DISEÑO DE MURO DE CONTENCION

β= 0 0.3 m
β= 0 rad

Ƴ= 1.62 tn/m3
Φ= 19
Φ= 0.33 rad
D 3.00 m
B

1.2 m 0.3 m
0.2 1.2 m
0.4 m A

2.1 m
Qadm= 18.5 tn/m2

n° b (m) h (m) W mat(tn/m3) W (tn) Brazo M (tn/m)


A 2.1 0.4 2.4 2.016 1.05 2.1168
B 0.3 2.60 2.4 1.872 0.65 1.2168
C 0.1 2.60 2.4 0.624 0.433 0.2704
D 1.2 2.60 1.62 5.0544 1.5 7.5816
9.5664 11.1856

Momento estabilizador:
Me= 11.1856
Coeficientes de empuje:
Cah= 0.5088
Cph= 1.9655
Empujes:
Eah= 3.7091 tn
Eph= 2.2925 tn
Analisis al volcamiento
Mv= 3.7090572352
FSV= 3.016 ≥ 1.5 OK
ANALISIS AL DESLIZAMIENTO
f= 0.34433
FSD= 1.506 ≥ 1.5 OK
ANALISIS ANTE FALLA POR CAPASIDAD DE CARGA
Excentricidad:
e= 0.2685
0.2685 < 0.35 OK
CARGA DE MURO CARGA ADMISIBLE DEL SUELO
Qmax = 8.050 < 18.5 tn/m2 OK
Qmin = 1.061 < 18.5 tn/m2 OK