Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
ADAMO II
Split System
High-Wall Type
MCW Series 50 Hz
2 MS-SVN003-EN
Contents
General Information 2
Typical Installation 4
Location and Preparation of Unit 5
Unit Installation 6
Wiring Diagram 12
Dimensional Data 13
Notes 14
MS-SVN003-EN 3
Typical Installation
3 ON
OFF
7 12
1. Wireless Remote Control
2 2. Air Filter
8 3. Evaporator Coil
4. Front Cover
5. Installation Plate
6. Front Panel
Remote Control Holder 7. Control Switch
8. Horizontal Vane
9. Bind Tape
10. Drain Pipe
11. Two AAA Baterries
12. Nano Filter
1
9
11
10
Condensing Unit
Installation Items
The following items are supplied with the
indoor unit to provide proper system
installation:
1 Installation
: Plate : For indoor unit
installation
4 Tapping Screw (Large) : For wall
bracket installation
2 Tapping Screw (Small) : For remote
control mounting bracket installation
1 Remote Control Holder : For remote
control unit holder
Figure 1
4 MS-SVN003-EN
Location and Preparation of Unit
General Instructions • For the air conditioning system to Selecting the Mounting
• All phases of the installation of this operate properly and reliably, it
must be installed in accordance
Locations
air conditioning system must
with these instructions. Determine the mounting location with
conform to all national, provincial,
• The maximum length of the piping the customer as follows:
state and local codes.
• Read these instructions carefully is to10 meters. If the units are
and completely before attempting further apart than this, correct Indoor Unit
to install the air conditioning operation can not be guaranteed. • Install the indoor unit level on a
system. strong wall which is not subject
to vibration.
• The inlet and outlet ports should
100 mm 100 mm not be obstructed. The air should
be able to blow throughout the
150 mm
150 mm
room.
• Install the indoor unit where
connection to the outdoor unit
can be made easily.
• Install the unit where the drain pipe
can be easily installed.
• Take servicing into consideration
and leave the spacing shown in
Figure 2. Also, install the unit where
the filter can be easily removed.
• Do not install the unit near a source
500 mm or more from eye level 500 mm or more from eye level
of heat, steam, or flammable gas.
• Do not install the unit where it will
Floor level be exposed to direct sunlight.
120 cm or more
Figure 3
MS-SVN003-EN 5
Unit Installation
Indoor Unit Installation 2. Drilling the Hole in the Wall 4. For 1 left piping and 4 right
The piping can be connected in the for the Connecting Piping piping, drill the hole sligthly lower
five directions indicated by 1, 2, 3, 1. Drill a 65 mm diameter hole in so that the condensate water will
and 4 in Figure 4. When the piping is the wall at the desired position flow freely.
connected in direction 1, 2, or 4 cut shown in Figure 6.
along the piping groove in the side or
bottom of the base pan with a saw.
(Rear)
4. Left
outlet MCW509-512
1. Right
outlet 3. Rear outlet
2. Bottom
outlet
Figure 4
6 MS-SVN003-EN
Cut the piping groove
Cut the piping groove
with a hacksaw
with a hacksaw
Decorative tape
Right piping
Bottom piping
Left rear piping
For left outlet, house the connection cord
and piping at the position shown in the above
figure with the drain hose at the bottom. Drain hose Wall hole
Connection pipe
Drain hose cable
Figure 7 Figure 10
4. Install the piping so that the drain 5. After passing the indoor piping Indoor Unit Wiring
hose is at the bottom (Figure 7). and drain hose through the wall Both of the cable wires should be
hole, hang the indoor unit on the connect from the terminal block
Caution hooks at the top and bottom of of indoor unit (Figure 11).
• To prevent breaking of the pipe, the wall bracket.
avoid sharp bends. Bend the 6. Check to insure that: (Ref.
pipe with a radius of curvature of Figure 10).
100 mm or more. • The top and bottom hooks are
• If the pipe is bent repeatedly at the hooked firmly and the indoor unit
same place, it will break. does not move to the front and
• Do not remove the flare nuts rear or left and right.
from the indoor unit pipe • The indoor unit is accurately
immediately before connecting positioned horizontally and
the outdoor connection piping. vertically.
• The drain hose is at the bottom
of the wall hole pipe.
Top
hooks
Figure 8 Figure 9
MS-SVN003-EN 7
Outdoor Unit Installation 3. Remove the flare nut from the 6. If the copper tube is bent or pulled
1. Install the unit mounting pads unit and be sure to mount it on too often, it will become stiff. Do
(4 places) into the bottom channels the copper tube. not bend the pipe more than three
by tapping gently with a plastic or 4. Make a flare at the end of copper times at one place.
rubber tipped hammer. tube with a flare tool (Figure 14,15).
2. Set the unit on a strong surface Cautions before Connecting
such as one made of concrete to Flare nut Tubes Tightly
minimize shock and vibration and 7. Be sure to apply a sealing cap
to locate the unit securely. or water-proof tape to prevent
3. Do not set the unit directly on the dust or water from getting into
ground. the tubes before they are used.
Copper tubing 8. Be sure to apply refrigerant
lubricant to the matching
Connecting the Unit with surfaces of the flare and union
Flaring Procedure. Flare tool before connecting them together.
Flaring (If piping is procured or cut at This is effective for reducing gas
the site). Figure 14 leaks (Figure 16).
Deburring
A good flare should have the
following characteristics:
- Inside surface is glossy and
smooth. Union Flare nut
- Edge is smooth.
- Tapered sides are of uniform Figure 17
length.
Before After
Bending 10. Tighten the flare nut to the
Figure 13 5. When bending the tube, be careful specified tightening torque with
not to crush it. To prevent crushing torque wrench and adjustable
When reaming, hold the tube end of the tube, bend it gently and do wrench (Figure 18).
downward and be sure that no not bend the tube at a radius 11. Repeat the process above for the
copper scraps fall into the tube. curvature of less than 100 mm. remaining line.
8 MS-SVN003-EN
Remote Control Installation Evacuation and Refrigerant
Locate and attach the wireless Charge
remote control as follows: 1. Air Evacuation and Charging
1. Do not place the control and the 1. Remove the cap and connect the
remote control near heat sources gauge manifold and the vacuum
or expose to the direct rays of the pump to the charging port using
Wrench
sun. the service hoses (Figure 20).
Indoor unit pipe (adjustable). 2. Do not expose the control to the 2. Pump the indoor unit and the
indoor unit’s supply air stream. connecting pipes until the
3. Do not place in a confined space. pressure in them lowers to below
4. Attach the remote control holder 1.5 mmHg of vacuum.
as shown in Figure 19. 3. Stop the vacuum pump and close
the gauge manifold valve.
Torque wrench 4. Remove the blanking caps and
Connection pipe
Flare nut fully open the service valves with
a hexagon wrench (Torque: 70
to 90 kgf - cm).
Figure 18
Tapping Screw
(small)
Remote Control Holder
MS-SVN003-EN 9
Refrigerant pipe
Gauge manifold
Service valve
Outdoor Unit
Vacuum
Blank cap pump
Figure 20
10 MS-SVN003-EN
Finishing Run Test Outdoor Unit
1. Securely wrap the connection 1. Start the system and check items 1 5. Is there any abnormal noise and
cable along the refrigerant pipes through 7 below. vibration during operation?
with vinyl tape. (Starting at the 2. For the system start procedure, 6. Will noise, air flow, or drain water
lowest end of the pipes, each refer to the Owner Manual. from the unit disturb the neighbors?
wrap should be about 1/3 of the 7. Is there any refrigerant gas
tape width so that water does Indoor Unit leakage?
not enter).(Figure 22) 1. Is operation of the on and off button
2. Fasten the cable/piping to the and fan button normal? Customer Guidance
outside wall with clamps, etc. 2. Does each indicator on the remote Explain the following to the customer
3. Fill the gap between the outside control display panel light normally? in accordance with the Owner Manual.
wall cap and the pipe with sealer 3. Does the air deflection louver 1. Starting and stopping procedures,
so that rain water and wind cannot operate normally? mode switching, temperature
blow in. 4. Is the condensate drain normal and adjustment, timer and air flow
4. Fasten the drain hose to the outside freely flowing water? adjustment, and other remote
wall, etc (Figure 23 & Figure 24). control operations.
2. Filter removal and cleaning and
how to use the air louvers.
3. Give the operating and installation
manuals to the customer.
Wall
Clamp
Outside wall
cap sealer
Pipe (Outdoor)
Figure 23
Drain hose
Clamp
Lifted up
Wave
End in water
Figure 24
MS-SVN003-EN 11
Wiring Diagram
12 MS-SVN003-EN
Dimensional Data
MS-SVN003-EN 13
Notes
14 MS-SVN003-EN
Notes
MS-SVN003-EN 15
Literature Order Number: MS-SVN003-EN
Date: Jun 2009
Supersedes: Jan 2003
Trane Stocking Location: Bangkok, Thailand
www.trane.com
For more information, contact your local district Trane has a policy of continuous product and product data improvement and reserves the right to change
office design and specifications without notice.