Sei sulla pagina 1di 13

IET Generation, Transmission & Distribution

Research Article

Digital impedance pilot relaying scheme for ISSN 1751-8687


Received on 19th October 2016
Revised 20th February 2017
STATCOM compensated TL for fault phase Accepted on 24th February 2017
E-First on 7th July 2017
classification with fault location doi: 10.1049/iet-gtd.2016.1670
www.ietdl.org

Arvind R. Singh1 , Nita R. Patne1, Vijay S. Kale1, Piyush Khadke1


1Department of Electrical Engineering, VNIT, Nagpur, Maharashtra 440010, India
E-mail: arvindsinghwce@gmail.com

Abstract: This study presents calculation of fundamental frequency-based per phase digital impedance pilot relaying (DIPR)
scheme for static synchronous compensator (STATCOM) compensated transmission line (TL) using two end synchronised
measurement. DIPR involves computation of absolute value of ratio of estimated phasor sum of voltages to the phasor sum of
currents of both ends. DIPR inherently differentiate between internal and external faults on the line. For all internal faults,
computed value of DIPR ratio is equivalent to system and TL impedance value whereas for external faults, it is equal to line
capacitance impedance value. This novel pilot relaying scheme is easy to set once the system parameters are estimated and
has the ability to detect all types of faults and correctly classify faulty phase with mid-point connected STATCOM on TL. This
scheme is immune to effect of STATCOM compensation mode, level of injection and its dynamic response. Also it is not affected
by line charging capacitive current and fault transient resistance. The fault distance is estimated using the STATCOM current
injection information for various types of fault with high accuracy, considering maximum fault resistance of 20 Ω. Accuracy and
effectiveness of this scheme is evaluated in EMTDC/PSCAD simulation for 230 kV, 300 km, mid-point STATCOM compensated
TL and in hardware setup with mid-point STATCOM on 100 V supply voltage having 200 km TL in offline mode. Results bring
out the robustness, reliability and superiority of proposed novel pilot relaying scheme with fault location algorithm.

1 Introduction hold valid for external faults in shunt compensated line. In [14],
authors have used sequence component network to calculate
The protection of transmission line (TL) involves fault detection superimposed sequence components of voltage and current for
and classification for fast disconnection and restoration of faulted SVC compensated TL. The work presented is not suitable for
line to maintain the power system stability and reliability [1]. To STATCOM compensated TL as compensation remains unaffected
enhance the power transfer capability, flexible AC transmission due to drop in voltage.
system devices were introduced [2]. Static synchronous In this work, digital impedance pilot relaying (DIPR) using
compensator (STATCOM) has ability to offer inductive as well as phasors is proposed which is highly reliable for faults with high as
capacitive compensation [3]. These devices have fast response well as low resistance. DIPR involves computation of absolute
which may overlap with protection system response time leading to value of ratio of estimated phasor sum of voltages to phasor sum of
mal-operation of relaying devices connected in the system [4]. currents of both ends. Its value is large for external faults and small
Distance relay mainly mal-operates in the form of under- for internal faults. Hence, it can be used to differentiate between
reaching (UR) or over-reaching (OR) the faults in the presence of internal–external faults as well as it classifies faulty phase very
STATCOM device [5–9]. The coherent conclusion is early tripping accurately. The terminal voltages and currents of STATCOM bus
for no zone faults (OR), delayed tripping for in zone faults (UR) are estimated using the information of STATCOM impedance
and wrong calculation of fault location [10, 11]. The fault location variation and nearest bus voltage having high value. DIPR
algorithm was proposed in [8] using the optimisation technique. algorithm requires high-speed data communication link between
However, knowledge of the fault type is required, which has not both ends and measurement data must be GPS time stamped to
been reported in [8]. Adaptive mho distance zone relaying scheme nullify error [11]. The proposed pilot relaying algorithm is most
with static var compensator (SVC) on line was proposed in [9] suitable for STATCOM compensated TL and accuracy of this
wherein, the new formula to calculate new setting was derived. algorithm is validated using PSCAD EMTDC [15] and with
However, fault classification algorithm problem was not addressed. hardware setup in offline mode.
Pilot relaying schemes are free from the UR or OR problem [8].
Conventional pilot relaying is based on differential current
algorithm which detects faults with low-resistance but mal-operate 2 Test system and STATCOM modelling
to detect high-resistance faults [10, 12]. In [13], fault component The four generators and three TL power system with STATCOM
integrated impedance (FCII)-based pilot protection algorithm had connected at mid-point of line-1 is as shown in Fig. 1. STATCOM
been proposed for uncompensated TL. FCII algorithm can be used is modelled as 12-pulse voltage source converter. The control
for shunt compensation but variable impedance offered by system of this device has two modes of operation, namely voltage
STATCOM in phases can be seen as fault component due to which regulation mode and reactive power injection mode. In voltage
healthy phases may be classified as faulty phases. Integrated regulation mode, compensating device regulates the connection
impedance-based pilot relaying algorithm had been proposed for point voltage to maintain 1 per unit voltage in all conditions.
series-compensated line in [12]. This algorithm claimed to detect Reactive power required to be either absorbed or injected into
all faults having low resistance but it mal-operates for faults with system. For reactive power injection mode, the amount of reactive
high-resistance. Also, in [12, 13], effect of asymmetrical faults on power need to be injected is fixed (inductive or capacitive)
healthy phases has not been discussed. In [12], fault component irrespective of connection point voltage in this study. To study the
integrated power (FCIP)-based pilot relaying was presented for effect of shunt compensating device operation mode on fault
internal and external fault detection and phase classification. transient signal, the reactive power injection control mode is used.
However, sign convention presented for fault detection does not Transmission line is modelled using the structural information of

IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2586
© The Institution of Engineering and Technology 2017
Fig. 1  Test system with mid-point STATCOM

3 DIPR-based scheme for shunt compensated TL


3.1 DIPR for uncompensated TL for internal fault
The equivalent circuit for internal fault on TL without
compensation is shown Fig. 2(i). TL pi-equivalent model is
considered for analysis. Considering a fault at point F with fault
current I f . Z m1 and Z n1 are TL positive sequence impedance
between point F and end bus M and N, respectively. Z s and Z r are
equivalent system impedances connected at bus M and N,
respectively. Z l1 and Z l0 are positive and zero sequence impedance
of TL. V m, V n, I m and I n are voltage and current phasor estimated at
bus M and N, respectively. Per phase DIPR ratio for internal fault
without compensation is defined as

Vd
Z DIPR = abs (1)
Id

where

V d = V m + V n; Id = Im + In

3.2 DIPR for shunt compensated TL with internal fault


In this case, STATCOM is installed at the mid-point of TL and
internal fault is considered at point F as shown in Fig. 2(ii). During
internal fault, capacitive current is much smaller than line and fault
currents. Also, capacitive impedance is higher than that of TL
Fig. 2  Equivalent circuits impedance as well as system impedances. To carry out analysis in
(i) For internal fault without compensation, (ii) For internal fault with shunt
simplified manner, shunt charging currents at both buses is
compensation, (iii) For external fault with shunt compensation
neglected in derivation. Let p be ratio of fault point impedance
from bus terminals to the impedance of whole line length, then
tower data, circuit conductor data, circuit ground wire data, circuit
conductor bundling data and phase connection considering Z m1 = pZ l1, Z n1 = (1 − p)Z l1 (2)
frequency-dependant phase model in PSCAD. The fault current is
measured at bus M and N with ANSI/IEEE 1200:5, class C400 CT
model has been used to obtain the realistic CT response in For internal faults with shunt compensation, it has two conditions
simulations. of fault point.
For 0 ≤ p ≤ 0.5

IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2587
© The Institution of Engineering and Technology 2017
Z 1 = Z s + Z m1 = Z s + pZ l1 (3) 3.4 Digital pilot protection scheme threshold setting and fault
location
(Z r + Z n1)Z sh (Z r + (1 − p)Z l1)Z sh The analysis presented leads to conclusion that if fault is external
Z2 = = (4)
Z r + Z n1 + Z sh Z r + (1 − p)Z l1 + Z sh fault, DIPR ratio gives value which is equal to capacitive
impedance of TL. Per phase DIPR ratio value is always higher than
For 0.5 ≤ p ≤ 1 the per phase system and TL equivalent impedance values for all
external faults. Whereas for all internal faults per phase DIPR ratio
(Z s + Z m1)Z sh (Z s + pZ l1)Z sh gives value equal to per phase system, STATCOM and TL
Z1 = = (5) equivalent impedance and have less value. Considering 300 km,
Z s + Z m1 + Z sh Z r + pZ l1 + Z sh
230 kV, transmission system without compensation, the capacitive
impedance value is ∼1000 Ω. The problem arises due to connected
Z 2 = Z r + Z n1 = Z s + (1 − p)Z l1 (6) STATCOM device at mid-point of TL and it compensates
equivalent capacitive impedance severely. It was observed in
Fault current and voltage to calculate bus terminal voltage and simulation studies that when STATCOM injects capacitive
current is given as compensation of 100 MVAr, DIPR ratio value is reduced from
normal value and is in range of 600–800 Ω under no fault
Vf condition. When it injects inductive compensation of 100 MVAr,
If = = (I m + I n) = I d (7)
Rf + (Z 1 ∥ Z 2) the DIPR ratio value increased from normal value and is in the
range of 1500–1700 Ω under no fault condition. With above
Z2 discussion and simulation studies, the conclusion drawn is that
V m = If × × Zs (8) setting for DIPR ratio should be in the range of 300–500 Ω. The
Z1 + Z2
TL absolute value of impedance is ∼150 Ω for 300 km line length
Z1 and for detection of 200 Ω high-resistance faults including
V n = If × × Zr (9) STATCOM compensation effect, the value of 350 Ω is set as
Z1 + Z2 threshold for DIPR setting in this study system [16]. To maintain
the reliability and sensitivity of this new pilot protection algorithm
Substituting the values in (1) gives result as absolute value of per phase DIPR ratio is used for fault detection.
For universal per phase DIPR ratio setting for any line or different
(Z 2 × Z s) + (Z 1 × Z r) system is shown in (15). This new DIPR algorithm can detect,
Z DIPR = (10)
Z1 + Z2 classify faulty phases for all faults without and with fault resistance
up to 200 Ω with no false tripping. DIPR fault phase detection
It is considered that the impedance angles of the source and TL in scheme combining with fault location estimation algorithm become
high-voltage power transmission system are close to 90∘. Whereas more reliable and realistic for actual system implementation. It is
impedance angles Z 1, Z 2, Z m and Z n are approximately equal to possible to use fault location estimation algorithm by calculating
the mid-point voltage from TL model and shunt injected current
each other. The values of Z 1 and Z 2 are always higher than the
from STATCOM characteristics. To calculate the injected current
values of Z m and Z n due to the contribution of Z sh. Hence, Z 1 ≥ Z m by STATCOM from its V–I characteristics, voltage at its
and Z 2 ≥ Z n, due to p ∈ [0, 1]. Therefore modifying (10) based on connection point needs to be calculated using pi-model TL voltage
following assumptions and substituting Z m as Z 1 and Z n as Z 2 to get distribution formula. The STATCOM voltage connected at mid-
following inequalities conditions for internal fault: point of TL is given as

Z DIPR < | 2Z 1Z 2| (11) x


V yx
V ST = V yx − I yx − 0.5Z l1 (16)
Zc
From (11), it is evident that per phase DIPR ratio for internal fault
reflects equivalent system and TL impedances and DIPR ratio has x
Qref
effect of equivalent impedance offered by STATCOM. I ST = x
× X tr (17)
V ST × Xs
3.3 DIPR for shunt compensated TL with external fault
where x is phases a, b and c; y is M or N (sending or receiving
Current in per phase DIPR ratio calculation have only capacitive end); X s is the slope of STATCOM characteristics equal to 0.03%;
current value during external fault. The circuit diagram for external X tr is the coupling transformer reactance 0.1 p.u.; Qref is the
fault with STATCOM is shown in Fig. 2(iii). The current flowing STATCOM reactive power injection reference.
from both buses in the TL during external fault are I mc and I nc. To calculate the STATCOM voltage at bus ends, higher value of
From Fig. 2(iii), the per phase DIPR ratio currents can be found as voltage from (16) should be used due to the uncertainty of fault
point. Using the V–I characteristics of STATCOM shown in Fig. 3,
I d = I m + I n = I mc + I nc (12) injected current is calculated using (17) based on reactive reference
Qref in the study. Using calculated STATCOM injected current, the
Vm Vn per unit fault distance from any end of line for any phase,
I mc = and I nc = (13)
Zc Zc considering full length is given as [11]

Vm + Vn 0.5
pyx = 0.5 + (18)
Z DIPR = | | = | Z c| (14) x
1 + (I ST /(I yx + mI 0))
Im + In

From (14), it is evident that whenever external fault occurs, the where m = (Z l0 − Z l1 /Z l1), and I 0 is the zero sequence component of
DIPR ratio value is equal to Z c and has higher value in comparison current.
to system and TL equivalent impedance In next section, simulation results are presented for proposed
DIPR algorithm validation and evaluation.
DIPRSetting = abs(Z l1) + maximum fault resitance (15)

2588 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
Fig. 3  STATCOM characteristics for injected current calculation obtained
from simulation

Fig. 5  Internal A–g fault at 160 km of line with fault resistance 0.1 Ω
(i) Per phase DIPR ratio, (ii) Per phase relay trip decision

channel is available without any intentional delay at both ends. The


proposed relay is implemented at bus M with GPS synchronised
data received from N bus.
Fig. 4 shows the voltage and current waveform with STATCOM
at mid-point of TL for internal A–g fault at 160 km of TL from bus
M and having fault resistance of 0.1 Ω created at 0.604 s in
PSCAD simulation. The STATCOM injection is initiated into
system at 0.2 s for A–g fault with reactive power reference of 100 
MVAr (inductive). Fig. 5(i) presents the absolute value of DIPR
ratio calculated for internal A–g fault using (11) for each phase.
The DIPR threshold has been shown in Fig. 5(i) and the same
convention has been considered throughout.
The trip decision is shown in Fig. 5(ii) for each phase with
DIPR threshold 350 Ω. In relay design, flag counter is initiated
when DIPR ratio value is less than threshold value. When counter
value reach to 5, trip decision is issued. For an A–g fault, the DIPR
ratio value drops down to 275.2 Ω at 0.609 s, less than set
threshold value. Hence, initiating the counter in the relay
programming, whose value changes from 0 to 1 at 0.614 s as
Fig. 4  Internal A–g fault at 160 km of line with fault resistance 0.1 Ω, observed from Fig. 5(ii). Healthy phase values remain high as
created at 0.604 s depicted in Fig. 5(ii) with data tag.
(i) Voltage waveform, (ii) Current waveform DIPR calculated ratio values and phase wise trip decisions are
shown in Fig. 6 for ABC fault at 170 km of TL with negligible
4 Simulation results and discussion fault resistance with maximum inductive compensation. Respective
values w. r. t. time are shown in the figure for better illustration. It
The proposed new algorithm is verified by PSCAD/EMTDC
is evident from Figs. 5 and 6 that when STATCOM injects
simulation with fault and GPS time stamped sampled data
maximum inductive compensation, per phase DIPR ratio value is
generation at both the ends. Simulation time is assumed same as
in the range of 1500–1700 Ω and when fault occurs, per phase
GPS time for time tagging. The pilot relay is implemented in
DIPR ratio value is less than threshold value of equivalent system
MATLAB m-file programming with proposed threshold value for
and TL impedance value. The effect of STATCOM injection also
internal and external faults with and without compensation to
affects equivalent values but does not reduce to zero value.
verify the setting criterion. The data are fetched with sampling rate
It is evident from Fig. 6(i) that when STATCOM injects
of 1 kHz from CT and PT at both the ends as explained in Section
maximum inductive compensation, per phase DIPR ratio value is
2 and shown in Fig. 1. It is assumed that fast data communication
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2589
© The Institution of Engineering and Technology 2017
Fig. 7  Current waveform of CT primary and secondary for
(i) A–g fault at distance 0.1 km ahead of bus M with 0.1 Ω fault resistance created at
0.604 s, (ii) AB–g fault at distance 149.9 km ahead of bus M with 0.1 Ω fault
resistance created at 0.604 s
Fig. 6  ABC internal fault at 170 km of line with 0.1 Ω fault resistance
created at 0.604 s with maximum inductive compensation end measurements, the problems in fault detection due to CT
(i) Per phase DIPR ratio with inductive injection, (ii) Per phase DIPR ratio with saturation are minimum. Fig. 9 shows the current waveform of CT
capacitive injection primary and secondary for BC–g fault at distance 0.1 km before of
bus N with 0.1 Ω fault resistance created at 0.604 s. The effect of
in the range of 1500–1700 Ω and when fault occurs, per phase STATCOM injection is clearly observed in the current waveform
DIPR ratio value is less than threshold value of equivalent system during the fault period.
and TL impedance value. Fig. 6(ii) shows DIPR calculated ratio The proposed relaying algorithm is verified for faults near to
value for each phase in case of ABC internal fault with negligible bus at M, N and STATCOM connection point. Fig. 8(i) shows the
resistance with maximum capacitive compensation injected by fault at 0.1 km ahead of bus M with fault resistance of 0.1 Ω. The
STATCOM. Before the occurrence of fault, calculated DIPR ratio DIPR scheme is able to discriminate close-in fault which is very
value is in the range of 600–800 Ω and after fault it become less near to bus M. Fig. 8(ii) shows fault very near to STATCOM bus at
than threshold set value, trip decision is issued. Hence, it can be 149.9 km ahead of bus M with minimum fault resistance. It is
deduced that proposed algorithm for fault phase classification is observed that, as the fault is near to the mid-point of the TL, the
not affected by inductive or capacitive compensation. Also, per relaying algorithm detects the fault within one cycle. Hence, for
phase fault detection time is approximately half cycle taking into faults near to STATCOM bus, the proposed relaying algorithm
account flag counter time and can be made faster by reducing the detects the fault accurately but requires high detection time as
set flag counter value. The rigorous simulation studies have been compared to other location fault points. For closein faults, severe
performed considering different fault location with and without CT saturation is observed as shown in Fig. 7 and Fig. 9 and as a
fault resistance. The proposed algorithm is found to be accurate in result full cycle DFT phasor estimation has error and leads to larger
detecting the faults and classifying the faulty phases. fault detection time. Fig. 10(i) shows fault very near to bus N at
Fig 7(i) shows the current waveform of CT primary and 0.1 km before the bus. The relaying algorithm gives accurate
secondary for A–g fault at distance 0.1 km ahead of bus M with detection and detection time is within half cycle. Similarly,
0.1 Ω fault resistance created at 0.604 s. As the fault is very close Fig. 10(ii) shows results for external fault 0.1 km ahead of bus N.
to the sending end measurement device, the saturation in the CT is As observed from results, the proposed relaying algorithm is able
observed. It is due to the severe fault current caused due to close-in to discriminate close-in external faults accurately. The STATCOM
fault and results in delayed fault detection. Fig. 7(ii) shows the compensation is maximum 100 MVAr capacitive for results shown
current waveform for AB–g fault at distance 149.9 km ahead of in Figs. 8 and 10.
bus M with 0.1 Ω fault resistance created at 0.604 s. The saturation To evaluate the performance of the proposed algorithm for the
is observed in third cycle and provides enough time to detect and external faults, A–g and ABC faults are created after bus N,
identify the fault and faulty phase. In worst case scenario, severe respectively, with maximum capacitive compensation. Figs. 11(i)
CT saturation may lead to mal-operation of relaying device. and (ii) show the calculated per phase DIPR ratio values for A–g
However, in case of the proposed relaying scheme which uses two and ABC external faults. The impedance value for both fault

2590 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
Fig. 10  Per phase DIPR ratio for close-in faults
(i) BC–g fault at distance 0.1 km before of bus N with 0.1 Ω fault resistance created at
Fig. 8  Per phase DIPR ratio for internal faults 0.604 s, (ii) ABC fault at distance 0.1 km ahead of bus N with 0.1 Ω fault resistance
(i) A–g fault at distance 0.1 km ahead of bus M with 0.1 Ω fault resistance created at created at 0.604 s
0.604 s, (ii) AB–g fault at distance 149.9 km ahead of bus M with 0.1 Ω fault
resistance created at 0.604 s
is observed that proposed DIPR algorithm performs accurately for
STATCOM in inductive as well as capacitive compensation mode.
Table 3 shows dependability of proposed scheme with fault
resistance of 100 Ω for internal and external faults with STATCOM
compensation.
Table 4 shows % error in fault distance estimation using (17)
for STATCOM compensated TL. The maximum error observed
from Table 4 is 0.53% for 300 km TL. Results presented in Table 4
are for fault distance estimation with 20 Ω fault resistance for
various faults and locations. For fault having high resistance up to
200 Ω, error may increase up to 2% due to the effect of STATCOM
compensation as observed in simulation studies.
Table 5 shows the results for fault with 10 Ω resistance for three
different installation points of STATCOM. The tabulated results
show per phase DIPR ratio for internal as well as external fault. It
is observed from Table 5 that when STATCOM is installed at end
points, the phase having fault shows very less value while other
phases DIPR ratio value is much higher than the threshold setting.
Similar observations can be concluded when STATCOM is present
Fig. 9  Current waveform of CT primary and secondary for BC–g fault at
at mid-point of TL. Table 6 shows the per phase DIPR ratio for
distance 0.1 km before bus N with 0.1 Ω fault resistance created at 0.604 s
close-in fault with STATCOM installed at mid-point of the TL and
injecting maximum capacitive compensation. It is observed from
condition lies above threshold value and trip decisions are not
the tabulated results that proposed relaying algorithm gives
issued in both cases.
accurate discrimination for close-in faults as well as external faults.
Table 1 shows the calculated absolute values of DIPR ratio 0.1 
Hence, proposed relaying algorithm is reliable and dependable for
Ω fault resistance considering maximum inductive shunt
all types of internal and external faults.
compensation of 100 MVAr for internal and external faults. Table 2
shows calculated absolute values of DIPR ratio with 0.1 Ω fault
resistance considering maximum capacitive shunt compensation of
100 MVAr for internal and external faults. From both the tables, it

IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2591
© The Institution of Engineering and Technology 2017
Table 2 DIPR ratio with 0.1 Ω fault resistance for maximum
capacitive STATCOM compensation
Fault location, km Fault type Z DIPRa Ω Z DIPRb Ω Z DIPRc Ω
10 A–g 40.68 566.4 520.5
BC–g 554.9 33.59 33.57
ABC 31.32 31.84 31.06
100 A–g 110.2 553.5 608.6
BC–g 522.3 86.17 87.57
ABC 68.65 68.85 68.07
200 A–g 117.7 439.5 492.5
BC–g 421.9 88.35 88.45
ABC 72.03 72.45 72.67
280 A–g 46.78 432 502.4
BC–g 496.5 39.6 40.8
ABC 36.25 36.28 36.18
external 90 A–g 660.3 640.1 664.3
BC–g 559.7 621.4 615.4
ABC 565.4 565.8 565.1

Table 3 DIPR ratio with 100 Ω fault resistance for


STATCOM compensation
Fault location, km Fault type Z DIPRa Ω Z DIPRb Ω Z DIPRc Ω
10 A–g 206.6 1788 1529
BC–g 1636 201.8 201.1
ABC 77.71 77.71 77.71
100 A–g 238.5 1930 1426
BC–g 1747 215.9 214.8
ABC 92.47 92.45 92.1
200 A–g 227.4 648.4 648.7
BC–g 514.5 208 209
ABC 97.5 97.8 97.1
280 A–g 203.1 704.2 696.7
BC–g 615.8 203.5 203.7
ABC 76.23 76.32 76.29
Fig. 11  Per phase DIPR ratio for external faults
external 90 A–g 711 710.4 711.6
(i) A–g fault at distance 20 km ahead of bus N with 0.1 Ω fault resistance created at
BC–g 663.9 667.5 713.6
0.604 s, (ii) ABC fault at distance 50 km ahead of bus N with 0.1 Ω fault resistance
created at 0.604 s ABC 601.2 601.9 601.3

Table 1 DIPR ratio with 0.1 Ω fault resistance for maximum


inductive STATCOM compensation Table 4 Fault distance estimation using (17) for STATCOM
Fault location, km Fault type Z DIPRa Ω Z DIPRb Ω Z DIPRc Ω compensated/TL with 20 Ω fault resistance
Fault location, km Fault type Estimated fault distance, % error
10 A–g 36.92 1898 1506
km
BC–g 3398 33.29 34.51
160 A–g 160.5 0.17
ABC 29.68 29.89 29.73
BC–g 159.8 −0.23
100 A–g 107.3 2121 1782
AB 160.2 0.07
BC–g 537.5 76.18 77.10
ABC 160.1 0.03
ABC 67.07 67.68 67.23
200 A–g 199.8 −0.07
200 A–g 106.7 1845 1851
BC–g 201.3 0.43
BC–g 1186 82.78 82.86
AB 199.3 −0.23
ABC 72.12 72.19 72.14
ABC 200.9 0.3
280 A–g 44.24 1770 852
240 A–g 241.3 0.43
BC–g 3102 40.02 40.66
BC–g 241.8 0.53
ABC 33.64 33.59 33.39
AB 240.6 0.20
external 90 A–g 1449 1605 1647
ABC 241.6 0.53
BC–g 1664 1523 1529
ABC 1527 1576 1578
5.1 Two-machine system hardware details

5 Hardware setup and per phase fault detection Two-machine system with STATCOM controller hardware setup is
shown in Fig. 12 for proposed per phase DIPR algorithm
algorithm validation validation. The sending end generator has on-board AVR with
shunt DC motor as a prime mover having capacity of 3 kW. The
receiving end generator has manual excitation control with VFD
induction motor as a prime mover having 2 kW capacity.

2592 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
STATCOM controller is connected at the mid-point of 200 km TL. programme which implements the proposed relaying algorithm at
The STATCOM has DSP-based closed loop controller to regulate 1 kHz after downsampling in offline mode. The recorded samples
mid-point voltage to 1 p.u. Transmission lines are pi-equivalent are used to calculate voltage and current phasors using recursive
models with four sections, namely 30, 70, 70 and 30 km. CT6841 discrete Fourier transform.
sensor used for current measurements are HIOKI make. Power
analyser 3390 HIOKI make is used as real-time data recorder for 5.2 DIPR per phase fault detection algorithm validation for
acquiring current and voltage signals for different fault cases. The two-machine system
real-time data recorder has sampling rate of 10 kHz and has four
voltage and current channels. Due to the limited number of In proposed per phase DIPR ratio-based fault phase detection
channels and considering the same time stamping on both end algorithm, the threshold value is decided after observing >100
measurements on two phases of each bus are recorded for recorded fault events. The overall impedance of the 200 km
algorithm validation. The proposed faulty phase detection hardware setup TL is 12 Ω. Considering the sensitivity, accuracy
algorithm is based on per phase and fault location algorithm and reliability for the proposed algorithm and taking into account
requires measurement of all the three phases, hence only faulty of fault resistance value of 10 with 1 Ω lead wire resistance, the
phase detection and classification algorithm is validated in threshold value is set to 23 Ω to verify more 900 recorded fault
hardware. Recorded samples of fault events are fed to MATLAB events. For different hardware setup or in real-time system,

Table 5 Per phase DIPR ratio with 10 Ω fault resistance for different installation STATCOM point with maximum capacitive
compensation
STATCOM installation point Fault location, km Fault type Z DIPRa Ω Z DIPRb Ω Z DIPRc Ω
AtbusM 50 A–g 92.50 1939.40 1879.1
BC–g 1884.10 64.53 63.63
ABC 53.16 53.27 52.98
100 A–g 116.30 2017.90 2000.98
BC–g 1951.50 75.22 74.89
ABC 65.91 65.31 64.89
200 A–g 116.72 2022.90 1999.46
BC–g 1989.90 75.79 74.86
ABC 65.72 66.53 64.74
280 A–g 52.90 2037.5 2037.3
BC–g 2043.10 71.76 70.02
ABC 32.63 32.83 31.97
Ext.10 A–g 2047.8 2047.3 2047.1
BC–g 1982.7 1983.1 1982.9
ABC 1853.1 1851.9 1852.7
Atmid-point 50 A–g 85.32 483.25 484.81
BC–g 507.33 58.16 57.96
ABC 49.91 50.49 49.18
100 A–g 120.27 564.01 618.24
BC–g 531.25 95.89 97.61
ABC 73.62 72.89 73.87
200 A–g 123.39 434.24 454.23
BC–g 451.90 94.97 94.85
ABC 76.78 78.68 77.81
280 A–g 53.37 471.65 475.97
BC–g 504.74 44.17 43.86
ABC 45.29 44.23 44.84
Ext.10 A–g 552.8 609.36 607.36
BC–g 488.04 486.03 487.15
ABC 487.39 487.54 486.98
AtbusN 50 A–g 93.74 1944.7 1923.6
BC–g 1896.8 64.09 63.12
ABC 53.30 55.11 54.89
100 A–g 117.75 2021.9 2019.8
BC–g 1961.2 75.23 74.80
ABC 65.16 65.54 64.95
200 A–g 114.88 2021 2017.9
BC–g 1998.7 74.67 73.89
ABC 62.96 61.47 62.42
280 A–g 50.65 2041.7 2040.3
BC–g 2037.4 41.34 40.37
ABC 31.52 30.38 30.68
Ext.10 A–g 2051.1 2053.6 2052.3
BC–g 1915.9 1912.6 1913.3
ABC 1838.3 1839.1 1838.9

IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2593
© The Institution of Engineering and Technology 2017
Table 6 Per phase DIPR ratio with 1 Ω fault resistance for different close-in faults with mid-point STATCOM and maximum
capacitive compensation
Fault location, km Fault type Z DIPRa Ω Z DIPRb Ω Z DIPRc Ω
2 A–g 45.89 493.89 491.77
BC–g 469.80 41.97 42.08
ABC 38.11 38.16 37.84
4 A–g 46.42 495.52 493.17
BC–g 471.39 42.14 43.24
ABC 39.87 39.64 38.45
6 A–g 46.94 496.97 495.51
BC–g 471.08 43.31 44.93
ABC 41.10 40.84 40.48
146 A–g 136.46 435.23 432.78
BC–g 431.68 135.40 136.19
ABC 78.41 78.85 78.69
148 A–g 137.36 419.55 421.24
BC–g 419.63 76.83 76.43
ABC 74.57 74.09 74.36
152 A–g 137.56 419.88 420.85
BC–g 420.17 76.97 79.01
ABC 74.49 74.97 74.86
154 A–g 136.66 435.71 433.50
BC–g 431.68 78.45 78.93
ABC 78.53 78.12 78.83
294 A–g 37.27 414.94 413.72
BC–g 411.29 36.43 35.89
ABC 31.98 31.21 31.54
296 A–g 36.16 413.19 412.40
BC–g 409.94 35.24 34.22
ABC 30.24 30.31 30.46
298 A–g 34.24 411.65 411.49
BC–g 406.85 33.87 33.14
ABC 28.60 28.71 28.66
Ext.2 A–g 544.85 536.97 543.99
BC–g 422.44 416.69 413.71
ABC 409.98 409.39 409.55
Ext.4 A–g 545.96 538.27 545.44
BC–g 422.79 416.89 415.17
ABC 410.13 410.86 410.75
Ext.6 A–g 546.43 538.97 546.27
BC–g 423.21 417.56 415.93
ABC 410.27 411.09 410.97

heuristic fault data of voltage and current signal are required for cycle. Due to limited number of channels in the real-time data
best tuning and setting of proposed algorithm. Fig. 13 shows the recorder, three-phase fault types are not verified. From rigorous
recorded waveform from real-time data recorder for A–g fault at case studies of >1000 cases of recorded fault events it was
30 km TL from sending end generator with mid-point STATCOM observed that the proposed algorithm performed accurately in per
controller for 0.1 Ω fault resistance. phase fault detection. The fault location algorithm and external
Internal A–g fault at 30 km from sending end generator of line fault cases are not verified due to hardware limitation but
in hardware setup recorded results is shown in Fig. 14 with mid- analytically and in simulation results DIPR algorithm performs
point connected STATCOM. As this fault event is recorded in real- superiorly. The recorded hardware setup fault events and presented
time digital data recorder, saved sampled data for the events are simulation results prove the robustness and applicability of
retrieved for algorithm validation. Fig. 14(i) shows voltage proposed algorithm for industrial use and its application in real-
waveform of phase A at sending end bus with estimated phasor time system.
magnitude by recursive DFT at 1 kHz sampling frequency and The proposed per phase DIPR ratio-based pilot relaying scheme
current waveform of phase A with estimated phasor magnitude. is accurate and has no effect of STATCOM compensation level,
Fig. 14(ii) shows the proposed per phase DIPR algorithm installation point and its dynamic in comparison with the one given
calculated ratios with per phase trip decisions. As observed from in [7–9]. The proposed scheme is tested with hardware results, and
Fig. 14(ii), fault was occurred at 0.36 s and trip decision is issued results prove the superiority of the proposed scheme over the other
within half cycle as ratio of phase A is less than set threshold schemes. In comparison with that in [14], this scheme has fixed
value. Fig 15(i) shows recorded result for line-to-line fault at 130  threshold setting, even STATCOM is active or inactive. The fixed
km with voltage and current waveform of phases A and B at threshold setting makes proposed relaying scheme simpler in
sending end generator with its estimated phasor magnitudes. comparison to other conventional schemes [10, 12]. Threshold
Fig. 15(ii) shows proposed DIPR algorithm calculated per phase setting can be calculated for any other transmission system using
ratios and trip decisions. Fig. 15 it is observed that fault is created formula given in (15). In comparison with [7–9], the proposed
at 0.26 s and trip decisions for both phases are issued within half relaying algorithm detects faults with high fault resistance and

2594 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
Fig. 12  Two-machine system with STATCOM controller hardware setup

Fig. 13  Real-time data recorder waveforms for A–g fault at 30 km with mid-point STATCOM controller for 0.1 Ω fault resistance

gives accurate detection of faulty phase. The computation burden is less value than half cycle by sacrificing relay reliability. This
less when compared with other scheme in [14]. scheme has high dependability and sensitivity for all types of faults
with and without fault resistance and it is well suited for
6 Conclusion STATCOM compensated TL.

A per phase DIPR-based novel pilot relaying scheme for mid-point


STATCOM compensated TL is proposed in this work.
Mathematical analysis and simulation results show that the per
phase DIPR ratio reflects capacitive impedance of TL in the
presence of STATCOM at mid-point under healthy condition or
during external fault condition. The per phase DIPR ratio value is
>500 Ω for capacitive and >1400 Ω for inductive compensation.
Whereas, the per phase DIPR ratio gives value equal to equivalent
system and TL impedance value for all the internal faults with
compensation and its value is always <350 Ω. Considering the
abovementioned differences in the per phase DIPR ratio values,
internal or external faults can be classified and detected accurately.
Proposed scheme gives correct fault phase detection and selection
ability in the presence of STATCOM compensation. The DIPR
scheme is not affected by capacitive charging current, STATCOM
operation dynamics, fault inception angle and fault distance which
is main highlight of this scheme. The performance of proposed
scheme is verified and evaluated for recorded fault events in
hardware setup of two-machine system with mid-point STATCOM
controller in offline mode using MATLAB. DIPR scheme works on
per phase mode with the requirement of GPS time stamped both
end measured data of corresponding phase. The detection time of
proposed scheme is well within one cycle and can be brought to a
IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2595
© The Institution of Engineering and Technology 2017
Fig. 14  Hardware setup recorded results for A–g fault at 30 km with 0.1 Ω fault resistance
(i) (a) Voltage waveform of phase A (b) Estimated phasor (c) Current waveform of phase A (d) Estimated phasor, (ii) (a) DIPR ratio of phase A (b)Trip decision of phase A (c) DIPR
ratio of phase B (d) Trip decision of phase B

2596 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017
Fig. 15  Hardware setup recorded results for AB fault at 130 km with 0.1 Ω fault resistance
(i) (a) Voltage waveform (b) Estimated phasor (c) Current waveform (d) Estimated phasor, (ii) (a) DIPR ratio of phase A (b) Trip decision of phase A (c) DIPR ratio of phase B (d)
Trip decision of phase B

7 References [6] Albasri, F.A., Sidhu, T.S., Varma, R.K.: ‘Performance comparison of distance
protection schemes for shunt-FACTS compensated transmission lines’, IEEE
[1] Phadke, A.G., Thorp, J.S.: ‘Computer relaying for power systems’ (John Trans. Power Deliv., 2007, 22, (4), pp. 2116–2125
Wiley & Sons, 2009, 2nd edn.) [7] Ghorbani, A., Khederzadeh, M., Mozafari, B.: ‘Impact of SVC on the
[2] Padiyar, K.R.: ‘FACTS controllers in power transmission and distribution’ protection of transmission lines’, Int. J. Elect. Power Energy Syst., 2012, 42,
(New Age International, 2007) (1), pp. 702–709
[3] Hingorani, N.G., Gyugyi, L.: ‘Understanding FACTS’ (IEEE Press, 2000) [8] Ghazizadeh-Ahsaee, M., Sadeh, J.: ‘Accurate fault location algorithm for
[4] El-Arroudi, K., Joos, G., McGillis, D.T.: ‘Operation of impedance protection transmission lines in the presence of shunt-connected flexible AC
relays with the STATCOM’, IEEE Trans. Power Deliv., 2002, 17, (2), pp. transmission system devices’, IET Gen. Transm. Distrib., 2012, 6, (3), pp.
381–387 247–255
[5] Sidhu, T.S., Varma, R.K., Gangadharan, P.K., et al.: ‘Performance of distance [9] Singh, A.R., Dambhare, S.S.: ‘Adaptive distance protection of transmission
relays on shunt FACTS compensated transmission lines’, IEEE Trans. Power line in presence of SVC’, Int. J. Elect. Power Energy Syst., 2013, 53, pp. 78–
Deliv., 2005, 20, (3), pp. 1837–1845 84
[10] He, S., Suonan, J., Bo, Z.Q.: ‘Integrated impedance-based pilot protection
scheme for the TCSC-compensated EHV/UHV transmission lines’, IEEE
Trans. Power Deliv., 2013, 28, (2), pp. 835–844

IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598 2597
© The Institution of Engineering and Technology 2017
[11] Singh, A.R., Patne, N.R., Kale, V.S.: ‘Adaptive distance protection setting in [14] Gupta, O.H., Tripathy, M.: ‘An innovative pilot relaying scheme for shunt-
presence of mid-point STATCOM using synchronized measurement’, Int. J. compensated line’, IEEE Trans. Power Deliv., 2015, 30, (3), pp. 1439–1448
Electr. Power Energy Syst., 2015, 67, pp. 252–260 [15] PSCAD/EMTDC-4.5.2.0: ‘Electromagnetic transients program including DC
[12] Suonan, J., Liu, K., Song, G.: ‘A novel UHV/EHV transmission-line pilot systems’. Manitoba HVDC Research Centre, Winnipeg, MB, Canada, 2013
protection based on fault component integrated impedance’, IEEE Trans. [16] De Andrade, V., Sorrentino, E.: ‘Typical expected values of the fault
Power Deliv., 2011, 26, (1), pp. 127–134 resistance in power systems’. Proc. IEEE/Power Energy Society Transmission
[13] He, S., Suonan, J., Kang, X., et al.: ‘Fault component integrated impedance- and Distribution Conf. and Exposition: T& D Latin America, 2010, pp. 602–
based pilot protection scheme for EHV/UHV transmission line with thyristor 609
controlled series capacitor (TCSC) and controllable shunt reactor (CSR)’, Sci.
China Technol. Sci., 2013, 56, (2), pp. 342–350

2598 IET Gener. Transm. Distrib., 2017, Vol. 11 Iss. 10, pp. 2586-2598
© The Institution of Engineering and Technology 2017

Potrebbero piacerti anche