Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
to direct the flow of power to various feeders and to isolate apparatus and
circuits from the power system. These parts include the busbars, circuit
breakers, fuses, disconnection devices, current transformers (CTs), voltage
transformers (VTs), and the structure on or in which they are mounted.
The essentials of LV/MV/HV substation bus overcurrent and differential protection (on photo: HV
Contents:
To isolate bus faults, all power source circuits connected to the bus are
opened electrically by circuit breakers responding to relay action, by direct-
acting trip devices on low-voltage circuit breakers, or by fuses. This
disconnection shuts down all loads and associated processes supplied by
the bus and may affect other parts of the power system.
In view of the system downtime resulting from a bus fault, the equipment
should be designed to be as nearly fault proof as practicable. For
example, the use of metal-clad switchgear enhances reliability because the
enclosure protects the bus from direct lightning strokes.
Go back to contents ↑
Go back to contents ↑
time protection (Isd); Short-circuits: Instantaneous protection (Ii), Additional ground fault protection
Separate circuitry detects ground faults at much lower levels and clears
them much faster than is possible with direct-acting electromechanical
phase-overcurrent devices alone.
Go back to contents ↑
This goal justifies the extra cost of high-speed bus differential relaying.
For example, open outdoor buses have a high degree of exposure, and
metal-clad switchgear, properly installed and in a clean environment, have
minimum exposure. Contaminated environments increase the possibilities
of faults, and equipment located in these environments needs better
protection.
Effects of bus failure on other parts of the power system and associated
processes. If a long scheduled outage period for repairs can be tolerated,
differential protection may not be economically justified.
The differential protection methods generally used (in the order of the
quality of protection they provide) are:
Go back to contents ↑
All CTs should have the same ratio unless high-impedance relays suitable
for use with different ratio CTs are used. Auxiliary CTs should not be used
to match ratios.
All CTs should have low secondary leakage reactance. Wound CTs are
generally not suitable.
For the fault F3 indicated, the fault current I3 flows through Circuit Breaker
3 with the currents flowing through Circuit Breaker 1 and Circuit Breaker
2. Each current is smaller than, but together sum up to, I3.
If, for some reason, the CT secondary current at Circuit Breaker 3 does
not balance the sum of the currents produced by the CTs at Circuit
Breaker 1 and Circuit Breaker 2, excess or difference current is forced to
flow through CT 3 and cause the voltage across Point A and Point B to
increase to a point where the relay (Device 87B) will tend to operate.
From the point of view of the relay, the worst condition would be
where the CTs at Circuit Breaker 3 saturate almost completely
and hence produce no detectable secondary current, while the CTs
at Circuit Breaker 1 and Circuit Breaker 2 do not saturate at all
and, hence, reproduce the current faithfully.
The differential relay is set so that it does not operate for this voltage. It is
obvious that this voltage depends on the magnitude of the fault current, the
type of fault, and the total resistance. In the case of internal faults, the
secondary currents do not circulate, but rather result in a high enough
secondary voltage to cause the relay to operate.
Go back to contents ↑
The operating time for one type of linear coupler system is 1 cycle
or less above 150% of pickup and 1 cycle for another type of
linear coupler system. This scheme eliminates the difficulty due
to differences in the characteristics of iron-core CTs by using
air-core mutual inductances without any iron in the magnetic
circuit.
where:
For the conductor within the toroid, 5 V is induced per 1000 A of primary
current. Therefore, by design, the mutual impedance M is 0.005 W, 60 Hz.
In other words, Esec = Ipri × M.
Go back to contents ↑
Where relatively few circuits are connected to the bus, relays using the
percentage differential principle may be employed. These relays are similar
to transformer differential relays.
Go back to contents ↑
This method may be used as primary protection for buses with loads
protected by fuses, as backup to a complete differential protection scheme,
and as local backup protection for stuck load circuit breakers, which fail to
operate when they should.
The phase overcurrent relays are set above the total bus load or the total
rating of all loads supplied from the bus section.
When a normally closed tie breaker separates loads as shown in Figure 10,
this scheme can provide selectivity between the two sources.
Go back to contents ↑
However, those schemes are normally applied only on buses where the
extra expense can be economically justified.
Go back to contents ↑
Go back to contents ↑
Fast clearing of faults also can save lives by minimizing explosion and
fire aftermath. Furthermore, fast clearing of human-contact faults has
saved lives or reduced injury.