tabled in Table 2.
Similarly, Bending Moment and Shear Force of a sample column is given in Table 3
Design results of a sample beam and column by STAADPro and ETABS are given in below
Table 4
2.2 Case 2
A 25mtx25mt 5 storey multi storey plan irregular structure as per IS 1893:2002 is considered
for the study. Modeling, analysis and design of the structure is done separately on both
STAADPro and ETABS software. Plan of the building considered is shown in Figure 2.
Loads acting on the structure are dead load (DL), Live Load (IL) and Earthquake Load (EL)
• DL: Self weight of the structure, Floor load and Wall loads
• LL: Live load 3KN/sq.m is considered
• SL: Zone: II
• Soil type: II
• Response reduction factor: 5
• Importance factor: 1
• Damping: 5%
• Time period: 0.246 sec (calculated as per IS 1893: 2002)
Results of vertical reactions of a sample node for different loads have been tabled in Table 6.
Similarly, Bending Moment and Shear Force of a sample column is given in Table 7.
Design results of a sample beam and column by STAADPro and ETABS are given in below
Table 8.
Design results comparison of a sample beam and column designed by STAADPro and
ETABS with manual calculations are given in below Table 9.
3. Conclusion
From the design results of beams, we may conclude that ETABS gave lesser area of required
steel as compared to STAAD PRO. It is found out from previous studies on comparison of
STAAD results with manual calculations that STAADPro gives conservative design results
which is again proved in this study by comparing the results of STAADPro, ETABS and
Manual calculations (refer below table). Form the design results of column; since the required
steel for the column forces in this particular problem is less than the minimum steel limit of
column (i.e., 0.8%), the amount of steel calculated by both the softwares is equal. So
comparison of results for this case is not possible.
4. References
1. Bureau of Indian Standards: IS-875, part 1 (1987), Dead Loads on Buildings and
Structures, New Delhi, India.
2. Bureau of Indian Standards: IS-875, part 2 (1987), Live Loads on Buildings and
Structures, New Delhi, India.
3. Bureau of Indian Standards: IS-1893, part 1 (2002), Criteria for Earthquake Resistant
Design of Structures: Part 1 General provisions and Buildings, New Delhi, India.