IMPULSE TESTING OF

TRANSFORMERS

Dharmesh. Y
High Voltage Division
Central Power Research Institute
Bangalore

26th October 2018


Seminar on Transformer Technologies, Best Design Practices,
Standards and Testing Techniques
OVERVIEW
• Introduction
• Surge Phenomenon in Winding
• Recommended Impulse Test Connections
• Impulse Generation Issues
• LI test procedures
• SI test procedure
• Std. presented different failure cases
• LI testing of Transformers Case Studies with
TF&CF analysis
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
INTRODUCTION

System generated over voltages


-Continuous, Transient(Switching)

Nature generated over voltages


-Lighting over voltages

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Table 1 – Classes and shapes of overvoltages, Standard voltage shapes and Standard withstand voltage tests

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
SURGE PHENOMENON IN WINDING

g g
s

g g

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
SURGE PHENOMENON IN WINDING

Simple Equivalent Circuit

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
SURGE PHENOMENON (Initial: t=0+)

𝑑2 𝑒 1 𝐶𝑔 𝑙−𝑥
𝑐𝑜𝑠ℎ 𝛼 𝐶𝑔 Capacitance between winding and ground
− 𝑒=0 𝑙 𝛼=
𝑑𝑥 2 𝑙 2 𝐶𝑠 𝑒 = 𝐸0 𝐶𝑠 line end and neutral end
cosh(𝛼)

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
SURGE PHENOMENON (Initial: t=0+)

𝑑2 𝑒 1 𝐶𝑔 𝑙−𝑥
𝑐𝑜𝑠ℎ 𝛼
− 𝑒=0 𝑙
𝑑𝑥 2 𝑙 2 𝐶𝑠 𝑒 = 𝐸0
cosh(𝛼)

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
SURGE PHENOMENON (After t=0+)

𝒅𝟒 𝒆 𝑳 𝑪𝒔 𝒅𝟒 𝒆 𝑳 𝑪𝒈 𝒅𝟐 𝒆 𝒙 𝟐𝝅𝒏𝒙
− + =𝟎 𝒆 = 𝑬𝟎 − 𝑬𝒏 𝒔𝒊𝒏 𝒄𝒐𝒔𝝎𝒏 𝒕
𝒅𝒙𝟒 𝒍𝟐 𝒅𝒙𝟐 𝒅𝒕𝟐 𝒍𝟒 𝒅𝒕𝟐 𝒍 𝒍
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
SURGE PHENOMENON (After t=0+)

𝒅𝟒 𝒆 𝑳 𝑪𝒔 𝒅𝟒 𝒆 𝑳 𝑪𝒈 𝒅𝟐 𝒆 𝟐𝝅𝒏𝒙
− + =𝟎 𝒆 = 𝑬𝟎 − 𝑬𝒏 𝒄𝒐𝒔 𝒄𝒐𝒔𝝎𝒏 𝒕
𝒅𝒙𝟒 𝒍𝟐 𝒅𝒙𝟐 𝒅𝒕𝟐 𝒍𝟒 𝒅𝒕𝟐 𝒍
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
INFERENCES

Voltage distribution is not uniform

Voltage distribution varies with 𝛂 (design


parameter)

Voltage distribution varies with time

Voltage distribution depends on type of connection


at other end(neutral end) of the winding.
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
METHODS TO IMPROVE INITIAL VOLTAGE
DISTRIBUTION

• Co-ordinated insulation on the windings where the


insulation is proportional to control and to withstand
the surges which appear across it.

• Increasing Cs by interleaving winding conductors


or adding capacitors in parallel with the winding

• Neutralizing Cg by electrostatic shields

• Connecting nonlinear resistors in parallel with the


winding.
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
Lightning Impulse Test Connections

3 phase auto transformer


winding connections
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
Switching Impulse Test Connections

Fig.(a)

Fig.(b)

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Lightning Impulse Test Waveforms
 Based on data compiled on natural lightning by
AIEE and NEMA, it was concluded that system
disturbances were best represented by THREE
basic waveforms-
 Full wave

 Chopped wave

 Front-of-wave
 Standards stipulate, both shape and level of
voltages, to be used in a HV impulse test
 Apparatus are to be tested by these waveforms
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
Stresses and Test Waveforms
 The three waves are different in shape, duration and
rate of rise & fall, so, produces different stresses

 FW 
 relatively long-duration causes major oscillations
to develop in winding and hence stresses large
portions of winding & between winding & ground
 CW 
 because of rapid dv/dt (rise, fall) stresses turn-
turn and disk-disk insulation

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
HV Impulse Generation - Basics

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
HV Impulse Generation - Basics

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
HV Impulse Generation - Basics

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Tests for Different Rating Transformers

Um ≤ 72.5 kV 72.5 kV < Um Um > 170 kV


Rating ≤ 170 kV
Test
Full wave lightning impulse test for the
line terminals (LI)
Type Routine ---
Chopped wave lightning impulse test
for the line terminals (LIC)
Special Special Routine
Lightning impulse test for the neutral
terminals (LIN)
Special Special Special
Switching impulse test for the line
terminal (SI)
--- Special Routine

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI Parameter Definition as per IEC 60060-1

Vtest±3%, T1±30%, T2±20%, Overshoot≤10%


T1: 1.2𝛍s, T2: 50𝛍s
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
LI Parameter Definition as per IEC 60060-1

Vtest±3%, T1±30%, Overshoot≤10%, 0<Undershoot<30%


T1: 1.2𝛍s, TC: 2 to 5𝛍s

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Practical Difficulties

 Double-exponential waveforms are far too idealistic


 Can be generated ONLY for purely capacitive test
objects, and under controlled lab conditions
 Practical difficulties encountered during waveform
generation (e.g. during test on transformers) are-
 Stray Inductances
 Large Loops
 Ground Transients
 Single Point Grounding
 Actual HV impulses are often superimposed with
• - Oscillations, Overshoot and Noise !!

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI Waveform Generation Issues

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI Waveform Generation Issues

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI Waveform Generation Issues
Energy Requirement of Generator

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI Waveform Generation Issues
Wave form relaxations in the Standard
• For Chopped LI test - T1≤2.5𝛍s

• With agreement between manufacturer and


purchaser the T2 can be less than 40 𝛍s.

• Minimum tail time should be 20𝛍s≤T2 (Vtest should be


increased by 1% for each 2𝛍s less than the 40𝛍s)

• For Um˃800kV rating transformers winding the


T1>2.5 𝛍s (with agreement)

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI test sequence
Test type IEC/IEEE
RFW
Full wave 3 no. of FW
RFW
FW
Chopped
wave test RCW
2 no of CW
2 no of FW

RFW: Reduced Full Wave(50-70% of BIL)


FW: Full Wave (100% of BIL)
RCW: Reduced Chopped Wave(50-70% of BIL)
CW: Chopped Wave (110% of BIL)

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI test sequence on
Transformers with non-linear elements
Full Wave Test
a) one reference impulse  50% to 60% of BIL
≥10% of BIL
b) one reference impulse 60 % to 75 % of BIL
≥10% of BIL
c) one reference impulse 75 % to 90 % of BIL
d) three consecutive 100 % full wave impulses
e) a comparison impulse APA the same voltage as c) above
f) a comparison impulse APA the same voltage as b) above
g) a comparison impulse APA the same voltage as a) above

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LIC test sequence on
Transformers with non-linear elements
Chopped Wave Test
a) One reference impulse  50% to 60% of BIL
≥10% of BIL
b) One reference impulse 60 % to 75 % of BIL
≥10% of BIL
c) One reference impulse 75 % to 90 % of BIL
d) One full wave of 100% BIL
e) Two chopped waves of 110% BIL
f) Two full waves of 100% BIL
g) a comparison impulse APA the same voltage as c) above
h) a comparison impulse APA the same voltage as b) above
i) a comparison impulse APA the same voltage as a) above

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Tap position under LI test
If Tap rang is <±5% and transformer rating ≤2500kVA then
Test shall be conducted at Principal tapping

LI test on neutral terminal


 Only Full Wave LI test
 The allowable T1≤13𝛍s

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Switching Impulse
T1 ≥ 100uS, Td ≥ 200uS, T2 ≥ 500uS

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Switching Impulse

• The impulses are applied either directly or


inductively

• In a three-phase transformer,
Utest ( line-line) ~ 1.5 Utest (line-earth)

• Lower level opposite polarity shots shall


be applied to avoid saturation of the core
and change in the wave form
• sudden collapse of voltage or discontinuity in
the voltage or current
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
Measurement and Recording of
Impulse waveforms
 Lightning Impulse
• Voltage waveforms (There should not be any
terminating resistance at digitizers)
1. CW: 5 to 10𝛍s
2. FW: 50 to 100𝛍s

• Earth current waveforms (There should be 75ohms


terminating resistance at digitizers) : 100 to 600𝛍s

 Switching Impulse
• Voltage waveforms (There should not be any
terminating resistance at digitizers): 1000 to 3000𝛍s
(should cover first zero crossover point)
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore
Std. reference of failed cases-LI Full Wave

Voltage Earth current

Line-to-neutral breakdown across high-voltage winding of 400 kV


generator transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Std. reference of failed cases-LI Full Wave

Earth current
Voltage

interlayer breakdown in coarse-step tapping winding of a 400/220 kV


transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Std. reference of failed cases- LI Full Wave

Earth current
Voltage

Breakdown short-circuiting one section of the fine-step tapping winding of a


220 kV transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Std. reference of failed cases- LI Full Wave

Earth current
Voltage

Breakdown between parallel conductors of a main high-voltage winding


of a 220/110 kV transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
Std. reference of failed cases- LI Chopped Wave

Earth current
Voltage

Breakdown between turns in the main high-voltage winding of a 115 kV


transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI Chopped Wave with identical chop timings

Voltage Earth current


Impulses at different voltage levels with identical times to chopping
when testing a 115 kV transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
LI Chopped Wave with different chop timings

Voltage Earth current


Effects of differences in times to chopping when testing a 220 kV transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
SI test

Voltage Earth current

Satisfactory test on a 400 kV three-phase generator transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
SI test

Voltage Earth current

Breakdown by axial flashover of the main high-voltage winding of a 525 kV


single-phase, generator transformer

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 1

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 1

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 1

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 1

Reduced Full Wave: 1st Shot


Last Full Wave: 7th Shot

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 2

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 2

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 2

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 2

Reduced Full Wave: 1st Shot


First Full Wave: 2nd Shot

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 2

Reduced Full Wave: 1st Shot


Full Wave: 6th Shot

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
CASE 2

Reduced Full Wave: 1st Shot


Last Full Wave: 7th Shot

High Voltage Division


26 October 2018 Central Power Research Institute
Bangalore
DISCUSSIONS
&
CLOSURES
High Voltage Division
26 October 2018 Central Power Research Institute
Bangalore