Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Enrique Betancourt R.
Xose M. Lopez-Fernandez
Krishnamurthy Vijayan
Hamid Abdelkamel
2
Agenda
1. Scope of the Guide and Systems Engineering Framework– E.
Betancourt
2. Function and Application of tertiary and Stabilizing Windings –
Dr. X. Lopez-Fernandez
3. Specification and Testing of Tertiary and Stabilizing Windings –
K. Vijayan
4. Utility Examples – H. Abdelkamel
5. Conclusion and further work- Enrique
3
Enrique Betancourt
4
Unbalanced systems
• Circuit analysis: Mesh and Node equations using Kirchhoff’s Laws
• Network analysis with impedance/admittance matrix transformations
• Symmetrical components
Three-phase
system
Neutral
conductor
Self impedance Mutual impedance
[Figure from Happoldt, H., Oeding, D., “Elektrische
General three-phase network with self and mutual impedances Kraftwerke und Netze”, Springer, 1978.]
14
Symmetrical components
Reduced system equations:
[See Alexander, G.W, McNutt, W.J., “EHV Application of Autotransformers”, IEEE T PAS, 1967.]
17
• By floating primary neutral, the delta winding carries 33% of the secondary
single phase load.
20
Classically
Content
- Exciting current on single-phase ferromagnetic cores
- Exciting current on a transformer bank. Neutral grounded v.s. UNgrounded
- Potential negative effects without stabilizing winding (SW)
- Stabilizing and tertiary windings in Y connections
- Need for SW in modern transformers
- Modeling and circuit analysis
- Heating hazard: faults and temporary unbalanced loads
24
Since the B/H curve of the core magnetic material is not linear, the magnetizing
current will not be sinusoidal (fundamental component plus the third harmonic
as predominate).
25
Zero-Sequence flux
Windings Short-circuit forces
thermal rating (stresses in winding conductors)
No three-legged
(Conductor size) (Conductor size)
Voltage unbalanced
cooling clamping structural strength
(Zero-sequence voltage)
* Tank walls
* Yoke clamps
* Leg plates
36
PTI Transformers LP
- Terminal Connections
- Some special aspects
- Testing
38
Note: Depending on test plant limitation, all 3 terminals of the SW winding can be
brought out for test purpose. After test, the unit is connected for the operating
condition
49
Dielectric testing
Testing
1. Impulse test on SW not required if the corner is to be grounded during
operation
2. If all terminals of the SW are not brought out, impulse and induced
tests to be performed in the operating condition
Design considerations
1. During HV and LV impulse test, the ungrounded corners of SW may
have higher transient voltages
2. Any current limiting reactor in SW may result in higher transient
voltages at the connecting points
50
4. Utility Examples
Stabilizing or Tertiary Winding Effect on
Relaying and Arresters
Hamid Abdelkamel, PE, PMP
habdelkamel@Ameren.com
10/18/18
Stabilizing Winding Effect on Relaying and
Arresters
1) Ground over current coordination Issues
2) Delta back feed
3) Stabilizing winding sizing
Transformer Zero Sequence Models:
YG-YG Y-D-YG
YG-D-YG
Transformer Zero Sequence Models (Cont’ed)
• D-YG
• YG-YG AUTO
(w/o Stabilizing)
• YG-D-YG AUTO
(w/ Stabilizing)
Sequence Network for L-G Fault:
- For Transformer low-side L-G fault, how ground current passes through transformer dependent on
winding configuration:
,
Effect on Ground Overcurrent Relaying:
• YG-YG
HS Pickup > LS Pickup x Turns Ratio
HS Pickup = 240A < LS Pickup 1200 x 69/138=600A
Possible mis-coordination
240A 240A
• YG-D-YG
HS Pickup > LS Pickup x Turns Ratio x Current Divider
Per case shown:
Possible mis-coordination
• Y-D-YG or D-YG
Low-side Ground fault Current does not reflect to high-side
• Due to lower zero sequence impedance to ground ‘YG-D-YG’ can prevent correct 59N
operation, which can result in over-voltage failure of LAs and Transformers:
Conclusion
• Stabilizing windings reduce the zero-sequence impedance of Y-connected
transformers and improve their performance under unbalanced operating
conditions
• As those windings impact cost of the equipment, their application should be
driven by zero-sequence needs for system grounding, and control of third
harmonic phenomena
• The Guide C57.158 is a source of practical recommendations for specification,
testing and application of stabilizing and tertiary windings
• Systems and protections engineers should be involved in decisions that impact the
zero-sequence performance of power transformers
67
Further work
Still to consider recommendations for:
• Thermal effects of circulating currents on delta windings of transformers
subjected to DC currents
• Comparison of behavior of Y-connected transformers subjected to switching
transients, with and without a delta winding
• Circulating currents in transmission transformers by temporary bi-polar operation
of the lines
• Thermal behavior of SWs subjected to extended loading
• Role of delta windings in Y-connected transformers during ferro-resonance
conditions
• Closer coordination with protection relaying practice
68
Bibliography
- See Annex A of C57.158 -