STRUCTURAL

DESIGN CALCULATION

Project:
TWO (2) STOREY COMMERCIAL BLDG
Marigman Rd , Antipolo, Rizal

NAMAKPAKAN RESIDENCES

Page 1 of 36
PART I. DESIGN CRITERIA

1.0 REFERENCE CODES AND STANDARDS

1.1 The codes of practice used in design and analysis are:

1.1.1 National Structural Code of the Philippines (NSCP Vol. 1, 7th Ed 2015)
1.1.2 National Building Code of the Philippines
1.1.3 American Concrete Institute (ACI Code)

1.2 Design assumption

1.2.1 Fixed type connection between column and foundation.


1.2.2 Moment type connection shall be used in connecting beam and column at
strong axis.

2.0 COMPUTER ANALYSIS SOFTWARE & PARAMETERS

2.1 The computer design and analysis used:

2.1.1 STAAD PRO V8I SelectSeries 5

2.2 Structural Concrete

2.2.1 Density = 23.5616 kN/ m3


Poisson Ratio = 0.17
Modulus of Elasticity = 2.17185e+007
Compressive Strength = 20.7 MPa

2.3 Steel Reinforcement


2.3.1 Density = 77 kN/ m3
Modulus of Elasticity = 2.0e+008
Rebars 12mmØ & Below = 276 MPa
Rebars 16mmØ & Above = 414 MPa

Page 2 of 36
3.0 LOADING CRITERIA

3.1 Dead Load, DL Self weight (Modelled)


Super Imposed Dead Load, SDL
Floor Finish Tiles (2nd Flr) = 1.10 kPa
Floor Cement Finish (3rd Flr) = 1.53 kPa
Ceiling Suspended = 0.12 kPa
Partition = 1.00 kPa
Utilities = 0.24 kPa
CHB wall (both face plastered) = 3.30 kPa

3.2 Live Load, LL


Basic Floor Area (Residential) = 1.9 kPa
Roof Decks = 1.9 kPa

3.3 Seismic Loads, EQ

Seismic loads have been determined in accordance with UBC – Uniform


Building Code 97. The site is designated Seismic Zone 4 as per National
Structural Code of the Philippines Seismic Hazard Map. The following
seismic parameters were used in the analysis:
Location (Antipolo City) = zone 4 (value, 0.40)
Nearest Earthquake Fault = West Valley Fault System
Distance from nearest seismic source = 11.5 km
Seismic coefficients
Na, near source factor =1.0
Nv, near source factor =1.2
OverStrength factor, Rw =8.5
Importance factor, I =1.0
Occupancy Category = IV

3.4 Wind Load, WL


Code specified wind load parameters were used in the analysis as outlined
below:

Location ( Antipolo City, Rizal) = max wind speed, 260 kph


Main Wind force resisting system = qh*G*Cp
Velocity pressure,q = 47.3E-
Gust effect factor,G =0.85
Pressure coefficients =(NSCP fig. 207-3)

Page 3 of 36
4.0 LOAD COMBINATION

Page 4 of 36
5.0 STRUCTURE 3D MODEL (STAAD Pro. V8i)

5.1 Structural Frame Model

Isometric view

Roof Deck Level

Second Floor Level

Natural Grade Line

Front View

Page 5 of 36
Roof Deck Level

Second Floor Level

Natural Grade Line

Left Side View

5.2 Structure under bending stress

Natural Grade Line

Page 6 of 36
5.3 Structure under extreme conditions

PART II. STRUCTURAL ANALYSIS / RESULT

****************************************************
* *
* STAAD.Pro V8i SELECTseries5 *
* Version 20.07.10.64 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= MAR 28, 2019 *
* Time= 11:58:59 *
* *
* USER ID: ABR *
****************************************************

Page 7 of 36
INPUT:

1. STAAD SPACE
INPUT FILE: TWO STOREY MIX COMMERCIAL BLDG.STD
2. START JOB INFORMATION
3. ENGINEER DATE 26-MAR-19
4. JOB NAME TWO STOREY MIX COMMERCIAL BLDG
5. JOB NO 2019-003-026
6. JOB REV 00
7. ENGINEER NAME ABR
8. CHECKER NAME RC
9. APPROVED NAME ROA
10. JOB CLIENT NAMAKPAKAN RESIDENCE
11. END JOB INFORMATION
12. INPUT WIDTH 79
13. UNIT METER KN
14. JOINT COORDINATES
15. 1 0 0 0; 2 8.6 0 0; 3 2.8 0 0; 4 5.8 0 0; 5 0 0 2.9; 6 8.6 0 2.9; 7 2.8 0 2.9
16. 8 5.8 0 2.9; 9 0 0 5.8; 10 8.6 0 5.8; 11 2.8 0 5.8; 12 5.8 0 5.8; 13 0 0 8.6
17. 14 8.6 0 8.6; 15 2.8 0 8.6; 16 5.8 0 8.6; 17 0 0 13; 18 8.6 0 13; 19 2.8 0 13
18. 20 5.8 0 13; 21 0 -1.2 0; 22 8.6 -1.2 0; 23 2.8 -1.2 0; 24 5.8 -1.2 0
19. 25 0 -1.2 2.9; 26 8.6 -1.2 2.9; 27 2.8 -1.2 2.9; 28 5.8 -1.2 2.9
20. 29 0 -1.2 5.8; 30 8.6 -1.2 5.8; 31 2.8 -1.2 5.8; 32 5.8 -1.2 5.8
21. 33 0 -1.2 8.6; 34 8.6 -1.2 8.6; 35 2.8 -1.2 8.6; 36 5.8 -1.2 8.6; 37 0 -1.2 13
22. 38 8.6 -1.2 13; 39 2.8 -1.2 13; 40 5.8 -1.2 13; 41 0 3 0; 42 8.6 3 0
23. 43 2.8 3 0; 44 5.8 3 0; 45 0 3 2.9; 46 8.6 3 2.9; 47 2.8 3 2.9; 48 5.8 3 2.9
24. 49 0 3 5.8; 50 8.6 3 5.8; 51 2.8 3 5.8; 52 5.8 3 5.8; 53 0 3 8.6; 54 8.6 3 8.6
25. 55 2.8 3 8.6; 56 5.8 3 8.6; 57 0 3 13; 58 8.6 3 13; 59 2.8 3 13; 60 5.8 3 13
26. 61 0 6 0; 62 8.6 6 0; 63 2.8 6 0; 64 5.8 6 0; 65 0 6 2.9; 66 8.6 6 2.9
27. 67 2.8 6 2.9; 68 5.8 6 2.9; 69 0 6 5.8; 70 8.6 6 5.8; 71 2.8 6 5.8
28. 72 5.8 6 5.8; 73 0 6 8.6; 74 8.6 6 8.6; 75 2.8 6 8.6; 76 5.8 6 8.6; 77 0 6 13
29. 78 8.6 6 13; 79 2.8 6 13; 80 5.8 6 13; 81 0 3 11.5; 82 2.8 3 11.5; 83 0 6 11.5
30. 84 2.8 6 11.5
31. MEMBER INCIDENCES
32. 1 1 21; 2 2 22; 3 3 23; 4 4 24; 5 5 25; 6 6 26; 7 7 27; 8 8 28; 9 9 29
33. 10 10 30; 11 11 31; 12 12 32; 13 13 33; 14 14 34; 15 15 35; 16 16 36; 17 17 37
34. 18 18 38; 19 19 39; 20 20 40; 21 1 41; 22 2 42; 23 3 43; 24 4 44; 25 5 45
35. 26 6 46; 27 7 47; 28 8 48; 29 9 49; 30 10 50; 31 11 51; 32 12 52; 33 13 53
36. 34 14 54; 35 15 55; 36 16 56; 37 17 57; 38 18 58; 39 19 59; 40 20 60; 41 41 61
37. 42 42 62; 43 43 63; 44 44 64; 45 45 65; 46 46 66; 47 47 67; 48 48 68; 49 49 69
38. 50 50 70; 51 51 71; 52 52 72; 53 53 73; 54 54 74; 55 55 75; 56 56 76; 57 57 77
39. 58 58 78; 59 59 79; 60 60 80; 61 1 3; 62 3 4; 63 4 2; 64 5 7; 65 7 8; 66 8 6
40. 67 9 11; 68 11 12; 69 12 10; 70 13 15; 71 15 16; 72 16 14; 73 17 19; 74 19 20
41. 75 20 18; 76 1 5; 77 5 9; 78 9 13; 79 13 17; 80 3 7; 81 7 11; 82 11 15
42. 83 15 19; 84 4 8; 85 8 12; 86 12 16; 87 16 20; 88 2 6; 89 6 10; 90 10 14
43. 91 14 18; 92 41 43; 93 43 44; 94 44 42; 95 45 47; 96 47 48; 97 48 46; 98 49 51
44. 99 51 52; 100 52 50; 101 53 55; 102 55 56; 103 56 54; 104 57 59; 105 59 60
45. 106 60 58; 107 41 45; 108 45 49; 109 49 53; 110 53 81; 111 43 47; 112 47 51
46. 113 51 55; 114 55 82; 115 44 48; 116 48 52; 117 52 56; 118 56 60; 119 42 46
47. 120 46 50; 121 50 54; 122 54 58; 123 61 63; 124 63 64; 125 64 62; 126 65 67
48. 127 67 68; 128 68 66; 129 69 71; 130 71 72; 131 72 70; 132 73 75; 133 75 76
49. 134 76 74; 135 77 79; 136 79 80; 137 80 78; 138 61 65; 139 65 69; 140 69 73
50. 141 73 83; 142 63 67; 143 67 71; 144 71 75; 145 75 84; 146 64 68; 147 68 72

Page 8 of 36
51. 148 72 76; 149 76 80; 150 62 66; 151 66 70; 152 70 74; 153 74 78; 154 81 57
52. 155 82 59; 156 81 82; 157 83 77; 158 84 79; 159 83 84
53. START GROUP DEFINITION
54. FLOOR
55. _2NDFLR 92 TO 122 154 TO 156
56. _3RDFLR 123 TO 153 157 TO 159
57. END GROUP DEFINITION
58. DEFINE MATERIAL START
59. ISOTROPIC CONCRETE
60. E 2.17185E+007
61. POISSON 0.17
62. DENSITY 23.5616
63. ALPHA 1E-005
64. DAMP 0.05
65. TYPE CONCRETE
66. STRENGTH FCU 27579
67. END DEFINE MATERIAL
68. CONSTANTS
69. MATERIAL CONCRETE ALL
70. MEMBER PROPERTY AMERICAN
71. 123 TO 140 142 TO 144 146 TO 148 150 TO 152 159 PRIS YD 0.3 ZD 0.2
72. 92 TO 109 111 TO 113 115 TO 117 119 TO 121 141 145 149 153 156 TO 157 -
73. 158 PRIS YD 0.35 ZD 0.2
74. 110 114 118 122 154 155 PRIS YD 0.4 ZD 0.2
75. 61 TO 91 PRIS YD 0.25 ZD 0.2
76. 1 TO 60 PRIS YD 0.4 ZD 0.2
77. SUPPORTS
78. 21 TO 40 FIXED
79. DEFINE REFERENCE LOADS
80. LOAD R1 LOADTYPE DEAD TITLE REF DL
81. SELFWEIGHT Y 1
82. FLOOR LOAD
83. _2NDFLR FLOAD 2.46 GY
84. _3RDFLR FLOAD 1.89 GY
85. MEMBER LOAD
86. 92 TO 94 107 TO 110 119 TO 122 154 UNI GY 8.91
87. 104 TO 106 123 TO 125 135 TO 141 150 TO 153 156 157 159 UNI GY 3.96
88. END DEFINE REFERENCE LOADS
89. DEFINE UBC ACCIDENTAL LOAD
90. ZONE 0.4 I 1 RWX 8.5 RWZ 8.5 STYP 1 NA 1 NV 1.2
91. REFERENCE LOAD Y
92. R1 1.0
93. DEFINE WIND LOAD
94. TYPE 1 WIND 1
95. <! STAAD PRO GENERATED DATA DO NOT MODIFY !!!
96. ASCE-7-2010:PARAMS 260.000 KMPH 0 1 3 0 0.000 FT 0.000 FT 0.000 FT 1 -
97. 1 6.000 M 13.000 M 8.600 M 2.000 0.010 0 -
98. 0 0 0 0 0.621 1.000 1.000 0.850 0 -
99. 0 0 0 0.875 0.800 -0.550
100. !> END GENERATED DATA BLOCK
101. INT 2.02284 2.02284 2.03028 2.03761 2.04481 2.0519 2.05887 2.06575 2.07252 -
102. 2.07919 2.08576 2.09225 2.09864 2.10495 2.11117 HEIG 0 4.572 4.68185 -
103. 4.79169 4.90154 5.01138 5.12123 5.23108 5.34092 5.45077 5.56062 -
104. 5.67046 5.78031 5.89015 6

Page 9 of 36
105. LOAD 1 LOADTYPE SEISMIC TITLE SEISMIC @ X DIRECTION
106. UBC LOAD X 1 ACC 1
107. PERFORM ANALYSIS

P R O B L E M S T A T I S T I C S
-----------------------------------

NUMBER OF JOINTS 84 NUMBER OF MEMBERS 159


NUMBER OF PLATES 0 NUMBER OF SOLIDS 0
NUMBER OF SURFACES 0 NUMBER OF SUPPORTS 20

SOLVER USED IS THE OUT-OF-CORE BASIC SOLVER

ORIGINAL/FINAL BAND-WIDTH= 40/ 15/ 78 DOF


TOTAL PRIMARY LOAD CASES = 1, TOTAL DEGREES OF FREEDOM = 384
TOTAL LOAD COMBINATION CASES = 0 SO FAR.
SIZE OF STIFFNESS MATRIX = 30 DOUBLE KILO-WORDS
REQRD/AVAIL. DISK SPACE = 12.5/1889324.0 MB

***********************************************************
* *
* X DIRECTION : Ta = 0.321 Tb = 0.337 Tuser = 0.000 *
* T = 0.337, LOAD FACTOR = 1.000 *
* UBC TYPE = 97 *
* UBC FACTOR V = 0.0941 x 1713.12 = 161.24 KN *
* *
***********************************************************

108. CHANGE
109. LOAD 2 LOADTYPE SEISMIC TITLE SEISMIC @ Z DIRECTION
110. UBC LOAD Z 1 ACC 1
111. PERFORM ANALYSIS
112. CHANGE
113. LOAD 3 LOADTYPE DEAD TITLE DEAD LOAD
114. REFERENCE LOAD
115. R1 -1.0
116. PERFORM ANALYSIS
117. CHANGE
118. LOAD 4 LOADTYPE LIVE REDUCIBLE TITLE LIVE LOAD
119. FLOOR LOAD
120. _2NDFLR FLOAD -1.9 GY
121. _3RDFLR FLOAD -1.9 GY
122. PERFORM ANALYSIS
123. CHANGE
124. LOAD 5 LOADTYPE WIND TITLE WINDLOAD @ X DIR_CASE 1
125. WIND LOAD X 1 TYPE 1
126. PERFORM ANALYSIS
127. CHANGE
128. LOAD 6 LOADTYPE WIND TITLE WINDLOAD @ X DIR_CASE 2

Page 10 of 36
129. WIND LOAD -X 1 TYPE 1
130. PERFORM ANALYSIS
131. CHANGE
132. LOAD 7 LOADTYPE WIND TITLE WINDLOAD @ Z DIR_CASE 1
133. WIND LOAD Z 1 TYPE 1
134. PERFORM ANALYSIS
135. CHANGE
136. LOAD 8 LOADTYPE WIND TITLE WINDLOAD @ Z DIR_CASE 2
137. WIND LOAD -Z 1 TYPE 1
138. PERFORM ANALYSIS
139. CHANGE
140. LOAD COMB 9 GENERATED NSCP STRENGTH DESIGN 1
141. 3 1.4
142. LOAD COMB 10 GENERATED NSCP STRENGTH DESIGN 2
143. 3 1.2 4 1.6
144. LOAD COMB 11 GENERATED NSCP STRENGTH DESIGN 3
145. 3 1.2 4 0.5
146. LOAD COMB 12 GENERATED NSCP STRENGTH DESIGN 4
147. 3 1.2 4 0.5 5 1.0
148. LOAD COMB 13 GENERATED NSCP STRENGTH DESIGN 5
149. 3 1.2 4 0.5 6 1.0
150. LOAD COMB 14 GENERATED NSCP STRENGTH DESIGN 6
151. 3 1.2 4 0.5 7 1.0
152. LOAD COMB 15 GENERATED NSCP STRENGTH DESIGN 7
153. 3 1.2 4 0.5 8 1.0
154. LOAD COMB 16 GENERATED NSCP STRENGTH DESIGN 8
155. 3 1.2 4 0.5 1 1.0
156. LOAD COMB 17 GENERATED NSCP STRENGTH DESIGN 9
157. 3 1.2 4 0.5 2 1.0
158. LOAD COMB 18 GENERATED NSCP STRENGTH DESIGN 10
159. 3 0.9 5 1.0
160. LOAD COMB 19 GENERATED NSCP STRENGTH DESIGN 11
161. 3 0.9 6 1.0
162. LOAD COMB 20 GENERATED NSCP STRENGTH DESIGN 12
163. 3 0.9 7 1.0
164. LOAD COMB 21 GENERATED NSCP STRENGTH DESIGN 13
165. 3 0.9 8 1.0
166. LOAD COMB 22 GENERATED NSCP STRENGTH DESIGN 14
167. 3 0.9 1 1.0
168. LOAD COMB 23 GENERATED NSCP STRENGTH DESIGN 15
169. 3 0.9 2 1.0
170. PERFORM ANALYSIS
171. START CONCRETE DESIGN
172. CODE ACI
173. FC 20685 ALL
174. FYMAIN 413688 ALL
175. FYSEC 275800 ALL
176. MAXMAIN 16 ALL
177. MINMAIN 12 ALL
178. REINF 0 ALL
179. RHOMN 0.01 MEMB 1 TO 60
180. WIDTH 0.2 MEMB 61 TO 159
181. DESIGN BEAM 61 TO 159

Page 11 of 36
OUTPUT:
=====================================================================

BEAM NO. 62(TIE BEAM) DESIGN RESULTS - FLEXURE PER CODE ACI 318-08

LEN - 3000. MM FY - 276. FC - 21. MPA, SIZE - 200. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 0. 2346. YES NO


2 193. 2 - 12MM 0. 894. YES NO
3 193. 2 - 12MM 1231. 3000. NO YES

B E A M N O. 62 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 2.16 KNS Vc= 29.00 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 0.8 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 1314. MM

AT END SUPPORT - Vu= 2.18 KNS Vc= 29.00 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 0.8 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 1314. MM

___ 3J____________________ 3000X 200X 250_____________________ 4J____


| |
||===================== ============================================||
| 2No12 H 193.| 0.TO 894 2No12 H 193.1231.TO 3000| | |
| 15*12c/c 97 | | | | | | | | | | | | | 15*12c/c 97 |
| 2No12 H 57.| 0.TO 2346 | | | | | | | | | | |
||========================================================== |
| |
|___________________________________________________________________________|
___________ ___________ ___________ ___________ ___________
| | | | | | | | | |
| oo | | oo | | oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 | | 2#12 | | 2#12 |
| | | | | | | | | |
| 2#12 | | 2#12 | | 2#12 | | 2#12 | | |
| oo | | oo | | oo | | oo | | oo |
| | | | | | | | | |
|___________| |___________| |___________| |___________| |___________|

Page 12 of 36
=====================================================================

BEAM NO. 91(TIE BEAM) DESIGN RESULTS - FLEXURE PER CODE ACI 318-08

LEN - 4400. MM FY - 276. FC - 21. MPA, SIZE - 200. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 0. 3820. YES NO


2 193. 2 - 12MM 0. 1494. YES NO
3 193. 2 - 12MM 1989. 4400. NO YES

B E A M N O. 91 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 3.28 KNS Vc= 28.74 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 0.8 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 2014. MM

AT END SUPPORT - Vu= 3.36 KNS Vc= 28.74 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 0.8 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 2014. MM

___ 14J____________________ 4400X 200X 250_____________________ 18J____


| |
||======================== =========================================||
| 2No12 H 193.| |0.TO 1494 |2No12|H|193.1989.TO|4400 | | | |
| 22*12c/c 97 | | | | | | | | | | | | | | | | | | | |22*12c/c 97 |
| 2No12 H |57.| |0.TO 3820 | | | | | | | | | | | | | | | | |
||================================================================ |
| |
|___________________________________________________________________________|
___________ ___________ ___________ ___________ ___________
| | | | | | | | | |
| oo | | oo | | oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 | | 2#12 | | 2#12 |
| | | | | | | | | |
| 2#12 | | 2#12 | | 2#12 | | 2#12 | | |
| oo | | oo | | oo | | oo | | |
| | | | | | | | | |
|___________| |___________| |___________| |___________| |___________|

Page 13 of 36
=====================================================================

BEAM NO. 93(B-1) DESIGN RESULTS - FLEXURE PER CODE ACI 318-08

LEN - 3000. MM FY - 414. FC - 21. MPA, SIZE - 200. X 350. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 16MM 0. 2410. YES NO


2 293. 3 - 16MM 0. 894. YES NO
3 293. 2 - 16MM 1731. 3000. NO YES

B E A M N O. 93 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 21.66 KNS Vc= 44.04 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 1.2 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 147. MM C/C FOR 1214. MM

AT END SUPPORT - Vu= 21.72 KNS Vc= 44.04 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 1.2 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 147. MM C/C FOR 1214. MM

___ 43J____________________ 3000X 200X 350_____________________ 44J____


| |
||===================== ================================||
| 2No16 H 293.| 0.TO |894 2No16 H 293.1731.TO 3000 |
| 10*12c/c147 | | | | | | | 10*12c/c147 |
| 3No16 H |57.| 0.TO 2410 | | | | |
||============================================================ |
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______
| | | | | | | | | |
| oo | | oo | | | | oo | | oo |
| 2#16 | | 2#16 | | | | 2#16 | | 2#16 |
| | | | | | | | | |
| 2#16 | | 2#16 | | 3#16 | | 2#16 | | |
| oo | | oo | | ooo | | oo | | |
| | | | | | | | | |
|_______| |_______| |_______| |_______| |_______|

Page 14 of 36
=====================================================================

BEAM NO. 122(B-2) DESIGN RESULTS - FLEXURE PER CODE ACI 318-08

LEN - 4400. MM FY - 414. FC - 21. MPA, SIZE - 200. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 3 - 16MM 0. 3933. YES NO


2 343. 4 - 16MM 0. 1246. YES NO
3 343. 3 - 16MM 2971. 4400. NO YES

B E A M N O. 122 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 38.11 KNS Vc= 51.37 KNS Vs= 0.00 KNS
Tu= 0.04 KN-MET Tc= 1.5 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 172. MM C/C FOR 1864. MM

AT END SUPPORT - Vu= 32.30 KNS Vc= 51.37 KNS Vs= 0.00 KNS
Tu= 0.04 KN-MET Tc= 1.5 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 172. MM C/C FOR 1864. MM

___ 54J____________________ 4400X 200X 400_____________________ 58J____


| |
||==================== ========================||
| 3No16 H 343.| 0.TO 1246 3No16|H 343.2971.TO 4400 |
| 12*12c/c172 | | | | | | 12*12c/c172 |
| 4No16 H 57.| 0.TO 3933 | | | | | |
||================================================================== |
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______
| | | | | | | | | |
| ooo | | ooo | | | | ooo | | ooo |
| 3#16 | | 3#16 | | | | 3#16 | | 3#16 |
| | | | | | | | | |
| 3#16 | | 3#16 | | 4#16 | | 3#16 | | |
| ooo | | ooo | | oooo | | ooo | | |
| | | | | | | | | |
|_______| |_______| |_______| |_______| |_______|

Page 15 of 36
=====================================================================

BEAM NO. 127(RB-1) DESIGN RESULTS - FLEXURE PER CODE ACI 318-08

LEN - 3000. MM FY - 414. FC - 21. MPA, SIZE - 200. X 300. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 16MM 0. 2385. YES NO


2 243. 3 - 16MM 0. 894. YES NO
3 243. 2 - 16MM 1481. 3000. NO YES

B E A M N O. 127 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 13.90 KNS Vc= 35.94 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 10
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 122. MM C/C FOR 1264. MM

AT END SUPPORT - Vu= 13.91 KNS Vc= 35.94 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 10
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 122. MM C/C FOR 1264. MM

___ 67J____________________ 3000X 200X 300_____________________ 68J____


| |
||===================== ======================================||
| 2No16 H 243.| 0.TO |894 2No16 H 243.1481.TO 3000 |
| 12*12c/c122 | | | | | | | | | 12*12c/c122 |
| 3No16 H |57.| 0.TO 2385 | | | | | | |
||=========================================================== |
| |
|___________________________________________________________________________|
_________ _________ _________ _________ _________
| | | | | | | | | |
| oo | | oo | | oo | | oo | | oo |
| 2#16 | | 2#16 | | 2#16 | | 2#16 | | 2#16 |
| | | | | | | | | |
| 2#16 | | 2#16 | | 3#16 | | 2#16 | | |
| oo | | oo | | ooo | | oo | | |
| | | | | | | | | |
|_________| |_________| |_________| |_________| |_________|

Page 16 of 36
=====================================================================

BEAM NO. 149(RB-2) DESIGN RESULTS - FLEXURE PER CODE ACI 318-08

LEN - 4400. MM FY - 414. FC - 21. MPA, SIZE - 200. X 350. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 16MM 209. 4007. NO NO


2 293. 4 - 16MM 0. 1128. YES NO
3 293. 2 - 16MM 3089. 4400. NO YES

B E A M N O. 149 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 17.00 KNS Vc= 44.39 KNS Vs= 0.00 KNS
Tu= 0.01 KN-MET Tc= 1.3 KN-MET Ts= 0.0 KN-MET LOAD 9
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 147. MM C/C FOR 1914. MM

AT END SUPPORT - Vu= 23.52 KNS Vc= 48.73 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.3 KN-MET Ts= 0.0 KN-MET LOAD 10
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 147. MM C/C FOR 1914. MM

___ 76J____________________ 4400X 200X 350_____________________ 80J____


| |
||================== ======================||
| 2No16 H 293.| 0.TO 1128 2No16|H 293.3089.TO 4400 |
| 15*12c/c147 | | | | | 15*12c/c147 |
| 4No16 H| 57. 209.TO 4007 | | | | | | |
| =================================================================== |
| |
|___________________________________________________________________________|
_______ _______ _______ _______ _______
| | | | | | | | | |
| oo | | oo | | | | oo | | oo |
| 2#16 | | 2#16 | | | | 2#16 | | 2#16 |
| | | | | | | | | |
| | | 2#16 | | 4#16 | | 2#16 | | |
| | | oo | | oooo | | oo | | |
| | | | | | | | | |
|_______| |_______| |_______| |_______| |_______|

********************END OF BEAM DESIGN**************************

Page 17 of 36
182. DESIGN COLUMN 1 TO 60

====================================================================

COLUMN NO. 1 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 2 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 3 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

Page 18 of 36
COLUMN NO. 4 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 5 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 6 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 7 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED

Page 19 of 36
ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 8 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 9 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 10 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

Page 20 of 36
4 - 16 MM 1.005 9 END 0.650
(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 11 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 12 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 13 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

Page 21 of 36
====================================================================

COLUMN NO. 14 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 15 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 16 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 17 DESIGN PER ACI 318-08 - AXIAL + BENDING

Page 22 of 36
FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED
ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 18 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 19 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM
STAAD SPACE -- PAGE NO. 113

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 20 DESIGN PER ACI 318-08 - AXIAL + BENDING

Page 23 of 36
FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED
ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 21 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 22 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 23 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI

Page 24 of 36
----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 24 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 25 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 26 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

Page 25 of 36
====================================================================

COLUMN NO. 27 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 28 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 29 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

Page 26 of 36
====================================================================

COLUMN NO. 30 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 31 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 32 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

Page 27 of 36
COLUMN NO. 33 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 34 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 35 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 36 DESIGN PER ACI 318-08 - AXIAL + BENDING

Page 28 of 36
FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED
ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 37 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 38 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 39 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

Page 29 of 36
BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI
----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 40 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 41 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 42 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650

Page 30 of 36
(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 43 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 44 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 45 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

Page 31 of 36
COLUMN NO. 46 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 47 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 48 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 49 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED

Page 32 of 36
ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 50 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 51 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 52 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

Page 33 of 36
4 - 16 MM 1.005 9 END 0.650
(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 53 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 54 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 55 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

Page 34 of 36
====================================================================

COLUMN NO. 56 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 57 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

====================================================================

COLUMN NO. 58 DESIGN PER ACI 318-08 - AXIAL + BENDING

FY - 413.7 FC - 20.7 MPA, RECT SIZE - 200.0 X 400.0 MMS, TIED


ONLY MINIMUM STEEL IS REQUIRED.
AREA OF STEEL REQUIRED = 800.0 SQ. MM

BAR CONFIGURATION REINF PCT. LOAD LOCATION PHI


----------------------------------------------------------

4 - 16 MM 1.005 9 END 0.650


(PROVIDE EQUAL NUMBER OF BARS ON EACH FACE)
TIE BAR NUMBER 12 SPACING 200.00 MM

********************END OF COLUMN DESIGN RESULTS********************

Page 35 of 36
183. END CONCRETE DESIGN
184. FINISH

*********** END OF THE STAAD.Pro RUN ***********

**** DATE= MAR 28,2019 TIME= 11:59:36 ****

************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2014 Bentley Systems, Inc.
* http://www.bentley.com *
************************************************************

Prepared By:

(Civil /Structural Engineer)

PRC REG NO.


PTR NO.
ISSUED ON
ISSUED AT

Page 36 of 36