STORMWATER & SUBSOIL DRAINAGE SYSTEMS VOLUME IV- TECHNICAL SPECIFICATIONS

a. The surface of the PVC-u fitting shall be roughened to accept a


100mm wide GRP lamination on the inside of the fitting and a 25 mm
wide GRP lamination on the inside of the fitting.

b. Isopthalic resin shall then be applied to the roughened areas and one
layer of chopped strand mat 300 g/m2 applied and wetted out with the
resin.

c. The PVC-u fitting shall be inspected by the Engineer prior to placing in


the benching.

op V1
10.2.5.5 GRP Formwork

1. GRP formwork, which remains in place, shall be fabricated as follows unless


otherwise approved by the Engineer.

C -
y
a. The outer layer shall comprise one layer of glass surface veil 30 g/m2
C
of approved type impregnated with corrosion resistant vinylester resin
of approved type.
C
b. The structural layer shall comprise one layer of chopped strand mat
Q

450 g/m2, two layers of 800 g/m2 woven roving and one layer of
chopped strand mat 450 g/m2 of approved type impregnated with
corrosion resistant isophthalic resin of approved type.

c. The inner layer shall comprise one layer of glass surface veil 30 g/m2
of approved type impregnated with corrosion resistant vinylester resin
of approved type.

d. Resin to glass ratio shall be 70% to 30% by weight with a tolerance of


± 5%.

e. Total minimum thickness shall be 4 mm.

2. Suitable straps or anchors shall be fitted to the formwork to prevent handling damage
and hold the formwork in place during concreting.
3. Any exposed surfaces shall be given a 100 micron thick gel coat with ultra violet
inhibitor.

10.2.6 Waterproof Membrane


1. The waterproof membrane system shall have a proven track record of not less than 5
years in Abu Dhabi or in similar environmental conditions.

2. The waterproof membrane shall be an impervious torch applied purpose formulated


modified bituminous membrane consisting of an atactic polypropylene (APP) bitumen
compound reinforced with a polyester fabric core

PAGE 143

DIVISION 03 - SECTION 03600 FIRST EDITION -DECEMBER 2016


STORMWATER & SUBSOIL DRAINAGE SYSTEMS VOLUME IV- TECHNICAL SPECIFICATIONS

3. Self-adhesive tanking membranes shall not be used.

4. Waterproof membrane shall meet or exceed the properties given in Table 10-5
below.
Table 10-5:– Waterproof Membrane Requirements
Property Test Method Value
Nominal thickness - 4 mm (for single layer) 6mm
(for double layer)
Weight of reinforcing fabric - 200 g/m2
Tensile strength ASTM D146 500 N/50mm in either
direction

op V1
Elongation at break ASTM D146 40% in either direction
Tear resistance ASTM D4073 440 N in transverse direction
550 N in longitudinal
direction
Softening point ASTM D36 110°C
C -
y
1. Accessories
C
a. Waterproof membrane primer shall be:
C
1. Compatible with the waterproof membrane.
Q

2. Recommended by the membrane manufacturer.

3. Formulated for use in hot climates.

b. Bituminous mastic for moulding into 40 mm by 40 mm fillets for use at


90 degree internal junctions and sealing around pipes and
penetrations through walls shall be a cold applied gun grade
rubber/bitumen compound as recommended by the membrane
manufacturer and be formulated for use in hot climates.

c. 40 mm x 40 mm triangular fillets shall be hollow triangular PVC


extrusions, fixed to the concrete or other surfaces using adhesives as
recommended by the manufacturer.

d. Protection board shall be minimum 6mm thick plywood or blockboard


as approved by the Engineer.

e. Cement sand screed shall comprise 1 part cement to 3 parts sand


(5mm maximum aggregate size) or as approved by the Engineer.

f. Flashing shall be 1 mm thick aluminum.

10.3 Part 3 Execution


10.3.1 General
1. Prior to the application of coatings, membranes, insitu lamination or waterproofing

PAGE 144

DIVISION 03 - SECTION 03600 FIRST EDITION -DECEMBER 2016