Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
the sum of two components, the component in phase with a reference signal (the real part), and the
cos( + ) = [ ( )
+ ( )
] ( 1)
cos( + ) = Re" ( )
# = Re$cos( + ) + sin( + )%
Consider for example the sum of two sinusoidal voltages & cos( + &) + ' cos( + ')
The sum of these voltages (or indeed any other combination of operations on sinusoidal signals)
could be done using trigonometric identities. However it is far simpler to use complex number
notation, so that the problem then reduces to the sum of complex numbers, ie:
= ( "( &
) + '
* ) #
1.1 Phasors
Above, the variables were written in lower case as they represented explicit functions of time. In
phasor notation we assume an exponential time variation at the given frequency, and simply write
the complex number in capitals corresponding to the RMS value and the phase.
Phasors can be written using in rectangular co-ordinates or one of two notations in polar co-
ordinates, for example:
+& = |+& | cos & + |+& |sin & -. +& = |+& | ) /0 |+& |∠ &
negative angle (∠-90). A consequence of this is that an inductive impedance (V/I) has a positive
imaginary part, as the imaginary part changes sign during division. You will learn that an inductor
has a lagging power factor (see inset box). We can re-use the same diagram if we re-use the phasor
Vb as the current in a lossy inductor (Z=R+jωL) with a voltage Va applied. The phasor orientation
shows that the current lags by about 30° so this is quite a lossy inductor.
For later: A lagging power factor (e.g. inductor) is deemed to be positive, just like the sign of the imaginary part
of its impedance, even though the current has a negative phase angle.
cos( ) ∗ cos( ) = + cos(2 ) ), but we are usually more concerned with the practical
in a purely resistive load therefore oscillates at 100Hz with amplitude between 0 and Pmax (since
1 ;
< 4 > = 8 VI dt
T <
The average power <P> over interval T is ( 2)
First consider linear networks. If the load is linear (V=IR) and we know R, we can use V∝ I to
allow calculation from just one measurement (V or I), which is where (and only where) the concept
of RMS (Root Mean Square) is strictly applicable. Substituting V=IR,
1 ; R ;
< 4 > = 8 VI dt = 8 I dt
T < T <
R ;
< 4 > = R. I@AB = 8 I dt
T <
Crest factor for sine waves is of course the familiar √2. Crest factor for other common waveforms are
Furthermore, we define Crest Factor as Crest Factor = Ipeak/IRMS ( 4)
√2
DC constant signal 1 1
Sine wave 0
√3
Square wave 0 1
√3
Triangle wave 0
1/√D
Sawtooth wave 0
Pulse train wave with duty cycle D D
We must remember that we assumed a linear circuit, so that V∝ I. Power can only be calculated
from RMS if this is true. i.e. RMS only makes sense in a linear circuit (eg resistive, inductive, &
capacitive only). If you make this mistake in a lab report, you lose 2 marks! See Non-Linear
Power below.
Please also note: despite what audio retailers say, “RMS power” doesn’t make sense either. This
will also cost you marks in a lab report. What they mean is the average power, evaluated for a long
time, calculated from (VRMS)2 / RLoad If you actually evaluated the RMS power, it wouldn’t even
have the units of power. [not Joules/sec but Joules/(second)3/2]
2.1.2 RSS
if they are independent (orthogonal). For example, if x(t) and y(t) are orthogonal (i.e. L E MN . =
A related concept is Root Sum Squares (RSS) which is a rule for adding RMS quantities if and only
0 ) then the RMS of M( ) + N( ) is sqrt(R + S ) , where X,Y are the RMS values of M( ), N( ).
This applies to harmonics, with T = UT< for U integral. You can simply add the squares and take
the square root. This is also true of sin and cosine. A “proof” is loosely (consider RMS squared)
RMS2 (x+y) = L
E(M + N) . = L E(M + 2MN + N^2) . = L E M . + L E N . + L E MN .
= RMS2(x) + RMS2(y) + 0
Another viewpoint is that RSS can be used to combine powers of different frequency components
because products of I and V have zero average unless frequencies of V and I match, causing real
power dissipation.
For the case of a square wave1 whose amplitude is 1, the RMS is 4/π √(1 + XY + ZY …) × 1/√2 = 1.
1
note that the Fourier series for a square wave is 4/][sin( ) + 1/3 sin(3 ) + 1/5 sin(5 ) + … ].
E. Franklin, B. Blackwell p5/50
ENGN4625/6625 2014 eBrick 1 - 6
Ultimately, we must use ( 2) < 4 > = E< VI dt, to calculate average power for non-linear
;
2.1.3 Non-Linear Power Calculations
;
circuits (since the RMS shortcut cannot be used). This can be done on a digital oscilloscope with
taking care that the zeros are correct (especially important for a Hall current probe). However there
are two special cases which occur in the lab. If one of V or I is constant, it can be factored out of
the average:
which is just the DC meter reading of V times the DC meter reading of I. (the DC or direct current
value of a waveform is its average). Thus if you simply measure with a DC (NOT AC or RMS)
meter, AND you check with your oscilloscope that at least one of V or I is constant, then you have
the power!
We obtain
1 c 1 c1 1 1
< 4 > = 8 ` de = 8 f1 + cos(2 )gcos + sin(2 )sin . = cos
c 0 c 0 2 2 2
less for a reactive load. Because cos is an even function (same value regardless of the sign of
the angle), the fraction of power delivered is independent whether the phase is leading or lagging,
we need to add one of those two words to make it clear – e.g.
describes a significantly inductive load with a phase lag of 60° - I lags V by 60°, so = -π/3.
Such a load heats the wiring and the transformers (and ultimately the generator) supplying it twice
as much as an ideal load, so it must be compensated for by “power factor correction”.
Careful with signs! A lagging power factor (e.g inductor) is deemed to be positive, just like the sign
of the imaginary part of its impedance, even though the current has a negative phase angle. The
maths is consistent, but the wording is tricky. Don’t assume lagging means negative or positive
without considering what quantity you are describing: a lagging power factor is given a positive
angle (corresponds to the complex power and impedance), but the current in that circuit (which
lags the voltage) has a negative angle and imaginary part.
The complex conjugate produces a real result for V and I in phase, for any complex V and I. The
real part of the complex power is the Real Power or average power as we have just calculated in (
6). The imaginary part is the Reactive Power, which corresponds to power oscillating in and out
of a circuit, and transferring no energy on the average. In an LC circuit the energy sloshes between
the inductor and capacitor, backwards and forwards. The only real power is a small amount which
is absorbed due to losses.
4j = 4/|i| = cos ( 9)
where Apparent Power is the RMS voltage times the RMS current = |V| × |I| = |S|, the power you
would assume if you didn’t know the phase (quite a common situation).
Reactive power is measured in units of VAr (Volt-Amps-reactive), pronounced Vars, whereas the
units of apparent power are Volt-Amps or VA, pronounced Vee-Ay, not var.
The apparent power |S| = |V||I| = 1200VA, the power (real power P) is 1200cos(60) = 600W, and
the reactive power is √3/2 × 1200 ~ 1039VAr.
The waveforms and phasors are plotted below. Note how the power into the load is positive for
much of the cycle but negative for a significant part of it (ie. some power flows in and out of the
E. Franklin, B. Blackwell p7/50
ENGN4625/6625 2014 eBrick 1 - 8
load and does no useful work). Despite the total waveform amplitude being 2400 W, the average of
the instantaneous power is only 600 W (it would be 1200 W if the load was resistive only). This is
the same as the real component of the apparent power phasor.
2000 2
1.5 600
1
1000 1039
0.5
500 0
-0.5 VL
0
0 10 20 30 40 -1
-500 Power
-1.5
Voltage (normalised) IL
-1000 Current (normalised) -2
Figure 2. Plot of instantaneous voltage, current and power waveforms, and phasor diagram.
Example: Calculate the power when Z = 1Ω (i.e. real), and V = 2+j. (so |V|=√5).
This is correct as V and I are in phase, so we expect P=V2/R, and it is. If we had (incorrectly) used
V× I, (omitting the *) we would have calculated 3Watts + 4[VAr] (4 units of reactive power).
Remember Power = Real(S), and VArs = Imag(S). Power usually means real power, unless we say
“complex power”.
Given we have a largely inductive (i.e. lagging) load. Z has a positive imaginary part, and as
Z=V/I, V=ZI, so S=VI* = Z(I.I*), so S=Z|I|2. That is, S has the same sign imaginary part as Z.
- very handy for circuit calculations, but be careful of the 1/S*, the sign flips twice (division and
conjugate).
hr
2.2.6 Extension of Power Factor to non-Sinusoidal Waveforms:
4j = × s4j
hr
The non-linear power factor ( 12)
here we consider both the linear power factor treated above (called the Displacement Power Factor
(DPF) and the fraction of the RMS current that is in the fundamental frequency. See Mohan p43,
but we will postpone covering this in more detail until the Power Quality Labs.
The simplest and most common method for power factor correction is by adding reactive
components (eg capacitors or inductors) across the load. Consider the circuit and corresponding
phasor diagram in the figure below, where the capacitor has been added across a load with lagging
power factor. The power factor at the load remains unchanged, but the power factor supplied by the
ac system is now much closer to unity. The same amount of real power is still supplied by the
source but a vastly reduced amount of reactive power is supplied from it. The balance of the
reactive power is supplied by the capacitor.
Figure 3. Power factor correction capacitor added across a load with lagging power factor.
Of course the value of the capacitance required depends upon load itself. And if the load had a
leading power factor then inductance would be required instead. For the power factor correction to
E. Franklin, B. Blackwell p9/50
ENGN4625/6625 201 eBrick 1 - 10
2014
Figure 4.. Combined power factor correction and harmonic filtering (from Mohan p470)
Power is constant during a cycle – +t + +u + +v = Const (= 4152 for domestic three phase).
system would work too, but neutral is not balanced, so still need three wires)
•
• Interfaces better with rectifiers – load current has much less ripple, line current drawn is
closer to a sinusoid than single or two phase.
• Naturally extends to 6 phase by simple inversion using a 3φ transformer. (invert Voltage)
VC –e.g. 240∠-240°
(240° lagging ≡
120° leading)
Va
rotation
Va Va 0°–e.g.
240∠0°
t=0 t =T/3 Va t =2T/3 Vb e.g. 240∠-120°
(120° lagging)
To demonstrate some important features of three phase networks, consider the three separate single
phase circuits of figure 3. Each circuit shares a common neutral potential but has its own return
wire, and identical load impedance. If the three single phase voltage sources have the same
magnitude, V, but have phases of 0°, -120° and 120°C, then:
+& = + = +, +' = + =− +− +, +z = + =− ++ +
Yx Yx
< √X √X
y y
The total current that returns in the three neutral wires is sum of Ia + Ib + Ic:
+& +' +z 1 1 √3 1 √3
h& + h' + hz = + + = {+ − + − +− ++ +| = 0
o o o o 2 2 2 2
Hence the return wires could all be combined into a single wire, which for a balanced set of circuits
carries no current and can therefore even be removed without any impact. The circuit then becomes
Va Vb Vc Ic Ib Ic
Z Z Z
Figure 6. Three separate single phase circuits, can be compared to a Wye connected 3-phase circuit
Another important relationship for three phase systems is the relationship between line-neutral and
line-line voltages. In the circuit shown Va, Vb, and Vc are the line-neutral voltages, and it is
straightforward to calculate the line-line voltages Vab, Vbc ,and Vca:
1 √3 3 √3 ‚
+&' = +& − +' = + − {− + − +| = + + + = √3+ ƒ
2 2 2 2
Another important result: in a balanced three phase network line-line voltages are à times
larger in magnitude and are phase shifted +30° compared to line-neutral voltages. This is also
shown in the phasor diagram of figure 4 (the line-line phasors are not drawn from the origin in this
case to help visualise the graphical subtraction of vectors)
E. Franklin, B. Blackwell p12/50
ENGN4625/6625 2014 eBrick 1 - 13
VC Vca
Vbc Va
Vb
Vab = Va - Vb
Figure 7. Line-neutral and line-line phasors shown for a balanced three-phase system
C
“Wye” “Delta”
C
YCA
YC
YA
A YBC A
N
YB
YAB
B
B
ordinates, ℎ =
Yx
y .
So for a balanced three phase set of voltages (sequence ABC) we can write [+t , +u , +v ] =
+t [1, ℎ , ℎ]. The H matrix will be introduced later in the symmetric component transform.
E. Franklin, B. Blackwell p13/50
ENGN4625/6625 2014 eBrick 1 - 14
B
VB If the supply and cables have negligible impedance, and the neutral
is well grounded,
I A := V A /Z A I A = 23.18+ -6.212i ∣I A∣= 24.00
I B := V B / Z B I B = -12.04+ -15.97i ∣I B∣= 20.00
I C := V C /Z C I C = 2.094+ 59.96 i ∣I C∣= 60.00
I N := − ( I A+ I B+ I C ) I N = -13.24+ -37.78 i ∣I N ∣= 40.03
Figure 9: Unbalanced star load with neutral intact
This shows a large neutral current, a result of the imbalance in magnitude and the deviations in
phase of the currents in the three unbalanced loads.
i = + L × h∗ ( 13)
In the above expressions, V may actually either be the line-neutral voltages and line-neutral currents
(eg for a Wye connected load), or may be line-line voltages and line-line currents (eg for a Delta
connected load). Since the voltage and currents in the loads are different by a factor of √3 in an
ideal balanced circuit (if balanced VCA = √3 VCN), it therefore very important to be consistent
E. Franklin, B. Blackwell p14/50
ENGN4625/6625 2014 eBrick 1 - 15
Note: if we measure for example VCN, then we should use the corresponding current into terminal C
(IC) when calculating power. VCN is known as VLINE-NEUTRAL or VLN (sometimes referred to as
VPHASE). IC is known as ILINE-NEUTRAL or ILN (also sometimes referred to as ILINE). Similarly VCA is
known as VLINE-LINE, or VLL, and ICA is known as ILINE-LINE, or ILL. To avoid confusion, try to
always use the long form in each case. Also note that IC = ICA+ICB or ICA-IBC
The real power in a balanced system is given by: 4 = 3 +‰Š h‰Š cos = 3 +‰‰ h‰‰ cos ( 15)
4 = √3 +‰‰ h‰Š cos = 3√3 +‰Š h‰‰ cos , which is confusing and hence best to avoid!
However if we were to use mixed quantities, then our expression would become equivalent to:
The Nodal Admittance Matrix method solves for the injected current from voltage generators i.e.
I=Y· V
I is the n x 1 matrix (or column vector) representing the currents injected into each node, V is n x 1
matrix representing the voltage at each node of the network, and Y is an n x n matrix, the so-called
Nodal Admittance Matrix.
For large networks the admittance matrix Y will of course be very large (and as you will see is
usually a sparse matrix – lots of zeros), however by using this method the solution to any network
can be reduced to a series of matrix manipulations. These are time-consuming (to say the least) by
hand, but can be handled very reliably and efficiently by computers. This is the basis for all
complex power network solutions. The method also forms the basis for computer simulations such
as Spice, which solve this equation at each discrete time-step (with the added complication that
iterative solutions are required when non-linear elements such as diodes are included).
Starting with node 1 which has a generator connected, a shunt admittance to the common node 0
and connections to several other nodes. Applying Kirchoff’s Current Law to express injected
current I1 in terms of voltages and admittances:
etc. where the colours show where the terms came from
This leads to the general rules for the formulation by inspection of the Nodal Admittance Matrix for
any power network:
Thus the nodal admittance matrix can be written down in an automated manner without any
reference to network topology apart from noting which nodes each admittance connects to. Here it
is written for the previous network segment but extended for a general N node network.
S < + S + ⋯ S Š −S −S X …
−S S < + S + ⋯ S Š −S X …
S=‹ …•
−S X −S X SX< + SX + ⋯ SXŠ
…
… … …
If the supply and cables have negligible impedance, and the neutral
is open circuit, we obtain Y by inspection (rules in eBrick 2)
Figure 10: Unbalanced load with broken neutral
[ ]
YA 0 0 −Y A
The nodal admittance matrix is very 0 YB 0 −YB
Y :=
simple to write in this case, many 0 0 YC − YC
− Y A − Y B − Y C Y A+ Y B + Y C
terms are zero – e.g. no connection
across phases. We need to evaluate I := Y V , but first we need V N
I N = − ( I A+ I B+ I C )= 0 , or from the bottom line of the matrix,
The trick is that we don’t know VN, V N := (Y A V A+ Y B V B+ Y C V C )/(Y A+ Y B + Y C )= -6.530+ 93.73 i
so we have to solve for it. If we look
We see the neutral voltage is far from zero!
back at how the nodal admittance was V := [V A ,V B , V C ,V N ]
Now make the vector V:
obtained in the section above, at is
[
21.39+ -15.43i
essentially setting the bottom line of
the equations to zero on the LHS
(IN=0). Or you could just use KCL.
then I := Y V =
-12.45+ -23.79i
T
-8.939+ 39.23i
0
]
and ∣I 0∣= 26.37 ∣I 1∣= 26.85 ∣I 2∣
= 40.23 ∣I 3∣= 0
We see also that the neutral current is zero as expected.
The technique we used in the above example essentially to remove the neutral node N can also be
generalised to remove any number of internal nodes. This is done via a technique known as matrix
partitioning. The matrices are first reordered such that the matrix equation can be re-written as:
h ” • +•
h = S. + → • • ’ = “ —• ’
h‘ – s +‘
Here A, B, C and D are different size sub-matrices chosen in such a way that Is corresponds to all
the source currents (which we are trying to find solution for), Ii are the internal nodes with no
current injection (=0), Vi are the internal node voltages (which we don’t know values for) and Vs are
the source voltages.
The admittance matrix equation (containing unknown node voltages) has thus been reduced to a
simple calculation matrix calculation with known source voltages only. After the solution has been
found, internal node voltages can then easily be calculated if required.
Going back to our prevuious example, the NAM can be re-written in the same format, with:
Y A 0 0 − YA
A = 0 YB 0 , B = − Y , C = [-Y –Y –Y ] and
B A B C D = [YA+YB+YC]
0 0 YC − YC
œ St +t − St D •ž •Ÿ • F£
•ž pž •Ÿ pŸ • p
ht +t
› ¢
hr = ˜hu ™ = (” − •s –) ˜+u ™ = ›Su +u − Su D • • • F¢
•ž pž •Ÿ pŸ • p
hv +v › ¢
ž Ÿ
š Sv +v − Sv D •ž •Ÿ • F¡
•ž pž •Ÿ pŸ • p
C
“Wye” “Delta”
C
YCA
YC
YA
A YBC A
N
YB
YAB
B
B
Consider the nodal admittance matrices for Wye (Y) and Delta (∆) networks. We’ve already looked
at the Wye network; writing the matrix for the Delta network is even simpler:
St 0 0 −St
Stu + Svt −Stu −Svt
0 Su 0 −Su
S• = ‹ 0 Sv •, S∆ = ˜ −Stu Stu + Suv −Suv ™
0 −Sv
−St −Sv −Svt −Suv Svt + Suv
−Su St + Su + Sv
Question: What is the equivalent “Delta” circuit to a general “Wye” or “Star” arrangement of
admittances YA, YB, YC? – i.e. what component values make the two circuits above equivalent
from the point of view of their external nodes A, B and C?
Call the Delta equivalents YAB, YBC, YCA, as they connect two nodes, in contrast to the Wye with a
single subscript, as admittances here go from one node to neutral. We could obtain the result from
general nodal analysis, however it is even simpler to show, by comparing the Nodal Admittance
Matrix for both circuits, that
St Su )
Stu =
St + Su + Sv
Star→Delta ( 17)
This is referred to “straddle” / “sum”. (meaning product of the straddling nodes over the sum of all
nodes). For the special case YA = YB = YC = Y, YAB = Y/3. etc. In other words, a star
arrangement of 10Ω loads would be indistinguishable from a delta arrangement of 30Ω loads (in
terms of any measured external currents or voltages).
Conversely, the delta to star transform is of the same form, but in terms of Z’s
e.g.
otu ovt
ot =
Delta→Star otu + ouv + ovt ( 18)
If expressed in terms of Y’s, this looks a bit different: 7 Y terms, and is harder to remember.
For balanced three phase loads, Wye and Delta connections can be considered interchangeable by
the rest of the network provided that Y∆ = YY / 3, or Z∆ = 3.ZY ( 19)
Using this transformation makes calculations for a combination of star and delta loads trivial to
incorporate: e.g. the delta connected 10kVA load in Tutorial questions 1 - transform to Star (YY =
3Y∆ ), then add in the admittance to the first three (single phase) loads.
5 Power Transmission
We have seen already some of the reasons why electrical power systems normally use 3 phase
power. Power networks typically consist of combinations of generators, transformers, and
transmission and distribution lines, and distributed loads. In the circuits we have considered so far
we ignore any effects of line impedance. In practice however, voltage sources (generators or
transformers) and loads are typically spaced apart by some distance and the transmission lines
joining them have some non-zero impedance associated with them which must be taken into
consideration for real power networks.
Another (usually reasonable) assumption that we make is that voltage sources maintain a constant
supply voltage regardless of load. In reality voltages are also supplied by real transformers which
usually don’t maintain constant voltage as load is increased, although network operators can use
voltage regulation at the transformer to combat this. This is dealt with in more detail later in the
transformers section of the course.
As an interesting aside, in Australia the low voltage distribution network operators are required to
deliver mains voltage within the range 230V (or 398V line-line for 3-phase) +10% -6%. The
standard used to be 240V (415V for 3-phase) the majority of distribution networks will still operate
at this voltage until hardware is gradually changed. The network operator will check the local
network carefully before allowing a retail customer to connect a large new load to the network, or a
large source (such as a large PV system), since this can easily bring the mains voltage out of spec.
Each conductor experiences an induced voltage due to magnetic flux generated by itself and also
from both of the other two conductors. Likewise the capacitance associated with one conductor is
influenced by the charge on each other conductor. However, in the normal case where the system is
balanced (ie each conductor carrying same current with normal phase sequence) then the per unit
length line inductance and line to neutral capacitance can be given by the simple expressions
(derived in Bergen Chapter 3):
¦= ¦-
§¨ ©
, where -< is the permeability in free space
‚ <.ª« ¬
H/m ( 20)
®=
2]¯0
s , where ¯< is the permittivity in free space
¦-(
F/m ( 21)
It can be seen that inductance can be reduced and capacitance increased by decreasing the spacing
D or by increasing the conductor radius. Usually inductance is more significant and so such a
change is desirable. However D can only be safely reduced so far; the solution usually employed is
E. Franklin, B. Blackwell p20/50
ENGN4625/6625 2014 eBrick 1 - 21
to bundle conductors (the characteristic close-spaced square or triangular layout of conductors that
is often seen in transmission lines) which effectively increases the conductor radius. In this case D
is replaced by a quantity known as the geometric mean distance (GMD) between bundles and R is
replaced by the so-called geometric mean radius (GMR) of the conductor bundles.
sinh ³¦
o ° = ±¦
³¦
I1 Z' I2
³¦
S ° N¦ tanh 2
V1 V2
=
2 2 ³¦
Y'/2 Y'/2
³ = µN±
Here z is per unit length line impedance (z = r + jwl) and y is the per unit line-neutral admittance (y
¾¿
¶·¸¹ º» ¼½¸¹
Y
º» ¾¿
- For ‘medium length’ transmission lines (less than about 240 km), both and are
Y
typically close to 1. Hence the same lumped model can be used but with much simplified
parameters:
o ° = o = ±¦ and S ° = S = N¦
The so-called characteristic impedance Z0 of the transmission line is given by o< = CÁ = C• which
À q
- For ‘short’ transmission lines (less than about 80 km) the admittance can be neglected
entirely and the lumped model is reduced to a simple line impedance Z = R + jwL
This brings us to a general model that we can use for most three phase networks where line
impedance needs to be considered. A simple three phase system with transmission line impedances
included is shown in figure 9. Recalling that unbalanced currents result in mutual inductances M
between phases, the transmission network for a more general unbalanced network is also shown.
R L
M
R L M
M
R L
Figure 12: A three network with transmission line impedances (top) and mutual inductances, M,
between phases shown. Note that for a balanced network, mutual inductances are not present.
Å=
Æ
√Ç€
( 22)
√Ç€
= 3 x 108 m/s (ie. the speed of light). In practice the speed of
speed of light). The wavelength È = of a propagating 50Hz signal is thus (for v = 66% of speed
Å
propagation is somewhat less than this, but is still nonetheless fast! (typically 60% to 80% of the
É
of light) 4000 km. And the propagation delay Ê = Å for a 40km line (for eg) would be 0.2 mSec.
Ç
È=É
Å
Wavelength of oscillating signal on transmission line:
Ê=Å
Ç
Propagation delay for a transmission line length l:
VS
ZT
Transmission line, Z0
A second important property is that propagating waves reflect at the end of a transmission line and
a reflected wave propagates in the reverse direction. The reflected fraction is given by the following
reflection coefficients Rv and Ri for voltage and for current respectively, where Z0 is the
E. Franklin, B. Blackwell p22/50
ENGN4625/6625 2014 eBrick 1 - 23
characteristic line impedance and ZT is the termination impedance at the terminated end of the line
(eg a load impedance). The same applies at the source end of the line, with the source impedance
(Ë = (‘ = −
qÌ q¨ qÌ q¨
qÌ q¨ qÌ q¨
and ( 23) & ( 24)
1. If the line termination is open-circuit, then Rv = 1 and Ri = -1. The voltage at the open-
circuit terminal will then be twice the ‘sent’ voltage and the current will be zero. This is a
particular concern for designers when considering voltage surges (a lightning strike an
extreme but real example).
2. If the line termination is short-circuit, then Rv = -1 and Ri = 1. The voltage at the open-
circuit terminal will then be zero and the current will be double.
3. If the line termination ZT is matched to the characteristic impedance Z0 , then Rv = 0 and Ri
= 0. There is then no reflected wave. This is especially important for communication
systems, audio systems (you are probably familiar with this already)
The two travelling waves (one in each direction) interfere constructively or destructively, and for
lossless lines (no resistance elements) of certain length (eg multiples of quarter wavelengths – 1000
km for our previous example) and with particular termination conditions standing waves can even
be set up. These can be handled the same way and have similar consequences as for waves in other
mediums (eg sound waves). In all other situations the reflected waves are of diminishing magnitude
after each reflection and hence die out after a given time period, resulting in classic damped
oscillation (see figure below).
40KM Line example; Vin = step of 1000. V magnitude.
Voltage into line and at 20km and open circuit end.
2000
[V]
800
Source = red
400
green - mid (20km)
blue - end (40km)
0
0 1 2 3 4 [ms] 5
(file anusurge01.pl4; x-var t) v:SURGE v:20KM v:40KM
Figure 14: Propagation of a constant voltage applied to source end of a 40km transmission line with
propagation delay equal to 0.22 ms.
The frequency of the oscillation (or ringing) is determined by the propagation time of the line and
the whether the reflected signal is inverted at one or both ends. The signal decay in time (damping)
is determined by the magnitude of reflection coefficients and the propagation delay. For a lossy line
(series resistance and shunt conductance not negligible) the travelling wave is also attenuated
during propagation.
TÍ•z =
ÎÏ
If signal is inverted at one end and not other, we have two round trips per cycle:
TÍ•z =
Ï
If signal is inverted at both ends, we have one round trip per cycle:
6 Coordinate Transformations
6.1 Introduction
Just as transformation to polar coordinates can simplify analysis, transformation of circuit
quantities to different basis sets is useful. The concept is to change to a frame where the variables
are decoupled from each other, ideally producing equations in one or two variables instead of three,
six or more. A simple example is the floating neutral example, which caused the currents and
voltages to be coupled, compared to the earlier grounded neutral case, where each phase could be
analysed separately. Even with grounded neutrals, mutual inductance between windings in motors
act to couple the circuit of one phase to another. Rotating machinery is particularly complicated as
the inductance values vary as the rotor rotates.
We will consider two such transformations, the Symmetric Component Transform which can
simplify any three phase system, and the DQ0 transform which works in a frame that rotates with
the shaft of a rotating machine (motor or generator). The latter works because it transforms the
variation of rotor and stator inductance with angle into just another variation with time.
section) is also 3x3 – 3 coefficients for each component of the original quantity (e.g+t , +u , +v . ) to
A general transformation matrix (for example the symmetric component or H matrix in the next
make the 3 new quantities. Take such a transformation matrix A (from 012 to ABC)
This is an important property – if it doesn’t hold, then you have to transform back to the original
frame to calculate power. The following particular transform, the Symmetric Component
Transform, doesn’t have the power invariance property.
The basis of the symmetric component transform is the theory that any arbitrary set of three phasors
(for example the three phases of an unbalanced 3-phase system) can be represented instead by three
balanced ‘sequence sets’ of three phasors (ie 9 phasors in total). Specifically the three sequence sets
are known as the positive-sequence set (phase sequence ABC), the negative-sequence set (phase
sequence ACB) and the zero-sequence set (all in phase).
These sequence sets were introduced by Fortesque (in 1918) who noticed that for static components
(not rotating like motors and generators), the diagonal (‘self’ impedances) of the impedance matrix
such as ( 26) has values almost the same, and the off-diagonal (‘mutual’ impedances – see box at
top) are almost the same as each other.
The symmetric component transform notation we use is that the positive sequence set is represented
by V1 (and I1), the negative sequence set is represented by V2 (and I2), and the zero sequence set is
represented by V0 (and I0). Note that some texts use V+, V-, V0 for these sets. We should note
for the positive sequence set we can denote the three voltage phasors as +& , +' and +z . Of course
further that each set consists of three phasors which we can still denote as a,b, and c; for example
since each set is a balanced set, it is possible to relate the phasors to one another, ie , +' = ℎ +&
and +z = ℎ+&
The transformation makes each of +t , +u , +v out of a linear combination of +< , + , + and similarly
for current I. Working in currents (the same can be done though for voltages), we can easily write
the original three current phasors in terms of the new symmetric components:
I a I a I a I a
0 1 2
I abc = I b = I b0 + I b1 + I b2
I c I c0 I c1 I c2
I a 1 1 1 1 1 1 I a
0
which we
I abc = I b = I a0 1 + I a1 h 2 + I a2 h = 1 h 2 h I a1 = HI 012 ( 30)
expand as
2 2
I c 1 h h 1 h h I a
2
This takes the three phasors h< , h , h , and multiplies each by three coefficients (1,1,1) for the top
row, which in total gives IA, and similarly for IB 1, ℎ , ℎ and IC 1, ℎ, ℎ , where h is the 120°
a matrix (H) multiplied by the vector h< , h , h . The notation h&< is to remind us that the phasor I0 is
rotation operator (the cube root of 1) as introduced earlier. The combined operation is equivalent to
the same as the “A” phase component of itself when transformed into ABC space. (the top row of H
is all 1’s). The symmetric component phasors are shown diagrammatically below. It must be noted
however that the symmetric components are all shown here to have their A phases in phase with
each other. This is certainly not necessarily the case (as we will soon show with an example).
[I0A, I0B, I0C] , [I1A, I1B, I1C ] and [I2A, I2B, I2C]
IC IB
All in phase
IC rotation rotation
IA 0° e.g. IA 0° e.g.
IB
240∠0° 240∠0°
IA
I0: Zero I1: Positive I2: Negative
Sequence IB Sequence IC Sequence
1 1 1 1 1 1
Ó = ˜1 ℎ ℎ ™ from which it follows that Ó ∗ = ˜1 ℎ ℎ ™
1 ℎ ℎ 1 ℎ ℎ
So ( 31)
1 ∗
Ó = Ó
3
And you can confirm
( 32)
That is to get our symmetrical components from the original ‘real’ phase currents or voltages we
need to use:
I a0 1 1 1 I a
1
= I a = H −1 I abc = 1 h h 2 I b
1
I 012 ( 33)
3
I a2 1 h 2 h I c
This tells it that the symmetric component transform is NOT power invariant. This definition is
chosen so that the voltages and currents can be related easily. If we were to redefine the SCT
transform to include 1/√3 in both directions, then the voltages and currents would not be directly
comparable – a [Va,Vb,Vc] set of 11kV each would correspond to a [V0,V1,V2] set of [0,19kV,0],
which would be even more confusing. As above, we just need to convert back to ABC to get the
true power. Because of the simple relationship between components, we usually consider only the
+&< = X 0.9 ∠0° + 1.25 ∠280° + 0.6 ∠110° = X 0.9 + 0.22 − j1.23 − 0.21 + j0.56 = 0.38 ∠ − 36°
+& = 0.9 ∠0° + 1.25 ∠40° + 0.6 ∠350° = 0.9 + 0.95 + j0.8 + 0.59 − j0.10 = 0.85 ∠16°
X X
+& = X 0.9 ∠0° + 1.25 ∠160° + 0.6 ∠230° = X 0.9 − 1.17 + j0.43 − 0.39 − j0.46 = 0.22 ∠183°
The remaining symmetric component phasors can of course be calculated from these by angular
rotation. You can always check that you have got this right by summing to get Va.
It should be quite obvious, but if our three-phase system is balanced and has positive sequence then
if we calculate the symmetric components we would find that +&< = 0, +& = +& and +& = 0. This is
very useful since we can often perform the transformation on impedance matrices and solve
circuits more simply in symmetric components (and the positive sequence symmetric component is
the only one that requires solving).
where Zs and Zm are the self and mutual impedances respectively. The symmetric component
transform diagonalises this (try it!).
o• + 2oØ 0 0
o< = Ó otuv Ó = ˜ 0 o• − oØ 0 ™
0 0 o• − oØ
from ( 27) ( 35)
16 + 39 0 0
o012 = Ó−1 o”•– Ó = Ù 0 7 + 18 0 Ú
0 0 7 + 18
The significance of this ( 35) is that we have reduced an arbitrary balanced (static) circuit to three
sequence set, V1), so we are down to one equation: ÛÆ = ÂÆÆ }Æ = ÂÜ − ÂÝ }Æ , other I’s are 0.
simple equations – and if the drive term is balanced, then we only have one source (the positive
Further development of this idea leads to great simplification analysing in the consequences of
faults (short circuits) in power distribution system. The separation into separate circuits for each
component, and some simple properties allow reduction of the network to a much smaller
equivalent. The MEng course will cover this in some more detail.
E. Franklin, B. Blackwell p27/50
ENGN4625/6625 2014 eBrick 1 - 28
i+Þ+U 0 0
o_012 = ˜ 0 i + ℎ Þ + ℎU 0 ™
0 0 i + ℎ Þ + ℎ U
Transforms to ( 37)
which shows that the impedance of a rotating machine is quite different for different excitations –
in particular the if all windings are connected to the same phase, the current drawn will be very
different to the current when connected to a normal rotating three phase supply.
If we assume a motor can be represented by a delta equivalent circuit, with balanced winding
impedances / admittances and driven from a normal balanced source.
In good condition, with all windings balanced Yab=Ybc=Yca = 10∠ 40°
– SCT of I = [0, 7200, 0] Good – all positive sequence
Assume Yca has a partial short – Y doesn’t change, gets a little more resistive
Yca = 10∠ 30°
– SCT of I = [0, 7176, 418] 7% of power in neg seq, fights pos
– output is only 84% (rest is heat! – burns out?)
So simply detecting the negative sequence component > few percent detects many types of faults as
below
– Missing Phase (i.e. Vabc=240*[0, h^2, h], A phase is zero
– Short in any of the phases
– Subtle change in impedance/admittance as per the above example
Negative sequence relays are used in real systems to avoid damage to motors. The negative
sequence is far more readily detected for unbalanced operation than when any over-current
protection would kick in.
Usually problems with supply imbalance are local to a building or a single circuit. The mains feed
and distribution feed a large number of loads, so the imbalance is averaged in the distribution
circuits where the fault is likely to occur. If it is not, then the supply authority or plant management
will probably do something to correct it, such as rearranging loads into different circuits.
So we can assume a balanced source and a balanced load, apart from the fault itself, which is
invariably highly unbalanced. You can easily show (from ( 32): H-1 = 1/3 H*) that a single line (A
phase) current of 1 Amp IFABC = [1,0,0] can be represented as [I0, I1, I2] = [1/3, 1/3, 1/3].
This means we can replace the unbalanced fault current by three balanced source – the symmetric
components of IF. This then means that the impedance/admittance matrix is diagonal, and we only
need to analyse a single phase at a time, a great simplification. The circuit with a fault can be
redrawn as a circuit with three sets of balanced current sources. Although the circuit looks a lot
more complicated (9 new sources instead of one – remembering that the fault can be represented by
a current source) it is actually simpler to solve (though it probably will seem complicated still when
you first see the method!).
Figure 15: Single line fault, showing the actual circuit and the replacement of the fault by 3 sets of symmetric
component sources. Figure from Bergen 12.2
Solution to the problem comes from two important results of performing the SCT transformation:
1. we now have a balanced system (each phase is identical) and hence we can solve by per-
phase analysis
2. we can now use superposition and consider the three sequence networks separately
The three resulting networks (positive-sequence network, negative-sequence network, and zero-
sequence network) are shown in the figure below, noting that the system voltage source is a
positive sequence source. Zg is omitted from the positive and negative sequence networks because
E. Franklin, B. Blackwell p30/50
ENGN4625/6625 2014 eBrick 1 - 31
for a balanced Wye connected network there is no return current. By the same reasoning the zero
sequence network contains an open-circuit where the voltage source is because there cannot be any
zero sequence currents owing to it being a 3-wire Wye connection.
Figure 16: Per-phase sequence networks for the SLG problem (note ‘+’ used instead ‘1’, ‘-‘ instead of ‘2’) Figure from
Bergen 12.2
Figure 17: The single phase analysis for the positive sequence, and (right) the equivalent circuit used to calculate the
voltage at the fault point (Va'g), based on the top line of the SCT from V012 to VABC. That equation states that the “A”
phase voltage is the sum of the three symmetric components – therefore they can be connected in series as above.
For the SLG fault considered here we need to realise how the three sequence networks need to be
combined. Once you become familiar with the individual sequence networks working out how to
combine them for a given fault condition is the main step which requires thinking about.
We can use superposition, or simply use the first line of the SCT to realise that
+&°à = +&°à
<
+ +&°à + +&°à .
âã
X
Hence the networks can in our case be combined by series connection with a common current
So the networks are combined as shown in the figure below. The solution can be found via simple
circuit theory (you can do this to check it), and we find that:
1ä
há = 2
2ä o + o + o
3 à á
This means that analysis and control system transforms working in real, instantaneous variables
(v(t), i(t) ) have advantages. The Clarke Transform is one such example.
phase – reduces to just one component. This component would ideally be +t + +u ℎ + +v ℎ, but
the symmetric component transform that – for the most common situation – normal, balanced three
we can’t do the h operator without phase information. A close approximation is to use the 180°
component instead, and adjust the coefficients. Noting that VB + VC is at 180° to VA
+å = ® +t − ® +u + +v
To sense rotation direction, note that VB and VC interchange when rotation reverses, the difference
of these is at 90° to VA and will change sign when the rotation direction changes.
VC
-1/√2VB
Vβ VC
Figure 18: Linear combinations of VABC (using only REAL coefficients) to obtain in-phase and quadrature (90°)
components
So make a similar linear combination based on the components at 90° (the difference +v − +u so
that normal three phase produces
which when combined can represent all possible three phase phasor configurations (in the same
way as the symmetric component transform.
š√X √X
√X ¡ š√X √X √X ¡
is the Clarke transform from ABC to α, β, 0. Note that the order is different to V0,1,2 – the zero
sequence is last. This is one of the most common conventions in time domain transforms (and there
are very few conventions in transforms that are agreed by most authors)..
[V]
V C := V 0 cos(ωt − 2 ϕ3 ) -100 V_C
-200
plotxy ( t ,V A , t , V B , t , V C )
-300
Current Australian 3 ϕcolours
T -400
V ABC := [ V A , V B ,V C ] 0 0.01 0.01 0.02 0.02 0.03 0.03 0.04
[s]
2/ √6 − 1/ √6 − 1/ √6
ClarkeT :=
[ 0 − 1/ √2 1 / √2
1/ √3 1 / √3 1/ √3 ] 500
[ ]
1.000 0 0 400 V_A
T
ClarkeT ClarkeT = 0 1.000 0 Power Invariant V_alpha
300
0 0 1.000 V_beta
200 V_0
Note: In α ,β , 0 order (0 last, c.f. SCT where 0 is first).
100
VT := ClarkeT V ABC 0
[V]
-100
-200
T T T
plotxy ( t ,V A , t , VT 0, ind , t , VT 1, ind ,t ,VT 2, ind ) -300
-400
-500
0 0.01 0.01 0.02 0.02 0.03 0.03 0.04
[s]
Figure 19: Clarke transform operating on balanced three phase inputs VA,B,C (above) producing Vα (in phase) and Vβ (90°) and zero
sequence outputs. In the CompPad script above, VT is the transformed voltage vector, the plotting function plotxy requires column
vectors (hence the superscript T indicating transpose in the final line).
Unfortunately, there are many variations on the other details of these transformations, you have to
make sure you use a consistent set of matrices. We use the “modern” convention following the
EMTP theory book and “Power Systems Analysis” by Bergen and Vittal (although Bergen orders
0,α,β and 0,d,q). Apart from whether the order is α, β,0 (which we use) or (0,α,β – Bergen p227),
more modern texts (Bergen, EMTP theory) usually use the sign of the β row [0, -1/√2, 1/√2 ], that
we use, which means that for normal rotation the β component leads, and others (Fitzgerald, Bose,
MIT lecture notes) the opposite sign (and β lags). Also, there is a popular alternative that is not
power invariant, but preserves the voltage instead (contains numbers like 2/3). Differences between
authors are summarised in a footnote on the following page. Although the Clarke transform is
simple to write down, the true usefulness becomes clearer when we consider the DQ0 transform
below.
The D (direct) axis is the axis of the magnet in this simple picture. In a large motor with an
electromagnet for the rotor, that electromagnet is complex, and has windings with equivalent axes
both in the D direction and the 90° or Q direction. Whether the Q direction is taken to lead or lag
the D direction again depends on conventions. We choose Q lagging the D direction in rotation
(although the component VQ leads VD), and that means with the rotor is lagging the rotating
magnetic field by 90° under load, the magnetic field lines up with the negative Q direction.
The DQO transform can be written as a simple 2x2 rotation on the α,β coordinates of the Clarke
transform combined with that transform.
+© cos − sin +å
•+ ’ = “ — • + ’
ç sin cos æ
( 39)
Alternatively it can be written as a time varying 3x3 as follows. Again, be wary of differences in
ordering of components and constant factors according to author2, and be careful to use consistent
ordering and the matching inverse. (You can retrieve the Clarke transform by putting θ = 0)
2
Bergen orders 0,d,q and is power invariant. EMTP orders d,q,0 and is power invariant. Fitzgerald orders d,q,0 and his
transformation is not power invariant (he lists one that is). Bose(p59), Kraus orders q,d,0, and is also not invariant.
Bergen takes θ as D axis relative to A axis(p222), and D leads Q, the q row is (p8-6)+ sin(θ -2π/3), +sin(θ+2π/3.
Krause takes θ as Q axis relative to A axis(p274), the Q axis leads, and the q row (p311) is + cos(θ -2π/3), +cos(θ+2π/3)
Fitzgerald θ as D axis relative to A axis(p271), the Q axis leads, and the q row (p271) is -sin(θ -2π/3), -sin(θ+2π/3)
EMTP theory θ as D axis relative to A phase axis(p8-21), Q axis lags, the q row is (p8-6)+ sin(θ -2π/3), +sin(θ+2π/3)
3
Actually θ is the angle of the rotor/Npp where Npp = the number of pole pairs (=1 in this case, one North, 1 South).
More on this in motors chapter.
E. Franklin, B. Blackwell p35/50
ENGN4625/6625 2014 eBrick 1 - 36
2] 2]
œ cos cos é − ê cos é + ê£
+© › 3 3 ¢
2› 2] 2] ¢ +t
+
Ù çÚ = è sin sin é − ê sin é + ê ¢ ˜+u ™
3› 3 3
¢ +v
DQ0
+< › 1 1 1
( 40)
› ¢
transform
š √2 √2 √2 ¡
where θ is the angle of rotation of the rotor3, and is typically ωt. This is suggestive of a constantly
changing transformation matrix, whose coefficients vary so as to put the amplitude of the in-phase
component into one output (VD), the quadrature component (not Vβ) into another (VQ) and the zero
sequence into the remaining one. Normal rotating three phase, with VA peaking at t=0 would
correspond to (VD=1, VQ=0, V0=0). The same waveform delay by 90° would produce (0,1,0), and a
further 90° → (-1,0,0). This is a nice alternative way to view the transform. Recall the picture in
Figure 18 of the Clarke transform as a linear combination (with real coefficients) of VABC. Ask
so that ô( )+t + ( )+u + _( )+v removes the time variation of the Clarke transform Vαβ0?
Noting the constant power property of three phase +t + +u + +v = Const (typically 415V) the
coefficients are cosine functions like VA, VB.VC respectively - that is cos , cos ( − 2]⁄3),
cos ( + 2]⁄3) as in the top row of ( 40). Similarly for the second row (sin), and the last is just
the same as the zero sequence in the previous transformations. This is spelt out in more detail in
the example given in class, which is on the next page.
Although this results in a much more slowly varying output, as shown in Figure 21, in fact the
output is available with a very short delay (or latency) time – there is no need to average over a
cycle (or half cycle) to obtain the amplitude and phase. This is therefore highly suitable for high
performance motor control systems with fast response times, without risking instability – vector
control. The information required for control is available instant by instant, provided that the
variation of θ with time is known accurately. (Simulink induction motor control example :
http://www.mathworks.com.au/help/toolbox/physmod/powersys/ug/f4-10148.html)
Figure 21: Motor startup voltage waveforms, for a simple model of a motor. Current waveforms would be very similar (not shown).
The right figure shows the effect of the dq0 transform on current waveforms, making them much simpler. The D cpt (red) represents
the real power, Q (yellow) the reactive power. Both show an inertial lag during acceleration, which mainly changes the reactive
impedance during that time. The dashed lines show the current waveforms with the lag eliminated. Note that these are stator
currents. The most common application is for rotor currents (fictitious and actual).
This highlights one of the potential problems in application – how to obtain the angle (θ) of the rotor?
3
Actually θ is the angle of the rotor/Npp where Npp = the number of pole pairs (=1 in this case, one North, 1 South).
More on this in motors chapter.
E. Franklin, B. Blackwell p36/50
ENGN4625/6625 2014 eBrick 1 - 37
Rotary encoders are one mechanical solution. Various intelligent algorithms from phase locked loops to
neural networks can be used to estimate θ if encoder information is not available.
Example:
We can obtain this transform in a different way if we ask the following questions (an expanded
form of the question asked on the previous page):
How can we obtain the instantaneous voltage from a three phase system?
This reflects the amplitude of all three components, but loses phase information (Error! Reference
source not found.). This may be useful but sometimes we must have phase information.
How can we obtain both magnitude and phase information quickly from a 3 phase system?
Answer – replace VA2 above with VA cos(ωt); that is one of the terms is the actual VA, including
any phase shifts, and the other is a copy of VA that is fixed in phase, and so on for VB2 and VC2.
Figure 22: Three phase system showing a phase jump at 20ms, a decrease in magnitude from 40-60ms and a frequency
shift (equivalent to a linear increase in phase) from 100-120ms. Magnitude is quickly and accurately measured by
√(VA2+VB2+VC2), but phase variations are ignored. The right graph shows that replacing VA2 by VA cos(ωt) etc., a
quadrature pair of signals VD, VQ (dashed green and yellow respectively) are generated, returning instantaneous values of
both amplitude (√(VD2 + VQ2)) and phase (atan(VD/VQ)).
This is just the first line of the DQ0 transform, replacing θ by ωt:
Now the in-phase component is in VD, and the 90 phase component is in VQ. This can be related to
the answer to the first question (VM3): VD = VM3 cos(ϕ) and VQ = VM3 sin(ϕ), where ϕ is the phase
delay of the voltage set being measured. Figure 23 shows a typical real time controller using these
techniques. The coordinate transforms can be performed by high speed digital signal processors
(DSP) such as the TMS320C30 .
Figure 23: Block diagram of "Vector Controller" using the dq0 transform for high speed estimation of motor variables,
and fast responding control (Wikimedia commons)
Another simplification provided by this transformation is that the inductances, which depend on the
shaft rotation, are made independent of time by this transformation. Considering Figure 20, the
iron in the rotor would strongly couple the A+ coil to the A- coil, in the orientation shown,
increasing the self inductance of the A coil set. 90° later, this coupling would disappear (and
would cross-couple B and C). We therefore need to use V = d/dt(LI) = I dL/dt + L dI/dt in KVL.
The transformation to the rotating rotor frame removes this dependence to a reasonably good
approximation. How this happens is beyond the scope of this course.
The Kron transform refers variables to the frame of the rotating magnetic field generated by the
stator windings, instead of the rotor frame. In equilibrium, for a synchronous motor, the two frames
rotate together. Differences between the two frames occurs mainly during start-up and load
changes, so the Kron approach is used for analysis of such dynamic problems.
There are many more concepts and terms associated with motor/generator theory that we will cover
in a little more detail in the chapter on motors.
The main advantage of using per-unit notation is when transformers are involved (or fault currents
are being calculated in power distribution systems). In this case impedance and voltage drop
calculations can be done without considering the transformer ratio and a complex power system is
somewhat simplified and easier to inspect with meaningful interpretation. In addition, often the %
voltage drop is more meaningful than the actual. When the real units are required, the actual units,
taking into account the turns ratio, are multiplied in.
These are not recommended for beginners, because a lot of information is lost in the process, so it is
harder to find mistakes. However any electrical power engineer does need to know the notation.
Per unit notation is the standard in power systems analysis.
Since the four basic system variables - power, voltage, current and impedance (or admittance) – are
linked via two equations S = VI* and V = IZ we can only arbitrarily choose two base quantities and
the other base units will follow. It is normal for power systems to choose power and voltage as the
chosen base units and then calculate the base current and base impedance quantities, but this can be
different depending upon the situation. Remember that base quantities are magnitudes only, so the
variables all still retain the same relative complex values in per units notation.
i +
So if for example we choose base power SB and a base voltage VB (which might be the rated power
of our load and the system voltage) then we can use hu = uä+ and ou = uäh . We then simply
u u
convert all of our real variable (which are phasors) to per unit values via +÷ø = +ä+ etc. and then
u
all analysis can take place as per normal.
Translation! 350kVA means the total kVA over three windings (as it doesn’t say otherwise).
Impedance in this type of problem refers to the Thevenin equivalent series impedance, sometimes
called short circuit impedance. It is usually mainly leakage inductance, deliberately included
during manufacture to limit short circuit (fault) currents. It is not stated whether the transformer is
delta or wye, but we can assume that the primary and secondary have the same topology. (One of
the virtues of per unit notation is that you can get the answer without knowing all the details, such
E. Franklin, B. Blackwell p40/50
ENGN4625/6625 2014 eBrick 1 - 41
as is it delta or wye?). No voltage regulation in the source means that the source voltage doesn’t
change when connected to this circuit. The X:R ratio is given because the phasor relationship
between the terminal voltage and the voltage drop across the impedance matter, as they
add/subtract vectorially. Note that the problem already lets us know that we need to use per unit
notation (with impedance being measured as a %).
If we call the rated transformer voltage v := 1 per unit and the current
− acos (0.7071) j
i L := 1 e = 0.7071− 0.7071 j , then the impedance is
j atan(4)
z L := 0.045 e = 0.01091+ 0.04366 j
Set the primary voltage v inp := 1 , the the secondary voltage is
v LD := v inp − i L z L = 0.9614− 0.02315 j
So voltage drop is v drop := ∣v inp∣− ∣v LD∣= 0.03831 per unit.
It is worth noting that a change of base in per unit system analysis is simple. It is typically required
when analysing at systems with several components. A conversion to a new per unit base can be
done simply without having to go back to real quantities first. You can probably work out
yourselves how to do this… we won’t cover it in this course.
In power electronics, waveforms are mostly periodic and are symmetric is various respects. This
allows the use of Fourier series in place of integrals (if f(t) is periodic), and allows simplification by
the use of the trigonometric form (i.e. cosine, sin instead of ejθ), by exploiting symmetries. In power
electronics it is extremely useful to consider a waveform in terms of its fourier series.
We will see that the Fourier series for the input current to a 3 phase rectifier needs only cosine
terms, and of those, only odd harmonics (f = nf1, where f1 is the fundamental (50Hz) and n is odd).
= ‚ E< T cos -_ . _
‚
ú ( 42)
ûú = ‚ E< T sin -_ . _
‚
( 43)
8.1.1 Symmetry
The symmetry of the periodic function (symmetry about the y-axis) can be taken advantage of to
simplify the fourier series coefficients further since only some are non-zero. The following table
(taken from Mohan Chapter 3) shows the coefficients for common symmetries and their definitions:
• all sin terms will go to zero, as the product will be a symmetric odd function
• for the remainder, we only need to integrate to the right of the origin.
Half wave symmetry means that the wave repeats with inversion every half cycle. (like the current
in a full wave rectifier (confusing ‼).
And another commonly useful symmetry is even quarter wave symmetry (which is just even and
half wave combined). – waveforms with this symmetry only have one in four of the components
non-zero.
2π wt
2 ‚ 2 −cos -_
‚
ûú = 8 sin -_ . _ =
] < ] - <
2
= − cos -] + 1
-]
E. Franklin, B. Blackwell p43/50
4
ENGN4625/6625 2014 eBrick 1 - 44
4 4 4 4
T = sin _ + sin 3_ + sin 5_ + sin 7_ +⋯
π 3π 5π 7π
These first four terms are plotted below, along with the sum of these terms. The square wave
waveform can clearly be seen taking shape. These harmonic components of the
1.5
0.5
0
0 5 10 15 20 25 30 35
-0.5
-1
-1.5
1.5
0.5
0
0 5 10 15 20 25 30 35
-0.5
-1
-1.5
sin -_
äY
T =
«t
‚Y úY
úý ,X,Z…
ü
T = sin -_
Ît
‚ úý ,X,Z… ú
ü
T = + sin _ − cos -_
t t t
‚ ‚ úý ,Î,ƒ… ú
Y
ü
T = − cos -_
t Ît
‚ ‚ úý ,Î,ƒ… ú
Y
8.4 Power factor revisited (Non-linear Power Factor) & harmonic distortion
We previously introduced power factor, defined as the cosine of the phase angle between voltage
and current, or equivalently the angle of the complex power variable. This is otherwise known as
the Displacement Power Factor (DPF) – displacement referring to the displacement in time or phase
difference.
However, in power electronics we often have a sine wave voltage supply and a non-linear circuit
which results in the current waveform consisting of the fundamental (with the same frequency as
the voltage waveform) plus various harmonics. Recalling that each of the harmonics are orthogonal
to the fundamental it follows then that only the fundamental current waveform draws any real
average power from the source; current is drawn from the supply for all other harmonics but with
no net power transfer (analogous with current being drawn to supply reactive power only). The true
Power Factor or Non-Linear Power Factor (NLPF) (sometimes even just referred to as Power
Factor) is then the ratio of the fundamental to the total current multiplied by the Displacement
Power Factor.
s4j = cos
h¬ör
U 4j = . s4j
h¬ör
Another commonly used term is the Total Harmonic Distortion (THD). It is a measure of the
combined magnitude of the harmonics as a fraction of the fundamental waveform… so ideally it
E. Franklin, B. Blackwell p45/50
ENGN4625/6625 2014 eBrick 1 - 46
would be close to 0. THD is defined by the squares of voltage or current waveforms (since it can
be related to power) as follows (values are RMS values):
h + hX + hÎ + ⋯ + hü
cÓs = è
h
h + h + hX + hÎ + ⋯ + hü h
cÓs + 1 = =
h h
And thus easily re-write the expression for NLPF in terms of THD:
1
U 4j = . s4j
√1 + cÓs
ATP will only be available this year to Master’s students who are willing to tackle this powerful but
formidable tool.
4 Figure 24: Screen shot of the ATP simulation of various generators and
Simulation Program with Integrated Circuit Emphasis
motors connected by three phase buses.
E. Franklin, B. Blackwell p46/50
ENGN4625/6625 2014 eBrick 1 - 47
Spice can be used to simulate power electronics (although originally for ICs) LTSpice is more
suitable than pSpice, as there are no limitations, and optimised for Power. Power circuits are
usually non-linear, so transient solutions (time-dependent solutions for V and I) are frequently
required.
9.2.1 Accuracy:
1) Most commonly, the values are accurate, but the point spacing on the graph may undersample
the data, giving the wrong impression – e.g. jagged waveform. Use Maximum Timestep (LT)
or Step Ceiling (pSp) under Setup/Transient to request finer steps (the temporary output file will
grow…)
2) .OPTIONS: Typically Power Electronics problems require relaxed accuracy – calculating a
100Amp current to 1picoAmp accuracy is neither necessary nor efficient. Two typical tuning
adjustments are abstol=1e-6 and gmin=1e-6. This is under Setup/Options(pSp) and
Simulate/Control Panel/Spice(LT). In LT, most of these setting are not saved, so it is better to
use Spice directive text (next to comments), they will stay with the circuit, and be easily visible
so you don’t forget.
Example: .options abstol=1e-6 gmin=1e-6 ; LTSpice – relaxed accuracy.
• Be careful relaxing accuracy if you are using low power devices as well – such as a micropower
comparator or Opamp. They will probably operate on much smaller currents. The alternative is
to use behavioural voltage/current sources (bv). As a last resort, you can try reltol=0.003 or
0.01, but check that the results don’t change appreciably with reltol (except you would expect
the computation to run faster – that is the point!
• No spaces allowed in values: (e.g. 10 Ohm gives an error “Missing value”: instead use 10.Ohm -
decimal point separates the “Oh” from the zero clearly (or 10Ohm or 10R or 10ohm) ) Also
need to spell MEG 10Mohm means 10 milliohm, similarly 7MegaHz for frequency (MegaHz
is OK at least in LTSpice).
• You need an earth somewhere e.g GND_EARTH.
• AC Sweep analysis does not need a particular input voltage source, except that it cannot be
0Volts.
2. If you set up complicated analysis, and wish to repeat that for a number of circuit changes, you
can check “Restore Last Probe session” under Analysis/Probe Setup in the Schematic editor.
Downside can be error messages about “missing” traces when changing files.
3. For LTSpice, you can save a plot file (.plt) with the plot setup you like (variables, scales etc). If
it has the same first name as the .asc main file, it will automatically determine what is plotted,
scales etc.
9.2.3 Libraries:
• The pSpice library browser is tricky to use. This works: put * in the left box (Part name). Put
*fet* in the right (Description search) and press the search button, then click on the returned
(FET) part names to see the description. There are only a few transistors, JFETs, two
MOSFETs one IGBT and one SCR (2N1595). The 1N4002 diode model (D1N4002) is quite
good.
• The LTSPice library has fewer components at first sight, but many are multi-function – e.g.
there are >30 NPN transistors in the properties of the NPN device. (and many of their
proprietary devices) . You can also easily use manufacturer’s library files. Some .sub files can
be fond in the Simulations handout folder to show the syntax, and they should be put in the
directory c:/Program Files/LTC/SwCADIII/lib/sub. (see the example PWM_Half_Single.asc)
.sub files are the simplest, they only have electrical data, and need to be attached to an image.
The generic devices in lib/sym/misc (e.g. NIGBT) are easy to attach models to, just put the
model name (not filename) in the SpiceModel row in the properties (right click symbol). For
the components that have multiple choices (e.g. Diode), you need to right click on the diode
model name (not the symbol) to be able to type you own model name in. pSpice should also be
able to accept this type of file, but I haven’t worked out how yet, and you will quickly run into
the component count limit.
• Generic devices: pSpice has “BREAK” devices (very simple model) and LTSPice has a
skeleton IGBT symbols to which you can attach properties or .sub circuits (see the example
PWM_Half_Single.asc)
RMS: The simplest is the RMS() function in add/Trace. However if there is time dependence
(transients), then to calculate the final or “steady state” value, you must either remove data from
early times and ensure that enough time has elapsed, or use a one cycle average, which
converges much more rapidly. For example sqrt(avgx(I(R1)*I(R1),20ms)) is a 50Hz 1 cycle
(i.e. over 20ms: avgx is a running average) - this gives the RMS current in R1. To discount data
early times, use the “No Print Delay” field in pSpice (Setup/Transient) or the “Time to start
saving data” under LTSpice. Note: in LTSpice, RMS and Average under ctl-Left mouse (trace
title)
avgpwr(a) = avgx((v(a:1)-v(a:2))*i(a),20ms).
rms20(a) = sqrt(avgx(a*a,20ms))
Note: the default file type is “probe utility” file .prb, which I tend to delete often……careful.
• Power in LTSpice – Alt left click brings up a “thermometer” icon, and adds the VI product to the
plotted quantities. Doesn’t work in AC sweep mode. Also, there doesn’t seem to be a running
average, (avgx in pSpice), but you can “low pass filter” power by making a b voltage source
with I and V in the expression, and feeding a filter.
• Bode (dB/phase vs freq) or Nyquist (Complex plane, freq is parameter) available in LTSpice –left
click on axis.