Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Research Article
Abstract: This study presents calculation of fundamental frequency-based per phase digital impedance pilot relaying (DIPR)
scheme for static synchronous compensator (STATCOM) compensated transmission line (TL) using two end synchronised
measurement. DIPR involves computation of absolute value of ratio of estimated phasor sum of voltages to the phasor sum of
currents of both ends. DIPR inherently differentiate between internal and external faults on the line. For all internal faults,
computed value of DIPR ratio is equivalent to system and TL impedance value whereas for external faults, it is equal to line
capacitance impedance value. This novel pilot relaying scheme is easy to set once the system parameters are estimated and
has the ability to detect all types of faults and correctly classify faulty phase with mid-point connected STATCOM on TL. This
scheme is immune to effect of STATCOM compensation mode, level of injection and its dynamic response. Also it is not affected
by line charging capacitive current and fault transient resistance. The fault distance is estimated using the STATCOM current
injection information for various types of fault with high accuracy, considering maximum fault resistance of 20 Ω. Accuracy and
effectiveness of this scheme is evaluated in EMTDC/PSCAD simulation for 230 kV, 300 km, mid-point STATCOM compensated
TL and in hardware setup with mid-point STATCOM on 100 V supply voltage having 200 km TL in offline mode. Results bring
out the robustness, reliability and superiority of proposed novel pilot relaying scheme with fault location algorithm.
1 Introduction hold valid for external faults in shunt compensated line. In [14],
authors have used sequence component network to calculate
The protection of transmission line (TL) involves fault detection superimposed sequence components of voltage and current for
and classification for fast disconnection and restoration of faulted SVC compensated TL. The work presented is not suitable for
line to maintain the power system stability and reliability [1]. To STATCOM compensated TL as compensation remains unaffected
enhance the power transfer capability, flexible AC transmission due to drop in voltage.
system devices were introduced [2]. Static synchronous In this work, digital impedance pilot relaying (DIPR) using
compensator (STATCOM) has ability to offer inductive as well as phasors is proposed which is highly reliable for faults with high as
capacitive compensation [3]. These devices have fast response well as low resistance. DIPR involves computation of absolute
which may overlap with protection system response time leading to value of ratio of estimated phasor sum of voltages to phasor sum of
mal-operation of relaying devices connected in the system [4]. currents of both ends. Its value is large for external faults and small
Distance relay mainly mal-operates in the form of under- for internal faults. Hence, it can be used to differentiate between
reaching (UR) or over-reaching (OR) the faults in the presence of internal–external faults as well as it classifies faulty phase very
STATCOM device [5–9]. The coherent conclusion is early tripping accurately. The terminal voltages and currents of STATCOM bus
for no zone faults (OR), delayed tripping for in zone faults (UR) are estimated using the information of STATCOM impedance
and wrong calculation of fault location [10, 11]. The fault location variation and nearest bus voltage having high value. DIPR
algorithm was proposed in [8] using the optimisation technique. algorithm requires high-speed data communication link between
However, knowledge of the fault type is required, which has not both ends and measurement data must be GPS time stamped to
been reported in [8]. Adaptive mho distance zone relaying scheme nullify error [11]. The proposed pilot relaying algorithm is most
with static var compensator (SVC) on line was proposed in [9] suitable for STATCOM compensated TL and accuracy of this
wherein, the new formula to calculate new setting was derived. algorithm is validated using PSCAD EMTDC [15] and with
However, fault classification algorithm problem was not addressed. hardware setup in offline mode.
Pilot relaying schemes are free from the UR or OR problem [8].
Conventional pilot relaying is based on differential current
algorithm which detects faults with low-resistance but mal-operate 2 Test system and STATCOM modelling
to detect high-resistance faults [10, 12]. In [13], fault component The four generators and three TL power system with STATCOM
integrated impedance (FCII)-based pilot protection algorithm had connected at mid-point of line-1 is as shown in Fig. 1. STATCOM
been proposed for uncompensated TL. FCII algorithm can be used is modelled as 12-pulse voltage source converter. The control
for shunt compensation but variable impedance offered by system of this device has two modes of operation, namely voltage
STATCOM in phases can be seen as fault component due to which regulation mode and reactive power injection mode. In voltage
healthy phases may be classified as faulty phases. Integrated regulation mode, compensating device regulates the connection
impedance-based pilot relaying algorithm had been proposed for point voltage to maintain 1 per unit voltage in all conditions.
series-compensated line in [12]. This algorithm claimed to detect Reactive power required to be either absorbed or injected into
all faults having low resistance but it mal-operates for faults with system. For reactive power injection mode, the amount of reactive
high-resistance. Also, in [12, 13], effect of asymmetrical faults on power need to be injected is fixed (inductive or capacitive)
healthy phases has not been discussed. In [12], fault component irrespective of connection point voltage in this study. To study the
integrated power (FCIP)-based pilot relaying was presented for effect of shunt compensating device operation mode on fault
internal and external fault detection and phase classification. transient signal, the reactive power injection control mode is used.
However, sign convention presented for fault detection does not Transmission line is modelled using the structural information of
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2586
© The Institution of Engineering and Technology 2017
Fig. 1 Test system with mid-point STATCOM
Vd
Z DIPR = abs (1)
Id
where
V d = V m + V n; Id = Im + In
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2587
© The Institution of Engineering and Technology 2017
Z 1 = Z s + Z m1 = Z s + pZ l1 (3) 3.4 Digital pilot protection scheme threshold setting and fault
location
(Z r + Z n1)Z sh (Z r + (1 − p)Z l1)Z sh The analysis presented leads to conclusion that if fault is external
Z2 = = (4)
Z r + Z n1 + Z sh Z r + (1 − p)Z l1 + Z sh fault, DIPR ratio gives value which is equal to capacitive
impedance of TL. Per phase DIPR ratio value is always higher than
For 0.5 ≤ p ≤ 1 the per phase system and TL equivalent impedance values for all
external faults. Whereas for all internal faults per phase DIPR ratio
(Z s + Z m1)Z sh (Z s + pZ l1)Z sh gives value equal to per phase system, STATCOM and TL
Z1 = = (5) equivalent impedance and have less value. Considering 300 km,
Z s + Z m1 + Z sh Z r + pZ l1 + Z sh
230 kV, transmission system without compensation, the capacitive
impedance value is ∼1000 Ω. The problem arises due to connected
Z 2 = Z r + Z n1 = Z s + (1 − p)Z l1 (6) STATCOM device at mid-point of TL and it compensates
equivalent capacitive impedance severely. It was observed in
Fault current and voltage to calculate bus terminal voltage and simulation studies that when STATCOM injects capacitive
current is given as compensation of 100 MVAr, DIPR ratio value is reduced from
normal value and is in range of 600–800 Ω under no fault
Vf condition. When it injects inductive compensation of 100 MVAr,
If = = (I m + I n) = I d (7)
Rf + (Z 1 ∥ Z 2) the DIPR ratio value increased from normal value and is in the
range of 1500–1700 Ω under no fault condition. With above
Z2 discussion and simulation studies, the conclusion drawn is that
V m = If × × Zs (8) setting for DIPR ratio should be in the range of 300–500 Ω. The
Z1 + Z2
TL absolute value of impedance is ∼150 Ω for 300 km line length
Z1 and for detection of 200 Ω high-resistance faults including
V n = If × × Zr (9) STATCOM compensation effect, the value of 350 Ω is set as
Z1 + Z2 threshold for DIPR setting in this study system [16]. To maintain
the reliability and sensitivity of this new pilot protection algorithm
Substituting the values in (1) gives result as absolute value of per phase DIPR ratio is used for fault detection.
For universal per phase DIPR ratio setting for any line or different
(Z 2 × Z s) + (Z 1 × Z r) system is shown in (15). This new DIPR algorithm can detect,
Z DIPR = (10)
Z1 + Z2 classify faulty phases for all faults without and with fault resistance
up to 200 Ω with no false tripping. DIPR fault phase detection
It is considered that the impedance angles of the source and TL in scheme combining with fault location estimation algorithm become
high-voltage power transmission system are close to 90∘. Whereas more reliable and realistic for actual system implementation. It is
impedance angles Z 1, Z 2, Z m and Z n are approximately equal to possible to use fault location estimation algorithm by calculating
the mid-point voltage from TL model and shunt injected current
each other. The values of Z 1 and Z 2 are always higher than the
from STATCOM characteristics. To calculate the injected current
values of Z m and Z n due to the contribution of Z sh. Hence, Z 1 ≥ Z m by STATCOM from its V–I characteristics, voltage at its
and Z 2 ≥ Z n, due to p ∈ [0, 1]. Therefore modifying (10) based on connection point needs to be calculated using pi-model TL voltage
following assumptions and substituting Z m as Z 1 and Z n as Z 2 to get distribution formula. The STATCOM voltage connected at mid-
following inequalities conditions for internal fault: point of TL is given as
Vm + Vn 0.5
pyx = 0.5 + (18)
Z DIPR = | | = | Z c| (14) x
1 + (I ST /(I yx + mI 0))
Im + In
From (14), it is evident that whenever external fault occurs, the where m = (Z l0 − Z l1 /Z l1), and I 0 is the zero sequence component of
DIPR ratio value is equal to Z c and has higher value in comparison current.
to system and TL equivalent impedance In next section, simulation results are presented for proposed
DIPR algorithm validation and evaluation.
DIPRSetting = abs(Z l1) + maximum fault resitance (15)
2588 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
Fig. 3 STATCOM characteristics for injected current calculation obtained
from simulation
Fig. 5 Internal A–g fault at 160 km of line with fault resistance 0.1 Ω
(i) Per phase DIPR ratio, (ii) Per phase relay trip decision
2590 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
Fig. 10 Per phase DIPR ratio for close-in faults
(i) BC–g fault at distance 0.1 km before of bus N with 0.1 Ω fault resistance created at
Fig. 8 Per phase DIPR ratio for internal faults 0.604 s, (ii) ABC fault at distance 0.1 km ahead of bus N with 0.1 Ω fault resistance
(i) A–g fault at distance 0.1 km ahead of bus M with 0.1 Ω fault resistance created at created at 0.604 s
0.604 s, (ii) AB–g fault at distance 149.9 km ahead of bus M with 0.1 Ω fault
resistance created at 0.604 s
is observed that proposed DIPR algorithm performs accurately for
STATCOM in inductive as well as capacitive compensation mode.
Table 3 shows dependability of proposed scheme with fault
resistance of 100 Ω for internal and external faults with STATCOM
compensation.
Table 4 shows % error in fault distance estimation using (17)
for STATCOM compensated TL. The maximum error observed
from Table 4 is 0.53% for 300 km TL. Results presented in Table 4
are for fault distance estimation with 20 Ω fault resistance for
various faults and locations. For fault having high resistance up to
200 Ω, error may increase up to 2% due to the effect of STATCOM
compensation as observed in simulation studies.
Table 5 shows the results for fault with 10 Ω resistance for three
different installation points of STATCOM. The tabulated results
show per phase DIPR ratio for internal as well as external fault. It
is observed from Table 5 that when STATCOM is installed at end
points, the phase having fault shows very less value while other
phases DIPR ratio value is much higher than the threshold setting.
Similar observations can be concluded when STATCOM is present
Fig. 9 Current waveform of CT primary and secondary for BC–g fault at
at mid-point of TL. Table 6 shows the per phase DIPR ratio for
distance 0.1 km before bus N with 0.1 Ω fault resistance created at 0.604 s
close-in fault with STATCOM installed at mid-point of the TL and
injecting maximum capacitive compensation. It is observed from
condition lies above threshold value and trip decisions are not
the tabulated results that proposed relaying algorithm gives
issued in both cases.
accurate discrimination for close-in faults as well as external faults.
Table 1 shows the calculated absolute values of DIPR ratio 0.1
Hence, proposed relaying algorithm is reliable and dependable for
Ω fault resistance considering maximum inductive shunt
all types of internal and external faults.
compensation of 100 MVAr for internal and external faults. Table 2
shows calculated absolute values of DIPR ratio with 0.1 Ω fault
resistance considering maximum capacitive shunt compensation of
100 MVAr for internal and external faults. From both the tables, it
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2591
© The Institution of Engineering and Technology 2017
Table 2 DIPR ratio with 0.1 Ω fault resistance for maximum
capacitive STATCOM compensation
Fault location, km Fault type Z DIPRa Ω Z DIPRb Ω Z DIPRc Ω
10 A–g 40.68 566.4 520.5
BC–g 554.9 33.59 33.57
ABC 31.32 31.84 31.06
100 A–g 110.2 553.5 608.6
BC–g 522.3 86.17 87.57
ABC 68.65 68.85 68.07
200 A–g 117.7 439.5 492.5
BC–g 421.9 88.35 88.45
ABC 72.03 72.45 72.67
280 A–g 46.78 432 502.4
BC–g 496.5 39.6 40.8
ABC 36.25 36.28 36.18
external 90 A–g 660.3 640.1 664.3
BC–g 559.7 621.4 615.4
ABC 565.4 565.8 565.1
5 Hardware setup and per phase fault detection Two-machine system with STATCOM controller hardware setup is
shown in Fig. 12 for proposed per phase DIPR algorithm
algorithm validation validation. The sending end generator has on-board AVR with
shunt DC motor as a prime mover having capacity of 3 kW. The
receiving end generator has manual excitation control with VFD
induction motor as a prime mover having 2 kW capacity.
2592 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
STATCOM controller is connected at the mid-point of 200 km TL. programme which implements the proposed relaying algorithm at
The STATCOM has DSP-based closed loop controller to regulate 1 kHz after downsampling in offline mode. The recorded samples
mid-point voltage to 1 p.u. Transmission lines are pi-equivalent are used to calculate voltage and current phasors using recursive
models with four sections, namely 30, 70, 70 and 30 km. CT6841 discrete Fourier transform.
sensor used for current measurements are HIOKI make. Power
analyser 3390 HIOKI make is used as real-time data recorder for 5.2 DIPR per phase fault detection algorithm validation for
acquiring current and voltage signals for different fault cases. The two-machine system
real-time data recorder has sampling rate of 10 kHz and has four
voltage and current channels. Due to the limited number of In proposed per phase DIPR ratio-based fault phase detection
channels and considering the same time stamping on both end algorithm, the threshold value is decided after observing >100
measurements on two phases of each bus are recorded for recorded fault events. The overall impedance of the 200 km
algorithm validation. The proposed faulty phase detection hardware setup TL is 12 Ω. Considering the sensitivity, accuracy
algorithm is based on per phase and fault location algorithm and reliability for the proposed algorithm and taking into account
requires measurement of all the three phases, hence only faulty of fault resistance value of 10 with 1 Ω lead wire resistance, the
phase detection and classification algorithm is validated in threshold value is set to 23 Ω to verify more 900 recorded fault
hardware. Recorded samples of fault events are fed to MATLAB events. For different hardware setup or in real-time system,
Table 5 Per phase DIPR ratio with 10 Ω fault resistance for different installation STATCOM point with maximum capacitive
compensation
STATCOM installation point Fault location, km Fault type Z DIPRa Ω Z DIPRb Ω Z DIPRc Ω
AtbusM 50 A–g 92.50 1939.40 1879.1
BC–g 1884.10 64.53 63.63
ABC 53.16 53.27 52.98
100 A–g 116.30 2017.90 2000.98
BC–g 1951.50 75.22 74.89
ABC 65.91 65.31 64.89
200 A–g 116.72 2022.90 1999.46
BC–g 1989.90 75.79 74.86
ABC 65.72 66.53 64.74
280 A–g 52.90 2037.5 2037.3
BC–g 2043.10 71.76 70.02
ABC 32.63 32.83 31.97
Ext.10 A–g 2047.8 2047.3 2047.1
BC–g 1982.7 1983.1 1982.9
ABC 1853.1 1851.9 1852.7
Atmid-point 50 A–g 85.32 483.25 484.81
BC–g 507.33 58.16 57.96
ABC 49.91 50.49 49.18
100 A–g 120.27 564.01 618.24
BC–g 531.25 95.89 97.61
ABC 73.62 72.89 73.87
200 A–g 123.39 434.24 454.23
BC–g 451.90 94.97 94.85
ABC 76.78 78.68 77.81
280 A–g 53.37 471.65 475.97
BC–g 504.74 44.17 43.86
ABC 45.29 44.23 44.84
Ext.10 A–g 552.8 609.36 607.36
BC–g 488.04 486.03 487.15
ABC 487.39 487.54 486.98
AtbusN 50 A–g 93.74 1944.7 1923.6
BC–g 1896.8 64.09 63.12
ABC 53.30 55.11 54.89
100 A–g 117.75 2021.9 2019.8
BC–g 1961.2 75.23 74.80
ABC 65.16 65.54 64.95
200 A–g 114.88 2021 2017.9
BC–g 1998.7 74.67 73.89
ABC 62.96 61.47 62.42
280 A–g 50.65 2041.7 2040.3
BC–g 2037.4 41.34 40.37
ABC 31.52 30.38 30.68
Ext.10 A–g 2051.1 2053.6 2052.3
BC–g 1915.9 1912.6 1913.3
ABC 1838.3 1839.1 1838.9
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2593
© The Institution of Engineering and Technology 2017
Table 6 Per phase DIPR ratio with 1 Ω fault resistance for different close-in faults with mid-point STATCOM and maximum
capacitive compensation
Fault location, km Fault type Z DIPRa Ω Z DIPRb Ω Z DIPRc Ω
2 A–g 45.89 493.89 491.77
BC–g 469.80 41.97 42.08
ABC 38.11 38.16 37.84
4 A–g 46.42 495.52 493.17
BC–g 471.39 42.14 43.24
ABC 39.87 39.64 38.45
6 A–g 46.94 496.97 495.51
BC–g 471.08 43.31 44.93
ABC 41.10 40.84 40.48
146 A–g 136.46 435.23 432.78
BC–g 431.68 135.40 136.19
ABC 78.41 78.85 78.69
148 A–g 137.36 419.55 421.24
BC–g 419.63 76.83 76.43
ABC 74.57 74.09 74.36
152 A–g 137.56 419.88 420.85
BC–g 420.17 76.97 79.01
ABC 74.49 74.97 74.86
154 A–g 136.66 435.71 433.50
BC–g 431.68 78.45 78.93
ABC 78.53 78.12 78.83
294 A–g 37.27 414.94 413.72
BC–g 411.29 36.43 35.89
ABC 31.98 31.21 31.54
296 A–g 36.16 413.19 412.40
BC–g 409.94 35.24 34.22
ABC 30.24 30.31 30.46
298 A–g 34.24 411.65 411.49
BC–g 406.85 33.87 33.14
ABC 28.60 28.71 28.66
Ext.2 A–g 544.85 536.97 543.99
BC–g 422.44 416.69 413.71
ABC 409.98 409.39 409.55
Ext.4 A–g 545.96 538.27 545.44
BC–g 422.79 416.89 415.17
ABC 410.13 410.86 410.75
Ext.6 A–g 546.43 538.97 546.27
BC–g 423.21 417.56 415.93
ABC 410.27 411.09 410.97
heuristic fault data of voltage and current signal are required for cycle. Due to limited number of channels in the real-time data
best tuning and setting of proposed algorithm. Fig. 13 shows the recorder, three-phase fault types are not verified. From rigorous
recorded waveform from real-time data recorder for A–g fault at case studies of >1000 cases of recorded fault events it was
30 km TL from sending end generator with mid-point STATCOM observed that the proposed algorithm performed accurately in per
controller for 0.1 Ω fault resistance. phase fault detection. The fault location algorithm and external
Internal A–g fault at 30 km from sending end generator of line fault cases are not verified due to hardware limitation but
in hardware setup recorded results is shown in Fig. 14 with mid- analytically and in simulation results DIPR algorithm performs
point connected STATCOM. As this fault event is recorded in real- superiorly. The recorded hardware setup fault events and presented
time digital data recorder, saved sampled data for the events are simulation results prove the robustness and applicability of
retrieved for algorithm validation. Fig. 14(i) shows voltage proposed algorithm for industrial use and its application in real-
waveform of phase A at sending end bus with estimated phasor time system.
magnitude by recursive DFT at 1 kHz sampling frequency and The proposed per phase DIPR ratio-based pilot relaying scheme
current waveform of phase A with estimated phasor magnitude. is accurate and has no effect of STATCOM compensation level,
Fig. 14(ii) shows the proposed per phase DIPR algorithm installation point and its dynamic in comparison with the one given
calculated ratios with per phase trip decisions. As observed from in [7–9]. The proposed scheme is tested with hardware results, and
Fig. 14(ii), fault was occurred at 0.36 s and trip decision is issued results prove the superiority of the proposed scheme over the other
within half cycle as ratio of phase A is less than set threshold schemes. In comparison with that in [14], this scheme has fixed
value. Fig 15(i) shows recorded result for line-to-line fault at 130 threshold setting, even STATCOM is active or inactive. The fixed
km with voltage and current waveform of phases A and B at threshold setting makes proposed relaying scheme simpler in
sending end generator with its estimated phasor magnitudes. comparison to other conventional schemes [10, 12]. Threshold
Fig. 15(ii) shows proposed DIPR algorithm calculated per phase setting can be calculated for any other transmission system using
ratios and trip decisions. Fig. 15 it is observed that fault is created formula given in (15). In comparison with [7–9], the proposed
at 0.26 s and trip decisions for both phases are issued within half relaying algorithm detects faults with high fault resistance and
2594 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
Fig. 12 Two-machine system with STATCOM controller hardware setup
Fig. 13 Real-time data recorder waveforms for A–g fault at 30 km with mid-point STATCOM controller for 0.1 Ω fault resistance
gives accurate detection of faulty phase. The computation burden is less value than half cycle by sacrificing relay reliability. This
less when compared with other scheme in [14]. scheme has high dependability and sensitivity for all types of faults
with and without fault resistance and it is well suited for
6 Conclusion STATCOM compensated TL.
2596 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
Fig. 15 Hardware setup recorded results for AB fault at 130 km with 0.1 Ω fault resistance
(i) (a) Voltage waveform (b) Estimated phasor (c) Current waveform (d) Estimated phasor, (ii) (a) DIPR ratio of phase A (b) Trip decision of phase A (c) DIPR ratio of phase B (d)
Trip decision of phase B
7 References [6] Albasri, F.A., Sidhu, T.S., Varma, R.K.: ‘Performance comparison of distance
protection schemes for shunt-FACTS compensated transmission lines’, IEEE
[1] Phadke, A.G., Thorp, J.S.: ‘Computer relaying for power systems’ (John Trans. Power Deliv., 2007, 22, (4), pp. 2116–2125
Wiley & Sons, 2009, 2nd edn.) [7] Ghorbani, A., Khederzadeh, M., Mozafari, B.: ‘Impact of SVC on the
[2] Padiyar, K.R.: ‘FACTS controllers in power transmission and distribution’ protection of transmission lines’, Int. J. Elect. Power Energy Syst., 2012, 42,
(New Age International, 2007) (1), pp. 702–709
[3] Hingorani, N.G., Gyugyi, L.: ‘Understanding FACTS’ (IEEE Press, 2000) [8] Ghazizadeh-Ahsaee, M., Sadeh, J.: ‘Accurate fault location algorithm for
[4] El-Arroudi, K., Joos, G., McGillis, D.T.: ‘Operation of impedance protection transmission lines in the presence of shunt-connected flexible AC
relays with the STATCOM’, IEEE Trans. Power Deliv., 2002, 17, (2), pp. transmission system devices’, IET Gen. Transm. Distrib., 2012, 6, (3), pp.
381–387 247–255
[5] Sidhu, T.S., Varma, R.K., Gangadharan, P.K., et al.: ‘Performance of distance [9] Singh, A.R., Dambhare, S.S.: ‘Adaptive distance protection of transmission
relays on shunt FACTS compensated transmission lines’, IEEE Trans. Power line in presence of SVC’, Int. J. Elect. Power Energy Syst., 2013, 53, pp. 78–
Deliv., 2005, 20, (3), pp. 1837–1845 84
[10] He, S., Suonan, J., Bo, Z.Q.: ‘Integrated impedance-based pilot protection
scheme for the TCSC-compensated EHV/UHV transmission lines’, IEEE
Trans. Power Deliv., 2013, 28, (2), pp. 835–844
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2597
© The Institution of Engineering and Technology 2017
[11] Singh, A.R., Patne, N.R., Kale, V.S.: ‘Adaptive distance protection setting in [14] Gupta, O.H., Tripathy, M.: ‘An innovative pilot relaying scheme for shunt-
presence of mid-point STATCOM using synchronized measurement’, Int. J. compensated line’, IEEE Trans. Power Deliv., 2015, 30, (3), pp. 1439–1448
Electr. Power Energy Syst., 2015, 67, pp. 252–260 [15] PSCAD/EMTDC-4.5.2.0: ‘Electromagnetic transients program including DC
[12] Suonan, J., Liu, K., Song, G.: ‘A novel UHV/EHV transmission-line pilot systems’. Manitoba HVDC Research Centre, Winnipeg, MB, Canada, 2013
protection based on fault component integrated impedance’, IEEE Trans. [16] De Andrade, V., Sorrentino, E.: ‘Typical expected values of the fault
Power Deliv., 2011, 26, (1), pp. 127–134 resistance in power systems’. Proc. IEEE/Power Energy Society Transmission
[13] He, S., Suonan, J., Kang, X., et al.: ‘Fault component integrated impedance- and Distribution Conf. and Exposition: T& D Latin America, 2010, pp. 602–
based pilot protection scheme for EHV/UHV transmission line with thyristor 609
controlled series capacitor (TCSC) and controllable shunt reactor (CSR)’, Sci.
China Technol. Sci., 2013, 56, (2), pp. 342–350
2598 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017