VS Series
Submittal Guide
VS Series
Initiating
Devices
Intelligent fire alarm solutions up to 1,000 points
Notification
Appliances
Hazardous Location
Devices
Door Holders
& Relays
Se
w.
S
e e w
e
w hat’s le no
ha
t's possib ...
possible now
Analog Control
Technology that saves lives
VS Series
Project: ___________________________
Contact: ___________________________
Date: ___________________________
Initiating
Devices
Thank you for giving us the opportunity to provide this submittal for an
VS Series Life Safety System. VS Series combines analog addressable
detection with technologically advanced sensor diagnostic capabilities.
Together these innovations offer unsurpassed stability, reliability, and flexibility.
Notification
Appliances
comprehensive presentation of related system components and devices.
Products we are submitting for your consideration are indicated by a
checkmark in the margins of the pages that follow.
Hazardous Location
useful product information, are available electronically on our VitalSigns
CD-ROM. This exhaustive collection of life safety related literature is fully
Devices
searchable.
Thank you for giving us the opportunity to provide this submittal. Please do
not hesitate to contact us should you require further information.
Door Holders
& Relays
_____________________________
VS Series Initiating Notification Hazardous Location Door Holders
Analog Control Devices Appliances Devices & Relays
iii
Intelligent fire alarm solutions up to 1,000 points
VS Series
Submittal Guide
VS Series Submittal Guide
Intelligent fire alarm solutions for small buildings
SERIES
Intelligent Fire Alarm Solutions
Analog Control
VS Series
Cohesive, VS Series Analog
Specifications.................................................................... 2
1
Initiating
Devices
buildings.
Intelligent Initiating Devices 11
With control panels, devices, and accessories all Fire/CO Detector............................................................. 12
V-Series Detectors.......................................................... 13
engineered to work in unison, VS Series systems
Duct Detectors................................................................ 14
provide reliable performance and the advanced Input/Output Modules..................................................... 14
Manual Pull Stations........................................................ 18
features you need for successful installation and
worry-free operation. Best of all, VS Series leaves
Notification
Appliances
you in control – not hemmed in by a limited product Notification Appliances 19
line. Kidde’s extensive range of fire alarm products Wall Strobes, Horns & Chimes......................................... 21
Low Frequency Horns and Horn-Strobes........................ 22
gives you the freedom to tailor each system to the Ceiling Strobes and Horn-Strobes................................... 22
particular needs of the building – and the budget Outdoor Horns & Strobes................................................ 23
Wall Speakers & Speaker-Strobes................................... 24
of the building owner – while a robust feature set Ceiling Speakers, Horns & Strobes.................................. 25
Hazardous Location
leaves plenty of room for upgrades, expansions, Outdoor Speakers & Strobes........................................... 26
LED Strobes and Horn-Strobes....................................... 27
and retrofits long into the future.
Audible Signals................................................................ 27
But innovative features tell only part of the
Devices
Harsh Environment Signals.............................................. 28
Accessories..................................................................... 29
story: when you specify VS Series you’re getting
Audio Notification System................................................ 30
more than outstanding value in a fire alarm panel;
you’re benefitting from a whole family of control,
Hazardous Location Devices 31
detection, and notification appliances finely tuned
Initiating Devices............................................................. 32
to work together – engineered and tested to func- Notification Appliances.................................................... 33
ing the needs of the future, VS Series is the chang- Door Holders & Relays 34
Door Holders................................................................... 34
ing face of small building fire detection today.
Relays............................................................................. 35
SPDT Relays................................................................... 35
v
VS
VS Series
SERIES
Analog Control
Specifications p. 2
Control Panels p. 3
Analog Control
Option Cards p. 4
VS Series
Power Supplies p. 6
Remote annunciation p. 8
Accessories p. 10
Initiating
Devices
VS Series life safety systems are a powerful intelligent solu- Clear-cut remote annunciation
tion for small to mid-sized buildings. Advanced analog tech- Remote annunciation is a strong suit of VS Series. Up to
nology delivers the benefits of flexible system installation, eight annunciators can be installed on a single system.
while a clean and easy-to-operatate user interface makes Compatible annunciators include a range of LED and LCD
panel operation and system maintenance quick and intuitive. models that provide zone or point annunciation, as well as
common control capabilities.
The smart choice
VS Series also supports graphic annunciation with optional
Notification
VS Series electronic device addressing eliminates the tedium
Appliances
RA Graphic Annunicator interface modules. Each interface
of setting dipswitches, and innovative programming features
provides common control, indicators, and 32 LEDS.
allow the system designer to customize powerful built-in
features to precisely suit the needs of the building owner. A complete line of accessories
VS Series life safety systems are supported by a complete
Flexibility built right in line of intelligent detectors, modules and related equipment,
Two fully-programmable front panel switch/LED combina- each of which is fully tuned and tested to operate in concert
tions provide an added measure of flexibility. Their slide-in with one another to provide highly reliable service and years
labels take the mystery out of custom applications, and of trouble-free operation.
present a clean finished appearance.
Hazardous Location
Perfect for retrofits
VS Series is particularly well-suited to retrofit applications.
Devices
All connections are made over standard wiring – no shielded
cable required. This means that in most situations existing
wiring can be used to upgrade a legacy control panel to
VS Series technology without the expense or disruption of
rewiring the entire building.
1
VS
SERIES
Analog Control
Analog Control
System Layout
VS Series
VS4
Any combination of two single- or dual device loop modules
Standard Loop: 250 points (one expansion slot) V-SLC2 Expander, Loop 1 of 2: 250 points
Up to 125 sensors and 125 modules per loop (one expansion slot)
V-SLC2-1 Expander Loop: 250 points (one expansion slot) V-SLC2 Expander, Loop 2 of 2: 250 points
Up to 20,000 feet of wiring per loop
Four Class B or two optional Class A NACs Four Class B or two optional Class A NACs
Optional 10 A or 6.5 A Booster
Ethernet (SA-ETH)
DACT/Dialer (SA-DACT) Up to eight remote annunciators
RS-232 (SA-232) Sixteen Conventional IDCs,
Relays: Two Form C, one Form A two additional NACs with RZI16-2 module
Each VS4 panel has room for up to two device loop controller modules in any combination
of single or dual 250-device loops. VS4 comes with one loop that supports up to 125 detectors and 125 modules.
VS1
Two Class B or two optional Class A NACs Loop supports up to 64 intelligent devices of any type.
Optional 10 A or 6.5 A Booster Power Supply
Each VS1 panel ships with one device loop controller that supports 64 devices of any type.
This panel’s device capacity cannot be expanded.
2
VS
VS Series
SERIES
Analog Control
SUBMIT
Control Panels
Analog Control
VS Series
Standard Features
The attractive appearance of VS Series control pan-
els means they won’t be a blemish on an expensive
architectural design. Their gently curved doorfronts offer
a distinctive flair with available red or silver finishes. Con-
trols are discreetly inset behind a striking black bezel.
• Auto-programming speeds installation time VS1 VS4
• Supports VS Series analog addressable modules and
detectors Dimensions
Initiating
Devices
Surface mounting holes Backbox with Backbox with door and
• Form C contacts for alarm and trouble, Form A for D2 D3 door attached trim ring attached
supervisory D7
labeling
D6
D9 D9
• Supports Genesis horn silence over two wires and UL
Notification
D5
Appliances
1971-compliant strobe synchronization Panel dimensions, in (cm)
D1* D2 D3 D4 D5* D6 D7 D8 D9
• Supports up to eight serial annunciators, (LCD, LED-
21.50 3.85 7.5 15.5 14.25 10.25 3.9 21.7 2.7
only, and graphic interface). VS1
(54.6) (9.8) (19) (39.4) (36.2) (26) (9.9) (55.1) (6.8)
• Can use existing wiring for most retrofit applications 28.0 3.85 9.0 22.0 15.75 10.25 3.9 28.2 2.7
VS4
(71.1) (9.8) (22.8) (55.8) (40.0) (26.0) (9.9) (71.6) (6.8)
• Upload/download remotely or locally *Add 1-1/2 in. (3.81 cm) to D1 and D5 dimensions for trim kit.
Hazardous Location
VS4-G-2 Four loop system with one 250-point loop installed. 230v, gray door.
VS4-GC Four loop system, one 250-point loop installed. 110v, gray door, LED strips, Canada.
VS4-GD Four loop system, one 250-point loop installed. 110v, gray door, with dialer.
Devices
VS4-GF Four loop system, one 250-point loop. 110v, gray door, LED strips, French Canada.
VS4-R Four loop system with one 250-point loop installed. 110v, red door.
VS4-R-2 Four loop system with one 250-point loop installed. 230v, red door.
VS4-RD Four loop system, one 250-point loop installed. 110v, red door, with dialer.
SA-TRIM2 VS4 Flush mount trim, black.
VS1-GD One loop system, one 64-point loop installed. 110v, gray door, with dialer.
& Relays
VS1-GL One loop system, one 64-point loop installed. 110v, gray door, English Canada.
VS1-GL-F One loop system, one 64-point loop installed. 110v, gray door, French Canada.
VS1-R One loop system with one 64-point loop installed. 110v, red door.
VS1-R-2 One loop system with one 64-point loop installed. 230v, red door.
VS1-RD One loop system, one 64-point loop installed. 110v, red door, with dialer.
SA-TRIM1 VS1 Flush mount trim, black
3
VS
SERIES
Analog Control
SUBMIT
Option Cards
Analog Control
VS Series
VS Series panels are supported by a complete line of modules and related equipment that
enhance performance and extend system capabilities. Option cards are easy to install and set
up. They simply plug directly into the control panel main circuit board or are connected to it
with a ribbon cable. After installation, terminals remain easily accessible for quick connection of
field wiring. The cabinet provides ample room for wire routing, keeping wiring neat and easy to
service at all times.
SA-232 RS-232
V-SLC2 Loop Expander Card interface
Class B wiring
SA-CLA
Class A Module RZI16-2 Remote Zone Interface
Loop 1 SEC
-
Data Line
+
- + +
Loop 1 PRI
+ - -
Loop Loop
Loop card device device
with VS4 control panels only. The loop expander card Loop 1 SEC
-
SA-CLA wiring
TB2 on main NAC1
+ + SA-CLA Class A Module
circuit board NAC1+
NAC2
+ + The SA-CLA card provides Class A capability for NAC and annuncia-
NAC2+ tor wiring. Its terminal block provides the wiring connection for NAC
return wiring. The card is required for annunciator Class A wiring even
+ though this wiring does not return to the SA-CLA card. The SA-CLA
is compatible with VS1 control panels only. VS4 panels are Class
+ A ready. The SA-CLA is installed directly to the control panel circuit
Class A card installed
board using its plastic standoffs and plug connection.
on main circuit board
SA-CLA VS1 Class A adapter module. Provides Class A capacity on NACs. Mounts in cabinet on main board.
4
VS
VS Series
SERIES
Analog Control
SUBMIT
Analog Control
VS Series
SA-ETH wiring
The SA-ETH card provides a standard 10/100 Base T Ethernet network connection
for connecting to an intranet, a local network, or the Internet. The card can be used
to upload and download panel configuration, history, and current status from the
VS-CU to the panel over the network.
The Ethernet card is installed on the plastic assembly and connects to the main
Ethernet card circuit board via a ribbon cable.
Initiating
Devices
SA-ETH Ethernet Port, Slave, for Ethernet connection to local area networks. Mounts in cabinet on base plate.
SA-232 wiring
GND (black wire) SA-232 RS-232 interface
TXD (white wire)
RXD (red wire) The SA-232 card provides an RS-232 interface with VS Series panels. It can be used
for connecting a printer to the control panel to print system events. The card also
can be used for connecting a computer to download a configuration program from
the VS-CU to the control panel.
The RS-232 card is installed on the plastic assembly and connects to the main circuit
board via a ribbon cable.
Notification
Appliances
SA-232
Serial Port (RS-232), for printers & computers, mounts in cabinet to base plate
Hazardous Location
telephone numbers. The modem feature of the SA-DACT can also be used for uploading
and downloading panel configuration, history, and current status to a PC running the VS-CU.
The dialer phone lines connect to connectors on the dialer’s main circuit board. Phone line
Devices
1 connects to connector J4 and phone line 2 connects to connector J1.
SA-DACT Dual Line Dialer/Modem, supports Contact ID, mounts in cabinet on base plate
device types. It requires 18 consecutive addresses on the Signaling Line Circuit (SLC).
& Relays
Addresses are assigned electronically. There are no address switches to set. The RZI16-2
incorporates two 8-segment DIP switches that are used to select the Alarm or Supervisory default device type for each of the
16 IDC circuits. The module also includes one 4-segment DIP switch used to select the default Relay or NAC output device
type. Device types other than the default are accomplished through programming.
RZI16-2 Remote Zone Interface Module. 16 Class B IDCs, 2 Class B Output. Includes bracket.
5
VS
SERIES
Analog Control
SUBMIT
Power Supplies
Analog Control
VS Series
Booster
mainthatpanel’s notification appliance circuit. This allows seamless expansion of existing NACs.
can be connected
together is limited by wire
Power Supply run length and available current
For comprehensive configuration and wiring details, refer to the MIRBPS Application Guide,
85001-0582.
Parallel Connection
The number of boosters
that can be connected
together is limited by wire
run length and available current
6
VS
VS Series
SERIES
Analog Control
SUBMIT
Analog Control
VS Series
Auxiliary Power Supply (APS)
TB1
Notification
The Auxiliary Power Supply (APS) is a self-
+
NAC1 appliance contained 24 Vdc power supply designed
circuit (NAC)
to augment fire alarm audible and visual
+
NAC2
Notification
power requirements as well as provide
+
NAC3 appliance
circuit (NAC) auxiliary power for life safety and security
+
NAC4
200 mA AUX
applications. The APS contains all of the
TB5
IN
Sense 1 COM
+
batteries, control and supervise four Class
Initiating
-
B or two Class A NAC circuits and moni-
Devices
OUT To next signaling device, NAC
IN
+
Notification
Appliances
Batteries and Battery Cabinets
12 Volt Batteries 12V4A (4.5 Ah) 12V6A5 (7.2 Ah) 12V10A (11 Ah) Data Sheet K85005-0127
12V24A (26 Ah) 12V17A (18 Ah) Data Sheet K85005-0127
6 Volt Batteries 6V8A (8 Ah) 6V10A (12 Ah) Data Sheet K85005-0127
Data Sheet K85005-0127
Hazardous Location
Battery Cabinet BC-1 (holds up to two 40 Ah batteries)
Devices
Door Holders
& Relays
7
VS
SERIES
Analog Control
SUBMIT
Remote annunciation
Analog Control
VS Series
Power
Signal Silence
Drill
Lamp Test
RLCD
Reset
Signal Silence
Reset
Lamp Test
RLCD-C RLED-C Two models have an LCD text display, and one has 16 pairs of
LEDs for zone annunciation. LCD models feature a large back-lit,
FACP Annunciator Annunciator
RS-485 CH1 (+) IN CH1 (+) IN
Power
Fire Alarm
Supervisory
four by twenty
CH1 +character per line, super-twist
CH1 (–) IN liquid crystal
CH1 (display.
–) IN
Ground Fault
Trouble CH1 – CH1 (+) OUT CH1 (+) OUT
4-inch square electrical box, usingCH2the included mounting CH2 (–) IN They
ring.
CH2 – CH2 (+) IN CH2 (+) IN
(–) IN
ables or disables common controls. The graphic annunicator interface cards supports 32 LEDs and 16 switches on
Power
Fire Alarm 24V (–) OUT 24V (–) OUT
Supervisory
Ground Fault
Trouble
Signal Silence
Lamp Test
GROUND GROUND
GROUND GROUND
LCD Annunciators
K-RLCD LCD text annunciator without common controls. English. Data Sheet K85005-0128
FACP Annunciator Annunciator
Annunciator First Expander Second Expander
RS-485 CH1 (+) IN CH1 (+) IN
OUT IN OUT IN OUT
K-RLCD-R
CH1 + LCD text annunciator
CH1 (–) IN without common
CH1 (–controls.
) IN English. Red. V (–) V (–) Data
V (–) Sheet K85005-0128
V (–) V (–)
CH1 – CH1 (+) OUT CH1 (+) OUT
V (+) V (+) V (+) V (+) V (+)
K-RLCD-C LCD text annunciator
CH1 (–) OUT with common controls.
CH1 (–) OUT English. F F Data
F Sheet K85005-0128
F F
CH2 (+) IN CH2 (+) IN
E E E E E
K-RLCD-CR LCD text annunciator
CH2 (–) IN with common controls.
CH2 (–) IN English. Red. D D Data
D Sheet K85005-0128
D D
LISTED 24 VDC CH2 (+) OUT CH2 (+) OUT
C C C C C
SUPPLY CH2 (–) OUT CH2 (–) OUT
LED Annunciators
24 VDC + 24V (+) IN 24V (+) IN
B
A
B
A
B
A
B
A
B
A
K-RLED-CR 16-pair LED zone annunciator with common controls. English. Red.
24 VDC – 24V (–) IN 24V (–) IN
Data Sheet K85005-0128
24V (+) OUT 24V (+) OUT
8 D D D D D
C C C C C
B B B B B
VS
VS Series
SERIES
Analog Control
SUBMIT
Analog Control
VS Series
Annunciator Enclosures
The RA Remote Annunciator Enclosures provide secure, surface mounted protec-
tion for annunciators and extenders. Each consists of a back plate, hinged cover,
and key lock. The enclosures are 16-gauge welded steel with a white, painted
finish. Each enclosure includes a security lock and two keys. The two- and three-
position enclosures have wiring channels for correct routing of interconnections.
RA-ENC1
The enclosures attach to a standard electrical box, and provide a mounting lip
that takes the place of the integral mounting ring supplied with the annunciators
and expanders.
Initiating
RA-ENC3
Devices
RA-ENC2
Notification
Appliances
The FireWorks Graphical Annunciation Interface is a software platform that provides
end users with clear, concise, and coordinated site incident information. FireWorks also
supports optional text-based web clients to provide remote status updates. Five configu-
rable graphical viewports offer simultaneous insight into different aspects of an incident,
while the underlying software dynamically manages content in each viewport based on
real-time events and user interaction. Facility maps, embedded HTML viewer, and live
event flow from vital equipment all come together instantly within view of an operator fac-
ing events that require solid information and split-second timing.
FW-CGSVM FireWorks Graphics Software. Fiveviewport display. No common control. Data Sheet K85005-0068
Hazardous Location
FW-IPMON1000 IP Monitoring, 1000 connections. Requires FW-DARCOM. Data Sheet K85005-0068
FW-DARCOM For Communication to DACRs and/or IPMON1000. Data Sheet K85005-0068
approved power supply. Always ensure that National and Local approv- RS-485 NETWORK DATA RS-485 NETWORK DATA
als and requirements are met when selecting a graphic panel supplier. FROM PREVIOUS PANEL TO NEXT PANEL
9
VS
SERIES
Analog Control
SUBMIT
Accessories
Analog Control
VS Series
+ +
Circuit Pair 1 IN Circuit Pair 1 OUT
- -
16 15 14 13 3-2-1 12 11 10 9
JP1
The GFD module is designed to detect ground fault conditions on either
LED 1 LED 2 of two independent power or data circuits. Each circuit must be balanced
8 7 6 5 4 3 2 1 with respect to ground. The module will detect when the resistance be-
To earth ground
tween any of the monitored conductors and earth ground drops below 10
From UL/ULC listed 24 VDC+ + To next GFD
or EOLR [3] [4]
K Ohms. Two LEDs are provided to indicate the conductor with the ground
fire alarm panel [4] 24 VDC- -
From IDC or + condition. A normally energized Trouble/Ground Fault relay is provided with
previous GFD
NO/NC relay contacts for interfacing with monitoring systems.
-
CDR-3 Coder
The CDR-3 Coder is an auxiliary circuit option module that provides two audio outputs, March Time and PSNI, (Positive,
successive, non-interfering). Dry relay contacts are provided for PSNI code, march time and duration. For the PSNI code,
the RS-232C input provides communications, between VM Series’s RS-232 communications card and the CDR-3.
CDR-3 PSNI Coder Module Data Sheet K85003-02709
10
VS
SERIES
Analog Addressable Initiating Devices
Detector Bases p. 13
Duct Detectors p. 13
Input/Output Modules p. 14
KI-Series
Intelligent
Manual Pull Stations p. 18
Initiating Devices
Initiating
Devices
Kidde brand Intelligent addressable detectors are meticulously engineered Standard Features
to deliver high-performance features, superb reliability, and unbeatable
quality. With their highly stable design, these detectors resist air movement • Optical, CO, heat, and multisensor models avail-
caused by heating and air conditioning, making them reliable performers able
ideally suited to modern building interiors. • Compatible standard, relay, isolator, and audible
The installation and maintenance advantages of Kidde brand Intel- bases
ligent addressable detectors add value throughout their service life. The • Electronic Addressing including mapping loca-
twist-and-lock design makes short work of installation and maintenance tion
operations. A plastic breakout on the detector housing optionally prevents
removal from the base except with a special tool. • Bases mount to standard North American two-
gang or 4" square electrical boxes
A bright, easy-to-see LED flashes red when the detector is in alarm, thus
eliminating much of the guesswork when responding to front-panel indica- • Tamper-resistant feature
Notification
Appliances
tions. • Self diagnostic capability with on-board storage
of results
KI-Series Device loop
• Optical detectors feature automatic rate com-
KI-Series control panels provide one device loop circuit that supports 125
pensated sensitivity adjustment, as well as dirty
detectors and 125 module addresses. V-SLC2 Loop Expander Cards
sensor warnings
provide additional device loops on the VS4 control panel. The V-SLC1-1
provides one loop with 250 additional addresses, and the V-SLC1-2 pro- • Manufactured to strict international ISO 9001
vides two loops totalling an additional 500 device addresses. standards
Class B wiring
Circuit specifications • Assembled using surface mount technology for
Hazardous Location
Device loops One loop, expandable to four (VS4), Class A or B. RF resistance
-
EachLoop
loop1 SEC
support
+
up to 250 device
Data Line addresses
• Conformally coated components resist dust and
Com. line voltage Maximum 20 V peek-to-peek humidity
- + +
Circuit current 0.5 A max
Devices
Loop 1 PRI
- -
Circuit impedance
+
66Ω total, 0.5 µF, max • Automatic detector test
Loop Loop
Isolators Loop card 64 maximum device device
• Low Profile Design
Class B wiring
Typical Wiring
Class A wiring
Class B Class A
- -
Loop 1 SEC Loop 1 SEC
Data Line
+ +
- + +- + +
Loop 1 PRI Loop 1 PRI
+ - -+ - -
Loop Loop Loop Loop
device Loopdevice
card device device
Loop card
Door Holders
Data Line
& Relays
Class Aheat
Kidde wiring
and smoke detectors comprehensive self-diagnostic capabil-
ity. The KI-PD, KI-PCD, and KI-PHD optical detectors continuously adjust
their sensitivity- to compensate for changes in the environment such as the
Loop 1 SEC
presence of dirt, + smoke, temperature, and humidity. These detectors issue
a dirty sensor- warning when +they reach+ their preset limit.
Loop 1 PRI
+ - -
Loop Loop
Loop card device device
Data Line
11
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
KI-Series
Analog Control
VS Series
Intelligent
Detectors
12
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Heat Detectors
Thanks to advanced thermistor technology, KI-Series heat detectors are ideal
for sensing fast, flaming fires and for applications where smoke detection is
inappropriate. They are particularly well-suited to areas such as kitchens and
shower rooms, where the ambient temperature is relatively constant, but
where steam and smoke are present. These heat detectors are capable of
performing comprehensive self-diagnostics and storing the results on board.
Initiating
Devices
The KI-HRD Rate-of-Rise Heat Detector provides a 15°F (8°C) per minute rate-of-rise
heat sensor for the detection of heat due to fire. The heat sensor monitors the tempera-
ture of the air and determines whether an alarm should be initiated.
Notification
Appliances
KI-HFD Fixed Temperature Heat Detector provides a 135°F (57°C) fixed-temperature
heat sensor for the detection of heat due to fire. The heat sensor monitors the tempera-
ture of the air and determines whether an alarm should be initiated.
KI-HFD Intelligent Addressable Fixed Temperature Heat Detector Data Sheet K85001-0647
Hazardous Location
Carbon Monoxide (CO) is the leading cause of accidental poisoning deaths in
America. Known as The Silent Killer, CO is odorless, tasteless, and colorless.
It claims nearly 500 lives, and results in more than 15,000 hospital visits
annually. CO detection has rapidly become a standard part of life safety
Devices
strategy. Monitored CO detection is mandated with increasing frequency in
all types of commercial applications, but particularly in occupancies such as
hotels, rooming houses, dormitories, day care facilities, schools, hospitals,
assisted living facilities, and nursing homes. In fact, more than half of the U.S.
population already lives in states requiring the installation of CO detectors in
some commercial occupancies.
mance CO sensor to detect carbon monoxide. The detector analyzes the smoke and
& Relays
13
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
KI-Series
Analog Control
VS Series
Bases
Detector mounting bases have wiring terminals that are accessible from the
room-side after mounting the base to the electrical box. The bases mount to
North American one-gang boxes and to 3½ inch or 4 inch octagon boxes, 1½
inches (38 mm) deep. They also mount to European BESA and one-gang boxes
with 60.3 mm fixing centers. The KI-SB4, KI-RB4, and KI-IB4 also mount to
North American 4 inch sq. electrical boxes. They include the GSA-TS4 Trim Skirt, Base with 4-inch
which is used to cover the “mounting ears” on the base. The KI-ABST mounts to trim skirt
Initiating
Devices
KI-SB KI-SB4 (c/w 4-inch trim skirt) Standard Detector Base Data Sheet K85001-0646
GSA-LED Remote alarm LED (use with standard base only) Data Sheet K85001-0592
KI-IB KI-IB4 (c/w 4-inch trim skirt) Isolator Detector Base Data Sheet K85001-0646
KI-RB KI-RB4 (c/w 4-inch trim skirt) Relay Detector Base Data Sheet K85001-0646
14
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Sounder Bases for CO and fire detectors add From power supply 24 VDC (+)
or previous base 24 VDC (-)
24 VDC (+) To next base
24 VDC (-) or EOL relay
Initiating
KI-ABLT Low Frequency Sounder Base for KI-Series Detectors, 520 hz, T3/T4 Data Sheet K85001-0651
Devices
KI-ABDT Sounder Base for KI-Series Detectors, 3k hz, T3/T4 Data Sheet K85001-0651
KI-ABST Sounder Base for KI-Series Detectors, 3k hz, fire only Data Sheet K85001-0646
AB4G-SB Surface Box for Audible Base Data Sheet K85001-0646
AUX_RISER_IN + AUX_RISER_OUT +
Notification
panel sends synchronization and channel commands to the GSA-
Appliances
T3T4; the channel selection determines the pattern. From previous device
SLC_IN +
To next device
SLC_OUT +
GSA-T3T4 Temporal Pattern Generator for KI-ABDT or KI-ABLT Sounder Bases Data Sheet K85001-0623
SuperDuct
Hazardous Location
Duct Detectors
Devices
Alarm relay output Remote Less than two inches deep, SuperDuct Intelligent addressable smoke
test station
detectors are ideal for installation in ductwork, where space is always at a
Duct smoke Return premium. Offering the most advanced and most reliable performance in
detector air
its class, SuperDuct represents the perfect balance of practical design and
HVAC
unit advanced technology.
Duct smoke Supply
detector air SuperDuct detectors feature a unique design that speeds installation and
simplifies maintenance. Removable dust filters, conformally coated circuit
Alarm relay output Remote
test station
boards, and optional water-resistant gaskets keep contaminants away
FACP
from components, ensuring years of trouble-free service. When cleaning
is required, the assemblies come apart easily and snap back together in
seconds.
Door Holders
& Relays
15
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Addressable initiating
Analog Control
Input/Output
VS Series
boards.
The actual function of each module is determined by its installer-selected personality code. This is downloaded
to the module from the device controller during system configuration. Because they are intelligent devices, all deci-
sions are made at the module. This allows lower communication speed but very fast control panel response time
and less sensitivity to line noise and loop wiring properties. As a result, twisted or shielded wire is not required.
Plug-in UIO
Plug-in UIO modules mount to UIO motherboards. Two- and six-
module UIO motherboards are available, making them ideal for instal-
lations where more than one module is required. Motherboards can
RM
ALA
FIRE DULE
MO
16
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Universal Class A/B Module
The Universal Class A/B Module is used to connect initiating, appliance, or two-wire smoke
GSA-UM
circuits in either Class A or Class B configurations. The plug-in version can also be used as a
Class A dry contact initiating device circuit. The actual function of this module is determined
by the “personality code” selected by the installer. Up to fifteen personalities are available. GSA-MAB
GSA-UM Universal Class A/B Module (Two-gang standard mount) Data Sheet K85001-0275
GSA-MAB Universal Class A/B UIO (Plug-in) Module Data Sheet K85001-0275
Initiating
Class B Input Module
Devices
The Class B Input Module is used to connect Class B normally-open Alarm, Supervisory, or
GSA-CT1/CT2
Monitor type dry contact initiating device circuits. The standard-mount version is available with
either one or two input connections. The plug-in version accepts two input connections. The
actual function of this module is determined by the “personality code” selected by the installer.
A total of four personalities are available. GSA-MCT2
GSA-CT1 Single Input Module (One-gang standard mount) Data Sheet K85001-0241
GSA-CT1HT Single Input High Temperature Module (One-gang standard mount) Data Sheet K85001-0241
GSA-CT2 Dual Input Module (One-gang standard mount) Data Sheet K85001-0241
GSA-MCT2 Dual Input UIO (Plug-in) Module Data Sheet K85001-0241
Notification
Appliances
Waterflow/Tamper Module
The GSA-WTM Waterflow/Tamper Module is a two circuit intelligent module. Circuit 1 is for Class
B normally-open waterflow alarm switches. When the input contact is closed for approximately 16
seconds, an “alarm” signal is sent to the loop controller. Circuit 2 is for Class B normally open dry
contact supervisory and tamper switches. When the input contact is closed, an “active” signal is sent GSA-WTM
to the loop controller. Conditions on both circuits are latched at the module.
GSA-WTM Waterflow/Tamper Module (One-gang standard mount) Data Sheet K85001-0297
Hazardous Location
Isolator Module
The GSA-IM Isolator Module is an intelligent device that allows part of the data loop to con-
Devices
tinue operating in the event of a short circuit. The module can be wired into a Class A data
loop at any point. A maximum of 64 isolator modules can be installed on one circuit. If a fault
occurs, the isolator cuts power to all devices beyond the isolator on the loop. Once activated,
the line fault isolator continuously checks the faulted side of the loop to determine if the short
still exists. When the fault is cleared, the module automatically restores the entire data loop GSA-IM
to its normal condition.
GSA-IM Fault Isolator Module (Two-gang standard mount) Data Sheet K85001-0271
Monitor Module
Door Holders
The GSA-MM1 is a single-circuit intelligent module that includes a Class B normally-open dry
& Relays
contact. This is used for monitoring input from devices such as fans, dampers, and doors.
When the input contact is closed, an “active” signal is sent to the loop controller. The active
condition is not latched at the module. GSA-MM1
17
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Signal Module
Analog Control
VS Series
The Signal Module is used to connect, upon command from the loop controller, supervised
Class B signal or telephone circuits to their respective power inputs. Models are available with
one or two power inputs. These may be either polarized 24 Vdc to operate audible and visual
GSA-CC1/CC2
signal appliances, or 25 and 70Vrms to operate audio evacuation speakers and firefighter’s
telephones. The actual function of this module is determined by the “personality code” selected
by the installer. A total of three personalities are available. GSA-MCC1/MCC2
GSA-CC1 Single Input Signal Module (Two-gang standard mount) Data Sheet K85001-0237
GSA-MCC1 Single Input Signal UIO (Plug-in) Module Data Sheet K85001-0237
GSA-CC2 Dual Input Signal Module (Two-gang standard mount) Data Sheet K85001-0237
GSA-MCC2 Dual Input Signal UIO (Plug-in) Module Data Sheet K85001-0237
Initiating
Devices
GSA-CR Control Relay Module (One-gang standard mount) Data Sheet K85001-0239
GSA-MCR Control Relay UIO (Plug-in) Module Data Sheet K85001-0239
GSA-CRH High Power Control Relay Module (One-gang standard mount) Data Sheet K85001-0644
the data loop. This module supports only one personality: no user configuration is required.
GSA-MCRR
GSA-CRR Polarity Reversal Relay Module (One-gang standard mount) Data Sheet K85001-0239
GSA-MCRR Polarity Reversal Relay UIO (Plug-in) Module Data Sheet K85001-0239
GSA-CC1S Synchronization Output Module (One-gang standard mount) Data Sheet K85001-0543
GSA-MCC1S Synchronization Output UIO (Plug-in) Module Data Sheet K85001-0543
Input/Output Module
The Input/Output Module is an intelligent device that provides
• Output with monitor input GSA-IO
• Input/programmable output
• Input/direct output
GSA-MMIO
GSA-IO Input/Output Module (One-gang standard mount) Data Sheet K85001-0533
GSA-MIO Input/Output UIO (Plug-in) Module Data Sheet K85001-0533
18
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Individual Riser 1 Input to each SIGA-UIO module than one module. This significantly reduces wiring
requirements. UIO motherboards mount inside the
Initiating
MFC-A cabinet or other suitable UL-listed electrical enclosure.
Devices
GSA-UIO2R Universal Input/Output Module Board with Riser Inputs — 2 Module Positions Data Sheet K85001-0365
GSA-UIO6R Universal Input/Output Module Board with Riser Inputs — 6 Module Positions Data Sheet K85001-0365
GSA-UIO6 Universal Input/Output Module Board — 6 Module Positions Data Sheet K85001-0365
Abort
Releasing Module
First alarm output
Manual Release Form C 3 A @24 Vdc
24 Vdc in
Notification
Appliances
DS5 DS3
DS4
and offers a wide range of options that Pre-release CCT1 (pulsed 15/60)
ing module includes a built-in timer that inhibits the deluge function 2
3
2
3
Hazardous Location
mounts inside an MFC-A cabinet or other suitable UL-listed electrical enclosure. Each MFC-A will hold one GSA-REL.
GSA-REL Intelligent addressable releasing module Data Sheet K85001-0531
Devices
RELA-ABT Abort station Data Sheet K85001-0531
RELA-SRV Service disconnect station Data Sheet K85001-0531
276A-REL Manual releasing station (single-action) Data Sheet K85001-0531
278A-REL Manual releasing station (double-action) Data Sheet K85001-0531
RELA-EOL Polarized end-of-line relay Data Sheet K85001-0531
Related Equipment
MFC-A Multi-function Cabinet (for UIO and Releasing modules)
27193-11 Surface Mount Box - Red, One-gang
Door Holders
19
VS
SERIES
Analog Addressable Initiating Devices
SUBMIT
Addressable initiating
Analog Control
VS Series
TB2
GSA-M270 series manual pull stations are made from Red LED
(Alarm/Active)
4 3 2 1
Green LED
(Normal)
or Previous Device
GSA-M270 One Stage Fire Alarm Station, English Markings Data Sheet K85001-0279
GSA-M270P Two Stage (Pre-signal) Fire Alarm Station, English Markings Data Sheet K85001-0279
276-K2 GA Key — for pre-signal station Data Sheet K85001-0279
270-GLR 20 Break-rods — for GSA-M270 series Data Sheet K85001-0279
276B-RSB Surface Mount Box, Red — for GSA-M270 series Data Sheet K85001-0279
REAR VIEW
8 7
red LEXAN. To initiate an alarm, first lift the upper door, TB1
GSA-M278 Double Action (One Stage) Fire Alarm Station, English Markings Data Sheet K85001-0279
276B-RSB Surface Mount Box, Red — for GSA-M278 series Data Sheet K85001-0279
276-GLR 20 Break-rods — for GSA-M278 series Data Sheet K85001-0279
Stopper II
This unique device helps prevent false alarms without restricting legitimate ones. It consists of a tamper-
proof clear LEXAN polycarbonate shield and frame that fits easily over manual pull stations. When lifted,
it sounds a piercing warning horn.
STI-1100 (Flush) STI-1130 (Surface) Stopper II with Horn Data Sheet K85001-0491
STI-1200 (Flush) STI-1230 (Surface) Stopper II without Horn Data Sheet K85001-0491
STI-3100 (2" Spacer) STI-3004 (Conduit Insert) Spacers Data Sheet K85001-0491
STI-3002 (Gasket) STI-3003 (Conduit Gasket) Weatherproofing Data Sheet K85001-0491
20
VS
SERIES
Notification Appliances
Notification
Outdoor Speakers & Strobes p. 26
Appliances
Audible Signals p. 27
Accessories p. 29
Notification
Class B with separate strobe and horn circuits
Appliances
combination horn-strobes, when used
with the innovative Signal Master Module,
support independent horn control over
a single pair of wires and precision
Notification Appliance Circuit
synchronization that exceeds UL Class A with combination horn-strobe circuit
requirements. This reduces wiring time while
meeting the requirements of even the most
demanding application.
Hazardous Location
Device Wiring, Speaker-strobes Device Wiring, Horn-strobes
Devices
To listed fire alarm control panel
(supervised amplifier signal circuit
– 25.2 or 70.7V rms) + +
To listed fire alarm control panel
(supervised signal circuit
– 20-24 Vdc) + +
SPKR
C
S+
S-
On a common circuit, strobes flash once per second (1 The following control panels, power supplies, and modules
fps) within 10 milliseconds over a two-hour time period. A provide synchronization sources that enable Genesis strobe
synchronization source is required to comply with UL 1971 devices to comply with UL 1971 synchronization standards:
synchronization standards. Temporal setting (private mode GSA-CC1S, GSA-MCC1S, SIGA-CC2A, GSA-MCC2A,
only): synchronized to temporal output on the same circuit. MG1M-RM, MIRBPS6A, MIRBPS10A, APS6A, APS10A, VM
Series, VS1, VS4, VM, FX Series Intelligent and Conventional
control panels.
19
VS
SERIES
Notification Appliances
Genesis Visual
Analog Control
VS Series
Signaling on-demand
Though designed for discretion, Genesis signals are also
Low Frequency Horns and Horn-
engineered to command attention. Wall-penetrating high
Strobes, p. 26
dB output and patented FullLight strobe technology im-
merse the protected area with levels of light and sound
Ceiling Horns, that simply can’t be ignored – all in exchange for the low-
Notification
Appliances
20
VS
SERIES
Notification Appliances
SUBMIT
Genesis strobes offer 15 to 110 candela output, which is selectable with a conveniently-located switch on the side of the
device. The candela output setting remains clearly visible even after final installation, yet it stays locked in place to prevent
unauthorized tampering. (Data Sheet K85001-0573)
White housing White housing Red housing Red housing Fire Alarm Appliances
no marking with “FIRE” no marking with “FIRE” (with “Running Man” icon)
EG1-VM EG1F-VM EG1R-VM EG1RF-VM Strobe only (15/30/75/110 cd)
EG1F-V1575 EG1RF-V1575 Strobe only (15/75 cd¹), 24 V
Genesis Horns and Horn-strobes reach output levels as high as 99 dB and features a unique multiple frequency tone that
results in excellent wall penetration and an unmistakable warning of danger. Horns may be configured for either coded or non-
Notification
Appliances
coded signal circuits. They can also be set for low dB output with a jumper cut that reduces horn output by about 5 dB.
(Data Sheet K85001-0573)
White housing White housing Red housing Red housing Fire Alarm Appliances
no marking with “FIRE” no marking with “FIRE” (with “Running Man” icon)
EG1-HD EG1F-HD EG1R-HD EG1RF-HD Horn only (high/low dB)
EG1-HDVM EG1F-HDVM EG1R-HDVM EG1RF-HDVM Horn-strobe (15/30/75/110, high/low dB)
EG1F-HDV1575 EG1RF-HDV1575 Horn-strobe (15/75 cd¹, high/low dB), 24 V
EG1-P EG1F-P EG1R-P EG1RF-P Steady horn (not compatible with Signal Master)
Hazardous Location
Genesis mass notification appliances bring the same high-performance fire alarm features and unobtrusive design to
mass notification applications. Available with amber lenses and optional “ALERT” housing labels, they are ideal for applica-
tions that require differentiation between fire alarm and mass notification alerts. (Data Sheet K85001-0573)
Devices
White housing White housing Mass Notification Appliances
no marking with “ALERT” (with no “Running Man” icon)
G1WN-VMA G1WA-VMA Strobe only, amber lens (A/B/C/D cd settings)
G1WN-VMC G1WA-VMC Strobe only, clear lens (15/30/75/110 cd)
Genesis chimes and chime-strobes produce a pleasing mellow tone. When steady (non-stroked) voltage is applied, the
chime automatically pulses at 60 strokes per minute, or may be field-configured for temporal output. When installed with
a GIM Signal Master Module, the chime may also be field-configured for coded operation. Chimes may be set for low dB
output with a jumper cut that reduces sound output by about 5 dB. (Data Sheet K85001-0574)
White housing White housing Red housing Red housing Fire Alarm Appliances, high/low dB
no marking with “FIRE” no marking with “FIRE” (with “Running Man” icon)
Door Holders
Trim plates for wall horns, chimes, and strobes are ideal for covering openings left behind during retrofits.
White plate White plate Red plate Red plate White plateFire Trim Plates
no marking with “FIRE” no “FIRE” with “FIRE” with “ALERT”
EG1T EG1T-FIRE EG1RT EG1RT-FIRE G1WT-ALERT Trim plate for 2-gang or 4” boxes
¹ 15/75 cd models provide fixed output. The 15 cd output component complies with UL1971. The 75 cd output component complies with UL 1638.
21
VS
SERIES
Notification Appliances
SUBMIT
UL
compliant
signals for
G4LF Series notification appliances provide the benefits of Genesis life safety signals with
output suitable for sleeping areas and other applications requiring low frequency audible tones.
These high-performance appliances generate a crisp 520 Hz tone in the standard 3-3 tem-
poral pattern. An optional setting configures the appliance for continuous audible output — a
critical feature for notification appliance circuits that are coded with a CDR-3 coder module.
All G4LF appliances feature field-configurable high and low dB output settings. Horn-Strobe
models feature field-selectable 15, 30, or 75 cd output settings.
Initiating
Devices
G4LFWN-HVM Horn-Strobe, 520 Hz, White Housing, No Marking, 15/30/75 cd Data Sheet K85001-0639
G4LFWF-HVM Horn-Strobe, 520 Hz, White Housing, FIRE Marking, 15/30/75 cd Data Sheet K85001-0639
G4LFRN-HVM Horn-Strobe, 520 Hz, Red Housing, No Marking, 15/30/75 cd Data Sheet K85001-0639
G4LFRF-HVM Horn-Strobe, 520 Hz, Red Housing, FIRE Marking, 15/30/75 cd Data Sheet K85001-0639
G4LFWN-H Horn, 520 Hz, White Housing, No Marking Data Sheet K85001-0639
G4LFWF-H Horn, 520 Hz, White Housing, FIRE Marking Data Sheet K85001-0639
G4LFRN-H Horn, 520 Hz, Red Housing, No Marking Data Sheet K85001-0639
G4LFRF-H Horn, 520 Hz, Red Housing, FIRE Marking Data Sheet K85001-0639
Notification
Appliances
Strobes and
Horn-Strobes
Genesis ceiling strobes are available in low- or high-candela output models featuring
Ceiling Strobes
15 to 95, or 95 to 177 cd output. The setting is selectable with a conveniently-located
Data Sheet K85001-0557
switch that remains clearly visible even after final installation, yet it is locked in place
to prevent unauthorized movement after installation. Ceiling Horn-strobes
Data Sheet K85001-0559
Genesis horn output reaches as high as 99 dB (peak) and features a unique multiple
frequency tone that results in excellent wall penetration. Horns may be set for low
dB output with a jumper cut that reduces horn output by about 5 dB.
All models are rated for both wall and ceiling installation.
22
VS
SERIES
Notification Appliances
SUBMIT
Notification
Appliances
WG4RF-H WG4RF-HVMC WG4WF-H WG4WF-HVMC WG4RN-H WG4RN-HVMC WG4WN-H WG4WN-HVMC
Light Output
Standard Candela Horn-strobes High Candela Horn-strobes
Strobe Switch Position Strobe Switch Position
Standard/rating Standard/rating
D C B A D C B A
Hazardous Location
UL 1971 Indoor 15 cd 29 cd 70 cd 87 cd UL 1971 Indoor 102cd 123cd 147cd 161cd
UL 1638 Outdoor @ -35°C 6 cd 12 cd 28 cd 35 cd UL 1638 Outdoor @ -35°C 41cd 50 cd 60 cd 65 cd
CAN/ULC-S526 Outdoor @ -40°C 1 cd 3 cd 8 cd 10 cd CAN/ULC-S526 Outdoor @ -40°C 11 cd 14 cd 17 cd 18 cd
Devices
White housing White housing Red housing Red housing Outdoor Fire Alarm Appliances
no marking with “FIRE” no marking with “FIRE”
WG4WN-H WG4WF-H WG4RN-H WG4RF-H Horn Only
WG4WN-HVMC WG4WF-HVMC WG4RN-HVMC WG4RF-HVMC Horn-Strobe, standard cd output
WG4WN-HVMHC WG4WF-HVMHC WG4RN-HVMHC WG4RF-HVMHC Horn Only, high cd output
WG4WTS (white) WG4RTS (red) Surface Skirt for Genesis WG4 Appliances
74347U (white) 449 (red) Surface mount box, outdoor rated
WG4GSKT Genesis WG4 Full Body Mounting Gasket for Smooth Surfaces
23
VS
SERIES
Notification Appliances
SUBMIT Genesis
Speakers and
Analog Control
ls
frequency signa
for sleeping
VS Series
areas!
Speaker-strobes
Genesis speakers combine high performance output with a low
profile design to deliver a life safety audio solution that’s as versatile Candela and wattage settings remain
as it is effective. Protruding no more than one inch from the wall, clearly visible even after final installation.
these appliances blend inconspicuously with any decor. All speak-
ers feature selectable ¼, ½, 1, or 2 watt operation. The ingenious Genesis G4E
Mass Notification Expander
Speaker-strobes feature field-configurable candela output, select- provides a separate,
able with a conveniently-located switch on the bottom of the device. independently-controlled
strobe that fits behind a
Initiating
Devices
Genesis high fidelity Speakers are can generate UL compliant low Genesis G4 Series speaker
frequency signals now required for sleeping areas! or speaker-strobe. (Data
Sheet K85001-0610)
High fidelity speakers and speaker-strobes meet new standards for audible tones in sleeping areas and produce
crisp, clear voice audio output that is highly intelligible over large areas. (Data Sheet K85001-0642)
White housing White housing Red housing Red housing Fire Alarm Speakers
no marking with “FIRE” no marking with “FIRE” (no “Running Man” icon)
G4HFN-S2 G4HFWF-S2 G4HFRN-S2 G4HFRF-S2 25 V Speaker
G4HFN-S7 G4HFWF-S7 G4HFRN-S7 G4HFRF-S7 70 V Speaker
G4HFN-S2VM G4HFWF-S2VM G4HFRN-S2VM G4HFRF-S2VM 25 V Speaker-strobe (15/30/75/110 cd settings)
G4HFN-S7VM G4HFWF-S7VM G4HFRN-S7VM G4HFRF-S7VM 70 V Speaker-strobe (15/30/75/110 cd settings)
High fidelity mass notification speakers and speaker-strobes feature optional amber lenses and “ALERT” lettering on
white housings, and meet new standards for audible tones in sleeping areas. (Data Sheet K85001-0642)
Clear lens Amber lens Amber lens High Fidelity Mass Notification Speakers
“ALERT” no marking “ALERT” — white housing, no “Running Man icon”
G4HFWA-S2VMC G4HFWN-S2VMA G4HFWA-S2VMA 25 V Speaker-strobe (A/B/C/D cd settings)
G4HFWA-S7VMC G4HFWN-S7VMA G4HFWA-S7VMA 70 V Speaker-strobe (A/B/C/D cd settings)
Speaker only models: G4HFWA-S2 (25 V, “ALERT” marking) G4HFWA-S7 (70 V, “ALERT” marking)
Mass notification speakers and speaker-strobes feature amber lenses and optional “ALERT” lettering. They are ideal for
applications that require differentiation between fire alarm and mass notification alerts. (Data Sheet K85001-0642)
Clear lens Clear lens Amber lens Amber lens Mass Notification Speakers
no marking “ALERT” no marking “ALERT” — white housing, no “Running Man” icon
G4WN-S2VMC G4WA-S2VMC G4WN-S2VMA G4WA-S2VMA 25 V Speaker-strobe (A/B/C/D cd settings)
G4WN-S7VMC G4WA-S7VMC G4WN-S7VMA G4WA-S7VMA 70 V Speaker-strobe (A/B/C/D cd settings)
G4EWN-C G4EWF-C G4EWN-A G4EWA-A Mass notification expander, white
G4ERN-A G4ERA-A Mass notification expander, red
Speaker-only models, 25 V: G4WN-S2 (no marking) G4WA-S2 (“ALERT” marking)
Speaker-only models, 70 V: G4WN-S7 (no marking) G4WA-S7 (“ALERT” marking)
24
VS
SERIES
Notification Appliances
Genesis SUBMIT
high fidelity
Genesis GC Series Ceiling Models Speakers are als
UL compliant
o
low
Speakers and
ls
frequency signa
for sleeping
areas!
Speaker-Strobes
The Genesis line of multi-candela and multi-wattage ceiling
signals feature all the hallmarks that have made Genesis Select
products a big hit with designers, engineers, building own- 15/30/75/95 Select
ers, and installers everywhere. Precision timing electron- and 95/115/150/177 ¼, ½, 1, or 2
ics, and low current draw bring the benefits of the popular candela output! watt operation!
Genesis wall-mount models to ceiling applications. These
signals are 30 percent slimmer than comparable signals Data Sheet K85001-0641
on the market. They are compatible with standard 4-inch
(10 cm) square electrical boxes and don’t require extension
rings or trim plates.
Notification
GC-S2 GCFR-S2 Speaker-only models, 25 V
Appliances
GC-S7 GCF-S7 GCFR-S7 Speaker-only models, 70 V
Hazardous Location
GCHFWN-S2 GCHFWF-S2 GCHFRN-S2 GCHFRF-S2 Speaker-only models, 25 V
GCHFWN-S7 GCHFWF-S7 GCHFRN-S7 GCHFRF-S7 Speaker-only models, 70 V
Devices
High Fidelity Mass Notification Speakers and Speaker-strobes
Clear lens Amber lens Amber lens White housings
with “ALERT” no marking with “ALERT” No “Running Man” Icon
GCHFWA-S2VMC GCHFWN-S2VMA GCHFWA-S2VMA 25 V Speaker, four standard cd settings
GCHFWA-S2VMCH GCHFWN-S2VMAH GCHFWA-S2VMAH 25 V Speaker, four high cd settings
GCHFWA-S7VMC GCHFWN-S7VMA GCHFWA-S7VMA 70 V Speaker, four standard cd settings
GCHFWA-S7VMCH GCHFWN-S7VMAH GCHFWA-S7VMAH 70 V Speaker, four high cd settings
GCHFWA-S2 (25 V, “ALERT” marking) GCHFWA-S7 (70 V, “ALERT” marking) Speaker-only models
Door Holders
Clear lens Clear lens Amber lens Amber lens White housings
no marking with “ALERT” no marking with “ALERT” No “Running Man” Icon
GCWN-S2VMC GCWA-S2VMC GCWN-S2VMA GCWA-S2VMA Speaker-strobe, 25 V, four standard cd settings
GCWN-S2VMHC GCWA-S2VMHC GCWN-S2VMHA GCWA-S2VMHA Speaker-strobe, 25 V, four high output cd settings
GCWN-S7VMC GCWA-S7VMC GCWN-S7VMA GCWA-S7VMA Speaker-strobe, 70 V, four standard cd settings
GCWN-S7VMHC GCWA-S7VMHC GCWN-S7VMHA GCWA-S7VMHA Speaker-strobe, 70 V, four high output cd settings
GCWN-S2 (25 V) GCWA-S2 (25 V, “ALERT”) GCWN-S7 (70 V) GCWA-S7 (70 V, “ALERT”) Speaker-only models
25
VS
SERIES
Notification Appliances
SUBMIT
Weatherproof Speakers
VS Series
and Speaker-Strobes
Genesis WG4 Series speakers and speaker-strobes are among the most ver-
satile emergency signals of their kind. Rated for indoor or outdoor use, they are
suitable for a wide range of wet and harsh environments with a listed operating
temperature range of as low as -31°F to as high as 151°F (-35°C to 66°C).
Refer to Data Sheet K85001-0626 -- Genesis Outdoor Speakers and Strobes for details.
Initiating
Devices
mode signaling only. To set the device for temporal Candela mode selection
flash, snip the jumper at JP1.
WG4RF-S WG4RF-SVMC WG4WF-S WG4WF-SVMC WG4RN-S WG4RN-SVMC WG4WN-S WG4WN-SVMC WG4WN-SVMA WG4WA-SVMA WG4WA-SVMC
White housing White housing Red housing Red housing Fire Alarm Speakers
no marking with “FIRE” no marking with “FIRE”
WG4WN-S WG4WF-S WG4RN-S WG4RF-S 25/70 V Speaker
WG4WN-SVMC WG4WF-SVMC WG4RN-SVMC WG4RF-SVMC 25/70 V Speaker-strobe (15/29/70/87 cd)
WG4WF-SVMHC WG4RN-SVMHC WG4RF-SVMHC 25/70 V Speaker-strobe (102/123/147/161 cd)
Genesis mass notification speakers and speaker-strobes bring the same high-performance fire alarm features and
unobtrusive design to mass notification applications. Available with amber lenses and optional “ALERT” lettering, they are ideal
for applications that require differentiation between fire alarm and mass notification alerts.
White housing White housing Mass Notification Speakers
no marking “ALERT” — white housing, no “Running Man” icon
WG4WN-SVMA WG4WA-SVMA 25/70 V Speaker-strobe, amber lens (13/25/5962 cd output)
WG4WN-SVMHA WG4WA-SVMHA 25/70 V Speaker-strobe, amber lens (84/101/125/130 cd output)
WG4WA-SVMC 25/70 V Speaker-strobe, clear lens (15/29/70/87 cd output)
WG4WN-SVMHC WG4WA-SVMHC 25/70 V Speaker-strobe, clear lens (102/123/147/161 cd output)
WG4WA-S 25/70 V Speaker
Trim skirts
WG4WTS (white) WG4RTS (red) Surface Skirt for Genesis WG4 appliance family.
26
VS
SERIES
Notification Appliances
SUBMIT
White housing White housing Red housing Red housing All fire alarm appliances come
no marking with “FIRE” no marking with “FIRE” with the “Running Man” Icon
GL1WN-HDVMC GL1WF-HDVMC GL1RN-HDVMC GL1RF-HDVMC Horn-Strobe
GL1WN-HD GL1WF-HD GL1RN-HD GL1RF-HD Horn-only
GL1WN-VMC GL1WF-VMC GL1RN-VMC GL1RF-VMC Strobe-only
GL1WN-TP (white) GL1RN-TP (red) Trim Plate for four-inch square boxes
GL1WN-BB1G (white) GL1RN-BB1G (red) One-gang surface box
Audible Signals
Notification
Appliances
Fire Alarm Bells
Kidde fire alarm bells are of the underdome type with heavy-duty mechanisms. Gongs are
made of selected alloy steel to generate the loud, resonant tones. For weatherproof applica-
tion, optional surface weatherproof backboxes are available.
323D-10AW (Grey) 323D-10AW-R (Red) 10-inch Single Stroke, Diode — 20-24Vdc Data Sheet E85001-0333
439D-6AW (Grey) 439D-6AW-R (Red) 6-inch Vibrating, Diode — 20-24Vdc Data Sheet E85001-0333
439D-10AW (Grey) 439D-10AW-R (Red) 10-inch Vibrating, Diode — 20-24Vdc Data Sheet E85001-0333
Hazardous Location
Multiple Tone Signal
Devices
The 5530MD-24AW is a weatherproof heavy-duty industrial, tone-selectable, signaling de-
vice capable of producing volume-controlled, high-decibel tones. It uses a microprocessor
circuit to create 27 distinctive tones. A single tone may be selected by setting a miniature
dip switch within the unit.
5530MD-24AW 27-Tone Selectable Signal — 24Vdc Data Sheet K85001-0415
Multi-purpose Loudspeaker
The HPSA15 loudspeaker is a high-efficiency double re-entrant loudspeaker that operates within a
Door Holders
nominal frequency response range of 400-14,000 Hz, and provides audible output of 120 dB (peak
& Relays
at one meter) at the rated power level. It includes a versatile, three-way, 25/70.7 V line transformer
that meets a variety of distributed system needs. The transformer is adjustable by means of a
convenient seven-position, watts/impedance selection switch.
HPSA15R2570 15-watt loudspeaker, red Data Sheet K85001-0591
HPSA15G2570 15-watt loudspeaker, gray Data Sheet K85001-0591
27
VS
SERIES
Notification Appliances
SUBMIT
Enhanced Integrity Series
Analog Control
Harsh Environment
VS Series
North American
2-gang electrical box
Mounting Plate
Signals Housing
Surface Box (optional)
All Enhanced Integrity devices are UL 1971 listed for both wall and ceiling First Device
orientation. Enhanced Integrity strobes meet the latest UL1971 synchronization - Horn/Strobe Horn/Strobe
To Fire Alarm
H+ H+
requirements when used with the MG1M Signal Master. Integrity devices are
Control Panel
Signal Circuit H- H-
S+ S+
+
shipped with wall mount style “FIRE” lens markings. Other lens markings are
S- S- To Next Device
or EOL Resistor
-
available. +
Initiating
Devices
28
VS
SERIES
Notification Appliances
SUBMIT
Accessories
Bell/Strobe Plate
The bell/strobe plate is ideal for renovation and retrofit projects, and new construction.
It is equipped with a self-synchronizing strobe and is designed to allow on-site mount-
ing of the 439 series Vibrating Bell, providing instant conversion to Bell/Strobe audible/
visual signal appliances. The strobe is designed for 20 to 24Vdc operation and must
be connected to signal circuits which output a constant (not pulsed) voltage. A diode
is used to allow full signal circuit supervision.
403-5A-R (15 cd) 403-7A-R (15/75 cd) 403-3A-R (30 cd) 403-8A-R (110 cd) Data Sheet K85001-0441
Notification
Integrity Lens Marking Kits
Appliances
Integrity strobes are shipped with wall mount style “FIRE” lens markings. Where ceiling mount, other languages or dif-
ferent lens markings are required, optional LKW and LKC series Lens Marking Kits are available. Lens marking sleeves
snap right over the strobe lens providing a quick, easy, change.
LKW-1R (Wall orientation) “FIRE” (Red)
LKW-1 (Wall orientation) LKC-1 (Ceiling orientation) “FIRE”
LKW-2 (Wall orientation) LKC-2 (Ceiling orientation) “FEU”
LKW-3 (Wall orientation) LKC-3 (Ceiling orientation) “FIRE/FEU”
LKW-4 (Wall orientation) LKC-4 (Ceiling orientation) “SMOKE”
Hazardous Location
LKW-5 (Wall orientation) LKC-5 (Ceiling orientation) “HALON”
LKW-6 (Wall orientation) LKC-6 (Ceiling orientation) “CO2”
Devices
LKW-7 (Wall orientation) LKC-7 (Ceiling orientation) “EMERGENCY”
LKW-8 (Wall orientation) LKC-8 (Ceiling orientation) “ALARM”
LKW-9 (Wall orientation) LKC-9 (Ceiling orientation) “FUEGO”
LKW-10 (Wall orientation) LKC-10 (Ceiling orientation) “ALERT”
Mounting Accessories
Integrity Temporal Horn, Horn/strobe Integrity Chimes, Chime/strobes
757A-SB Surface Box, Red, Indoor 757A-SB Surface Box, Red, Indoor
757A-SBW Surface Box, White, Indoor 757A-SBW Surface Box, White, Indoor
757A-WB Weatherproof Box, Red, Surface
757A-WBW Weatherproof Box, White, Surface Genesis Signals
Door Holders
29
VS
SERIES
Notification Appliances
SUBMIT
Audio Notification System
Analog Control
VS Series
See Data Sheet K85001-0587 for complete specifications and ordering information.
EOLR
Devices
ALARM
1
TB2
Notification
Appliances
P2
Audio Notification Panels
MSG MIC
GAIN GAIN
J8
J3
Panels include DMR, Power Supply & Battery Charger, Standard Message, Microphone,
P3
and Cabinet.
P4
DR
ANS25MDG2 (Grey Cabinet) ANS25MDG2 (Red Cabinet) 25 Watt Audio Notification Panel. LED 5
LED 4
30
VS
SERIES
Hazardous Location Devices
Hazardous Location Devices
Initiating Devices p. 32
Hazardous
Notification Appliances p. 33
Location Devices
Kidde hazardous location devices provide reliable life safety protection and emergency signaling in areas where
atmospheres could become harsh or explosive. All hazardous location devices are UL rated under the full range of
classifications set out in the National Electrical Code.
The following classification definitions are an interpretive summary based on the 1996 edition of the National Elec-
trical Code (NEC, NFPA 70). Refer to the latest editions of NFPA 497M, NFPA 70 and the UL Hazardous Location
Equipment Directory for current and more detailed information. For more information on NEMA classifications, refer
to NEMA Standards Publication No. 250.
Classes Divisions
The Location Classes are broken down by the NFPA into
Class I - Hazardous Gases. Class I locations are areas in which flam- Divisions 1 and 2, defining different levels of risk. In general,
mable gases or vapors are or may be present in the air in quantities the risk of there being a hazardous presence of flammable/
sufficient to produce explosive or ignitable mixtures. combustible/ignitable materials is higher for Division 1 than
Typical Class I Hazardous Areas for Division 2. The specifics differ between the three classes
• Spray painting and finishing areas (I, II and III). Equipment suitable for Division 1 is also suitable
• Utility gas plants for Division 2 locations.
• Petroleum refining production plants
• Petroleum dispensing locations
• Dry cleaning facilities
Groups
Class I and II locations are divided by the NFPA into Group
• Dip tanks containing combustibles or flammable liquids
designations identifying specific gases, vapors and dusts by
• Plant facilities extracting solvents
characteristic similarities that relate to specific equipment
• Inhalation anesthetics areas
construction requirements. Class III locations are not divided
• Process facilities manufacturing pyroxylin type plastics
into separate group designations.
Class II - Hazardous Dusts. Class II locations represent areas that are
hazardous due to the presence of combustible dust. Class I Groups
Group A. Atmospheres containing acetylene.
Hazardous Location
Typical Class II Hazardous Areas
• Flour mills Group B. Atmospheres containing hydrogen, fuel and
• Feed mills combustible process gases containing more than 30 percent
• Grain elevators and grain handling facilities hydrogen by volume, or gases or vapors of equivalent hazard
• Aluminum manufacturing and storage areas such as butadiene, ethylene oxide, propylene oxide, and
Devices
• Magnesium manufacturing and storage areas acrolein.
• Coal preparation and handling facilities
• Starch manufacturing and storage areas Group C. Atmospheres such as ethyl ether, ethylene, or
• Confectionery plants other gases or vapors of equivalent hazard.
• Pulverizer sugar and cocoa manufacturing, and storage plants
Group D. Atmospheres containing acetone, ammonia,
• Spice grinding and storage plants
benzene, butane, cyclopropane, ethanol, gasoline, hexane,
Class III - Hazardous Fibers. Class III locations have easily ignitable methanol, methane, natural gas, naphtha (petroleum), pro-
fibers or flyings present, but not likely to be suspended in air in quantities pane, or gases or vapors of equivalent hazard.
sufficient to produce ignitable mixtures in the atmosphere.
Class II Groups
Typical Class III Hazardous Areas
Group E. Atmospheres containing combustible metal dusts,
• Textile mills
including aluminum, magnesium, and their commercial
• Woodworking plants*
alloys, or other combustible dusts whose particle size, abra-
Door Holders
• Furniture manufacturers*
siveness and conductivity present similar hazards in the use
• Cotton gins
& Relays
of electrical equipment.
• Cotton seed milling plants
• Flax plants Group F. Atmospheres containing combustible carbona-
• Carpet manufacturers ceous dusts, including carbon black, charcoal, coal, or dusts
that have been sensitized by other materials so that they
* Except if wood flour (dust), which is Class II Group G, is present
present an explosion hazard.
31
VS
SERIES
Hazardous Location Devices
SUBMIT
Initiating Devices
Analog Control
VS Series
302-AW-135 All-weather Heat Detector - Vertical Mounting FM & UL, 135 °F (57.2 °C) Data Sheet: K85001-0589
302-AW-194 All-weather Heat Detector - Vertical Mounting FM & UL, 194°F (90 °C) Data Sheet: K85001-0589
Notification
Appliances
302-ET-135 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 135 °F (57.2 °C) Data Sheet: K85001-0589
302-ET-194 All-weather Heat Detector - Vertical, Box Mount (½" NPT), FM & UL, 194°F (90 °C) Data Sheet: K85001-0589
302-EPM-135 Heat Detector - Explosionproof Mounting UL (Not FM approved), 135 °F (57.2 °C) Data Sheet: K85001-0589
302-EPM-194 Heat Detector - Explosionproof Mounting UL (not FM approved), 194°F (90 °C) Data Sheet: K85001-0589
AP-P Adaptor plate for mounting 302 and 302-AW to any 3" box or 4" octagon outlet box Data Sheet: K85001-0589
JALX11 Explosion proof outlet body with cover - Killark Data Sheet: K85001-0589
Hazardous Location
MPSR Series explosionproof/weatherproof manual pull stations are noncoded fire alarm
stations solidly constructed of die-cast material. They are rated for Class I Group B (hy-
drogen) C & D, Class II Groups E. F, G, Class III environments, and are rated NEMA 4X for
outdoor use. Key and screw reset models feature terminal connections and come complete
with backbox.
Hex Screw Reset Cat 45 Key Reset Manual Stations Data Sheet: K85001-0588
MPSR1-DHTWX-GE MPSR1-D45WX-GE Explosionproof Single-action, SPST with backbox.
MPSR1-SHTW-GE MPSR1-S45W-GE Weatherproof Single-action, SPST with backbox.
MPSR1-DHTW-GE MPSR1-D45W-GE Weatherproof Single-action, DPDT with backbox.
MPSR2-SHTW-GE MPSR2-S45W-GE Weatherproof Double-action, SPST with backbox.
MPSR2-DHTW-GE MPSR2-D45W-GE Weatherproof Double-action, DPDT with backbox.
MPSR2-SHTW-GE-NYW MPSR2-S45W-GE-NYW Weatherproof Double-action, SPST with backbox, NYC white stripe.
For French markings add -F to the suffix of the model number. For bilinguial French/English markings add -B to the suffix of the model number.
32
VS
SERIES
Hazardous Location Devices
SUBMIT
Explosionproof Smoke Detector
Model 30-3013 detectors are high performance smoke detectors built for use in hazardous
locations. They are corrosion-resistant and feature a non-conducting aluminum alloy retaining
ring that protects the detector sensor against the effects of explosions and other catastrophic
events. The retaining ring mounts securely to a companion junction box, which offers several
common port configurations for conduit connection. Together, the ring and box provide a
sturdy protective shell for the detector head.
30-3013A1N12F Explosionproof Smoke Detector Data Sheet K85001-0645
Notification Appliances
Hazardous Location Strobes
• Class I, II, or III locations
116DEGEX-FJ hazardous location strobes are life safety signaling appliances designed for installation in
hazardous environments. State-of-the-art technology provide for high visual output and low maintenance.
The 116DEGEX-FJ has negligible in-rush current. When pendant, wall or ceiling mounted, the 116DEGEX-
FJ meets or exceeds the requirements of UL 1971 Signaling Appliance for the Hearing Impaired.
116DEGEX-FJ Explosionproof Strobe, Diode Polarized Data Sheet K85001-0624
116EX-B Wall bracket mounting elbow (required for wall mount applications) Data Sheet K85001-0624
116EX-C Ceiling/wall mounting module (required for wall mount applications) Data Sheet K85001-0624
116EX-P Pendant mounting module - 3/4” (19 mm) NPT Data Sheet K85001-0624
116-GRD Lens Guard Data Sheet K85001-0624
Hazardous Location
Hazardous Location Bells
• Class I groups B, C and D locations • Class III hazardous locations, for Divisions 1 and 2
Devices
• Class II groups E, F and G locations
430D series of hazardous location bells are diode-polarized, heavy duty fire bells for use in life safety applications
where a diode supervised signal is required. They can be mounted to any solid surface using two 3/8 inch (10 mm)
bolts and the supplied mounting brackets or to a rigid conduit. The integral explosion-proof housing is mechanically
terminated to accept a standard 3/4 inch -14 National Pipe Taper (NPT) nipple.
439DEX-6AW (6”) 439DEX-8AW (8”) 439DEX-10AW (10”) Bell – 24 Vdc, Red Data Sheet K85001-0399
439DEX-6AW-R (6”) 439DEX-8AW-R (8”) 439DEX-10AW-R (10”) Bell – 24 Vdc, Grey Data Sheet K85001-0399
• Class I groups B, C and D locations • Class III hazardous locations, for Divisions 1 and 2
& Relays
33
VS
SERIES
Notification Appliances
SUBMIT
Analog Control
VS Series
Door Holders
Electromagnetic Door Holders
Electromagnetic door holders keep doors open until signaled by the fire alarm
system, a heat detector, a smoke detector, or an electrical switch. Door holders
should be installed wherever doors may be effectively used to confine smoke
and fire, or where the release of a self-closing door from a remote location
is required. Fail-safe operation is an inherent feature of these door holders. If
power fails, doors are released automatically, but may be opened or closed
24 Vac 60 Hz manually at any time. All units are free of moving parts, are self-contained, and
Initiating
Devices
Relays
Four-Voltage SPDT/DPDT Control Relays
MR Series multi-voltage control relays are ideal for applications where local contacts are
required for system status, remote contacts, or for control of electrical loads and general pur-
pose switching. They are suitable for use with HVAC temperature control, fire alarm, security,
energy management, and lighting control systems. Relays provide 10-Amp contacts, which
Hazardous Location
may be operated by one of four input control voltages. Each relay position contains a red
LED that indicates the relay coil is energized. Relays may be snapped apart from a standard
four-module assembly and used independently.
Devices
MR101/T (with mounting hardware) MR101/C (in metal enclosure) Single SPDT relay Data Sheet K85300-02762
MR104/T (with mounting hardware) MR104/C (in metal enclosure) 4-position SPDT relay Data Sheet K85300-02762
MR201/T (with mounting hardware) MR201/C (in metal enclosure) Single DPDT relay Data Sheet K85300-02762
MR204/T (with mounting hardware) MR204/C (in metal enclosure) 4-position DPDT relay Data Sheet K85300-02762
M-199X-13 (relay only) M-199X-13/C (in metal enclosure) Power Relay — 24 VDC Data Sheet K85300-02766
MR199AX14 (relay only) MR199AX14/C (in metal enclosure) Power Relay — 120 VDC Data Sheet K85300-02766
34
VS
SERIES
Notification Appliances
SUBMIT
SPDT Relays
Single-pull/double-throw relays are ideal for applications where local or remote con-
tacts are required for control of electrical loads. They are suitable for use with HVAC,
temperature control, fire alarm, security, energy management, and lighting control
systems. Each relay position contains a high-intensity LED which, when illuminated,
indicates the relay coil is energized. Individual relay circuits may be snapped apart
from standard four- or eight-position modules, and are also available in a single-circuit
configuration. The common power to each relay position is bussed on the printed
wiring board, which permits power to be connected only once per multi-position
module.
PAM1 relays provide 10-Amp Form C contacts. The relay may be energized by one of three
input voltages: 24Vac, 24Vdc, or 115Vac. The PAM1 may be mounted with double-sided
adhesive tape, a self-tapping screw, or loosely placed in a backbox.
35
Value, efficiency, and a legacy
of fire protection innovation
When building owners and designers do business with Kidde, their
investment is underwritten by a 100-year history of dedication to the fire
alarm industry. That’s why today architects and engineers agree that when
it comes to protecting people and property, Kidde life safety systems
remain the technology of choice.
These strengths set Kidde installations apart, and have earned this
brand a special place among life safety solutions available today.
Contact us...
Email: kidde.fire@fs.utc.com
Web: Kidde.com/EngineeredSystems
K85005-0132