Technology and the research created the straight-way to- Electronic expansion devices on all units as standard.
wards innovation: Welcome to SyScrew Air. Compressors box is standard on all units – internal sound-
A completely new generation of modern Systemair Air proofing for Super Low Noise (SLN) version.
Cooled Chiller which were developed and built consist- High Temperature (HT) for high operating limits. The ver-
ently according to the market target: “For Air Conditioning sion is equipped with axial fans of large diameter (elec-
and Industrial process applications with lowest environ- tronic brushless type motor-EC).
ment impact”. In SyScrew Air range, all this has become External electrical box to improve internal aerodynamic
possible thanks to a new modular concept, equipped with (more air flow; which increases heat rejection by the
new microchannel coils, optimized screw compressors coils).
and advanced control. Hydro kits without buffer tank but with pump(s) only, fit-
SyScrew Air is Experience and Technology. ted on board of the chiller to perform outstandingly the
package solution and the plug & play concept.
New Microchannel coils. Polar version for application with low air temperature
High efficiency shell and tube counter flow evaporator. -18°C.
All the versions keep the same configuration of the base Brine version for application with low water tempera-
units (same structure, electrical board, compressors and ture below 0°C.
coils).
4 | SyScrew 360-1300 Air
-
CO
-
TR HT L
Sy Screw SIZES Air - FC*
HPF
Specifications 4P*
BC EC
S
General
The new units have been designed to operate with R134a HPF (High Pressure Fan) version: It has same equipment
refrigerant. All components have been optimized for this as STD units, except that the units are equipped with
refrigerant. Each unit consists of two independent refrig- special inverter fans driven by EC motors with integrated
erant circuits complete with screw compressors and one electronic inverter. The HPF version provides external
double circuit pure counterflow shell and tube heat ex- static pressure up to 120 Pa. This version can be sup-
changer. The condenser section is complete with new mi- plied with acoustic option only.
crochannel finned coils, of monobloc type, and new opti-
mized fan deck. All the units are equipped with electronic Also, 2 heat recovery options are available:
expansion valves, one for each circuit. Desuperheater: All the versions can be supplied with
The units are available in 19 sizes, with a nominal capacity plate type heat exchangers fitted, one on each refriger-
range from 360 to 1300 kW. ant circuit, on the compressor discharge line to recover
about 20 % of the total heat rejected to the condensers.
The version can be supplied with 3 acoustic options: Totaly Heat Recovery: The versions of the cooling only
Basic Low Noise (-): The units are equipped with delta units can be supplied with suitable heat exchanger ( dou-
connected fan motors. The chillers are not supplied with ble circuit plate or S&T type) to recover 100 % of heat
fan speed controller, but fitted with compressors box to rejection by the condensers. 4-way valves and a field
reduce the noise emissions. installed control sensor are also provided to ensure the
Low Noise (L): The units are equipped with star con- cooling/heat recovery mode changeover.
nected fan motors. The chillers are not supplied with fan
speed controller, but fitted with compressors box to re- Special Versions
duce the noise emissions. Polar Version: Special version with Electronic fans and
Super Low Noise (S): The units are equipped with star dedicate devices on refrigeration system allow the units
connected fan motors, fitted with a speed controller to operate at ambient temperature down to -18°C.
which allows the units to operate with a very low rpm. Brine Version: Special Version with dedicate devices on
The chillers are supplied with acoustically insulated (SLN) refrigeration system allow the units to operate with brine
compressors box and flexible pipes as well as mufflers ( ethylenic or propylenic glycol) down to -8°C.
on compressor discharge lines.
Cabinet and structure
In addition to the Standard version, the ranges offer 2 The unit cabinet and structure are made of heavy gauge
more versions: galvanized steel. All the galvanized steel components are
HT (High Temperature) version: It has same equipment individually painted, with a polyester powder based paint-
as that of the Standard version, except that the units are ing (RAL 7040), under a special painting process before the
equipped with special inverter fans, of large diameter, assembly of the unit. This painting system performs and
driven by EC (electronic brushless type) motors with in- stands a homogeneous protection of the corrosion.
tegrated electronic inverter. The HT version can be sup- All parts of the structure are totally fastened with stainless
plied with Basic Low Noise acoustic option only. steel bolts and rivets.
SyScrew 360-1300 Air | 5
It permits the integration of the unit with BMS with Bacnet protocol
Bacnet protocol kit for BMS Option BAC
trough RS485 port.
8 | SyScrew 360-1300 Air
Interface Kit ethernet/webctrl pcos It permits the integration of the unit with BMS with Modbus or
Option
(Modbus & Bacnet already included) Bacnet protocol trough Ethernet port (TCP/IP).
An electronic device that automatically starts up the compressors
Softstarter for compressor Option SS gradually. The starting current can be reduced by up to 40% of the
direct on line value.
Electronic speed controllers are designed to control the speed
of fan motors in Air Cooled Chiller and Heatpump. Fan Speed
controlled by Condensing Pressure in cool mode or by Air Temp in
Low ambient kit
Option FSC heat mode. Using variable fan speed controllers offers following
(pressostatic stepless fan speed control)
benefits in commercial refrigeration or air-conditioning applications
High Efficiency, Low Noise level, Low air temperature in cool mode
and High air temperature in heat mode.
Can manage two different applications (set point) selected by
Double set point Std DSP remote dry contact Circuit 1 and Circuit 2.
On/Off or Part Load by remote Dry contact.
The purpose of the power factor corrector capacitor is to minimize
the input current distortion and make the current in phase with the
Power factor corrector capacitors Option PFC
voltage. Target is to keep Power Factor about 0.90 in any running
condition.
Pressure gauges that display the operating pressure in the high and
Mechanical gauges kit (HP and LP manometers) Option KM
low pressure sections of the refrigerant circuit.
Accessories are loosed and to install in the field. Options are mounted in factory.
SyScrew 360-1300 Air | 9
EN 14511-2011
Starting 2012 Campaign Eurovent Certification Company took decision to start certify only performances declared in ac-
cording severe European Standard EN14511.
BEFORE 2012: GROSS PERFORMANCES
Before this date all capacity performances are declared, measured and certified by Eurovent, as GROSS performances.
COOLING or HEATING CAPACITY was rated without taking in account the negative contribution of the heat exchanger Pres-
sure Drop or the positive contribution of the Head Available prevalence in example.
OWER INPUT was rated as pure sum of all power input contribution from all motors fitted on the unit. Without taking in
account the correction due to power spent to win the exchanger Pressure Drop in example.
AFTER 2012: NET PERFORMANCES
After this date all data are certified according EN14511. Mainly consequences in example on Water chiller or heatpump are:
COOLING or HEATING CAPACITY is now rated taking in account the negative contribution of the heat exchanger Pressure
Drop or the positive contribution of the Head Available prevalence in example. In case of Water to Water unit, in example,
both exchanger Pressure Drop values are taken in account in the formula.
POWER INPUT is now rated as all power input contribution from all motors fitted on the unit taking in account also the
correction due to power spent to win the exchanger Pressure Drop in example.
As an important consequence of these new rules setted by Eurovent is that EER, COP and ESEER are also affected by
these correction. All efficiency index are now calculated, measured and certified according new rules setted by Eurovent
according EN14511.
Where:
Ph = NET heating capacity.
Pc = NET cooling capacity.
Pe = electrical power input.
Phm = is the gross heat capacity, expressed in Watts.
Pcm = is the gross cool capacity, expressed in Watts.
qwi = is the nominal liquid flow rate.
Δpe,wi = is the measured available external static pressure.
Δpi,wi = is the measured internal static pressure difference.
ηpi = is the efficiency of the pump.
Reference: Guidelines for the declaration of performances according to EN14511:2011 (available a copy upon request for
Syste mair customer).
10 | SyScrew 360-1300 Air
S A A AT
5
9
G
2
S B BT
6
S D
5
EXV UNIT
CONTROL CONTROL
E
4 3
F
Note: For reasons of readability, one circuit only is shown. The second circuit is identical.
SyScrew 360-1300 Air | 11
G
AT 2
S A A
5
7 D
5
S
8
3
9
10
13
H
1
S
S B 12
BT
6
11
S
EXV
CONTROL
UNIT
CONTROL
F 4
Operating Limits
40 40
30 30
T Air (°C)
T Air (°C)
20 20
14 2 1 14 2 1
10 10
0 0
4 3 4 3
-10 -10
16 15 16 15
-20 -20
-10 -5 0 5 10 15 -10 -5 0 5 10 15
LWT (°C) LWT (°C)
1 Water. 1 Water.
2 Water + Glycol. 2 Water + Glycol.
3 Water + FSC. 3 Water + FSC.
4 Water + Glycol + FSC. 4 Water + Glycol + FSC.
14 Brine Version. 14 Brine Version.
15 Polar Version. 15 Polar Version.
16 Polar + Glycol. 16 Polar + Glycol.
1 + 2 Standard unit. 1 + 2 Standard unit.
S Version HT Version
50 50
40 40
30 30
T Air (°C)
T Air (°C)
20 20
14 2 1
10 14 2 1 10
0 0
-10 -10
16 15 16 15
-20 -20
-10 -5 0 5 10 15 -10 -5 0 5 10 15
LWT (°C) LWT (°C)
1 Water. 1 Water.
2 Water + Glycol. 2 Water + Glycol.
14 Brine Version. 14 Brine Version.
15 Polar Version. 15 Polar Version.
16 Polar + Glycol. 16 Polar + Glycol.
1 + 2 Standard unit. 1 + 2 Standard unit.
Fouling factors
EVAPORATOR CONDENSER
Fouling factor Cooling capacity Power input Fouling factor Cooling capacity Power input
(m2.°C/kW) factor factor (m2.°C/kW) factor factor
0.044 1.000 1.000 0.044 1.000 1.000
0.088 0.987 0.995 0.088 0.987 1.023
0.176 0.964 0.985 0.176 0.955 1.068
0.352 0.915 0.962 0.352 0.910 1.135
Altitude factors
Altitude (m) Cooling capacity factor Power input factor
0 1.000 1.000
600 0.987 1.010
1.200 0.973 1.020
1.800 0.958 1.029
2.400 0.943 1.038
SyScrew 360-1300 Air | 15
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
16 | SyScrew 360-1300 Air
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
SyScrew 360-1300 Air | 17
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
18 | SyScrew 360-1300 Air
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
SyScrew 360-1300 Air | 19
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
20 | SyScrew 360-1300 Air
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
SyScrew 360-1300 Air | 21
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
22 | SyScrew 360-1300 Air
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
SyScrew 360-1300 Air | 23
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
24 | SyScrew 360-1300 Air
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
SyScrew 360-1300 Air | 25
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
26 | SyScrew 360-1300 Air
(1) Cooling mode conditions: evaporator EWT/LWT 12°C/7°C, condenser OAT 35 °C.
(2) GROSS value (without hydraulic contribute).
(3) NET value - According to standard EN 14511-3:2011.
(4) Sound power levels refers to standard ISO 3744 and Eurovent 8/1 for units certified - Units at fully loaded conditions.
(5) Sound pressure levels refers to unit in free field on refletive surface at 10 m - Values derived from sound power levels (standard ISO 3744 with parallepiped shape).
SyScrew 360-1300 Air | 27
L/S Version 360 410 450 480 500 540 580 650 720 800 850 910 970 1000 1070 1130 1170 1200 1300
Current Nominal A 199 220 247 267 282 302 321 353 377 398 440 477 506 521 549 578 617 662 706
input Maximum A 337 342 362 396 410 430 450 454 520 646 661 671 713 675 717 760 815 938 942
Power Nominal kW 119 133 147 155 163 175 187 208 226 243 265 284 302 312 330 348 371 392 422
input Maximum kW 199 201 215 239 249 261 274 276 300 364 395 424 443 426 446 465 498 577 579
Max Start-up current A 598 603 637 762 776 795 542 546 676 801 927 937 1.003 941 1.007 1.050 1.207 1.408 1.412
UNIT (aM) FUSES A 400 400 400 500 500 500 500 500 630 800 800 800 800 800 800 1.000 1.000 1.250 1.250
2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x
Phase WIRE SECTION mm2
120 120 120 185 185 185 185 185 240 300 300 300 300 300 300 400 400 400 400
HT/HPF Version 360 410 450 480 500 540 580 650 720 800 850 910 970 1000 1070 1130 1170 1200 1300
Current Nominal A 214 241 268 287 303 325 347 384 409 430 476 513 545 563 594 624 666 714 764
input Maximum A 353 362 382 416 430 453 476 486 552 678 697 707 752 717 762 806 864 990 1.000
Power Nominal kW 131 148 163 171 179 193 207 232 249 267 292 311 331 343 363 383 409 431 464
input Maximum kW 211 217 231 255 265 279 293 299 323 387 422 451 473 458 479 500 535 616 622
Max Start-up current A 614 623 657 782 796 818 568 578 708 833 963 973 1.042 983 1.052 1.096 1.256 1.460 1.470
UNIT (aM) FUSES A 400 400 400 500 500 500 500 500 630 800 800 800 800 800 800 1.000 1.000 1.250 1.250
2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x 2x
Phase WIRE SECTION mm2
120 120 120 185 185 185 185 185 240 300 300 300 300 300 300 400 400 400 400
30 | SyScrew 360-1300 Air
- Version
360 104 99 97 94 90 85 83 75 96 64
410 105 100 98 95 91 86 84 76 97 65
450 105 100 98 95 91 86 84 76 97 65
480 105 100 98 95 91 86 84 76 97 65
500 105 100 98 95 91 86 84 76 97 65
540 106 101 99 96 92 87 85 77 98 66
580 106 101 99 96 92 87 85 77 98 65
650 107 102 100 97 93 88 86 78 99 66
720 107 102 100 97 93 88 86 78 99 66
800 107 102 100 97 93 88 86 78 99 66
850 108 103 101 98 94 89 87 79 100 67
910 108 103 101 98 94 89 87 79 100 67
970 108 103 101 98 94 89 87 79 100 67
1000 108 103 101 98 94 89 87 79 100 67
1070 108 103 101 98 94 89 87 79 100 67
1130 109 104 102 99 95 90 88 80 101 68
1170 109 104 102 99 95 90 88 80 101 68
1200 109 104 102 99 95 90 88 80 101 68
1300 110 105 103 100 96 91 89 81 102 69
L Version
360 98 93 91 88 84 79 77 69 90 58
410 99 94 92 89 85 80 78 70 91 59
450 99 94 92 89 85 80 78 70 91 59
480 99 94 92 89 85 80 78 70 91 59
500 99 94 92 89 85 80 78 70 91 59
540 100 95 93 90 86 81 79 71 92 60
580 100 95 93 90 86 81 79 71 92 59
650 101 96 94 91 87 82 80 72 93 60
720 101 96 94 91 87 82 80 72 93 60
800 101 96 94 91 87 82 80 72 93 60
850 102 97 95 92 88 83 81 73 94 61
910 102 97 95 92 88 83 81 73 94 61
970 102 97 95 92 88 83 81 73 94 61
1000 102 97 95 92 88 83 81 73 94 61
1070 102 97 95 92 88 83 81 73 94 61
1130 103 98 96 93 89 84 82 74 95 62
1170 103 98 96 93 89 84 82 74 95 62
1200 103 98 96 93 89 84 82 74 95 62
1300 104 99 97 94 90 85 83 75 96 63
(*) Sound pressure level at 10 m.- Values refers to Standard UNI EN ISO 3744 with parallepiped shape.
SyScrew 360-1300 Air | 31
S Version
360 94 89 87 84 80 75 73 65 86 54
410 95 90 88 85 81 76 74 66 87 55
450 95 90 88 85 81 76 74 66 87 55
480 95 90 88 85 81 76 74 66 87 55
500 95 90 88 85 81 76 74 66 87 55
540 96 91 89 86 82 77 75 67 88 56
580 96 91 89 86 82 77 75 67 88 55
650 97 92 90 87 83 78 76 68 89 56
720 97 92 90 87 83 78 76 68 89 56
800 97 92 90 87 83 78 76 68 89 56
850 98 93 91 88 84 79 77 69 90 57
910 98 93 91 88 84 79 77 69 90 57
970 98 93 91 88 84 79 77 69 90 57
1000 98 93 91 88 84 79 77 69 90 57
1070 98 93 91 88 84 79 77 69 90 57
1130 99 94 92 89 85 80 78 70 91 58
1170 99 94 92 89 85 80 78 70 91 58
1200 99 94 92 89 85 80 78 70 91 58
1300 100 95 93 90 86 81 79 71 92 59
HT Version
360 110 105 103 100 96 91 89 81 102 70
410 111 106 104 101 97 92 90 82 103 71
450 111 106 104 101 97 92 90 82 103 71
480 111 106 104 101 97 92 90 82 103 71
500 111 106 104 101 97 92 90 82 103 71
540 112 107 105 102 98 93 91 83 104 72
580 112 107 105 102 98 93 91 83 104 71
650 113 108 106 103 99 94 92 84 105 72
720 113 108 106 103 99 94 92 84 105 72
800 113 108 106 103 99 94 92 84 105 72
850 114 109 107 104 100 95 93 85 106 73
910 114 109 107 104 100 95 93 85 106 73
970 114 109 107 104 100 95 93 85 106 73
1000 114 109 107 104 100 95 93 85 106 73
1070 114 109 107 104 100 95 93 85 106 73
1130 115 110 108 105 101 96 94 86 107 74
1170 115 110 108 105 101 96 94 86 107 74
1200 115 110 108 105 101 96 94 86 107 74
1300 116 111 109 106 102 97 95 87 108 75
(*) Sound pressure level at 10 m.- Values refers to Standard UNI EN ISO 3744 with parallepiped shape.
32 | SyScrew 360-1300 Air
1000
1300
100
410-480 1170-1200
500-540 650-720 1070-1130
10
10000 100000 1000000
(l/h)
SyScrew 360-1300 Air | 57
100
500-580 850-970
450-480 1000-1070
1200-1300
(kPa)
10
1130-
360-410 650-800 1170
1
1000 10000 100000 1000000
(l/h)
58 | SyScrew 360-1300 Air
Hydro options
Available Pressure (Low head - Pump “A” & “B”) Models 360-580
400
500-540-580
350
480
Avaliable Static Pressure [kPa]
300 410-450
360
250
200
150
100
50
0
30000 40000 50000 60000 70000 80000 90000
Water Flow [l/h]
Available Pressure (Low head - Pump “C” & “D”) Models 650-1070
350
300
Avaliable Static Pressure [kPa]
250
200
150
100
1070
850-910 970-
800
50 650-720 1000
0
90000 110000 130000 150000 170000 190000 210000
Water Flow [l/h]
60 | SyScrew 360-1300 Air
300
Avaliable Static Pressure [kPa]
250
200
150 1300
100
50 1130-1170-1200
0
50000 100000 150000 200000 250000 300000
Water Flow [l/h]
350
300
Avaliable Static Pressure [kPa]
410
250 360
200
150
100
50
0
30000 40000 50000 60000 70000 80000 90000
Water Flow [l/h]
SyScrew 360-1300 Air | 61
Available Pressure (High Head - Pump “G” & “H”) Models 450-720
450
400 650-720
350
Avaliable Static Pressure [kPa]
300
450-480
250
200
500-540-580
150
100
50
0
40000 50000 60000 70000 80000 90000 100000 110000 120000 130000 140000
Water Flow [l/h]
Available Pressure (High Head - Pump “I” & “J”) Models 800-1070
500
450 1070
400 910
Avaliable Static Pressure [kPa]
350
300
250
200
150
100 970-
1000
50 850
800
0
90000 110000 130000 150000 170000 190000 210000
Water Flow [l/h]
62 | SyScrew 360-1300 Air
400 1300
Avaliable Static Pressure [kPa]
350 1130-1170-1200
300
250
200
150
100
50
0
50000 100000 150000 200000 250000 300000 350000
Water Flow [l/h]
SyScrew 360-1300 Air | 63
Weights Distributions
Accessories Weights
L
L
M
2550
M
2550
E B
F E B
F
L2 L1
440
L2 L1
440
366 3496 LIFT 366
366 3496 LIFT
4228 366
4228
4641
4641
NOTES
Water connections 360 410-500
B E Water connection
F Electrical power supply H 440 440
L Main switch L1 722 725
M Control keypad / display L2 2.410 2.410
STD B E
B-E 360/5” 410-400/6”
1P/2P 5” 6”
Desuperheaters 2” 2”
66 | SyScrew 360-1300 Air
L
L
2550
M
2550
2410 1400
2410 1400
E B
E B
F
F
LIFT
LIFT
366
366 440
440 1918
1918
712
712
1918
1918
366
366
5280
5280
5693
5693
832
832
2192 2630 1918
2192 2630 1918
NOTES
Hydraulic option Water in Water out
B E Water connection
F Electrical power supply STD B E
L Main switch B-E 6” 6”
M Control keypad / display 1P/2P t.b.d. t.b.d.
Desuperheaters 2” 2”
SyScrew 360-1300 Air | 67
L
L
2550
M
2550
E B
E B
F
F L2
L2 L1
HH
L1
LIFT/AVM 799 2537 712 1918 366
LIFT/AVM 799 2537 6332 712 1918 366
6332
6744
6744
323
323
2192
2192
NOTES 650-720-
Water connections 580
B E Water connection 800
F Electrical power supply H 440 480
L Main switch L1 2.852 2.881
M Control keypad / display L2 2.410 2.360
STD B E
B-E 6” 6” (800 8”)
1P/2P t.b.d. t.b.d.
Desuperheaters 2” 2”
68 | SyScrew 360-1300 Air
L
2550
E B
F
H
L
2550
M L2 L1
LIFT/AVM 799 2537 2104 2630 366
8436
E 8850 B
F
H
L2 L1
LIFT/AVM 799 2537 2104 2630 366
8436
Back view Top view
8850
2082 AVM
2082 AVM
323
2192
323
2192
NOTES
Water connections 850-910 970-1000
B E Water connection
F Electrical power supply H 480 530
L Main switch L1 3.344 3.379
M Control keypad / display L2 2.360 2.860
STD B E
B-E 8” 8”
1P/2P 8” 8”
Desuperheaters 2” 2”
SyScrew 360-1300 Air | 69
L
2550
E B
F
530
2310 3818
L
LIFT/
2550
2310 3818
LIFT/
AVM 366 2630 3496 2630 366
9488
9900
376
2192
376
2192
NOTES
Hydraulic option Water in Water out
B E Water connection
F Electrical power supply STD B E
L Main switch B-E 8” 8”
M Control keypad / display 1P/2P 8” 8”
Desuperheaters 2” 2”
70 | SyScrew 360-1300 Air
L
2550
E B
F
530
2310 3820
AVM/
L LIFT 799 3249 3496 2630 366
10540
2550
M
12000
E B
F 530 2310 3820
AVM/
LIFT 799 3249 3496 2630 366
10540
12000
374
2082 AVM
2192
374
2192
NOTES
Hydraulic option Water in Water out
B E Water connection
F Electrical power supply STD B E
L Main switch B-E 8” 8”
M Control keypad / display 1P/2P 8” 8”
Desuperheaters 2” 2”
SyScrew 360-1300 Air | 71
L
2550
M
E B
F 2310 3820
530
AVM/
LIFT 366 4022 2816 4022 366
11592
12000
L
2550
M
E B
F 2310 3820
530
2082 AVM
AVM/
LIFT 366 4022 2816 4022 366
11592
Back view Top view
12000
374
2192
2082 AVM
374
2192
NOTES
Hydraulic option Water in Water out
B E Water connection
F Electrical power supply STD B E
L Main switch B-E 10” 10”
M Control keypad / display 1P/2P 10” 10”
Desuperheaters 2” 2”
72 | SyScrew 360-1300 Air
Space Requirements
>2000 mm >2000 mm
>2000 mm >2000 mm
>3000 mm
Notes
Notes
Italy
Systemair srl
info@systemair.it
Via XXV Aprile, 29
www.systemair.com
20825 Barlassina (MB)