CPU 31xC and CPU 31x: Installation

Resetting to the Delivery State

Resetting to the Delivery State

Delivery state of the CPU


Default values set at the CPU properties:

Table 1 Properties of the CPU in the delivery state


Properties Value

MPI address 2

MPI baud rate 187,5 kbit/s

Retentive bit memories, timers and counters All retentive bit memories, timers and counters are
deleted

Retentive range set for bit memories, timers and Default setting
counters (16 memory bytes, no timers, and 8 counters)

Contents of the diagnostics buffer deleted

IP address Not available

Device name Not available

Operating hours counter 0

Time 01.01.1994 00:00:00

Procedure
Proceed as follows in order to reset a CPU to the delivery state via the mode selector switch:
1. Switch off the supply voltage.
2. Remove the SIMATIC Micro Memory Card from the CPU.
3. Hold the mode selector switch in the MRES setting and switch the supply voltage on again.
4. Wait until LED lamp image 1 from the subsequent overview is displayed.
5. Release the mode selector switch, set it back to MRES within 3 seconds and hold it in this position.
6. Wait until LED lamp image 2 from the next overview is displayed.
This lamp image lights up for approximately five seconds, that is for the duration of RESET. During
this period you can abort the resetting procedure by releasing the mode selector switch.
7. Wait until LED lamp image 3 from the subsequent overview is displayed and release the mode
selector switch again.

The CPU is now reset to the delivery state. It starts without buffering (all LEDs are lit) and
changes to the STOP mode.

Lamp images while the CPU is being reset


While you are resetting the CPU to the delivery state, the LEDs light up consecutively in the
following lamp images:

This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims
all liability for the completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
3/28/2019
CPU 31xC and CPU 31x: Installation
Resetting to the Delivery State

Table 2 Lamp images


LED Color Lamp image 1 Lamp image 2 Lamp image 3

STOP Yellow ⃝ ⃞ ⃞

RUN Green ⃝ ⃞ ⃞

FRCE Yellow ⃝ ⃞ ⃞

5 VDC Green ∆ ∆ ∆

SF Red ⃞ ⃝ ∆

BFx Red ⃞ ⃞ ⃞

∆ = LED is lit
⃞ = LED is dark
⃝ = LED flashes at 0.5 Hz

Note
When removing a PROFINET CPU for use at a different location, or when putting it on shelf,
always restore the CPU to factory settings since its IP address and device name are usually
stored in retentive memory.