Sei sulla pagina 1di 4

Cisco Power Calculator -Power Results

Disclaimer: The Cisco Power Calculator is intended to be an educational resource and a starting point in
planning your power requirement; it is not a final recommendation from Cisco. This tool does not check for software
compatibility. To determine the power requirements and software most appropriate for your company we suggest you work
with a Cisco representative, Cisco channel partner or a solutions provider.

Product Family:Cisco ASR 900

Power Consumption/Heat Dissipation Summary


Slot Line Card
RSP A900-RSP3C-400-S
Redundant RSP A900-RSP3C-400-S
IM0 A900-IMA4OS
IM1 A900-IMA4OS
IM2 A900-IMA8S1Z
IM3 A900-IMA8S1Z
IM4 A900-IMA8S1Z
IM5 A900-IMA8S1Z

Power Supply Options Percentage Of Power Used


Two DC 550W Power supplies required with no redundancy 61.45 %

Two DC 1200W Power supplies required with redundancy 28.17 %

Total Input Current At 48V DC Total power used at 40C Total power used at 25C Total Heat Dissipation At 40C

15.65 Amps 676.00 Watts 546.00 Watts 2305.16 BTU/Hr


NOTE :

Total Input Current - Total Input Current (amperes) allocated to the line cards and powered devices in the chassis.

Total Power Used At 40C - Total power (P-Output) that the systems require from the power supply. From the power supply perspective, this is the
power out (P-output).

Total Power Used At 25C - Power used at 25C ambient temperature with full linerate IMIX traffic.

Total Heat Dissipation At 40C - Heat dissipation is a direct function of power used. To get heat in BTU/hr, multiply the power draw in watts by 3.41.
Example the power calculator says that a given system draws 2800W. This means the system dissipates (2800*3.41 -->9548 BTU/hr)of heat.

Percentage of Power Used is color-coded with green if the power consumption is up to 80 percent, orange if the power consumption is between 81
and 90 percent, and red if between 91 and 100 percent.

Quick Facts
Selected RSP/RP ASR-903
Selected Supervisor Engine A900-RSP3C-400-S
Selected Voltage 48V 1200W DC PSU
Selected FanTray A903-FAN-E
Chassis Slots 11
Power Supply Options Two DC 550W Power supplies
required with redundancy
Two DC 550W Power supplies
required with no redundancy
Two DC 1200W Power supplies
required with redundancy
Interface Module Slots 6
Rack Units 3
Configuration Details
Slot Line Card Input Current(A) Power Used At Power Used At Heat Dissipation Power Used At Heat Dissipation
On 48V DC Input 25C (W) 40C (W) At 40C(BTU/Hr) MAX At MAX
Temperature(W) Temperature(BT
U/Hr)
SYSTEM-FAN A903-FAN-E 0.00 28.0 80.00 272.80 80.00 272.80
RSP A900-RSP3C- 0.00 205.0 225.00 767.25 240.00 818.40
400-S
Redundant RSP A900-RSP3C- 0.00 205.0 225.00 767.25 240.00 767.25
400-S
IM0 A900-IMA4OS 0.00 24.0 25.00 85.25 26.00 88.66
IM1 A900-IMA4OS 0.00 24.0 25.00 85.25 26.00 88.66
IM2 A900-IMA8S1Z 0.00 15.0 24.00 81.84 29.00 98.89
IM3 A900-IMA8S1Z 0.00 15.0 24.00 81.84 29.00 98.89
IM4 A900-IMA8S1Z 0.00 15.0 24.00 81.84 29.00 98.89
IM5 A900-IMA8S1Z 0.00 15.0 24.00 81.84 29.00 98.89
Input Current(A) Power Used At Power Used At Heat Dissipation Power Used At Heat Dissipation
On 48V DC Input 25C(W) 40C(W) At 40C(BTU/Hr) MAX At MAX
Temperature(W) Temperature(BT
U/Hr)
Total 15.65 546.00 676.00 2305.16 728.00 2431.33
Power Supply Details At 40C
Power Supply Options Percentage of Power used Max load current allowed on Load current on this PSU Load current remaining on
this PSU configuration configuration @48V this PSU configuration
@48V @48V
Two DC 550W Power 61.45 % 25.46 15.65 9.81
supplies required with no
redundancy
Two DC 1200W Power 28.17 % 55.56 15.65 39.91
supplies required with
redundancy

NOTE :

Power used and Heat Dissipation numbers computed by the Cisco Power Calculator are maximum values and can be used for facility power and
cooling capacity planning. These figures are not indicative of the actual power draw or heat dissipation. Typical power draw is about 30% lower than
the maximum value shown.