Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
The schematic of an air handling system is given below. The supply air flow as well as the conditions of
the return air and supply air are marked on the schematic. The minimum fresh air requirement is 20% of
the supply air by mass.
Determine the cooling coil loads for outdoor conditions of 50ºFDB and 50%RH, if
(a) the system has no economizer control
(b) the system has integrated enthalpy economizer control.
M/A C H S/A = 10,000 cfm @ 55ºFDB, 90%RH
F/A C C
m
R/A @ 77ºFDB, 60%RH
er as
E/A
co
eH w
Assumptions: 1) Steady-state conditions, 2) Sea-level pressure, 3) Neglect the effects of fan, 4) No
o.
losses at ductwork.
rs e
ou urc
Solution:
m F A
Given that 0.20
m
o
S A min
aC s
vi y re
Btu ft lbmv
R/A: 77ºFDB, 60%RH iR A 31.5 , vR A 13.78 , WR A 0.0119
ar stu
(a) Without the economizer control, the fresh air requirement will always be at the minimum
Th
m F m F m F A
0.20
A A
Hence,
m M m S m
A A S A min
m F
The enthalpy of M/A is: i M A
m M A
iR A
A
i F A i R A 31.5 0.216.1 31.5 28.4
Btu
lbma
which is higher than the S/A enthalpy. Therefore, the cooling coil is turned on to cool down the
M/A to the required S/A conditions, as indicated on the schematic.
https://www.coursehero.com/file/27267211/Week-4-Tutorialpdf/
3
Q S 10,000 ft
m S
A
min 60 min 45660 lbma
A 3
vS A 13.14 ft hr hr
lbma
The cooling coil load is
q cc m S A i M A iS A 45660 lbma 28.4 22.2 Btu 283,000
Btu
hr lbma hr
Note: The cooling loads of the zone can be estimated using the approximate equations as:
Sensible: q sc , zone 1.1Q S / A t R A t S A 1.110,000 cfm 77 55 F 242,000
Btu
hr
q lc , zone 4840QS / A WR A WS A
Latent: lbmv Btu
m
484010,000 cfm 0.0119 0.0083 174,500
er as
lbma hr
co
Total: q c , zone 4.5Q S A i R A i S A 4.510,000 cfm 31.5 22.2
Btu Btu
418,500
eH w
lbma hr
o.
(b)
rs e
With integrated enthalpy economizer control, the economizer is activated in free cooling mode
ou urc
and t F A 50 F t S A 55 F (i.e., operating
Btu Btu
because iR A 31.5 iF A 16.1
lbma lbma
mode C, shown in Figure 4.1 in the handout on “Outdoor Air Economizer Control”). Therefore,
o
the economizer control may mix the R/A with the F/A to achieve free cooling by meeting tM/A =
aC s
In order to decide which option to meet, let’s check the sensible heat factor (SHF) of the zone:
q s m a c p t R / A t S / A c p t R / A t S / A
SHFzone
m a i R / A i S / A iR / A iS / A
ed d
q
ar stu
The cp of the moist air should be evaluated based on average humidity ratio:
0.0119 0.0083 Btu
c p 0.24 0.45Wave 0.24 0.45 0.2445
sh is
2 lbma F
Btu
77 55 F
Th
0.2445
lbma F
SHFzone 0.578
Btu
31.5 22.2
lbma
Since SHFzone > 0.5 , the sensible cooling load is more than the latent cooling load; therefore, it is
more important to satisfy the sensible cooling load by having the right S/A temperature (i.e., tM/A
= tS/A).
m F A
For tM/A = tS/A = 55F: For adiabatic mixing, we have t M / A t R A
m M A
t F A t R A .
m F A tM A tR A 55 77
0.815 0.2 (It is OK to use the M/A for free cooling.)
m M A tF A tR A 50 77
https://www.coursehero.com/file/27267211/Week-4-Tutorialpdf/
and the corresponding M/A humidity ratio, assuming that the R/A conditions remain the same,
is:
m F A
WM A WR A
m M A
WF A WR A
lbmv lbmv
0.0119 0.8150.0038 0.0119 0.0053 WS / A 0.0083
lbma lbma
Although the temperature of tR/A = 77ºF is met, i.e. the sensible cooling load provided by the M/A
is right, the latent cooling load provided by the M/A is in excess; therefore, if the M/A is directly
supplied to the zone, the zone will be maintained at 77F, but the zone humidity will drop over
time because the M/A humidity ratio is lower than the required S/A humidity ratio;
correspondingly the zone relative humidity (RH) will be lowered over time than 60%. The
integrated enthalpy economizer control has resulted in saving of 283,000 Btu/hr of cooling coil
m
load because the cooling coil is off.
er as
co
Comment:
eH w
1) The M/A conditions are not the same as the given S/A conditions. Therefore, we need the M/A
o.
properties to re-calculate the mass flow rate because the fan only maintains constant volume flow
rs e t M / A 55 FDB
i M / A 19 Btu / lbma
ou urc
rate, not constant mass flow rate: lbmv
WM / A 0.0053 v M / A 13.08 ft 3 / lbma
lbma
o
ft 3
Q M / A 10,000 min 60 min 45870 lbma
m M / A 3
v M / A 13.08 ft hr hr
lbma
ed d
Therefore, the cooling loads provided by the M/A can be estimated using the approximate equations
ar stu
as:
Sensible: q sc , M / A 1.1Q M / A t R A t S A 1.110,000 cfm 77 55 F 242,000
Btu
hr
sh is
lbma hr
Total: q c , M / A 4.5Q M A i R A i M A 4.510,000 cfm 31.5 19.0
Btu Btu
562,500
lbma hr
2) Let’s take a look if WM/A = WS/A = 0.0083 lbmv/lbma is to be achieved by the M/A:
m F A WM A WR A 0.0083 0.0119
0.444 (this ratio will meet the latent cooling of the zone)
m M A W F A WR A 0.0038 0.0119
and the corresponding M/A temperature, assuming that the R/A conditions remain the same, is:
https://www.coursehero.com/file/27267211/Week-4-Tutorialpdf/
m F A
tM A tR A
m M A
t F A t R A
(so the zone will be > 77ºF)
77 0.444 50 77 65 F t S / A 55 F
Although the humidity ratio of WR/A = 0.0119 lbmv/lbma is met, i.e. the latent cooling load provided
by the M/A is right, the sensible cooling load is insufficient; therefore, if this M/A is directly
supplied to the zone, the zone will be maintained at 0.0119 lbmv/lbma, but the zone temperature
will increase over time because the M/A temperature is higher than the required S/A temperature.
3) Let’s take a look if iM/A = iS/A = 22.2 Btu/lbma is to be achieved by the M/A:
m F A iM A iR A 22.2 31.5
0.604
m M iF A iR A 16.1 31.5
m
A
er as
and the corresponding M/A humidity ratio and temperature, assuming that the R/A conditions
co
eH w
remain the same, are:
o.
m F A
rs e WM A WR A WF A WR A
ou urc
m M A
lbmv lbmv
0.0119 0.604 0.0038 0.0119 0.0070 WS / A 0.0083
lbma lbma
o
m F A
t F A t R A
aC s
tM tR A
vi y re
A
m M A
77 0.604 50 77 60.7 F t S / A 55 F
ed d
Neither the temperature nor humidity ratio of R/A will be met. The latent cooling load provided by
the M/A is in excess, while the sensible cooling load is insufficient.
ar stu
m F A
4) Due to the fact that most buildings have more sensible load than latent load, the mixing ratio
m M A
sh is
based on tM/A = tS/A may be chosen by the economizer control for free cooling.
Th
https://www.coursehero.com/file/27267211/Week-4-Tutorialpdf/