Project Job no.

Calcs for Start page no./Revision


3
Calcs by Calcs date Checked by Checked date Approved by Approved date
F 20/06/2017

Negative internal pressure coefficient; C fig_ng = -0.30

Dynamic response factor; C dyn = 1.00


Density of air;  air = 1.20 kg/m 3
W ind pressure on windward side case 1; p zw1 = (0.5   air)  [V des. ]2  (C fig_we - C fig_ng )  C dyn = 0.96 kPa
W ind pressure on windward side case 2; p zw2 = (0.5   air)  [V des. ]2  (C fig_we - C fig_ps )  C dyn = 0.48 kPa
W ind pressure on leeward side case 1; p zl1 = (0.5   air)  [V des. ] 2  (C fig_le - C fig_ps )  C dyn = -0.91 kPa
W ind pressure on leeward side case 2; p zl2 = (0.5   air)  [V des. ] 2  (C fig_le - C fig_ng )  C dyn = -0.43 kPa
Design wind pressure; p z = max(abs(p zw1) , abs(p zw2) , abs(p zl1 ) , abs(p zl2 )) = 0.96 kPa

DL = 150.0 kN

1.5 m 2.5 m

1 2 3

1m 1m
1.2 m
2.1 m

0.7 m 0.6 m 0.7 m

Loading details for strip


No. Dead load Live load Wind load
DL e DL LL e LL WL
(kN) (mm) (kN) (mm) (kN/m)
Strip 1 57.0 0 0.0 0 1.2
Strip 2 93.0 0 0.0 0 1.5
Strip 3 0.0 0 0.0 0 1.2
Analysis for ultimate load state (ULS)

Load combination 1 - [1.2 DL + 1.5 LL]


No. Ultimate Primary MI of cracked Combined Design Design
moment section moment
load moment strength status
(check
Pu M ua Icr Mu M n - Mu
(kN) (kNm) (mm 4 ) (kNm) (kNm) Vs.
M n )