Cub EQUIPMENT DESCRIPTION N Qty [nst] [nst] Eff [nst] UNIT Feed Stby E Dem Power Simul In Ip Ip/In MAXIMUN AVERAGE MAXIMUN
No: NUMBER O HP kW kW See Note Brkr D Factor Factor Factor (Amp) (Amp) POSSIBLE DEMAND RUNNING DEMAND
NAMEPLATE NAMEPLATE T (en eje) (Pot. Elec) Size Type Size or S (V) Amps kW kVAr kVA Amps kW kVAr kVA REV
LINE 1 LINE 2 E n% A GENERAL SPECIFICATIONS
A FOR DETAILED SPECIFICATION SEE MCC DATA SHEET
1A 940-CE-001 EXTRACTOR CENTRIFUGO (AREA MECANIZADO) 1 1 335.12 250 95.60% 261.51 2 AFD D 440 1 0.85 0.75 405 2955 7.3 403.7 261.51 162.07 307.66 302.77 196.13 121.55 230.74 B B HORIZONTAL BUS RATING (MINIMUM) = 800A
1D 940-CE-002 EXTRACTOR CENTRIFUGO (FUNDICION) 1 1 268.09 200 95.90% 208.55 2 AFD D 440 1 0.86 0.75 319 2283 7.2 318.2 208.55 123.75 242.5 238.65 156.41 92.8 181.87 B C ARRANGENMENT - FRONT ONLY
1G 940-CE-003 EXTRACTOR CENTRIFUGO (VIA HÚMEDA) 1 1 214.48 160 95.70% 167.19 2 AFD D 440 1 0.87 0.75 251 1768 7.0 252.16 167.19 94.75 192.17 189.12 125.39 71.07 144.13 B D NUMBERING FROM RIGHT TO LEFT - INCOMING IN SECTION #1
1J 940-CE-004 EXTRACTOR CENTRIFUGO (ABSORCIÓN ATÓMICA / SOLUBLE / AMBIENTAL) 1 1 49.60 37 93.60% 39.53 2 AFD D 440 1 0.85 0.75 61 378 6.2 61.02 39.53 24.51 46.51 45.77 29.65 18.37 34.88 B
1A 940-ET-001 EXTRACTOR CENTRIFUGO TUBULAR (ABSORCION ATOMICA) 1 1 4.02 3 86.50% 3.47 2 FNVR D 440 1 0.78 0.75 5.85 40.9 7.0 5.84 3.47 2.79 4.45 4.37 2.6 2.08 3.33 B
1D 940-ET-002 EXTRACTOR CENTRIFUGO TUBULAR (ABSORCION ATOMICA) 1 1 4.02 3 86.50% 3.47 2 FNVR D 440 1 0.78 0.75 5.85 40.9 7.0 5.84 3.47 2.79 4.45 4.37 2.6 2.08 3.33 B NOTES
1G 940-SS-001 EXTRACTOR CENTRIFUGO DE CHIMENEA (940-SS-001) 1 1 193.03 144 95.50% 150.79 2 AFD D 440 1 0.86 0.75 232 1613 7.0 230.07 150.79 89.48 175.34 172.55 113.09 67.1 131.5 B 1 CARGAS CONSIDERADAS EN EL PROYECTO
1J 940-SS-002 EXTRACTOR CENTRIFUGO DE CHIMENEA (940-SS-002) 1 1 44.64 33.3 93.60% 35.58 2 AFD D 440 1 0.85 0.75 55 340.2 6.2 54.93 35.58 22.05 41.86 41.2 26.69 16.54 31.4 B 2 CARGAS EN STAND BY
1A 940-IA-006 INYECTOR DE AIRE (ABSORCION ATOMICA) 1 1 0.75 0.56 80.50% 0.7 2 FNVR D 440 1 0.81 0.75 1.51 9.97 6.6 1.13 0.7 0.5 0.86 0.86 0.53 0.38 0.65 B 3 RESERVAS PARA CARGAS FUTURAS
1D 940-IA-007 INYECTOR DE AIRE (ABSORCION ATOMICA) 1 1 0.75 0.56 80.50% 0.7 2 FNVR D 440 1 0.81 0.75 1.51 9.97 6.6 1.13 0.7 0.5 0.86 0.86 0.53 0.38 0.65 B
1G 940-IA-005 INYECTOR DE AIRE (SOLUBLE) 1 1 10.00 7.46 91.00% 8.2 2 FNVR D 440 1 0.84 0.75 12.9 102 7.9 12.81 8.2 5.29 9.76 9.61 6.15 3.97 7.32 B
1J 940-IA-004 INYECTOR DE AIRE (VIA HUMEDA) 1 1 10.00 7.46 91.00% 8.2 2 FNVR D 440 1 0.84 0.75 12.9 102 7.9 12.81 8.2 5.29 9.76 9.61 6.15 3.97 7.32 B
1A 940-IA-003 INYECTOR DE AIRE (FUNDICION) 1 1 15.00 11.19 91.70% 12.2 2 FNVR D 440 1 0.85 0.75 18.6 153 8.2 18.83 12.2 7.56 14.35 14.13 9.15 5.66 10.76 B LEGEND
1D 940-IA-002 INYECTOR DE AIRE (MECANIZADO) 1 1 7.50 5.6 90.00% 6.22 2 FNVR D 440 1 0.79 0.75 10.1 63.6 6.3 10.33 6.22 4.82 7.87 7.76 4.67 3.62 5.91 B FVNR : FULL VOLTAGE NON REVERSING
1G 940-IA-001 INYECTOR DE AIRE (MECANIZADO) 1 1 7.50 5.6 90.00% 6.22 2 FNVR D 440 1 0.79 0.75 10.1 63.6 6.3 10.33 6.22 4.82 7.87 7.76 4.67 3.62 5.91 B FDR : FEEDER
1J 940-SC-001 PANEL DE CONTROLTORRE DE LAVADO DE GASES (940-SC-001) 1 1 17.00 12.68 100.00% 12.68 FDR D 440 1 0.85 0.75 - - - 19.57 12.68 7.86 14.92 14.68 9.51 5.9 11.19 B AFD : VARIABLE FREQUENCY DRIVE
1A 940-SC-002 PANEL DE CONTROLTORRE DE LAVADO DE GASES (940-SC-002) 1 1 17.00 12.68 100.00% 12.68 FDR D 440 1 0.85 0.75 - - - 19.57 12.68 7.86 14.92 14.68 9.51 5.9 11.19 B RVNR : REDUCED VOLTAGE NON REVERSING
1D 940-CP-001 TRANSFORMADOR 1 1 2.02 1.5 100.00% 1.5 FDR D 440 1 0.85 0.75 - - - 2.32 1.5 0.92 1.76 1.74 1.13 0.7 1.33 B C1 : SOFT STARTER
1J RESERVA 3 1 10.00 7.46 91.00% 8.2 2 FNVR D 440 1 0.84 0.75 12.9 102 7.9 12.81 8.2 5.29 9.76 9.61 6.15 3.97 7.32 B
1G RESERVA 3 1 10.00 7.46 91.00% 8.2 2 FNVR D 440 1 0.84 0.75 12.9 102 7.9 12.81 8.2 5.29 9.76 9.61 6.15 3.97 7.32 B

B 07/09/2018 Emitido para Aprobacion del Cliente


A 30/08/2018 Emitido para Aprobacion del Cliente
N° DATE REVISIONS BY REV APPROV
ORANGE

EL TORO

MOTOR CONTROL CENTER LOW VOLTAGE


SUB TOTAL= 20 955.79 1466.21 955.79 578.19 1117.39 1099.71 716.86 433.63 838.05 LOAD REPORT
Total System Sub Total Sub Total Sub Total Sub Total Total Total Total Total MCC (440V)
instl. Power pos. Max. pos. Max. pos. Max. pos. Max. running running running running H-495-MC-1421
kW Factor A kW kVAR kVA A kW kVAR kVA (MAXIMA DEMANDA PROYECTADA)
ORANGE PROJECT DOCUMENT NUMBER REV
101169 XXXXXXXXXXXXXXX 0