Operating Manual
Ver.1.2
TABLE OF CONTENTS
Digital Excitation Equipment type RXEE-2C
1 OVERVIEW.................................................................................................................................4
4.1 SPECIFICATIONS.................................................................................................................6
4.2 PROTECTION FUNCTIONS..................................................................................................6
4.3 SYSTEM DATA....................................................................................................................7
5 EXCITATION REGULATOR...................................................................................................7
5.1 HARDWARE.........................................................................................................................7
5.1.1 Main Control Unit........................................................................................................8
5.1.2 Touch Panel Unit........................................................................................................10
5.2 SOFTWARE........................................................................................................................11
5.2.1 Basic Functions..........................................................................................................11
5.2.2 Function Modules.......................................................................................................12
5.2.3 Limit Functions...........................................................................................................14
6.1 STRUCTURE......................................................................................................................17
6.2 CONNECTION DESCRIPTION............................................................................................17
6.3 STATIC TEST.....................................................................................................................17
6.4 OPERATION SYSTEM TEST..............................................................................................17
6.5 OVER-VOLTAGE PROTECTION AND DE-EXCITATION CIRCUIT......................................17
2
睿信创和电气
RXCH Electric
8 APPLICATION ENVIRONMENT.........................................................................................27
10 TROUBLESHOOTING.......................................................................................................30
1 Overview
The RXEE series excitation system for synchronous generator is composed of the main
control module, intelligent thyristor converter and intelligent display module. CAN network is
3
Digital Excitation Equipment type RXEE-2C
adopted to connect each module. Main control unit uses 32-bit floating-point DSP chip as the core
of computing and control. The main circuit of RXEE excitation system adopts three-phase full-
controlled bridge rectifier and linear/nonlinear resistance de-excitation system. The RXEE
excitation system has a variety of automatic regulating modes such as Automatic Voltage
Regulating mode, Field Current Regulating mode, constant Power Factor regulating mode, constant
Reactive Power regulating mode and PSS. The system is in conformance with the relative standard
GB/T7409.3-1997, GB10585-89 and IEC34-16.
4
睿信创和电气
RXCH Electric
5
Digital Excitation Equipment type RXEE-2C
5 Excitation Regulator
5.1 Hardware
RXEE excitation regulator is composed of the main control unit, touch panel unit, power
transformer, measuring transformer and signal relays.
6
睿信创和电气
RXCH Electric
front view
R6 R5
R7
XD
wire socket
TERMINAL
Generator Reactive
Voltage power
K 012 K 017 K 020 K 021 K 022 K 025 K 026 K 027 K 028 K 029
PV 81 PV80 IN T E R N A L
wirer socket
P V 8 0 -1
K 030 K 031 K 032 K 033 K 034 K 035 K 015 K 016 K 045
wire socket
X3 X4
C M P
DSC DSC
(touch panel)
TERMINAL
TERMINAL
wire socket
XP E x te r n a l
E x te r n a l S1
wire socket
S061 S060 S010 S011 S070 S071 S030 S031
QM OFF QM ON CH I CH II AVR ON FCR ON FLASHING INVERT
ON
DY1 DY2 DY3 DY4
S020 S021 C001 C 002 C 003
RAISE LOWER X2
X1
wire socket
TERMINAL
Q1 Q 2 Q 3 Q 5 Q 6 Q 7 Q 10 CZ
E x te r n a l
KM 1 V2 V3 V 010 V 012 V 014 V 015 V 016
wire socket
g ro u n d tie r
T6 T4
X1
X6
7
Digital Excitation Equipment type RXEE-2C
Digital output i
ndication
JTAG
主控单元
Digital inpu
ton indicati
Comunication and Supply P
ower indication
X10
X11
X5 X4 X3
Figure 3 Main
control unit
8
睿信创和电气
RXCH Electric
AVR_INPUT
IE_LIMITER
励磁电流限制器
IEMIN_LIMITER MAX
×îСÀø´ÅµçÁ÷ÏÞÖÆÆ÷
Isin¦Õ
Icos¦Õ P_Q_LIMITER
Ç·ÀøÏÞÖÆÆ÷
FOLLOW_UP_CTRL
IE IEXC AVR_PID
SCALING
U_MACH1 -
~
+
= U_MACH2 GATE_CONTROL
Isin¦Õ
_
~ AVRÊäÈëÐźŴ¦Àí ×Ô¶¯Í¨µÀPIDµ¥Ôª
Icos¦Õ
= Ãſص¥Ôª
Uk
Uk
¸ú×Ù¿ØÖÆ
Ä£ÄâÁ¿
´¦Àíµ¥Ôª
FREQUENCY_SCALE
FREQUENCY_MOV
ƵÂʲâÁ¿ºÍ¼àÊÓ
AVR_REF_INFLUENCE
RAISE/LOWER_COMMANDS
AUTO AVR_SETPOINT
V/Hz
REF
AUTO LIM
×Ô¶¯Í¨µÀ ×Ô¶¯Í¨µÀ¸ø¶¨Öµ×ۺϵ¥Ôª
¸ø¶¨Öµ²úÉú
MAN_SETPOINT MANUAL_PI
REF Q REF Q_CTRL
+/- Icos¦Õ
REF + -
ºãQµ÷½Ú
MAN
¿ª¹ØÁ¿ÊäÈë
MAN ºãcos¦Õµ÷½Ú
ÊÖ¶¯Í¨µÀ¸ø¶¨µ¥Ôª
Ôö¼õ´Å¿ØÖÆ
5.2 Software CONTROL LOGIC
ON cos¦Õ CTRL U_MACH1 FAULT ALARM
5.2.1 Basic Functions EXCITATION_ON/OFF_CTRL ON Q CTRL
AUTO ON
I_EXC
I_cos¦Õ ALARM CH_FAL
MONITORING
¿ª¹ØÁ¿ÐźŸôÀë
¿ª¹ØÁ¿Êä³ö
¿ØÖÆÂß¼ Àø´Å¼à¿Ø
regulator, it must continuously compare the actual value with the set-point value and almost no-
IE
delay to G change the trigger angle. Besides regulating terminal voltage and reactive power,
3¡«
excitation regulator must fulfill the functions such as excitation limiter and excitation monitor.
In software design, according to the function, the asynchronous timing interrupt modular
design is used. A number of task groups are divided based on the features of each module.
9
Digital Excitation Equipment type RXEE-2C
10
睿信创和电气
RXCH Electric
11
Digital Excitation Equipment type RXEE-2C
AVR_REF_INFLUENCE
U A RA MP
- 1 0 s /D U RA MP
R EF1_A V R_R EL OLL O R EF4_A V R_R EL
D
Q _ D R O O P /C O M P E N S
OLL T
T
RUN O N -S O FTS TA R T
1 TO N O =U_MA CH
1>2
2 T C
D E L A Y _ V / H Z _ L IM _ A TD
& O N _ V / H Z _ L IM IT E R
A UTO _O N
f
1
4000
FLA SH_O FF
S O FTS TA RET_R A M P
12
Figure 5 V/Hz limiter and soft
staring 起励
睿信创和电气
RXCH Electric
value of field current. I e max is the maximum value, I eth is the thermal value ( The rotor can be
allowed long-term operation with I eth without thermal over-load ) ,OUT-IE-LIMITER is the
output value of limiter, IE-MAX-RETRIG is the input terminal of the limiter repeated trigger, tup
is the forcing excitation time, t down is cooling time constant, the total energy system allows is
Emax = I e max - 0.9 I eth )2 tup . In normal operation condition ( limiter is not working ) ,
the set value of limiter is I e max , the output is I e max -IE-REL. Because I e max > IE-REL, the
limiter is not working in AVR channel. If system failure occurs , field current increases to IE-REL
> I e max , the limiter immediately work in AVR channel and make IE-REL=Iemax. Field current
is the close-loop regulation object, at the same time, integrator start to work on the forced excitation
current(△i=IE-REL-0.9Ieth)energy integral△E=∫△i2dt, when △E=△Emax, the set value of
limiter lowers to IE-REL=Ieth. In the failure time, if Ieth<IE-REL<Iemax , immediate limitation
would not work but energy integral still working. If △E = △Emax, IE-REL would be lowered to
Ieth, over excitation time is proportional to over field current. After the fault removal, if IE-REL <
13
Digital Excitation Equipment type RXEE-2C
Ieth, △E would decreases with a time constant tdown until △E=0, and the set value of limiter turns
back to Iemax. If system failure occurs again when the energy did not decrease to 0, IE-MAX-
RETRIG would triggered to make the set value turn back to Iemax. But because △E is not reduced
to 0, the forcing excitation time(the time △E reaches △E max) would be shorten, which can protect
rotor from thermal over-load when system failure repeated.
IE_LIMITER
IE_REL
+
Ieth OUT_IE_LIMITER
ADD
-
Iemax
1
2
2
2>1
i dt
+
ADD
- reset
IE_MAX_REPRIG t up , t down
AVR
P/Q LimiterREF + MIN MAX PID
UG -
P/Q limiter (low-excitation limiter) is used to prevent generator from low excitation and out of
step. Limitation curve is composed of five points which are the maximum leading phase reactive
Figure6
values corresponding to active power P =Over
0 % , excitation
P = 25 % ,limiter
P = 50 % , P = 75 % , P = 100 % . These
reactive values is defined correspond to rated voltage, when the voltage is not rated value,
limitation curve moved according to the expression ( 1 u 2 ) /Xd to ensure the generator is
P/Q_LIMITER
I_SINPHI_REL
+
U_MACH_REL OUT_Q_LIM
ADD
P �
I_COSPHI_REL 1.0 Q(p) 1 U G2
0.75 X y Q( P)
0.5 Xd
0.25
Q
0
6 Intelligent Thyristor Converter
6.1 Structure
AVRthyristor converter is composed of controller unit, display unit, pulse amplification
Intelligent
U REF
and isolation unit, + rectifier and protection component, de-excitation circuit, operation circuit
bridge MIN MAX PID
UG �
and communication circuit.
Testing switch is used for self-test. Figure 7 P/Q limiter
Controller unit is a crate structure with width 483mm and high 310mm. The main controller
board is in the crate.
14
睿信创和电气
RXCH Electric
Pulse amplification and isolation unit includes two boards, a total of six amplification and
isolation.
LCD is located at the top of the main entrance.
6.2 Connection Description
Connect the correct port of the system:
The output of field breaker QM connects the rotor of generator.
The input of anode switch QD101 connects the output of excitation transformer.
Terminals are divided into three groups. XM1 is the ports connected with ones external this
system, XM2 and XM3 are the ports connected with excitation regulator. ( The specification of
connections between this system and excitation regulator is shown in the special terminal
connections diagram.)
6.3 Static Test
Static test should be taken according to the factory examination report.
Monitoring the output waveforms of thyristor converter with waveform recorder when test.
The waveform should change continuously and adjustable.
Observe on the LCD, communication should be regular and reliable.
6.4 Operation System Test
According to the operation chart, operation system should be regular and reliable.
Field breaker, fan start-stop and signal input should be regular and reliable.
6.5 Over-voltage Protection and De-excitation Circuit
The output of Thyristor converter connects with over-voltage protection which can absorb the
peak of over-voltage and protect the rotor when rotor is over-voltage.
Thyristor converter connects with non-linear de-excitation resister which can absorb the
energy and protect rotor when field breaker breaks.
LCD Screen
CANL
D
GRAN
CANL
D
GRAN
D
GRAN
+24V
CANH
CANH
RS485+
15
Power 24V CAN1 CAN2 RS485
Digital Excitation Equipment type RXEE-2C
Default screen
睿信创和电气
RXCH Electric
Press “Enter”, LCD displays analog menu and cursor stops at “Regulator Channel I”. Press
Mainneeded.
“Down” can move the cursor to position Menu
<< Analog >>
Regulator Channel I
Regulator Channel II
1# Thyristor Converter
2# Thyristor Converter
3# Thyristor Converter
4# Thyristor Converter
Press “Enter”, LCD displays analog information of regulator channel I.
<< Channel I Analog>>
Analog=Menu
Terminal Voltage 6300 V
Filed Current = 158 A
Trigger Angle = 68
Active Power = 8000 kW
Reactive Power = 6000 kVA
Frequency = 50 Hz
Stator Current = 1200 A
17
Main Menu
Digital Excitation Equipment type RXEE-2C
Press “Enter”, LCD displays digital menu. The cursor stops at “Regulator Channel I”. Press
“Down” can move the cursor to position needed.
18
睿信创和电气
RXCH Electric
Channel I”. Press “Down” can move the cursor to position needed.
Press “Up”, the figure increases. Press “Down”, the figure decreases.
Press “Left”, the underline cursor moves left. Press “Right”, the underline moves right.
Modifiable Parameters of Regulator Channel I
Press “Enter” to finish the modification.
Press “Esc” in the process of data modification to cancel the modification.
7.4.6 Time Settings
Press “MENU”, the main menu is displayed. Press “Down”, move the cursor to “4.Function
Parameters Settings”.
<< Main Menu >>
1. Analog Display
2. Digital Display
3. Modifiable Parameters
4. Function Parameters Settings
5. Network Communication State
19
Main Menu
Digital Excitation Equipment type RXEE-2C
Press “Enter”, LCD displays settings menu. The cursor stops at “Date setting”. Press “Down”
can move the cursor to position needed.
<< Settings>>
1. Date Setting
2. LCD Contrast Regulating
3. RS-485 Communication Settings
4. Waveform Recording
5. LCD Back Light Settings
6. Thyristor Converter number Select
7. CAN Baud Rate Setting
Year 08
Month 08
Day 28
Week 04
Hour 09
Minute 36
Second 58
20
Contrast Regulating
睿信创和电气
RXCH Electric
Baud Rate = 96
Device Address = 9
Indication: When the value of parameters is “1”, the system begins to record waveforms.
7.4.10 LCD Back Light Settings
According to the method in Waveform
7.4.6, makeRecording Settings
LCD displays the back light settings information. The
parameters can be modified according to the method in 7.4.5.
Indication: When “Close Back Light” is “0”, the back light is always on. When the “Close
Back Light” is “1”, the back light will be closed automatically when the no-operation time is longer
than “Time of Back Light” which can not be set “0”. Press any key can turn on the back light when
it is closed. The unit of “Time of Back Light” is minute.
7.4.11 Numbers of Thyristor Converters Select
According to the <<“Number ofBack
Thyristor
method in 7.4.6, Light Converters
make LCD Select”>>
displays
Settings “Numbers of Thyristor Converters
Select”. The parameters can be modified according to the method in 7.4.5.
Number of Thyristor Converters = 1
21
Digital Excitation Equipment type RXEE-2C
Indication: “Baud Rate (K)” is“500”indicating that CAN baud rate is 500K.
Attention:This value must be one CAN Baud
of the fourRate Settings
values (1000, 500, 250, 125).
7.4.13 Network Communication State
Press “MENU”, the main menu is displayed. Press “Down”, move the cursor to “5.Network
Communication State”.
22
Indication: “Fault” indicates that the device is in communication failure state. “Normal”
indicates that the device is in normal state.
8 Application Environment
Environmental Temperature: -5℃~+40℃.
Air humidity≤90%(20℃).The changes of relative humidity≤5% per hour and no dewdrops.
Operation location should avoid conductive and explosive dust, should avoid gas and steam
which can lead to metal corrosion and isolation failure.
Vibration condition allowed: vibration severe degree level is 10 ~ 150Hz, vibration
acceleration≤5m/s2.
Altitude≤1000m. Design and produce according to user protocol when attitude>1000m.
23
Digital Excitation Equipment type RXEE-2C
NAME INSTRUCTION
Fan ON Running the fan
Fan OFF Stopping the fan
9.4 Switches of intelligent thyristor converter cabinet
24
睿信创和电气
RXCH Electric
10 Troubleshooting
10.1 Flashing Failure
The internal field flashing contactor is switched on as “FLASHING” command is given, as
soon as the generator voltage should reach reference voltage. If Generator voltage cannot reach
reference voltage within flashing times, Alarm signal “FLASHING FAILURE” shall be send out,
CH. ON
the field circuit breaker shall be trip at the same time .
Generator
1
Voltage
1<2 TD & Flashing
failure
Reference 2
Voltage of
Field Flashing 25
Flashing EXC ON
time
Digital Excitation Equipment type RXEE-2C
channel
>=1 failure
PQ Limiter fault
AVR ON
Over Limiter Fault
26
EXC PT +
+
-1
- TD Exc. PT
1 〉2
+2 0.1s failure
Measurement
PT
+
1
+ 1>2
TD Measurement
- 0.1s PT failure
2
Over voltage on
unload
CH ON
27
Digital Excitation Equipment type RXEE-2C
28