WEST QURNA | ~SECTION-1
IR — INSPECTION REQUEST
Contractor No.: AWQ0109
ExonMobil a au
Produced Water Treatment M109
ROCATION:PS-S | IRNO:IR No CE-C0242 | IRISSUE DATE: 22 April 2017 DISCIPLINE: Civil
Al-Fa0 Lab
SUBJECT: Witness INSPECTION REQUIRED DATE:23 April 2017 TIME:09:00
REF.SPECIFICATION: ‘QW: FT-NSPDS-00-040901 REV.1 EARTHWORK
. TQWA-CE1O91-COFND-D8-0002 REV.2. FOUNDATION FOR PRE SEPARATOR IDB
REE DRAWINGS: ‘ABJ681050 PLAN SECTION & DETAIL; D8 _
REF. ITP: 1QWA-CE1092-CPCAC-00-0001 REV. 1 CIVIL INSPECTION AND TEST PLAN
OTHERS REF. |
"ATTACHMENT /CHECK LIST IF ANY:
[NAME OF CONTRACTOR/SUBCONTRACTOR: (CPECC/MFCO
‘Our request the inspection of the following works for certficate/witness that all tems has been properly executed
accordance with approved procedures, specifications, drawings and all items has been coordinated with future works.
DISCRIPTION OF WORK TO BE WITNESS:
‘Sampling the backfilling second layer around the tank foundation for the purpose of compaction degree test in
DS8 have been completed today 22-4-2017, Witness conducting the test.
‘COMMENTS:
Claccertep Dacceptep WITH COMMENTS | Giresecteo
Giwork is not ready
Clunacceptable inspection result
Ose comments
Tick THIS 60x IF “NO” EMIL / SOC and ifit isa “WITNESS” as per ITP,
(by ticking this box means CPECC needs to produce all the related documents and sign / close this IR)
SIGNATURE FOR NOTIFICATION/ ACKNOWLEGEMENT
SUBCONTRACTOR PEC COMPANY OTHERS
PRINT NAME: PRINT NAME: PRINT NAME PRINT NAME
Me Gry
‘SIGNATURE:
«S
DATE:ExonMobil
Ect
West Qurna | Form No. F70102Q
‘Contract:AWQ0109 Rev. 0
Project Location: Basra, Iraq Serial No.
QUALITY CHECKSHEET - FIELD COMPACTION TEST RECORD.
Tag Description [ SLEEPER Tag No. | Dss/mi109 ‘|
Contract No. ‘AWQOI09 System No.
| Contractor cPEcc. ‘Sub-System No.
Drawing Reference | IQVO-CHTOSI-CDIND DET ton ss
1QWe-FT-NSPDS-00-
1QWO-CEIO91-CDEND-DS- 040901 REV. 22147201
Drawing No, _O001 Specification No. _EARTHWORK TestDate _7
[peer Lif Thickness Min, Compaction Required: 92%
Laboratory Standard
20a
Type Date 2017 _ Max. Density Optimum Moisture
Field Test Equip:
Type SIN Correction Factor a
Te] Hominy] Monae pasion | Fea?
Location Sketch no [Toate | MN | poet | ORM | 4S
1 (S| 1433] 4 [ec
2 (6 |[-62] 9g [cc
3
4
6
Comments:
Contractor/Construction Rep. Contractor/Quality Rep. Company Rep.
Name: name: Mer Gees Kane Hameed AL
Signe Some? Slope C2
Date: Date: 7 8-4 - Jot Date:
*PLitAL FAO COMPANY.
FOR ENGINEERING TESTING
gol SNG5jib .
(cUBNI RA Wiesw) us] U fonmtons)
NO: 947
Date: 11/02/2017
Fao Code:738/17
‘yo\China Petroleum Engineering & Construction Corporation
Sub\ Test Report (Re-Compaction of Soil)
Information requested test :
No. @ Date of test request ‘Area Location Executing company
CE-C0027@ 05 -02-2017 DS-6 CPECC/MADAR
‘Test date : 09 -01-2017
Result:
No. | Moisture content (%) | Dry Density (gm/em") | Compaction Degree (%)
1,785 9o7
17 | 1.755 95
‘Max dry density (gm /em') 1.842
‘Optimum moisture content (%) 15.2
Notes: The test for M.D.D done according to(ASTM D 1557-002), and for soil test according to (D2937-07).
= The result represents sample tested only.
~The Sample brought and received by Mr: (
A « Executive Manager
Ablam Almansor
Shere M. Abass
FP13-04