Laminar-Flow Plenum Box

Description:
The operating theatre ceiling is the most important part of a hospital ventilation system. Also called UCVS (Ultra
Clean Ventilation System), these sophisticated systems are actually a combination of a variety of elements,
including gas tight welded pressure chambers, air filter housings or filter grids, HEPA filters, priming illumination
and air diffusers.
• Laminar Flow Ceiling for Operating Theatres
• to produce a germ- and particle lean area through an unidirectional air flow.
• The system is specially designed and suited for the use in Operating Theatres.
• The requirements according to DIN 1946-4:2008-12 are fulfilled.

Technical data:
Pressure Chamber made out of anodized Aluminium.
• Air sealed pressure chamber, made out of • Openings for the supply duct connections
stainless steel (1.4301), material thickness min. • Air sealed housing for the integration of the stand
1,5 mm of the O.T. light and openings for the service of the
• Smooth inner surfaces, therefore easy to clean O.T. light
and disinfect during filter changes • Aerosol port
• Special frame system for the integration of the • Port for pressure drop measurement
filter frames, the pressure chamber, all required • Supply air connections as flange made out of
receptacles of the surrounding air flow stabilizers, stainless steel (1.4301)
Laminar-Flow Plenum Box

Technical data (cont.):


Filter housing • Whole construction to the clean side smooth and
• Lateral attached, air sealed, disinfectant resistant without screws
varnished with connection flange for external duct
installation. Test port for LAF testing
• Mounted outside of the aluminum frame system
Diffuser- Frame with test connection for DEHS testing and
• Frame made out of anodized Aluminum profile for pressure drop, varnished RAL 9016.
the placement of the CG-Diffuser and has rails
for the easy and seamless placement of the false Technical Data:
sealing or other connecting equipment. • Air volume (in flow) 4760 m³/h
• The Aluminum profile is prepared for the integration • Outer dimension (length x width) 2400 x 2400
of the sterile field and O.T.-illumination, when mm
combined with the optional rail system for the O.T. • Sterile air-flow field (length x width) 2298 x 2298
illumination. mm
• Height of pressure chamber (height) 495 mm
HEPA Filters • Height of available ceiling space (minimum
• Integrated HEPA Filter-Cells with a frame made requirement) 550 mm
out of galvanized sheet steel • Average air velocity 0,25 m/s
• Optimized standard dimensions • Number of HEPA filters/Type 4 pcs. 305 x 610
• Extremely high filter surface for low initial pressure mm
drops • Filter Class according to EN 1822: H13
• EPDM profile gasket • Initial pressure drop 160 Pa
• Change of filters to the clean side • Recommended max. pressure drop before filter
change 600 Pa
Sterile Air Diffuser CG • Filter surface per m² face area 18,5 m²
• Transparent diffuser with double layer micro mesh,
made out of specialized textile Norms:
• Assembly and disassembly without screws or • DIN 1946-4
tools
• Air-flow optimized frame made out of Aluminum
profile
• Pass through of the stand of the O.T. light