Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Facebook.com/groups/EEE.Arabic
Facebook.com/EEE.Arabic
© ABB Power Technology
1_114Q07- 2 -
Power General
Transformers
AGENDA
INTRODUCTION
MAIN CHARACTERISTICS OF A POWER TRANSFORMER
Types of transformers
Transformation ratio
Insulation class
Rated output
Transformer connections
VOLTAGE CONTROL
TYPES OF COOLING
ACCESSORIES/ PRACTICAL ASPECTS
© ABB Power Technology
1_114Q07- 3 -
AGENDA
INTRODUCTION
MAIN CHARACTERISTICS OF A POWER TRANSFORMER
Types of transformers
Transformation ratio
Insulation class
Rated output
Transformer connections
VOLTAGE CONTROL
TYPES OF COOLING
ACCESSORIES/ PRACTICAL ASPECTS
© ABB Power Technology
1_114Q07- 4 -
Fundamental considerations
Static device whose function is to transfer
electrical energy from one circuit to
another whose common link is a magnetic
G
flux.
B1 B2
Z
characteristics.
1_114Q07- 6 -
Fundamental relationships
Primary energy Secondary energy
Hence Primary Power Secondary Power
If the transformer is single phase U1 I1 U2 I2
And with three phase √3 U1 I1 √3 U2 I2
At both cases hence U1/ U2 I2 / I1
On the other hand it is known that Voltage in a coil is proportional to
the generated flux and number of turns
U1= k1 n1 and U2= k1 n2
From where it is inferred:
U1 / U2 = n1 / n2 and I2 / I1 = n1 / n2
The ratio n1 / n2 is called Transformation Ratio
© ABB Power Technology
1_114Q07- 7 -
Fundamental relationships
We have then:
U1 / U2 = r1
I1 / I2 = 1 / r1
The former statements are true in an ideal transformer which complies
with the following
No reluctance at the magnetic circuit
No resistance at the windings
No histeresys, eddy-current or I2R losses
No leakage flux
Although this is not accomplished in a real case, all formerly said is
useful to understand the performance of a transformer and to obtain
© ABB Power Technology
On the other hand electrical energy is easier and safer to use when
handled at the lowest voltage.
1_114Q07- 10 -
Power transformer function
The power loss p in a 3-phase transmission line with a resistance R per
phase and a current I flowing in each phase is:
Equation (4) indicates that the power loss in the line is proportional to the
© ABB Power Technology
In other words, the power loss will be lower when the system voltage is
increased.
Power transformer function
The main
application of
transformers is
hence the one
depicted at the
following diagram :
To raise the
voltage and to
reduce the current
going out from
generation
stations (Step-up
substations).
To reduce the
© ABB Power Technology
voltage on arriving
to the points of
1_114Q07- 12 -
utilization (Step-
Down
substations).
AGENDA
INTRODUCTION
MAIN CHARACTERISTICS OF A POWER TRANSFORMER
Types of transformers
Transformation ratio
Insulation class
Rated output
Transformer connections
VOLTAGE CONTROL
TYPES OF COOLING
ACCESSORIES/ PRACTICAL ASPECTS
© ABB Power Technology
1_114Q07- 13 -
Main characteristics of a Power Transformer
Primario
Primario
Secundario
Secundario
core.
In general, the mean length of turn for the
1_114Q07- 17 -
Primario
Primario
Secundario
AT AT
BT AT
BT BT
Split windings
Concentric windings
© ABB Power Technology
1_114Q07- 21 -
Winding types
BT
AT AT
AT
BT
AT
BT
BT BT
Primary voltage : The most usual value of the voltage at the point of
the network where the transformer is going to be connected
When this voltage is expected to vary it could be necessary that the
transformer is equipped with an on load tap changer
Secondary voltage: The desired value at the secondary network
where the transformer will be connected.
© ABB Power Technology
1_114Q07- 31 -
Transformation ratio and voltage drop
The voltage ratio of a transformer is normally specified in no load
condition and is directly proportional to the ratio of the number of
turns in the windings.
When the transformer is loaded, the voltage on the secondary
terminals changes from that in no load condition, depending on
the angle φ between the voltage on the secondary terminals of the
transformer U2 and the secondary current I2
the value of the secondary current I2
the short-circuit impedance of the transformer Z and its active
and reactive components, r and ±jx respectively
© ABB Power Technology
1_114Q07- 32 -
Transformation ratio and voltage drop
At no load the secondary voltage is
U20.
With the load ZL connected, the
voltage at the secondary terminals
changes to U2.
For example, when a transformer
with values for ur=0,01 and ux=0,06
is loaded with rated current with a
power factor of 0,8 inductive the
voltage on the secondary terminals
decreases to 95,5% of the voltage
at no load.
© ABB Power Technology
1_114Q07- 33 -
Transformation ratio and voltage drop
Users and installation planners are recommended to take the
variation of the secondary voltage during loading into account when
specifying the transformer data.
This may be especially important for example in a case where a
large motor represents the main load of the transformer.
The highly inductive starting current of the motor may then be
considerably higher than the rated current of the transformer.
Consequently there may be a considerable voltage drop through the
transformer.
If the feeding power source is weak, this will contribute to an even
lower voltage on the secondary side of the transformer.
© ABB Power Technology
1_114Q07- 34 -
Short circuit impedance
Users have sometimes particular requirements regarding the short-
circuit impedance. Such requirements may be determined by:
parallel operation with existing units,
limitation of voltage drop,
limitation of short-circuit currents.
The transformer designer can meet the requirements in different
ways:
The size of the core cross-section. A large cross-section gives a low
impedance and vice versa,
A tall transformer gives a low impedance and vice versa.
For each transformer there is, however, a smaller range which gives
the optimum transformer from an economic point of view, that is the
lowest sum of the manufacturing costs and the capitalised value of
© ABB Power Technology
the losses.
1_114Q07- 35 -
Short circuit impedance
Short-circuit impedance Z is often expressed as uz in p.u. or in %
according to the following formulas:
Formulas (24) and (25) are valid for for single-phase transformers,
where Ir and Ur are rated values of current and voltage on either
side of the transformer. For 3-phase transformers the nominator
must be multiplied with √3.
Based on measured short-circuit voltage the value of Zk expressed
in ohm can be calculated from the following formula:
© ABB Power Technology
an indication of hottest-spot
temperature.
1_114Q07- 47 -
Loading Based on Measured Oil Temperat.
Allowable top-oil temperature for a
particular constant load may be
determined by subtracting the hottest-
spot copper gradient for that load from
95 C. The hottest-spot copper gradient
must be known from design information
for accurate results, though typical
values may be assumed for estimating
purposes. If the hottest-spot copper
gradient is known for one load condition,
it may be estimated for other load
conditions by reference to Fig. 18.
A conservative loading guide, based on
top-oil temperatures, is given in Fig. 19.
© ABB Power Technology
1_114Q07- 48 -
One or several transformers?
...... ......
...... ......
© ABB Power Technology
1_114Q07- 49 -
Parallel operation of transformers
When there are several transformers at the substation it is possible
to couple them or not.
On the other hand in transmission networks the transformers are
always coupled.
Advantages: No outage when one of the transformers is
disconnected (providing there is capacity enough at the network)
Drawbacks: Higher short circuit capacity
Provisions to be taken before coupling:
Same transformer ratio
Matching connection group
Matching phase rotation direction
© ABB Power Technology
Control
Power Voltage
Transformers
AGENDA
INTRODUCTION
MAIN CHARACTERISTICS OF A POWER TRANSFORMER
Types of transformers
Transformation ratio
Insulation class
Rated output
Transformer connections
VOLTAGE CONTROL
TYPES OF COOLING
ACCESSORIES/ PRACTICAL ASPECTS
© ABB Power Technology
1_114Q07- 56 -
Voltage control
The modern load tap changer had its beginning in 1925.
Since that time the development of more complicated transmission
networks has made tap changing under load more and more
essential to control the in-phase voltage of power transformers.
Tap-changing-under-load equipment is applied to power
transformers:
to maintain a constant secondary voltage with a variable primary
voltage;
to control the secondary voltage with a fixed primary voltage;.
Various types of tap-changing equipment and circuits are used
depending upon the voltage and kva.
Under-load-tap-changers are built for 8, 16, and 32 steps, with the
trend in recent years being toward the larger number of steps so as
to give a finer degree of regulation.
© ABB Power Technology
percent of the rated line voltage, with plus and minus 71/2 percent
and plus and minus 5 percent being second and third, respectively,
in popularity.
Voltage control
Figure illustrates schematically the operation of one type of
mechanism for changing taps under load.
Taps from the transformer winding connect to selector switches 1
through 9. The selector switches are connected to load transfer
switches R, S, and T.
The connections for the tap changer positions are shown on the
sequence chart.
The sequence of switching is so coordinated by the tap changing
mechanism that the transfer switches perform all the switching
operations, opening before and closing after the selector switches.
All arcing is thus restricted to switches R, S, and T, while switches 1
to 9 merely select the transformer tap to which the load is to be
transferred.
© ABB Power Technology
1_114Q07- 58 -
Voltage control
When the tap changer is on odd-numbered positions, the
preventive auto-transformer is short-circuited.
On all even- numbered positions, the preventive auto-
transformer bridges two transformer taps.
In this position, the relatively high reactance of the preventive
auto-transformer to circulating currents between adjacent taps
prevents damage to the transformer winding, while its relatively
low impedance to the load current permits operation on this
position to obtain voltages midway between the transformer
taps.
© ABB Power Technology
1_114Q07- 59 -
Voltage control
The operation in this case of the selector and transfer switches is
exactly as described for the former.
But this type also has a reversing switch which reverses the
connections to the tapped section of the winding so that the same
range and number of positions can be obtained with one-half the
number of tap sections, or twice the range can be obtained with
the same number of taps.
The reversing switch is a close-before-open switch which
operates at the time there is no voltage across its contacts.
© ABB Power Technology
1_114Q07- 60 -
Voltage control
This type of load tap changer
is applied to small power
transformers and large
distribution transformers.
The transfer switches are
eliminated, and each selector
switch serves as a transfer
switch for the tap to which it
is connected.
The schematic circuit
diagram and operations
sequence chart is shown in
Fig.
© ABB Power Technology
1_114Q07- 61 -
Load Tap changing.
3
© ABB Power Technology
Par Impar
1_114Q07- 62 -
Load Tap changing.
The transition switch begins the
new operation connecting in
parallel the initial position (4)
with the final one (5)
The transition resistances clear
4 3
away the energy stored at the
6 5
coil to be transferred preventing
6 overvoltages ( on the turns to
5
be taken off ) either contribute
4
to that the establishment of the
3
current, at the turns to add, is
Par Impar
in a smooth way.
© ABB Power Technology
1_114Q07- 63 -
Load Tap changing.
Par Impar
© ABB Power Technology
1_114Q07- 64 -
© ABB Power Technology
1_114Q07- 65 -
Transition switch
© ABB Power Technology
1_114Q07- 72 -
Cooling
Power Types of
Transformers
AGENDA
INTRODUCTION
MAIN CHARACTERISTICS OF A POWER TRANSFORMER
Types of transformers
Transformation ratio
Insulation class
Rated output
Transformer connections
VOLTAGE CONTROL
TYPES OF COOLING
ACCESSORIES/ PRACTICAL ASPECTS
© ABB Power Technology
1_114Q07- 73 -
Types of cooling
For 10 000 kva (OA) single-phase and 12 000 kva (OA) three-phase, and
above : kva (FA) = 1.333Xkva (OA). (22)
1_114Q07- 78 -
Accesories. Bushings
Installation. Handling and lifting
Only approved and suitable lifting equipment shall be used.
Use a forklift only on transport pallets or transformer bottom.
Do not apply load to corrugated fins or radiators and their supports.
Use the provided lifting lugs only.
When lifting a transformer with cable boxes on the cover, special
care must be taken.
When hydraulic jacks are used, only provided jacking points shall be
used, and in such a way that twisting forces on the transformer tank
are avoided.
© ABB Power Technology
1_114Q07- 100 -
© ABB Power Technology
1_114Q07- 101 -
transformer,
© ABB Power Technology
1_114Q07- 104 -
Transport
© ABB Power Technology
1_114Q07- 105 -
Transport
© ABB Power Technology
1_114Q07- 106 -
Transport
© ABB Power Technology
1_114Q07- 107 -
Transport
Maintenance
Inspection and maintenance during operation
Inspection during operation shall only be performed after taking
safety measures into consideration:
If there is a maximum indicator on the thermometer the
maximum temperature should be recorded,
Inspection for contamination, especially on bushings,
Inspection of surface condition,
Dehydrating breather. The silicagel shall be changed when
approx. 2/3 of the silica gel has changed from blue to red colour
(old type), or from pink to white, respectively. (Conservator type
only),
Inspection for liquid leakages.
© ABB Power Technology
be needed.
Maintenance. Transformer liquid and insulation
The task of liquid in a transformer is to act as an electrical insulation
and to transfer heat from the transformer’s active parts into coolers.
Liquid acts as a good electrical insulation only as long as it is
satisfactorily dry and clean.
Humidity balance between the oil and the insulation implies that
most of the humidity will gather in the paper insulation.
Testing of liquid in transformers should normally be performed 12
months after filling or refilling, subsequently every six years.
Testing of oil in on load tap changers must be performed according
to the tap changer supplier’s recommendations.
To take liquid samples from hermetically sealed transformers is
normally not necessary. The liquid in this type of transformers is not
in contact with the atmosphere, and less exposed to moisture.
© ABB Power Technology