Sei sulla pagina 1di 1

NO.

OF CB NUMBER & SIZE


CKT LOAD DESCRIPTION OUTLETS VOLTS VOLT AMPS AMPS RATING OF WIRE CONDUIT

2-3.5 MM SQ THHN/THWN &


PA LIGHTING OUTLET
9 230 900 3.91 1-2.0 MM SQ THHN/THWHN IN
EXPOSED 20MM DIA IMC

1 15 A
COMFORT ROOM

CONVENIENCE OUTLET
8 230 1600 6.96

WALK IN
COMFORT ROOM
KITCHEN DINING
2 TOTAL 2500 10.87
PA

WALK IN
COMFORT ROOM COMPUTATION TOTAL LOAD CURRENT = 10.87A
APPLY 100% D.F.
IL = 10.87(1.0)
IL = 10.87

MAIN CB: 15 AT, 2P, 240V


FEEDER: 20 #8 TW WIRE IN 20 MM RSC

LIVING ROOM LEGEND AND SYMBOL


BEDROOM1 BEDROOM2
1 SERVICE ENTRANCE

PA
NOTES AND SPECIFICATIONS
CONVINIENCE OUTLET
01. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE
INCANDESCENT LAMP WITH THE PROVISION OF THE ELECTRICAL CODE AND SHALL COMPLY
WITH RULES & REGULATIONS OF THE LOCAL GOVERNMENT AUTHORITIES
CIRCUIT BREAKER CONCERNED IN THE ENFORCEMENT OF THE ELECTRICAL LAW AND
ORDINANCE AND WITH THE REQUIREMENT OF THE LOCAL ELECTRICAL
AIR CONDITIONING UNIT UTILITY COMPANY CONCERNED.

02. SERVICE ENTRANCE TO THE BUILDING SHALL BE 230 VOLTS


MAIN CIRCUIT BREAKER
SINGLE PHASE, 2 WIRE , 60 HERTZ

03. TYPE OF WIRING INSTALLATION SHALL BE DONE IN RIGID STEEL CONDUIT


PANEL BOARD
( HOT DIP GALVANIZED MILD STEEL COAT ) FOR SERVICE ENTRANCE
TO PANEL BOARD AND EMT PIPE TO ALL BRANCH CIRCUIT WIRING.

WATER PUMP
SERVICE ENTRANCE SINGLE PHASE 04. UNLESS OTHERWISE SPECIFIED ON THE PLAN MINIMUM SIZE OF THE WIRE
SINGLE PHASE , 230 v
TO BE USE SHALL BE 3.5 mm THW TYPE IN 15 mmØ CONDUIT.

PATIO INDUCTION MOTOR


05. ALL ELECTRICAL EQUIPMENT TO BE USE SHALL BE EQUIPPED WITH
M KWHR METER PROPER AND ADEQUATE GROUNDING SYSTEM.
2 #8 TW WIRE IN
20 MM RSC

06. MOUNTING HEADS


LIGHT CONTROL SWITCH - 1.48 METERS ABOVE FINISHED FLOOR.

LIGHTING LAYOUT 15 AT MAIN C.B.


CONVINIENCE OUTLET
SPL PURPOSE OUTLET
- 0.30 METERS ABOVE FINISHED FLOOR.
- AS REQUIRED BY EQUIPMENT SERVICE.
PANEL BOARD - 1.50 METERS ABOVE FINISHED FLOOR
LINE OR AS DIRECTED BY FIELD CONDITION.
15 AT

07. ALL ELECTRICAL MATERIALS TO BE USED SHALL BE BRAND NEW AND


APPROVED TYPE FOR LOCATION AND PURPOSES.

08. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT
SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER OR A
PROFESSIONAL ELECTRICAL ENGINEER

SUBMITTED BY: PROJECT TITLE: SIGNED AND SEALED BY: SHEET NO.

LAO, JEROME T. 15 AMPERE


REE / PRC NO: / DATE: AUGUST 09, 2017 E
LUGTU, EXEQUIEL O. CIRCUIT BREAKER PROTECTION
SUBMITTED TO:
DESIGN 1 1
YUMUL, RIWEL C. ENGR. FLAVIANO D. DULA, REE. MPE.