Sei sulla pagina 1di 9

PCN ADA1409074

CUSTOMER DRAWING LIST


TRANSFORMER DIVISION DRG. No. 41CL1233 R0

CUSTOMER : M/s AIRTECH INDUSTRIES PVT LTD.

P.O No. : AIPL/PO/RAYCHEM/2018/01 DATED.16.07.2018

RATING : 500kVA, 11/0.433kV 3 PHASE TRANSFORMER

SR.
DESCRIPTION DRG. No. REV. STATUS
No.

1 GA OF TRANSFORMER 31GA2095 R0 FIRST SUBMISSION

2 RATING & DIAGRAM PLATE 31RD1772 R0 FIRST SUBMISSION

3 HV CABLE BOX 31CD5240 R0 FIRST SUBMISSION

4 LV CABLE BOX 31CD5241 R0 FIRST SUBMISSION

5 MARSHALLING BOX ASSLY 31CD5242 R0 FIRST SUBMISSION

6 MARSHALLING BOX WIRING DIAGRAM 31CD5243 R0 FIRST SUBMISSION

7 FOUNDATION DETAILS 31CD5244 R0 FIRST SUBMISSION

8 GTP ADA1409074 R0 FIRST SUBMISSION

Prepared Checked APPD


MN DG SP
Sign

Rev.no Revision Note Date sign Date 03.08.18 03.08.18 03.08.18


FORM NO:FM/TF/PMG/34
IEC 60076
PCN ADA1409074
DATE : 08-08-2018 REV NO 0
GUARANTEED TECHNICAL PARTICULARS
Customer - M/s AIRTECH INDUSTRIES PVT LTD.
SR.NO DESCRIPTION UOM PARTICULARS
1 Name Of Manufacturer RAYCHEM RPG (P) LTD
2 Service Outdoor
3 Reference Standard IEC 60076
4 KVA Rating ( HV / LV Winding ) kVA 500.0
5 Rated Voltage
A. H.V. Winding Volt 11000.0
B. L.V. Winding Volt 433
6 Rated Frequency Hz 50
7 No Of Phases 3
8 Winding Connection
A. H.V. Winding Delta
B. L.V. Winding Star
9 Vector Group Dyn11
10 Tappings On HV
A. Type Off Circuit Tap Changer
B. Number Of Steps 4 Steps, 5 Positions
C. Tap Range +5% to -5%, 2.5% steps
11 Winding Material Copper
12 Insulation Class A
13 Type Of Cooling ONAN
14 Temp. Rise Over Reference Amb. Temp. Of 50 °C
A. In Oil By Thermometer °C 50
B. In Winding By Resistance °C 55
15 Component Losses At Rated Voltage On Principal Tappings & Rated Frequency
A.No Load Loss (+/- IEC Tol) kW 0.70
B.Load Loss (+/- IEC Tol) kW 3.60
C.Auxiliary Loss kW 0.00
16 Impedance At Principal Tap (+/- IEC Tol) % 4.00
A. Reactance % 3.93
B. Resistance At 75°C % 0.72
17 Total losses kW 4.30
18 Insulation Level
-Separate Source Power Frequency Voltage Withstand
A. HV Winding kV RMS 28
B. LV Winding kV RMS 3
-Induced overvoltage withstand
A. HV Winding kV RMS 22.0
B. LV Winding kV RMS 0.866
-Full Wave Lighting Impulse Withstand Voltage
A. HV Winding kV PEAK 75
B. LV Winding kV PEAK -
19 Efficiency at 75°C & Unity power factor
A. At Full Load % 99.15
B. At 3/4 Full Load % 99.28
C. At 1/2 Full Load % 99.36
20 Regulation At Full Load & 75°C
A. At Unity Power Factor % 0.80
B. At 0.8 Power Factor Lagging % 2.97
21 Terminal Arrangements
A. HV Side Cable Box
B. LV Side Cable Box
22 Approx. Weight
A.Core & winding Kg 1275
B.Tank & Fitting Kg 680
C.Oil Kg 635
D.Oil volume Ltrs 750
E. Total Weight Kg 2590
23 Approx. Overall Dimensions
A.Length mm 2200
B.Width mm 2250
C.Height mm 2250

Note : 1. Performance figures guaranted above are subject to tolerances as per IEC
2. Efficiency and regulation values are calculated based on nominal values of NLL,LL & %Z.
3. Weights and dimensions are subject to +/- 10% tol

Page 1 of 1

Prepared by : DG Approved by : SP FORM NO.FM/TF/PMG/13

Potrebbero piacerti anche