Sei sulla pagina 1di 9

DESIGN PROCEDURE BLOCK DIAGRAM

FIELD DATA
A,r

CONDUCTOR SIZE
ts,d,Io

TOUCH & STEP


CRITERIA
Etouch70, Estep70

INITIAL DESIGN
D,n,LT,h

GRID RESISTANCE
Rg,LT
MODIFY DESIGN
D,n,LT,LR

GRID CURRENT
IG

YES
GPR < Etouch

NO

MESH & STEP


VOLTAGES
Em,Es,Km,Ks,Ki,Kii

NO
Em<Etouch

YES

NO
Es<Estep

YES

DETAIL
DESIGN
EARTHING CALCULATION

A GENERAL DESIGN DATA

1 Soil Resistivity, r : 600 Ohm-M

2 Gravel Resistivity, r s : 2000 Ohm-M

3 Symmetrical Short Circuit Current, Iefs : 50000 A

4 Duration of Earth Fault Current, ts : 0.3 Sec

5 Design Ambient Temperature : 50 ° C

6 Thickness of Crushed Gravel, hs : 0.3 m

7 Depth of Earth Grid, h : 0.8 m

8 Reference depth of the Grid, h o 1 m

9 Standard Used IEEE - 80 : 2000

B SIZE OF EARTHING CONDUCTOR :

I
Amm 2 =
 TCAP  10 4
  K 0  Tm  Eqn.: 40 Page : 43
  ln  
 t ca r r r   K T  IEEE Std. 80 - 2000
   0 a 

Where

Material Proposed

ar = Resistivity of Conductor Material 0.0032 Ohm - M

rr = Thermal co-efficient of resistivity at reference temperature Tr in 1/°C 20.1

Tm = Max. allowable temperature in °C 419 °C

Ta = Ambient temperature in °C 40 °C

Ko = 1/a0 or 1/ar - Tr in °C 293

Iefs = rms current in Ka 50 KA

tc = Duration of Current in s 0.3 Sec.

TCAP = thermal capacity per unit volume from Table 1 3.93 J/(cm³°C)

Amm² = Conductor cross section in mm² 402 mm²

SELECTED CONDUCTOR (GI Strip) = 75 mm x 6 mm = 450.0 mm²

Diameter of equivalent Grid Conductor ,d = 0.03 m


EARTHING CALCULATION

TOUCH & STEP CRITERIA

r  rs Eqn. 21, Page 21, IEEE 80 2000


K =
r  rs

 r 
0 .09  1   Eqn. 27, Page 23, IEEE 80 2000
 r s 
Cs =
2 hs  0 .09

K = Reflection factor between different material resistivities

r = Resistivity of the earth beneath the surface material in W.m

rs = Surface material resistivity in W.m

hs = Thickness of the surface material in m

Cs = Surface layer derating factor

K = -0.54

Cs = 0.91

0.157
Estep70 = (1000 6Cs  rs ) Eqn. 30, Page 27, IEEE 80 2000
ts
Where

Estep 70 = Step Voltage for body weight of 70 kg

Estep 70 = 3412.28 Volts

0.157 Eqn. 33, Page 27, IEEE 80 2000


Etouch70 = (10001.5Cs rs )
Where ts

Etouch70 = Touch Voltage for body weight of 70 kg

Etouch70 = 1068.05 Volts


EARTHING CALCULATION

C INITIAL DESIGN ASSUMPTIONS

Length Breadth
Preliminary Layout of Grid = 450 250

n = Number of parallel conductors = 15

D = Conductor Spacing = 30 m

h = Depth of grid burial = 0.8 m

LT = 2  Na  L

Lp = Length of the conductor across perimeter = 1800 m

Nr = No. of Ground Rods = 33

Lr = Length of Ground Rods = 3 m

LR = Total length of Ground Rods = 99 m

LC = Total length of buried condcutor = 8200 m

LT = Total length of buried conductors & rods = 8299 m

Lx = Maximum length of conductor in X-Axis = 450

Ly = Maximum length of conductor in Y-Axis = 250

D GRID RESISTANCE

1 1  1 
Rg = r   1  
 LT 20A  1  h 20/ A 

Where

A = Area of the Grid = 112500 m²

Rg = Grid Resistance

Rg = 0.87 W

E MAXIMUM GRID CURRENT

IG = D f  I g
Where

Ig = Maximum grid current in A 50000 A

Df = Decrement factor for the entire duration of fault, given in s 0.6

IG = 30000 A

F GROUND POTENTIAL RISE

GPR = I G  Rg

GPR = 26042.3 V
EARTHING CALCULATION

GPR

VERIFICATION FOR HUMAN SAFETY

The safety to personnel is specified by IEEE 80, which requires to limit the development of
electrical potential to dangerous value during earth fault current.

The regulation stipulates the following parameters to be within the permissible limit

a) Step Voltage (Foot to Foot Contact)

b) Touch Voltage(Hand to Foot Contact)

CALCULATION FOR ACTUAL DERIVED STEP & MESH VOLTAGE

A Mesh Voltage

r  IG  K m  K i
Emesh ( Design ) =
   Eqn. 80, Page 91,
L C  1 . 55  1 . 22    L
Lr IEEE 80, 2000
  L2  l 2  R

  x Ly 
Ki = Corrective factor for current irregu-
larity

K i = 0 . 644  0 . 148 n

Where

n = n a  n b  n c  n d

2  LT
n a =
LP
na = 9.1

nb = 1 for square grids = 1

nc = 1 for square and rectangular grids = 1

nd = 1 for square, rectangular and L-shaped grids = 1

n = 9.11

Ki = 1.99

Km = Spacing factor for Mesh Voltage Eqn. 68 Page 113 IEEE 80

Km =
1  D2
ln  
 D  2 h 2  h   Kii ln  8 
Eqn. 81, Page 93
   IEEE 80, 2000
2  16 hd 8 Dd 4 d  Kh    2 n  1 

Where

Kii = Corrective wieghting factor that adjusts the effect of inner conductors on the corner mesh

1
K ii = 2

(2  n) n
EARTHING CALCULATION

Kii = 0.64

Kii = 1.00 With Rods

Kh = Corrective weighting factor that empasising the grid depth

 h 
=  1  
 ho 
Where

ho = Reference depth of grid = 1

h = Depth of the ground grid conductor = 0.8

Kh = 1.34

Km = 0.96

Emesh (Design) = 4104.44 Volts

Calculated Mesh Voltage is Greater than the Tolerable Touch Voltage. MODIFY DESIGN

B Step Voltage

Voltage developed for step as per the earthing system proposed during full Earth fault current

Estep ( Design ) =
 Ks
 Ki  r  I G  Eqn. 92, Page 94
0 . 75  L C  0 . 85  L R  IEEE 80, 2000

Where

Ks = Spacing factor for Step voltage

1  1 1  1  0 .5 n  2

Ks =       Eqn. 94, Page 94, IEEE 80, 2000
  2 h D  h  D  

Ks = 0.220

K i = 0 . 644  0 . 148 n

Ki = 1.992444444

Estep (Design ) = 1265.62 Volts

Estep (Design ) = 1266 Volts

Calculated Step Voltage is Lower than the Tolerable Step Voltage.HENCE SAFE
EARTHING CALCULATION

SUMMARY

A EARTH GRID CONDUCTOR

Type of Conductor Zinc-coated steel rod

Size of Conductor 450 mm

Length of Conductor 8200 mtr

Depth of Conductor 0.8 m below GL

B GROUND RODS

Total Length of Ground Rods 99 mtr

Length of Individual Ground Rods 3 mtr

No. of Ground Rods 33 No.

C HUMAN SAFETY

UNIT Designed Value Permissible Value


Step Voltage
Volt 3412 1266
Mesh Voltage
Volt 1068.05 4104
TABLE 1 - MATERIAL CONSTANTS

Material Fusing
Description Conductivity ar factor K 0 at Temperature
at 20°C (0°C)
(%) Tm (°C)

Copper annealed
1 soft - drawn 1 100 1 0.00393 1 234 1 1083 1
Copper, commercial
hard - drawn
2 2 97 2 0.00381 2 242 2 1084 2
Copper-clad steel
3 wire 3 40 3 0.00378 3 245 3 1084 3
Copper-clad steel
4 wire 4 30 4 0.00378 4 245 4 700 4
Copper-clad steel
5 rod 5 20 5 0.00378 5 245 5 1084 5
Aluminium EC
6 Grade 6 61 6 0.00403 6 228 6 657 6
Aluminium 5005
7 alloy 7 53.5 7 0.00353 7 263 7 652 7
Aluminium 6201
8 alloy 8 52.5 8 0.00347 8 268 8 654 8
Aluminium-clad steel
9 wire 9 20.3 9 0.0036 9 258 9 657 9
Steel, 1020
10 10 10.8 10 0.0016 10 605 10 1510 10
Stainless - clad steel
11 rod 11 9.8 11 0.0016 11 605 11 1400 11
Zinc-coated steel
12 rod 12 8.6 12 0.0032 12 293 12 419 12
13 Stanless steel, 304 13 2.4 13 0.0013 13 749 13 1400 13
TCAP
rr Thermal
20°C(mW. Capacity
cm) [J/(cm³.°C]

1.72 1 3.42

1.78 2 3.42

4.4 3 3.85

5.86 4 3.85

8.62 5 3.85

2.86 6 2.56

3.22 7 2.6

3.28 8 2.6

8.48 9 3.58

15.9 10 3.28

17.5 11 4.44

20.1 12 3.93
72 13 4.03

Potrebbero piacerti anche