Panel No. CT Requirement 10.09.2018 (Offer with 2 CT) 14.09.2018 (Offer with Single CT) 20.09.

.09.2018 (Offer with Single CT) 20.09.2018(Offer with reducing B/B Diff Knee Voltage) Revised CT requirement Vk requirement TSL Reply SL reply on 5.10.18 TSL Reply Siemens Reply on 31.10.18 Siemens Reply on 11.01.19 TS Reply
H01, H05 C1 - C1 - C1 - C1 - C1 - Vk required for OK CT finalised point closed OK CT finalised point closed ok
- Core 1 :1500-750/1A, Core 1 :1500-750/1A, Core 1 :1500-750/1A, Core 1 :1500-750/1A, Core 1 :1500-750/1A, 1000/1A core 115V.
(C40,C43 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 Through fault current
Trafo Core 2 :1500-750/1A, Core 2 :1500-750/1A, Core 2 :1500-750/1A, Core 2 :1500-750/1A, Core 2 :1500-750/1A, at 13.2KV =
incomer) 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 6.55KA. 50 m lead
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, considered
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=300V, Ie<=30mA@Vk, Cl. PS, Vk>=600V,
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2,
Core 4 : 1000/5A, Core 4 : 1000/5A, Rct<=15 Ohm
C2 - C2 - Cl. PS, Vk>=150V, Ie<=30mA@Vk, Cl. PS, Vk>=200V, Ie<=30mA@Vk
Core 1 : 1000/5A, Core 1 : 1000/5A, Rct<=15 Ohm Rct<=2 Ohm C2 -
Cl. PS, Vk>=500V, Ie<=30mA@Vk, Cl. PS, Vk>=100V Core 5 : 2500/1A, Core 5 : 2500/1A, Core 1 : 1000/1A,
Rct<=5 Ohm Core 2 : 2500/1A, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=300V, Ie<=30mA@Vk, Cl. PS, Vk>=200V,
Core 2 : 2500/1A, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Rct<=15 Ohm Rct<=5 Ohm
Rct<=15 Ohm Core 2 : 2500/1A,
Cl. PS, Vk>=600V,
Ie<=30mA@Vk/2,
Rct<=15 Ohm

H06 (C55 C1 - C1 - C1 - C1 - C1 - Vk required at 1) Vk of REF CT C1 CT ok. Point closed. Please consider REF CT ratio as OK (Please refer SLD) ok
trafo) Core 1 :1500-750/1A, Core 1 :1500-750/1A, Core 1 :1500-750/1A, Core 1 :1500-750/1A, Core 1 :1500-750/1A, 1000/1A is 120V. should be C2 CT: 1500/1A without considering any ICT
15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 Through fault current consideringthe and match the Vk value as per the
Core 2 :1500-750/1A, Core 2 :1500-750/1A, Core 2 :1500-750/1A, Core 2 :1500-750/1A, Core 2 :1500-750/1A, at 13.2KV = 6.9KA. maximum dead short Core 1 : 1500/1A, requirement
15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 50 m lead circuit current to be Cl. PS, Vk>=300V, Ie<=30mA@Vk/2,
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, considered fed by the transformer Rct<=10 Ohm As communicated earlier also, Ie shall
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=300V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, and not based on Core 2 : 1000/1A, be <= 30mA.
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2, Vk required at Earth fault current Cl. PS, Vk>=150V, Ie<=30mA@Vk/2,
Core 4 : 1500-750/5A, Core 4 : 1500-750/5A, Rct<=15 Ohm 1500/5A is Rct<=3 Ohm
C2 - C2 - Cl. PS, Vk>=100-50V, Ie<=30-60mA@Vk, Cl. PS, Vk>=150-75V, Ie<=30-60mA@Vk Core 4 : 1500/5A, 49V. For REF 2) Two (2) nos. CTs Core 3 : 2500/1A,
Core 1 : 1500-750/5A, Core 1 : 1500-750/5A, Rct<=5-2.5 Ohm Rct≤2-1.5 ohms Cl. PS, Vk>=100V, protection only earth to be considered Cl. PS, Vk>=600V, Ie<=30mA@Vk/2,
Cl. PS, Vk>=750-350V, Ie<=30-60mA@Vk, Cl. PS, Vk>=50-25V Core 5 : 1000/5A, Core 5 : 1000/5A, Ie<=30mA@Vk/2, fault current
Rct<=15 Ohm
Rct<=5-2.5 Ohm. Cl. PS, Vk>=100V, Ie<=30mA@Vk, Cl. PS, Vk>=100V, Ie<=30mA@Vk Rct<=5 Ohm (1.32KA) considered
Core 2 : 1000/5A, Core 2 : 1000/5A, Rct<=15 Ohm Rct≤1.5 ohms Core 5 : 1000/1A,
For 1500/1A CTseparate ICT will be
Cl. PS, Vk>=500V, Ie<=30mA@Vk, Cl. PS, Vk>=50V Core 6 : 2500/1A, Core 6 : 2500/1A, Cl. PS, Vk>=150V, *Single set CT
provided for below value.
Rct<=5 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=300V, Ie<=30mA@Vk, Ie<=30mA@Vk/2, considered
1/5A, Vk>= 41.4, Rct <= 0.3 ohm
Core 3 : 2500/1A, Core 3 : 2500/1A, Rct<=15 Ohm Rct<=15 Ohm Rct<=5 Ohm
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Core 6 : 2500/1A, Io at <=60ma @Vk/2
Rct<=15 Ohm Rct<=15 Ohm Cl. PS, Vk>=600V,
Ie<=30mA@Vk/2,
Rct<=15 Ohm

H02, C1 - C1 - C1 - No comments from customer hence no change C1 - ok CT finalised point closed OK CT finalised point closed ok
H03, H09 Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A,
(C23,C24 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5
,C18 line Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A,
feeder) 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V,
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2,
Core 4 : 1200-600/1A, Rct<=15 Ohm
C2 - C2 - Cl. PS, Vk>=550-275V, Ie<=30-60mA@Vk,
Core 1 : 1200-600/1A, Core 1 : 1200-600/1A, Rct<=5-2.5 Ohm C2 -
Cl. PS, Vk>=550-275V, Ie<=30-60mA@Vk, Cl. PS, Vk>=550-275V, Ie<=30-60mA@Vk, Core 5 : 2500/1A, Core 1 : 1200-600/1A,
Rct<=5-2.5 Ohm Rct<=5-2.5 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=550-275V, Ie<=30-
Core 2 : 2500/1A, Core 2 : 2500/1A, Rct<=15 Ohm 60mA@Vk/2,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Rct<=5-2.5 Ohm
Rct<=15 Ohm Rct<=15 Ohm Core 2 : 2500/1A,
Cl. PS, Vk>=600V,
Ie<=30mA@Vk/2,
Rct<=15 Ohm

H04 (C9 C1 - C1 - C1 - C1 - C1 - Vk required for CT 1 finalised. As communicated earlier also, Ie shall Due to CT sizing best C1 - ok
trafo Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :300/1A, 300/1A core 148V. be <= 30mA. magnetizing current we can Core 1 :300/1A,
outgoing) 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 3.75VA, 0.2FS5 Through fault current CT 2 , core 1 offer is Ie<=60mA @Vk/2 for 3.75VA, 0.2FS5
Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :300/1A, at 13.2KV = Vk>=150, Ie <=60ma @ Vk/2, RCT <=3 300/1A Core 2 :300/1A,
15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 3.75VA, 5P20 3.46KA. 50m lead ohm 3.75VA, 5P20
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, considered. Core 3 : 2500/1A,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=300V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Cl. PS, Vk>=600V,
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2, Ie<=30mA@Vk/2,
Core 4 : 1250/5A, Core 4 : 1250/5A, Rct<=15 Ohm Rct<=15 Ohm
C2 - C2 - Cl. PS, Vk>=175V, Ie<=30mA@Vk, Cl. PS, Vk>=250V, Ie<=30mA@Vk
Core 1 : 1250/5A, Core 1 : 1250/5A, Rct<=15 Ohm Rct<=2 Ohm C2 - C2 -
Cl. PS, Vk>=550V, Ie<=30mA@Vk, Cl. PS, Vk>=125V Core 5 : 2500/1A, Core 5 : 2500/1A, Core 1 : 300/1A, Core 1 : 400/1A,
Rct<=5 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=300V, Ie<=30mA@Vk, Cl. PS, Vk>=150V, Cl. PS, Vk>=150V,
Core 2 : 2500/1A, Core 2 : 2500/1A, Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2, Ie<=30mA@Vk/2,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Rct<=3.5 Ohm Rct<=3 Ohm
Rct<=15 Ohm Rct<=15 Ohm Core 2 : 2500/1A, Core 2 : 2500/1A,
Cl. PS, Vk>=600V, Cl. PS, Vk>=600V,
Ie<=30mA@Vk/2, Ie<=30mA@Vk/2,
Rct<=15 Ohm Rct<=15 Ohm

H10(C17 C1 - C1 - C1 - C1 - C1 - Vk required for ok CT 1 finalised. Why CT2 has been changed. As it Due to CT sizing best C1 - ok
trafo Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :300/1A, 300/1A core 148V. was already finalised in last magnetizing current we can Core 1 :300/1A,
outgoing) 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 3.75VA, 0.2FS5 Through fault current CT 2 , core 1 communication. offer is Ie<=60mA @Vk/2 for 3.75VA, 0.2FS5
Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :300/1A, at 13.2KV = Vk>=150, Ie <=60ma @ Vk/2, RCT <=3 300/1A Core 2 :300/1A,
15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 3.75VA, 5P20 3.74KA. 50m lead ohm As communicated earlier also, Ie shall 3.75VA, 5P20
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, considered. be <= 30mA. Core 3 : 2500/1A,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=300V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Cl. PS, Vk>=600V,
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2, Ie<=30mA@Vk/2,
Core 4 : 1250/1A, Core 4 : 1250/1A, Rct<=15 Ohm Rct<=15 Ohm
C2 - C2 - Cl. PS, Vk>=550V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk
Core 1 : 1250/1A, Core 1 : 1250/1A, Rct<=5 Ohm Rct≤19 ohms C2 - C2 -
Cl. PS, Vk>=550V, Ie<=30mA@Vk, Cl. PS, Vk>=312.5V Core 5 : 2500/1A, Core 5 : 2500/1A, Core 1 : 300/1A, Core 1 : 400/1A,
Rct<=5 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=300V, Ie<=30mA@Vk, Cl. PS, Vk>=150V, Cl. PS, Vk>=150V,
Core 2 : 2500/1A, Core 2 : 2500/1A, Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2, Ie<=30mA@Vk/2,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Core 6 : 1200/1A, Core 6 : 1200/1A, Rct<=3.5 Ohm Rct<=3 Ohm
Rct<=15 Ohm Rct<=15 Ohm Cl. PS, Vk>=300 V, Ie<=30mA@Vk, Cl. PS, Vk>=500 V, Ie<=30mA@Vk Core 2 : 2500/1A, Core 2 : 2500/1A,
Core 3 : 1200/1A, Core 3 : 1200/1A, Rct<=15 Ohm Rct≤17 ohms Cl. PS, Vk>=600V, Cl. PS, Vk>=600V,
Cl. PS, Vk>=300 V, Ie<=30mA@Vk, Cl. PS, Vk>=300 V, Ie<=30mA@Vk, Ie<=30mA@Vk/2, Ie<=30mA@Vk/2,
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm

H07 (New C1 - C2 - C2 - No comments from customer hence no change C1 - Vk required for OK CT finalised point closed ok CT finalised point closed ok
Trafo Core 1 :1500-750/1A, Core 1 :1500-750/1A, Core 1 :1500-750/1A, Core 1 :1500-750/1A, 1250/1A core
C57) 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 15-7.5VA, 0.2FS5 91.27V. Through
Core 2 :1500-750/1A, Core 2 :1500-750/1A, Core 2 :1500-750/1A, Core 2 :1500-750/1A, fault current at
15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 13.2KV = 6.55KA.
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, 50 m lead
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, considered.
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2,
Core 4 : 1500-750/1A, Rct<=15 Ohm Vk required at
C2 - C1 - Cl. PS, Vk>=750-350V, Ie<=30-60mA@Vk, 1500/1A is 50V
Core 1 : 1500-750/1A, Core 1 : 1500-750/1A, Rct<=5-2.5 Ohm. C2 -
Cl. PS, Vk>=750-350V, Ie<=30-60mA@Vk, Cl. PS, Vk>=750-350V, Ie<=30-60mA@Vk, Core 5 : 1250/1A, Core 1 : 1500/1A,
Rct<=5-2.5 Ohm. Rct<=5-2.5 Ohm. Cl. PS, Vk>=750V, Ie<=30mA@Vk, Cl. PS, Vk>=200V, Ie<=30@Vk/2,
Core 2 : 1250/1A, Core 2 : 1250/1A, Rct<=5 Ohm Rct<=5
Cl. PS, Vk>=750V, Ie<=30mA@Vk, Cl. PS, Vk>=750V, Ie<=30mA@Vk, Core 6 : 2500/1A, Core 2 : 1250/1A,
Rct<=5 Ohm Rct<=5 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=150V,
Core 3 : 2500/1A, Core 3 : 2500/1A, Rct<=15 Ohm Ie<=30mA@Vk/2,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Rct<=5 Ohm
Rct<=15 Ohm Rct<=15 Ohm Core 3 : 2500/1A,
Cl. PS, Vk>=600V,
Ie<=30mA@Vk/2,
Rct<=15 Ohm

Unrestricted
H08, H14 C1 - C1 - C1 - No comments from customer hence no change C1 - Vk required at OK CT 1 finalised. Why CT2 has been changed. As it C1 - ok
(C16 & Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, 1200/1 A is 377V was already finalised in last Core 1 :1200-600-300/1A,
C27 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 considering 40KA CT 2 , core 1 communication. 15-7.5-3.75VA, 0.2FS5
reactor ) Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, fault level Core 2 :1200-600/1A,
15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 1200-600/1A, 15-7.5VA, 5P20
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Cl. PS, Vk>=250-125V It seems that both Vk and Ie value has Core 3 : 2500/1A,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, RCT<=3.5-1.75 Ohm, Ie<=30-60mA@Vk/2 been changed which is not accepted. Cl. PS, Vk>=600V,
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2, Core 2 : 1200-600/1A, Ie<=30mA@Vk/2,
Core 4 : 1200-600/1A, Rct<=15 Ohm Cl. PS, Vk>=250-125V Changed parameter is not accepted. Rct<=15 Ohm
C2 - C2 - Cl. PS, Vk>=750-350V, Ie<=30-60mA@Vk, RCT<=3.5-1.75 Ohm, Ie<=30-60mA@Vk/2. Please adhere to the previous Core 4 : 1200-600/1A,
Core 1 : 1200-600/1A, Core 1 : 1200-600/1A, Rct<=5-2.5 Ohm C2 - Core 3 : 2500/1A, parameter. Cl. PS, Vk>=377V@1200
Cl. PS, Vk>=750-350V, Ie<=30-60mA@Vk, Cl. PS, Vk>=300-150V Core 5 : 1200-600/1A, Core 1 : 1200-600/1A,
Cl. PS, Vk>=600V, Ie<=30mA@Vk/2, RCT<=3.5-1.75 Ohm, Ie<=30-
Rct<=5-2.5 Ohm Cl. PS, Vk>=750-350V, Ie<=30-60mA@Vk, Cl. PS, Vk>=300-150V
Rct<=15 Ohm 60mA@Vk/2
Core 2 : 1200-600/1A, Core 2 : 1200-600/1A, Rct<=5-2.5 Ohm RCT<=5-2.5 Ohm, Ie<=30-
Cl. PS, Vk>=750-350V, Ie<=30-60mA@Vk, Cl. PS, Vk>=300-150V Core 6 : 2500/1A, 60mA@Vk/2
C2 -
Rct<=5-2.5 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk, Core 2 : 1200-600/1A,
Core 3 : 2500/1A, Core 3 : 2500/1A, Rct<=15 Ohm Cl. PS, Vk>=300-150V
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, RCT<=5-2.5 Ohm, Ie<=30- Core 1 : 1200-600/1A,
Rct<=15 Ohm Rct<=15 Ohm 60mA@Vk/2. Cl. PS, Vk>=377V@1200
Core 3 : 2500/1A, RCT<=3.5-1.75 Ohm, Ie<=30-
Cl. PS, Vk>=600V, 60mA@Vk/2
Ie<=30mA@Vk/2, Core 2 : 2500/1A,
Rct<=15 Ohm Cl. PS, Vk>=600V,
Ie<=30mA@Vk/2,
Rct<=15 Ohm

H11, H13 C1 - C1 - C1 - No comments from customer hence no change C1 - OK CT finalised point closed CT finalised point closed ok
(Generat Core 1 : 2500/1A, Core 1 : 2500/1A, Core 1 : 2500/1A, Core 1 : 2500/1A,
or 15 VA, 0.2FS5 15 VA, 0.2FS5 15 VA, 0.2FS5 15 VA, 0.2FS5
incomer) Core 2 : 2500/1A, Core 2 : 2500/1A, Core 2 : 2500/1A, Core 2 : 2500/1A,
15 VA, 5P20 15 VA, 5P20 15 VA, 5P20 15 VA, 5P20
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V,
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Ie<=30mA@Vk/2,
Core 4 : 2500/1A, Rct<=15 Ohm
C2 - C2 - Cl. PS, Vk>=600V, Ie<=30mA@Vk,
Core 1 : 2500/1A, Core 1 : 2500/1A, Rct<=15 Ohm C2 -
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Core 5 : 2500/1A, Core 1 : 2500/1A,
Rct<=15 Ohm Rct<=15 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V,
Core 2 : 2500/1A, Core 2 : 2500/1A, Rct<=15 Ohm Ie<=30mA@Vk/2,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Rct<=15 Ohm
Rct<=15 Ohm Rct<=15 Ohm Core 2 : 2500/1A,
Cl. PS, Vk>=600V,
Ie<=30mA@Vk/2,
Rct<=15 Ohm
H15, H17 C1 - C1 - C1 - No comments from customer hence no change C1 - Vk required at OK CT finalised point closed CT finalised point closed ok
(NDPH Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, 1200/1 A is 377V
Bus#1 & 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5
NDPH Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A,
BUS#2 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20
line Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A,
feeder) Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk,
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm
Core 4 : 1200-600/1A,
C2 - C2 - Cl. PS, Vk>=550-275V, Ie<=30-60mA@Vk, C2 -
Core 1 : 1200-600/1A, Core 1 : 1200-600/1A, Rct<=5-2.5 Ohm Core 1 : 1200-600/1A,
Cl. PS, Vk>=550-275V, Ie<=30-60mA@Vk, Cl. PS, Vk>=550-275V, Ie<=30-60mA@Vk, Core 5 : 2500/1A, Cl. PS, Vk>=550-275V, Ie<=30-
Rct<=5-2.5 Ohm Rct<=5-2.5 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk, 60mA@Vk,
Core 2 : 2500/1A, Core 2 : 2500/1A, Rct<=15 Ohm Rct<=5-2.5 Ohm
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Core 2 : 2500/1A,
Rct<=15 Ohm Rct<=15 Ohm Cl. PS, Vk>=600V, Ie<=30mA@Vk,
Rct<=15 Ohm
H16 C1 - C1 - C1 - No comments from customer hence no change C1 - Vk required at OK CT finalised point closed CT finalised point closed ok
(15MVA Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, Core 1 :1200-600-300/1A, 1250/1 A is 115V.
back up 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 15-7.5-3.75VA, 0.2FS5 Through fault current
Trafo Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, Core 2 :1200-600/1A, at 13.2 KV is
outgoing) 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 15-7.5VA, 5P20 6.67KA.50 m lead
Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, Core 3 : 2500/1A, resistance
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=600V, Ie<=30mA@Vk, considered.
Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm Rct<=15 Ohm
Core 4 : 2500/1A,
C2 - C2 - Cl. PS, Vk>=500V, Ie<=30mA@Vk, C2 -
Core 1 : 2500/1A, Core 1 : 2500/1A, Rct<=15 Ohm Core 1 : 1250/1A,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=500V, Ie<=30mA@Vk, Core 5 : 2500/1A, Cl. PS, Vk>=200V,
Rct<=15 Ohm Rct<=15 Ohm Cl. PS, Vk>=500V, Ie<=30mA@Vk, Ie<=30mA@Vk/2,
Core 2 : 2500/1A, Core 2 : 2500/1A, Rct<=15 Ohm Rct<=10 Ohm
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=500V, Ie<=30mA@Vk, Core 6 : 2500/1A, Core 2 : 2500/1A,
Rct<=15 Ohm Rct<=15 Ohm Cl. PS, Vk>=500V, Ie<=30mA@Vk, Cl. PS, Vk>=600V,
Core 3 : 2500/1A, Core 3 : 2500/1A, Rct<=15 Ohm Ie<=30mA@Vk/2,
Cl. PS, Vk>=600V, Ie<=30mA@Vk, Cl. PS, Vk>=500V, Ie<=30mA@Vk, Rct<=15 Ohm
Rct<=15 Ohm Rct<=15 Ohm

Unrestricted