M30 grade M30 grade 0.5% M30 grade 0.75% M30 grade 1% M30 grade 1.25% M30 grade 1.5%
Cement 395 13.430 395 13.430 395 13.430 395 13.430 395 13.430 395 13.430
Water 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916
Fine aggregate 798 27.132 795 27.030 795 27.030 794 26.996 793 26.962 792 26.928
Coarse aggregate 1068 36.312 1065 36.210 1065 36.210 1063 36.142 1062 36.108 1060 36.040
Chemical admixture 0 0.000 1.975 0.067 3 0.101 4 0.134 5 0.168 6 0.201
Water - cement ratio 0.44 0.44 0.44 0.44 0.44 0.44
M40 grade M40 grade 0.5% M40 grade SP 0.75% M40 grade SP 1% M40 grade SP 1.25% M40 grade 1.5%
Cement 496 16.864 496 16.864 496 16.864 496 16.864 496 16.864 496 16.864
Water 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916
Fine aggregate 729 24.786 727 24.718 725 24.650 724 24.616 723 24.582 722 24.548
Coarse aggregate 1044 35.496 1040 35.360 1039 35.326 1037 35.258 1036 35.224 1034 35.156
Chemical admixture 0 0.000 2.480 0.084 3.72 0.126 4.96 0.169 6.20 0.211 7.44 0.253
Water - cement ratio 0.35 0.35 0.35 0.35 0.35 0.35
0.042 0.084
sp add
0.5 1% 1.25 % 1.5
1 slump 1 slump 1 slump
1 cast 1 cast 1 cast
2 2 2
Qty for 9cubes
1.74 59.16
386 13.124
174 5.916
805 27.37
1069 36.346
0 0
0.45
Acquired Strength (N) Target Strength
7 days 28 days 7 days
48.25
Target Strength
28 days
48.25
48.25
48.25
APPENDIX - A
A.1 Design mix for M40 grade concrete with cement A( with out Superplasticizer)
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.40
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.40
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.40
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.40
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.40
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.40
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.45
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.45
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.45
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.45
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.45
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.45
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.50
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
33.24444
3.015
APPENDIX - A
A.1 Design mix for M20 grade concrete with cement A( with out Superplasticizer)
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.50
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.50
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.50
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.50
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.50
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.45
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
FOR 4 CUBES
Cement 5.259 5.259 5.259 5.259 5.259 5.259
Water 2.629 2.629 2.629 2.629 2.629 2.629
Fine aggregate 12.663 12.633 12.618 12.603 12.603 12.588
Coarse aggregate 16.214 16.184 16.169 16.139 16.139 16.108
Chemical admixture 0.000 22.964 34.445 45.927 57.409 68.891
PEG 0.75 34.965
PEG 1 23.310
Water - cement ratio
M30 grade M30 grade 0.5% M30 grade 0.75% M30 grade 1% M30 grade 1.25% M30 grade 1.5%
Cement 395 13.430 395 13.430 395 13.430 395 13.430 395 13.430 395 13.430
Water 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916
Fine aggregate 798 27.132 795 27.030 795 27.030 794 26.996 793 26.962 792 26.928
Coarse aggregate 1068 36.312 1065 36.210 1065 36.210 1063 36.142 1062 36.108 1060 36.040
Chemical admixture 0 0.000 1.975 0.067 3 0.101 4 0.134 5 0.168 6 0.201
Water - cement ratio 0.44 0.44 0.44 0.44 0.44 0.44
M40 grade M40 grade 0.5% M40 grade SP 0.75% M40 grade SP 1% M40 grade SP 1.25% M40 grade 1.5%
Cement 496 16.864 496 16.864 496 16.864 496 16.864 496 16.864 496 16.864
Water 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916
Fine aggregate 729 24.786 727 24.718 725 24.650 724 24.616 723 24.582 722 24.548
Coarse aggregate 1044 35.496 1040 35.360 1039 35.326 1037 35.258 1036 35.224 1034 35.156
Chemical admixture 0 0.000 2.480 0.084 3.72 0.126 4.96 0.169 6.20 0.211 7.44 0.253
Water - cement ratio 0.35 0.35 0.35 0.35 0.35 0.35
M40 grade M40 grade 0.5% M40 grade SP 0.75% M40 grade SP 1% M40 grade SP 1.25% M40 grade 1.5%
Cement 386 13.124 386 13.124 386 13.124 386 13.124 386 13.124 386 13.124
Water 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916 174 5.916
Fine aggregate 805 27.370 805 27.370 805 27.370 805 27.370 805 27.370 805 27.370
Coarse aggregate 1069 36.346 1069 36.346 1069 36.346 1069 36.346 1069 36.346 1069 36.346
Chemical admixture 0 0.000 1.930 0.057 2.90 0.086 3.86 0.115 4.83 0.143 5.79 0.172
PEG 0.75 2.895 87.261 2.90
PEG 0.5 1.930 58.174
Water - cement ratio 0.45 0.45 0.45 0.45 0.45 0.45
FOR 4 CUBES
M40 grade M40 grade 0.5% M40 grade SP 0.75% M40 grade SP 1% M40 grade SP 1.25% M40 grade 1.5%
Cement 5.833 5.833 5.833 5.833 5.833 5.833
Water 2.629 2.629 2.629 2.629 2.629 2.629
Fine aggregate 12.164 12.164 12.164 12.164 12.164 12.164
Coarse aggregate 16.154 16.154 16.154 16.154 16.154 16.154
Chemical admixture 0.000 0.025 0.038 0.051 0.064 0.076
PEG .75 38.783
PEG 0.5 25.855
Water - cement ratio
For M20 LG 1 1
PEG 0.75 0.5
0.5
0.08874
386 13.124 2.916
174 5.916 1.315
805 27.37 6.082
1069 36.346 8.077
0 0 0.000
0.45
APPENDIX - A
A.1 Design mix for M20 grade concrete with cement A( with out Superplasticizer)
Where
f'ck = Target average compressive strength at 28days
From Table 5 of IS456:2000, Maximum water -cement ratio for Very se= 0.50
AS Superplasticizer is used, the water content can be reduced up to 20 percent and above
MIX CALCULATIONS:-
33.24444
3.015
M40 grade M40 grade 0.5% M40 grade SP 0.75% M40 grade SP 1%
Cement 386 13.124 386 13.124 386 13.124 386 13.124
Water 174 5.916 174 5.916 174 5.916 174 5.916
Fine aggregate 805 27.370 805 27.370 805 27.370 805 27.370
Coarse aggregat 1069 36.346 1069 36.346 1069 36.346 1069 36.346
Chemical admixt 0 0.000 1.930 0.057 2.90 0.086 3.86 0.115
PEG 0.75 2.895 87.261 2.90
PEG 0.5 1.930 58.174
Water - cement r 0.45 0.45 0.45 0.45
0.45 0.45
44.734