Sei sulla pagina 1di 16

Installation Manual

ADAMO II
Split System
High-Wall Type
MCW Series 50 Hz

50 Hz Models Cooling Only


MCW 509 7B
MCW 512 7B
MCW 518 7B
MCW 524 7B

June 2009 MS-SVN003-EN


General Information

General Information About The Unit Caution


This Installation Manual is given as a These MCW units are assembled, Cautions are provided at appropriate
guide to good practice in the pressure tested, dehydrated, charged places in this manual to indicate to
installation by the installer of MCW and run tested before shipment. The installers, operators, and service
mini-split system. Installation information contained in this manual personnel of potentially hazardous
procedures should be performed in applies to MCW units are designed to situations which, if not avoided, MAY
the sequence that they appear in this operate in cooling mode only. result in minor or moderate injury or
manual. malfunction of the unit.
Trane MCW series offer wall mounted
For installing the unit to operate installation to leave the floor space Your personal safety and the proper
properly and reliably, it must be uncluttered, and equipped with LCD operation of this unit require that you
installed in accordance with these wireless remote control. follow them carefully. The Trane
instructions. Also, the services of a Company assumes no liability for
qualified service technician should be Reception installations or servicing performed by
employed, through the maintenance On arrival, inspect the unit before unqualified personnel.
contract with a reputable service signing the delivery note. Specify any
company. damage of the unit on the delivery Warranty
note, and send a registered letter of Warranty is based on the general
Read this Installation Manual protest to the last carrier of the goods terms and conditions by country. The
completely before installing the within 72 hours of delivery. Notify the warranty is void if the equipment is
air conditioning system. dealer at the same time. modified or repaired without the
written approval of The Trane
About This Manual The unit should be totally inspected Company, if the operating limits are
Cautions appear at appropriate within 7 days of delivery. If any exceeded or if the control system or
places in this Installation Manual. concealed damage is discovered, the electrical wiring is modified.
Your personal safety and the proper send a registered letter of protest to
operation of this machine require that the carrier within 7 days of delivery Damage due to inappropriate
you follow them carefully. and notify the dealer. installation, lack of knowledge or
The Trane Company assumes no failure to comply with the
liability for installations or servicing Warning manufacturer’s instructions, is not
performed by unqualified personnel. Warnings are provided at appropriate covered by the warranty obligation.
All phases of the installation of this air places in this manual to indicate to If the installation does not conform to
conditioning system must conform to installers, operators and service the rules described in Installation
all national, provincial, state and local personnel of potentially hazardous Manual, it may entail cancellation of
codes. situations which, if not avoided, warranty and liabilities by The Trane
COULD result in death or serious Company.
injury.
Important
This document is customer property
and is to remain with unit. Please
place in service information pack upon
completion of work.
These instructions do not cover all
variations in systems, nor do they
provide for every possible contingency
to be met in connection with
installation.
Should further information be desired
or should particular problems arise
which are not covered sufficiently in
this manual, the matter should be
referred to your authorized Trane
dealer.

2 MS-SVN003-EN
Contents

General Information 2
Typical Installation 4
Location and Preparation of Unit 5
Unit Installation 6
Wiring Diagram 12
Dimensional Data 13
Notes 14

MS-SVN003-EN 3
Typical Installation

Fan Coil Unit


6
4

3 ON

OFF

7 12
1. Wireless Remote Control
2 2. Air Filter
8 3. Evaporator Coil
4. Front Cover
5. Installation Plate
6. Front Panel
Remote Control Holder 7. Control Switch
8. Horizontal Vane
9. Bind Tape
10. Drain Pipe
11. Two AAA Baterries
12. Nano Filter
1
9
11
10

Condensing Unit
Installation Items
The following items are supplied with the
indoor unit to provide proper system
installation:
1 Installation
: Plate : For indoor unit
installation
4 Tapping Screw (Large) : For wall
bracket installation
2 Tapping Screw (Small) : For remote
control mounting bracket installation
1 Remote Control Holder : For remote
control unit holder

Figure 1

4 MS-SVN003-EN
Location and Preparation of Unit

General Instructions • For the air conditioning system to Selecting the Mounting
• All phases of the installation of this operate properly and reliably, it
must be installed in accordance
Locations
air conditioning system must
with these instructions. Determine the mounting location with
conform to all national, provincial,
• The maximum length of the piping the customer as follows:
state and local codes.
• Read these instructions carefully is to10 meters. If the units are
and completely before attempting further apart than this, correct Indoor Unit
to install the air conditioning operation can not be guaranteed. • Install the indoor unit level on a
system. strong wall which is not subject
to vibration.
• The inlet and outlet ports should
100 mm 100 mm not be obstructed. The air should
be able to blow throughout the
150 mm

150 mm
room.
• Install the indoor unit where
connection to the outdoor unit
can be made easily.
• Install the unit where the drain pipe
can be easily installed.
• Take servicing into consideration
and leave the spacing shown in
Figure 2. Also, install the unit where
the filter can be easily removed.
• Do not install the unit near a source
500 mm or more from eye level 500 mm or more from eye level
of heat, steam, or flammable gas.
• Do not install the unit where it will
Floor level be exposed to direct sunlight.

Figure 2 Outdoor Unit


• Leave the spacing shown in
Figure 3 for required air flow.
• If possible, do not install the unit
60 cm or more
where it will be exposed to direct
25 cm or more sunlight.
• Do not install the unit near a source
of heat, steam, or flammable gas.
• Do not install the unit where a
strong wind consistently blows or
25 cm or more where it is extremely dusty.
• Do not install the unit where people
30 cm or more pass in front of the fan discharge
grille.

120 cm or more

Figure 3

MS-SVN003-EN 5
Unit Installation

Indoor Unit Installation 2. Drilling the Hole in the Wall 4. For 1 left piping and 4 right
The piping can be connected in the for the Connecting Piping piping, drill the hole sligthly lower
five directions indicated by 1, 2, 3, 1. Drill a 65 mm diameter hole in so that the condensate water will
and 4 in Figure 4. When the piping is the wall at the desired position flow freely.
connected in direction 1, 2, or 4 cut shown in Figure 6.
along the piping groove in the side or
bottom of the base pan with a saw.

(Rear)

4. Left
outlet MCW509-512
1. Right
outlet 3. Rear outlet
2. Bottom
outlet

Figure 4

1. Installing the Wall Bracket


1. Install the wall bracket so that it
is level from side to side. If the
wall bracket is tilted, condensate MCW518-524
water will drip to the floor. Figure 6
2. Install the wall bracket so that it
is strong enough to withstand a 2. Drill the hole so that the outside Caution
weight of 50 kilograms or more. end is lower (5-10 mm.) than the • Always drill the wall hole uniformly
3. Fasten the wall bracket to the inside end. and straight when the wall pipe is
wall with 6 or more screws 3. Cut the wall pipe length to match not used. If the hold center is not
through the holes near the outer the wall thickness, insert it into aligned, condensate leakage can
edge of the bracket. an accessory wall cap, fasten the occur.
4. Check to insure that there is no cap with vinyl tape, and insert the • If the wall pipe is not used, the
rattle of the wall bracket against pipe through the wall hole. (Wall wiring cable connecting the indoor
the wall. pipe and wall cap are procured and outdoor units may become
at the site). frayed and cause electric current
Anchor bolt hole leakage to earth.

Temporary fastening Mounting 3. Forming the Indoor Drain


plate Hose and Refrigerant Pipes
1. For 1 Left piping. 2 Bottom piping,
4 Right piping: Perform.
“Indoor Unit Wiring” before
performing the following steps
3.2 through 3.6.
2. Wrap the pipes of the indoor unit
that are visible from the inside
Screw
with decorative tape (Figure 7).
Thread 3. Insert the indoor unit piping into
the wall hole and bind the drain
Weight hose and pipe together with
Figure 5 Fit the level line
vinyl tape (Figure 8).

6 MS-SVN003-EN
Cut the piping groove
Cut the piping groove
with a hacksaw
with a hacksaw

Decorative tape

(Rear) Left piping


Indoor unit Connection
piping Pipe cable

Right piping
Bottom piping
Left rear piping
For left outlet, house the connection cord
and piping at the position shown in the above
figure with the drain hose at the bottom. Drain hose Wall hole
Connection pipe
Drain hose cable

Figure 7 Figure 10

4. Install the piping so that the drain 5. After passing the indoor piping Indoor Unit Wiring
hose is at the bottom (Figure 7). and drain hose through the wall Both of the cable wires should be
hole, hang the indoor unit on the connect from the terminal block
Caution hooks at the top and bottom of of indoor unit (Figure 11).
• To prevent breaking of the pipe, the wall bracket.
avoid sharp bends. Bend the 6. Check to insure that: (Ref.
pipe with a radius of curvature of Figure 10).
100 mm or more. • The top and bottom hooks are
• If the pipe is bent repeatedly at the hooked firmly and the indoor unit
same place, it will break. does not move to the front and
• Do not remove the flare nuts rear or left and right.
from the indoor unit pipe • The indoor unit is accurately
immediately before connecting positioned horizontally and
the outdoor connection piping. vertically.
• The drain hose is at the bottom
of the wall hole pipe.
Top
hooks

unit Wall ho Figure 11


(Rear) Indoor ok
(R r)
e a bracket
• The appliance shall be installed in
(Fitting) accordance with national wiring
Pipe (top)
Bind with Bottom hooks regulation.
vinyl tape After hooking the indoor unit to the top • Means for disconnection from the
Drain hose supply having a contact separation
hook, hook the fitting of the indoor unit to
(bottom) of at least 3 mm in all poles must
the two bottom hooks while lowering the
unit and pushing it against the wall. be incorporated in the field wiring.

Figure 8 Figure 9

MS-SVN003-EN 7
Outdoor Unit Installation 3. Remove the flare nut from the 6. If the copper tube is bent or pulled
1. Install the unit mounting pads unit and be sure to mount it on too often, it will become stiff. Do
(4 places) into the bottom channels the copper tube. not bend the pipe more than three
by tapping gently with a plastic or 4. Make a flare at the end of copper times at one place.
rubber tipped hammer. tube with a flare tool (Figure 14,15).
2. Set the unit on a strong surface Cautions before Connecting
such as one made of concrete to Flare nut Tubes Tightly
minimize shock and vibration and 7. Be sure to apply a sealing cap
to locate the unit securely. or water-proof tape to prevent
3. Do not set the unit directly on the dust or water from getting into
ground. the tubes before they are used.
Copper tubing 8. Be sure to apply refrigerant
lubricant to the matching
Connecting the Unit with surfaces of the flare and union
Flaring Procedure. Flare tool before connecting them together.
Flaring (If piping is procured or cut at This is effective for reducing gas
the site). Figure 14 leaks (Figure 16).

1. Cut the copper tube to the


required length with a tube cutter.
It is recommended to cut approx.
30-50 cm longer than the tubing L
length you estimate.
2. Hold each pipe downward when
Apply refrigerant lubricant here
cutting and remove burrs at the
end of the copper tube with a tube
reamer or file. This process is Figure 16
important and should be done
carefully to make a good flare
(Figure 12 and Figure 13).
Connection
Check if (L) is flared uniform 9. For proper connection, align the
and is not cracked or scratched. union tube and flare tube straight
L Dimension: with each other, then screw in the
1.4 to 1.7 mm (6.35 mm dia) flare nut lightly at first to obtain a
Copper smooth match (Figure 17).
tubing Reamer 1.8 to 2.0 mm (9.53 mm dia)
1.9 to 2.2 mm (12.7 mm dia)
2.1 to 2.4 mm (15.88 mm dia)
Figure 12
Figure 15

Deburring
A good flare should have the
following characteristics:
- Inside surface is glossy and
smooth. Union Flare nut
- Edge is smooth.
- Tapered sides are of uniform Figure 17
length.
Before After
Bending 10. Tighten the flare nut to the
Figure 13 5. When bending the tube, be careful specified tightening torque with
not to crush it. To prevent crushing torque wrench and adjustable
When reaming, hold the tube end of the tube, bend it gently and do wrench (Figure 18).
downward and be sure that no not bend the tube at a radius 11. Repeat the process above for the
copper scraps fall into the tube. curvature of less than 100 mm. remaining line.

8 MS-SVN003-EN
Remote Control Installation Evacuation and Refrigerant
Locate and attach the wireless Charge
remote control as follows: 1. Air Evacuation and Charging
1. Do not place the control and the 1. Remove the cap and connect the
remote control near heat sources gauge manifold and the vacuum
or expose to the direct rays of the pump to the charging port using
Wrench
sun. the service hoses (Figure 20).
Indoor unit pipe (adjustable). 2. Do not expose the control to the 2. Pump the indoor unit and the
indoor unit’s supply air stream. connecting pipes until the
3. Do not place in a confined space. pressure in them lowers to below
4. Attach the remote control holder 1.5 mmHg of vacuum.
as shown in Figure 19. 3. Stop the vacuum pump and close
the gauge manifold valve.
Torque wrench 4. Remove the blanking caps and
Connection pipe
Flare nut fully open the service valves with
a hexagon wrench (Torque: 70
to 90 kgf - cm).
Figure 18

Flare Nut Tightening Torque


Flare nut/Piping size Tightening torque
kgf, - cm lbf-in Remote
6.35 mm (1/4”) dia. 150~200 130~170 Control
Unit
9.53 mm (3/8”) dia. 350~400 300~340
12.7 mm (1/2”) dia. 500~550 430~470
15.88 mm (5/8”) dia. 600~650 520~570

Tapping Screw
(small)
Remote Control Holder

Wireless Remote Control


Figure 19

MS-SVN003-EN 9
Refrigerant pipe

Gauge manifold
Service valve
Outdoor Unit

Vacuum
Blank cap pump

Service hose Charging port


with valve core

Cap Service hose

Figure 20

5. Reinstall the blanking caps of the Outdoor Unit Wiring


service valves. 1. Remove the outdoor unit terminal
6. Disconnect the service hoses and cover (Figure 21).
reinstall the cap on the charging 2. Route the connection cable through
port. (Tightening torque: 70 to the cable entry brushing and up to
90 kgf - cm). the terminal block.
3. Insert the end of the cable wires
2. Additional Charge into the terminal block connectors
Refrigerant suitable for a piping length as shown on the unit wiring
of 3.5 to 5.0 meters is charged in the diagram (Figure 11).
outdoor unit from the factory. When the 4. Tighten the terminal block
piping is longer than 5 m, additional connector screws.
charging is necessary. For the (Torque: 7-12 kgf - cm). Figure 21
additional amount, see table below.
• The appliance shall be installed in
Pipe length 16ft 23ft 33ft accordance with national wiring
(5m) (7m) (10m)
regulation.
Additional refrigerant None 1.1 oz 2.8 oz
(R22) (32g) (80g) Caution
• The connector cable wires must be
Between 5 m and 10 m, when using connected such that terminal
connection pipe lengths other than numbers on the indoor unit match
that in the table, charge additional those on the terminal block of the
refrigerant with 0.56 oz (16g)/3.3ft. outdoor unit (Figure 11).
• Insert the connection cable wires
Caution into the terminal block firmly.
• FREON GAS “R22” ONLY Incorrect insertion may cause a Drain hose
• Always evacuate air from the piping safety problem.
before adding refrigerant. 5. Replace the outdoor unit terminal
• Add refrigerant through the cover. Figure 22
charging valve after the completion
of removing the blanking caps and
fully open the service valves.

Gas Leakage Inspection


After charging with refrigerant, check
the joints for gas leakage with gas leak
detector or a soap bubble solution.

10 MS-SVN003-EN
Finishing Run Test Outdoor Unit
1. Securely wrap the connection 1. Start the system and check items 1 5. Is there any abnormal noise and
cable along the refrigerant pipes through 7 below. vibration during operation?
with vinyl tape. (Starting at the 2. For the system start procedure, 6. Will noise, air flow, or drain water
lowest end of the pipes, each refer to the Owner Manual. from the unit disturb the neighbors?
wrap should be about 1/3 of the 7. Is there any refrigerant gas
tape width so that water does Indoor Unit leakage?
not enter).(Figure 22) 1. Is operation of the on and off button
2. Fasten the cable/piping to the and fan button normal? Customer Guidance
outside wall with clamps, etc. 2. Does each indicator on the remote Explain the following to the customer
3. Fill the gap between the outside control display panel light normally? in accordance with the Owner Manual.
wall cap and the pipe with sealer 3. Does the air deflection louver 1. Starting and stopping procedures,
so that rain water and wind cannot operate normally? mode switching, temperature
blow in. 4. Is the condensate drain normal and adjustment, timer and air flow
4. Fasten the drain hose to the outside freely flowing water? adjustment, and other remote
wall, etc (Figure 23 & Figure 24). control operations.
2. Filter removal and cleaning and
how to use the air louvers.
3. Give the operating and installation
manuals to the customer.

Wall
Clamp

Outside wall
cap sealer

Pipe (Outdoor)

Figure 23

Check the following:

Drain hose

Clamp

Lifted up

Wave
End in water

Figure 24

MS-SVN003-EN 11
Wiring Diagram

12 MS-SVN003-EN
Dimensional Data

MS-SVN003-EN 13
Notes

14 MS-SVN003-EN
Notes

MS-SVN003-EN 15
Literature Order Number: MS-SVN003-EN
Date: Jun 2009
Supersedes: Jan 2003
Trane Stocking Location: Bangkok, Thailand
www.trane.com

For more information, contact your local district Trane has a policy of continuous product and product data improvement and reserves the right to change
office design and specifications without notice.

Potrebbero piacerti anche