Sei sulla pagina 1di 1

TECHNICAL SPECIFICATIONS

STEEL-BOLTED TANK SPECIFICATION

DESCRIPTION SPECIFICATION

DESIGN CRITERIA

SOIL BEARING CAPACITY 2,000 psf

DECK LIVELOAD 20 psf


WORKING PRESSURE ATMOSPHERIC
BASIC DESIGN WIND LOAD 125 Mph
EARTHQUAKE ZONE
ZONE 4

SPECIFICATION

FLUID POTABLE WATER

NOMINAL CAPACITY 150 CU.M.

DIAMETER 7.5 M

HEIGHT 3.5 M
BOLTED & CORRUGATED PANELS W/
WALL CONSTRUCTION LATERAL NUT COVER (OR EQUIVALENT)

WALL COATINGS ZINC ALUMINUM COATING

TRUSS HOT-DIPPED STEEL TRUSS (OR EQUIVALENT)

ROOF VENTILATION TURBO VENT WITH EXTRACTOR FAN

NOZZLES 150 mmØ INLET DEFLECTOR (GALVANIZED OR HDPE)


100 mmØ OUTLET W/ ANTI-VORTEX (GALVANIZED OR HDPE)
75 mmØ BELL-MOUTH OVERFLOW (PVC)
75 mmØ PVC SCOUR DRAIN

EXTERNAL & INTERNAL LADDER REMOVABLE HOT-DIPPED GALVANIZED

ROOF ACCESS HATCH INCLUDED

ZINC ALUMINUM CORRUGATED STEEL


WALL PROFILES W/ MIN. THICKNESS OF 1.20mm SHEETING
ZINC ALUMINUM STEEL (55% ALUMINUM, 43.5% ZINC AND
STEEL GRADE 1.5% SILICON)

COATINGS ZINC ALUMINUM ALLOY COATING

LINER

GALVANIZED FLANGE HEAD, HIGH TENSILE BOLTS


BOLT AND NUT COVER

NOZZLES PE80 HDPE OR HOT DIPPED GALVANIZED

CORROSION PROTECTION
SACRIFICIAL MAGNESIUM ANODES ENGINEERED
TO ALLOY M3 ANALYSIS AND PERFORMANCE
STANDARD W/ PVC INSULATED CABLE

- TECHNICAL SPECIFICATIONS

CERTIFIED BY: PROJECT TITLE : SHEET CONTENTS : OWNER / S : SHEET No :

FIESTA COMMUNITIES DAPDAP STEEL BOLTED TANK AS SHOWN 01


ENGR. ROBERTO V. SUAREZ
REGISTERED CIVIL ENGINEER
VILLAGES WATER SUPPLY SYSTEM INC
SHEET TOTAL :
PROJECT LOCATION :
PRC No : 0049354 DATE ISSUED : 01-2019
PTR No : 7450622 PLACE : QUEZON CITY Brgy. Dapdap, Mabalacat,Pampanga ADDRESS : HLDC CORPORATE CENTRE, BLK 43 LOT 35,
TIN No : 125 485 223 DON BONIFACIO AVE, PULUNG MARAGUL, ANGELES CITY