Compressor Controller

MAM – 860

OPERATION MANUAL

Revision 1.0
04.08.2017
Notice
Please read all the operation manual before operating the set and keep this manual for further reference.

Installation of MAM—8** compressor controller can be performed only by professional technicians.

RC snubber must be connected to the two terminals of coil (such as AC contactor, valve, etc),which are
controlled by relay output.

Port connection shall be inspected carefully before power on.

PARAMETER is not allowed to be modified in running and stop delay status. Only user
parameter is allowed to be changed at running status

04.08.2017 Operation Manual MAM - 860 V1.0 -2-


Contents
1 Basic Operation ................................................................................................................................................... - 4 -
1.1 Button Explanation .................................................................................................................................. - 4 -
1.2 Indicator Instruction ................................................................................................................................ - 5 -
1.3 Status Display and Operation ................................................................................................................... - 6 -
1.4 Operating Parameter and Menu: ............................................................................................................. - 6 -
1.5 User Parameter View and Modification: ................................................................................................. - 7 -
1.6 User Parameter: ....................................................................................................................................... - 9 -
1.7 Factory Parameter: ................................................................................................................................ - 11 -
1.8 Calibration Parameter ............................................................................................................................ - 12 -
1.9 Operating Authorization and Password ................................................................................................. - 13 -
2 Controller Function and Technical Parameter .................................................................................................. - 13 -
3 Model and specification.................................................................................................................................... - 14 -
4 Overview .......................................................................................................................................................... - 15 -
5 Control process ................................................................................................................................................. - 16 -
6 Alarm Function ................................................................................................................................................. - 18 -
7 Alarm Function ................................................................................................................................................. - 19 -
7.2 Protection of High Discharge Air Temperature ...................................................................................... - 19 -
7.3 Protection of Air Compressor Reversal .................................................................................................. - 19 -
7.4 Protection of High Pressure ................................................................................................................... - 19 -
7.5 Protection of Sensor Failure................................................................................................................... - 19 -
7.6 Low Temperature Protection ................................................................................................................. - 19 -
8 Troubleshooting ................................................................................................................................................ - 20 -
9 Sequence Mode Control and Network ............................................................................................................. - 22 -
9.1 Sequence mode control ......................................................................................................................... - 22 -
9.2 Sequence Mode Setting ......................................................................................................................... - 23 -
9.3 Start, stop sequence control: ................................................................................................................. - 24 -
9.4 Sequence Communication Receiving and Sending Message: ................................................................ - 24 -
9.5 Network ................................................................................................................................................. - 25 -
10 Copyright ........................................................................................................................................................ - 26 -

04.08.2017 Operation Manual MAM - 860 V1.0 -3-


1 Basic Operation

1.1 Button Explanation

Start Button:
 When compressor is at stop status, press this button to start the compressor
 When compressor is set as master (No.1) in block mode, press this button to start the compressor and
activate block mode function at the same time.

Stop Button:
 When the compressor is at running status, press this button to stop the compressor
 When compressor is set as master (No.1) in block mode, press this button to stop compressor and block
mode function as well
 When compressor is at stop status, long press this button to display software edition

Set Button /Loading / unloading Button:


 When the compressor is at running status, press this button to load, unload
 When the compressor is at setting mode, press this button after modification to confirm and save the
modified data

04.08.2017 Operation Manual MAM - 860 V1.0 -4-


Move down button / Decreasing button:
 When viewing the menu, press this button to move downward the cursor
 When modifying data, press this button to decrease the data at current position

Move up button/Increasing button:


 When viewing the menu, press this button to move upward the cursor
 When modifying data, press this button to increase the data at current position

Shift button /Enter button:


 When modifying data, press this button to move to the next data bit
 When select menu, press this button to switch to submenu. If no submenu available, the controller will
shift to data setting mode.

Return button / Reset button:


 When modifying data, press this button to exist data setting mode;
 When viewing the menu, press this button to return to previous-menu;
 When the controller is at failure stop status, long press this button to reset.

1.2 Indicator Instruction


Power Indicator: Indicator on when controller is energized.
Run indicator: Indicator is on when motor is running.
Alarm indicator: Indicator is blinking when alarming; indicator on when fail to stop; indicator off when
error is cleared

04.08.2017 Operation Manual MAM - 860 V1.0 -5-


1.3 Status Display and Operation
The display screen will show as below after power on:

WELCOME USING

SCREW COMPRESSOR

After 5 seconds, the menu will switch as below:

AIR T: 78°C
AIR P: 0.53MPa
NORMAL STOP 0S
C16 REMOTE

Press to enter into selection menu:

RUN PARAMETER
USER PARAMETER
FACTORY PARAMETER
CALBR PARMETER

1.4 Operating Parameter and Menu:

Press or to move the cursor to “RUN PARAMETER”, then press to switch to secondary
menu:

MOTOR、FAN CURRENT
TOTAL RUN TIME
THIS RUN TIME
MAINTAIN PARAMETER

Press to check MOTORS CURRENT, TOTAL RUN TIME, TOTAL LOAD TIME, and other running parameter.

Press to return to the previous menu or main menu. If no operation in certain menu for 60s, machine
will return to the main menu automatically.

04.08.2017 Operation Manual MAM - 860 V1.0 -6-


1.5 User Parameter View and Modification:

USER PARAMETER and FACTORY PARAMETER


are not allowed to be modified in running and stop delay status.

In first menu press or to move the cursor to the “USER PARAMETER”.

Press to switch to the following menu

SET P、T
SET TIME
OPERATION MODE
BLOCKING MODE

Move the cursor to the “SET P, T”, then press to switch to secondary menu

LOADING P: 0.8MPa
UNLOADING P: 0.6MPa
FAN START T: 80℃
FAN STOP T: 70℃

User can check the CUSTOMER PARAMETER in this menu or press to switch to the following menu which
requires a user password input

ENTER PASSWORD
****

NOTE: Customer password can be set in CUSTOMER PARAMETER


and is set as 1688.

04.08.2017 Operation Manual MAM - 860 V1.0 -7-


In this menu the first data bit of password blinking, press or to modify the first bit of password.

Press move the cursor to the next data bit, modify the second data bit of password in accordeance with the

above. Modify the the third and fourth data of password in sequence, press to confirm the input data and the
menu will switch to the following menu after verification.

The upper right corner BLOCK LOAD P: 0.8MPa *


with “*” indicates the BLOCK UNLOAD P: 0.6MPa
system verification FAN START T: 80℃
of the password FAN STOP T: 70℃

In the menu above press , the first data of LOADING P start to blink, user can press or to modify the

present data in accordance with the above method. Press to move to next data bit and modify the target data in

sequence. When finished press to confirm and save the data. The controller prompt sends out a short sound to
tip the completion of parameter set.
Other CUSTOMER PARAMETER share the similar way for modification.

04.08.2017 Operation Manual MAM - 860 V1.0 -8-


1.6 User Parameter:

First Submenu Second Submenu Preset Value Function


1. In AUTO LOADING status, compressor will load if pressure
is below this set data
LOAD P 0,65 MPa 2. In STANDBY mode, compressor will start if the pressure
below this set data
1. Compressor will unload automatically if air
pressure is above this set data
P, T SET UNLOAD P 0,80 MPa 2. This data should be set above LOADING P, also should be
set below UNLD P LIM

FAN START 0080℃ Fan will start if AIR T is above this set data

FAN STOP 0070℃ Fan will stop if AIR T is below this set data

Set the HOST START TIME. Record time


when motor is activated, controller will not start overload
MOTOR START 0010s protection during this time to avoid impulse starting current
stopping the motor.

Set the FAN START TIME. Record time when fan is activated,
FAN START 0005s controller will not start overload protection during this time
to avoid impulse starting current stopping the fan.

STAR DELAY 0005S Interval time from star start to delta start.

LOAD DELAY 0003S Unloading in this set time after enter delta running
TIMER SET

When unloading continuously, compressor will


EMPTY DELAY 0600S automatically stop and enter to standby status if over this set
time

For NORMAL STOP operation, compressor will stop after it


STOP DELAY 0030S
continuously unloading over this set time

Machine cannot be restarted before this set time (stop and


START DELAY 0030S over time load free stop till this time)

LOCAL: only the button on the controller can turn on and


turn off the machine.
RUN MODE LOCAL / REMOTE
REMOTE: both the button on the controller and the remote
control button can turn on and turn off the machine;
MANUAL: only when the pressure is above
Unload P, compressor will unload automatically .For any
other case ,the Load/Unload function can only be executed
AUTO/
OPERATION MODE LOAD MODE by
MANUAL pressing “load/unload” key.
PRESET
AUTOMATICAL: the load/unload function can be executed by
the fluctuation of AIR P automatically
BAN: communication function is not activated.
MODBUS
MODBUS: compressor can communicate with computer or
COM MODE SEQ DCS as slave according to MODBUS-RTU.
BAN SEQ: compressors can work in a net
COM ADD 0255 Communication address

04.08.2017 Operation Manual MAM - 860 V1.0 -9-


1. When service as master in SEQUENCE, master controls
HOST/ slave; the COM ADD should be set as No.1
SEQ STATE 2. When service as slave in SEQ, slave is
SLAVE
controlled by master
When master pressure is between SEQ
LOAD P and SEQ UNLD P, master
TURN TIME 99 Hours determines slave to work alternatively after
working over this set time
SEQUENCE PARA SEQ NUMBER 0016 Number of air compressors in block net
SETTING
In SEQ mode, one compressor will start or
SEQ LOAD 1.36MPa load when master AIR P is below this set data

In SEQ mode, one compressor will stop or


SEQ UNL. 1.36MPa unload when master AIR P is above this set
data
In SEQ mode, when master sends two
SEQ DELAY 200S commands continuously, second command
signal delays for this set data
Record total running time of OIL filter. If
OIL FILTER 0000H changing new oil filter, the data should be reset
by manual operation.
Record total running time of O/A separator. If
O/A FILTER 0000H changing new O/A separator, the data should be reset by
manual operation.
Record total running time of AIR filter. If
AIR FILTER 0000H changing new AIR filter, the data should be reset by manual
operation.
CLR LIFE TIME
Record total running time of LUBE. If
LUBE 0000H changing lubricate, the data should be reset
by manual operation.
Record total running time of GREASE. If
GREASE 0000H changing new grease, the data should be reset
by manual operation.
Record total running time of BELT. If
BELT 0000H changing new belt, the data should be reset
by manual operation.
1, Alarm prompt when total running time of oil
filter is above the set data .
OIL FILTER 0500H 2, Set this data to “0000”, alarm function for
oil filter running time is not activated
1, Alarm prompt when total running time of
O/A separator is above the set data.
O/A FILTER 3000H 2, Set this data to “0000”, alarm function for
O/A separator running time is not activated
1, Alarm prompt when total running time of air
filter is above the set data.
AIR FILTER 0500H
2, Set this data to “0000”, alarm function for
MAX LIFE TIME air filter running time is not activated
PRESET 1, Alarm prompt when total running time of
lubricant is above the set data.
LUBE 0500H 2, Set this data to “0000”, alarm function for
lubricant running time is not activated.
1, Alarm prompt when total running time of
grease is above the set data.
GREASE 3000H 2, Set this data to “0”, alarm function for
grease running time is not activated
1, Alarm prompt when total running time of
belt is above the set data.
BELT 3000H 2, Set this data to “0”, alarm function for
grease running time is not activated
LAN. SEL English Change the display language.
User password User could modify the user password by old
modification **** user password or factory password

04.08.2017 Operation Manual MAM - 860 V1.0 - 10 -


1.7 Factory Parameter:
The view and modification of factory parameter requires a factory password, The modification step is same as
customer parameter modification. Main function is as below.

Menu Initial Data Function


Maximum motor overload data When the current of motor is more than 1.2 times of the set data ,
MOTOR CUR the unit will stop for overload feature. (see table2.1.1)
/1.2
Maximum fan overload When the current of fan is more than 1.2 times of the set data , the
FAN CUR
data/1.2 unit will stop for overload feature.
When discharge air temperature reaches this set data, compressor will
ALARM T. 105℃ alarm
When discharge air temperature reaches this set data, compressor will
STOP T. 110℃ alarm and stop
STOP P. 0.90MPa When pressure reaches this set data ,compressor will alarm and stop
This data is the maximum of UNLOADING P. The UNLOADING P in the
MAX U.L. 0.80MPa customer parameter must be set no higher than this data.
RUN TIME 000100Hours Modify the TOTAL RUN TIME
LOAD TIME 000095Hours Modify the TOTAL LOAD TIME
Input the password 8888 and press “set “button to clear all the history
CLR FAULT **** failure record.
MAX-MIN >= SET*MIN/10, respond time is 5s
CUR UN.BAL. 0006 If the set data ≥ 15, the unbalance protection will be invalid.
If OPEN PHASE protection ≥20 seconds, OPEN PHASE protection is
LACK PAHSE 002.0s invalid
DATA ****-**-** Production date
SERIAL ******** Product serial No.
ON: turn on phase sequence protection
PHASE PRO. ON/OFF OFF: turn off phase sequence protection
FRE. SEL 50HZ/60HZ Set the operation power frequency
Set as compatible mode, block mode is the same as the other series.
SEQ MODE ADV/COMP When block control with MAM 8*0 controller and set as advanced
mode, more block mode function is available
1. Controller detects the voltage higher than this set data, the
HIGH VOL. 0460V shutdown protection starts and reports HIGH VOL.
2. Set this data to 0000, the HIGH VOL. protection function is invalid
1. Controller detects the voltage lower than this set data, shutdown
LOW VOL. 0320V protection starts and reports LOW VOL.
2. Set this data to 0000, the LOW VOL. protection function is invalid
1. In stop mode, air compressor is not allowed to start when discharge
air temperature is lower than this set data
LOW T PRO- -0018℃ 2. Two minutes after turn on, when the air temperature is below this
data, compressor will stop and display T SENSOR FAULT
1. When the compressor is in a stop status and the TOTAL RUN TIME
exceeds this TIME LIM set, the controller will stop the compressor and
TIME LIM 0000H display USER MISTAKE;
2. If this data is set to ‘0000’, TIME LIMIT function is invalid.
Controller detects oil filter, O/A separator, air filter, lubricate oil, grease
ALM STOP 0010H and belt running with alarming over this ALARM STOP set, compressor
will stop and report ”ALARM LONG STOP ”
1. When set as ON, User can use DCS to set data through MODBUS
protocol
COM SET PARA ON/OFF 2. When set as OFF, User cannot use DCS to set data through MODBUS
protocol
3, User can use DCS to set data only when compressor is at stop status

PARA1 **** User could modify the factory password by old factory password.

04.08.2017 Operation Manual MAM - 860 V1.0 - 11 -


MPA
PRES UNIT BAR Change the pressure unit
PSI
°F
TEMP UNIT Change the temperature unit
°C

1.8 Calibration Parameter


You can set relative data of controller in CALBR PARA. It is not allowed to view and modify without manufacturers
authorization, so please verify the password before view and modification. The modification of CALBR PARA is similar
with CUSTOMER PARA. Main function is shown as below.

Menu Initial Value Function


Enter the current value, the controller will detect user input value divided by
TARGET CUR 0000
the current to the current value, calculate the current coefficient
MOTOR Calibration current, the input coefficients. Controller displays the current
COEF 1.000 value = sample value × COEF
A
Displays the current controller sampling current values. This value is the real
CUR ***.*A
value and cannot be set.
Enter the current value, the controller will detect user input value divided by
TARGET CUR 0000
the current to the current value, calculate the current coefficient
MOTOR Calibration current, the input coefficients. Controller displays the current
COEF 1.000
B value = sample value × COEF
Displays the current controller sampling current values. This value is the real
CUR ***.*A
value and cannot be set.
Enter the current value, the controller will detect user input value divided by
TARGET CUR 0000
the current to the current value, calculate the current coefficient
MOTOR Calibration current, the input coefficients. Controller displays the current
COEF 1.000
C value = sample value × COEF
Displays the current controller sampling current values. This value is the real
CUR ***.*A
value and cannot be set.
Enter the current value, the controller will detect user input value divided by
TARGET CUR 0000 the current to the current value, calculate the current coefficient
FAN
Calibration current, the input coefficients. Controller displays the current
A COEF 1.000 value = sample value × COEF
Displays the current controller sampling current values. This value is the real
CUR ***.*A value and cannot be set.
Enter the current value, the controller will detect user input value divided by
TARGET CUR 0000
the current to the current value, calculate the current coefficient
FAN Calibration current, the input coefficients. Controller displays the current
COEF 1.000
B value = sample value × COEF
Displays the current controller sampling current values. This value is the real
CUR ***.*A
value and can not be set.
Enter the current value, the controller will detect user input value divided by
TARGET CUR 0000
the current to the current value, calculate the current coefficient
FAN Calibration current, the input coefficients. Controller displays the current
COEF 1.000 value = sample value × COEF
C
Displays the current controller sampling current values. This value is the real
CUR ***.*A value and cannot be set.

04.08.2017 Operation Manual MAM - 860 V1.0 - 12 -


1.9 Operating Authorization and Password
Controller provides multiple passwords and access management. According to different levels of passwords, controller
provides different levels of operating authorization. Details are as following:

Customer Password: factory set ____________


Permissions: Allows to modify all Customer Parameter

Factory Password: fixed ____________


Permissions: Allows user to modify all Parameter

Calibrate Password: fixed ____________


Permissions: Allows user to modify CALBR PARAMETER

2 Controller Function and Technical Parameter

 Phase sequence protection:


When compressor is at stop mode an detects open phase, response time <2ms

 Open phase protection


When any phase opens, the response time equals to set time: This fuinction is not activated when OPEN
PHASE PROTECTION time is set over 20s

 Motor protection: This control unit has the following 5 basic protection functions to the motor and fan.
o Rotor lock protection: After the starting oft he motor, if the working current reaches 4 or 8 times oft he
set value, the protection activates. The activate time is less than 0,2s.
o Short circuit protection: If the detected current reaches 8times or more above the set value, the
protection activates, the activate time is less then 0,2s
o Lack phase protection: Any oft the phase lack, the protection activates and theactivate time ist he
setting time
o Unbalance protection: The current difference between any of the two phases reaches the percentage
of the setting value, the protection activates and the activate time is less than 5s.
o Protection features of overload, please see following table for your reference. Multiple=Iactual/Iset ,
response time is shown in following table according to overload multiples from 1.2 times an
3.0times.

Iact/I set
≥1.2 ≥1.3 ≥1.5 ≥1.6 ≥2.0 ≥3.0
Time Para

response time (s) 60 48 24 8 5 1

04.08.2017 Operation Manual MAM - 860 V1.0 - 13 -


3 Model and specification

 Main controller model description


MAM - 860 (B)(T) (V)
(40)

Max work current match with motor


With voltage detection & protection
RS485 communication
Pressure converter
860 controller
Products Series

 Power consumption table for corresponding motor

Parameter Adopted Host


Current Range
Spec. Motor Power Remarks Descriptions
(A)
(KW)
MAM—KY02S(20) 8~20 4~10
MAM—KY02S(40) 16~40 8~20 Fan has three levels of
MAM—KY02S(100) 30~100 15~50 current. Such as 0.2-2.5A,
MAM—KY02S(200) 80~200 40~100 1-5A and 4-10A,
determined by current of
MAM—KY02S(400) 160~400 80~200
motor.
MAM—KY02S(600/5) Connect to
100~600 50~300
CT

04.08.2017 Operation Manual MAM - 860 V1.0 - 14 -


4 Overview

、 △

21 20 19 11 12 13 14 15 16 17 18

22 23 24 25 26 27 28 29 30 31
C1
10 9 8 7 6 5 4 3 2 1

uc ub ua
a
b C T2

c
A A
R S -4 85 B C T1
B
FG
C

Figure 4.2.1 Terminal arrangement diagram

Cable connection of controller:


1 Common terminal for digital input 2 Input terminal for emergency stop 3 Input terminal for remote
signal control signal ( on/off )
4 Input terminal used to detect oil 5 N/A 6 RS485+
filter
7 RS485- 8 Terminal for ground connection 9 Terminal for the AC20V power
source
10 Terminal for the AC20V power 11 N/A 12 N/A
source
13 Common terminal for digital 14 Terminal to control fan 15 Terminal to control load valve
output
16 Terminal to control delta 17 Terminal to control star contactor 18 Terminal to control main contactor
contactor
19 Input terminal to detect the 20 Input terminal to detect the phase 21 Input terminal to detect the phase
phase sequence and voltage sequence and voltage sequence and voltage
22 Power terminal for pressure 23 Input terminal to receive pressure 24 Terminal for motor CT1 input
sensor sensor signal
25 Terminal for motor CT1 input 26 Terminal for motor CT1 input 27 Terminal for fan CT2 input
28 Terminal for fan CT2 input 29 Terminals for fan CT2 input 30 Terminal for discharge air
temperature sensor
31 Terminal for discharge air
temperature sensor

Attention: The magnetic coil must be connected to the surging absorber when wiring

04.08.2017 Operation Manual MAM - 860 V1.0 - 15 -


5 Control Process

Single Machine
Working principle (On/off mode: Local; Load mode: Auto)

①、 Press to start: (Y-△start)

The air compressor can not be started by pressing until 5 seconds self checking finished.
The start process of compressor is as followed: 18 terminal closed, KM2 is energized; 17 terminal
closed, KM3 is energized → Y start → STAR DELAY me starts record; when Y-△transfer time
over,17 terminal open, KM3 is de-energized and 16 terminal closed, KM1 is energized → motor
operates in △. (KM1 and KM3 are interlocked)
②、 Automatic operation control:
2.1: When motor enter delta status, LOAD DELAY starts, controller will load automatically after
LOAD DELAY.
2.2: If air pressure is detected higher than UNLOADING P set, 15 terminal opens, loading valve is
de-energized, and air compressor starts unloading, and also starts EMPTY DELAY time record,
if unloading time exceed EMPTY DELAY set, compressor will enter STANDBY mode; if
compressor loading again within “EMPTY DELAY” set (when pressure is below LOADING P or
receiving load command), compressor will reset “EMPTY DELAY”.
2.3: In STANDBY mode, controller start automatically if pressure detected is below LOADING P
③、 Manual loading/unloading operation under automatic status
3.1 When air pressure is between LOADING P and UNLOADING P, press “loading/ unloading” to
switch the current status of controller.
3.2 When air pressure is above the UNLOADING P, controller unloads automatically, the
loading/unloading button is invalid
3.3 When air pressure is below the UNLOADING P, controller loads automatically, the
loading/unloading button is invalid
④、 Normal stop:

Press , the loading magnetic valve will be de-energized, after a while of delay (stop delay),
all output relay stop working.
⑤、 The frequent starting control
Air compressor can not start again immediately after NORMAL STOP, EMPTY LONG STOP or
FAILURE STOP. It can start again after START DELAY.

04.08.2017 Operation Manual MAM - 860 V1.0 - 16 -


 Remote Automatic Control (Control Mode: Remote; Load Mode: Auto)
In this mode, compressor can be turned on or off by remote control.
 Local Control (Control Mode: Local, Load Mode: Manual)
a. Control of start and stop are same as automatic control, but device is in status of unloading after
finish starting process.

b. In unload status, press to load. When air pressure is higher than UNLOADING P set, the
device will unload automatically.

c. If not press ,the device will run unload until EMPTY DELAY.

d. In load status, press to unload.


 Net Work
a. Controller works as slave when communication mode is set as “MODBUS”, and communicates
with monitoring center through MODBUS.
b. Controller and other controller can block work when communication mode is set “SEQ” but the
master only can service as 1# compressor.
 Fan Operation
When discharge air temperature is higher than FAN START T, fan operates; when discharge air
temperature is lower than FAN STOP T, fan stops.

04.08.2017 Operation Manual MAM - 860 V1.0 - 17 -


6 Alarm Function

6.1 Monitor text

6.1.1 Air filter alarm


1. Use switching signal to detect alarm
The monitor displays AIR FILTER BLOCK by checking air filter differential pressure switch
2. Set AIR filter max. time
The monitor displays AIR LIFE END when the run time of air filter exhausts

6.1.2 Oil filter alarm


1. Use switching signal to detect alarm
The monitor displays OIL FILTER BLOCK by checking oil filter differential pressure switch
2. Set OIL filter max. time
The monitor displays OIL LIFE END when the run time of the oil filter exhausts

6.1.3 O/A alarm


1. Use switching signal to detect alarm
The monitor displays O/A BLOCK by checking O/A filter differential pressure switch
2. Set O/A max. time
The monitor displays O/A LIFE END when the run time of the O/A Separator exhausts

6.1.4 Lubricating oil alarm


The monitor displays LUBE LIFE END when run time of lubrication oil exhausts

6.1.5 Grease alarm


The monitor displays GREASE LIFE END when run time of the grease exhausts

6.1.6 Belt alarm


The monitor displays BELT LIOFE END when the run time of Belt exhausts

6.1.7 High discharge air temperature alarm


The monitor displays HIGH TEMPERATURE when controller detects the discharge air temperature is
higher than ALARM T set data in MANUFACTORY PARA

04.08.2017 Operation Manual MAM - 860 V1.0 - 18 -


7 Alarm Function
7.1 Motor Protection
MAM-860 air compressor controller provides overload, open phase, current unbalance, high voltage, low
voltage protection for motor and overload protection for fan.

Electronic Failure Failure Display Reason


Overload Display “MOTOR/FAN OVERLOAD” Overload, bearing wear and other mechanical failure

Open phase Display “MOTOR OPEN PHASE” Power supply, contactor and open phase of motor

Unbalance Display “MOTOR UNBALANCE” Poor contact of contactor, inside open-loop of motor

High Voltage Display “HIGH VOLTAGE” High supply voltage

Low Voltage Display “LOW VOLTAGE” Low supply voltage

7.2 Protection of High Discharge Air Temperature


When discharge air temperature is above the high limit of set temperature, the controller will send out the
alarm to shut down the machine. This fault displays HIGH T.

7.3 Protection of Air Compressor Reversal


When compressor stops and three phases sequence is not in order, this fault displays PHASE REVERSAL,
and the controller cannot star the motor. It is needed to check and alternate any two of the phase
sequence and investigate the motor rotation direction.

7.4 Protection of High Pressure


When the AIR P is above the STOP P, the controller will send out the alarm to shut down the machine. This
fault displays HIGH P

7.5 Protection of Sensor Failure


When pressure sensor or temperature sensor is disconnected, the controller will send out the alarm to
shut down the machine and this fault displays **SENSOR FAULT

7.6 Low Temperature Protection


When discharge air temperature is below LOW T PRO in manufacturing parameter, this fault displays P
SENSOR FAULT two minutes after compressor turns on, the controller will send out the alarm to shut down
the machine.

04.08.2017 Operation Manual MAM - 860 V1.0 - 19 -


8 Troubleshooting

8.1 This fault review


Failure stop caused by the external parts of controllers may be removed by checking this fault or history
fault, method is shown as below.

Press or to move the cursor to “RUN PARAMETER”, then press to switch to secondary
menu

MOTOR、FAN CURRENT
TOTAL RUN TIME
THIS RUN TIME
MAINTAIN PARAMETER

Press to move the cursor to “CURRENT FAULT”

HISTORY FAULT
PROD. DATE/NUM
CURRENT FAULT

Then press to reach the following failure cause:

Temperature sensor Failure


170℃

Check the temperature sensor to confirm if there is any line broken or damage.

04.08.2017 Operation Manual MAM - 860 V1.0 - 20 -


User can reset the error according to the following information:

Failure Causes Measurement to take


AIR T HIGH Bad vent condition, Oil lacking etc. Check the vent condition and lubricant amount etc.

AIR T SENSOR FAULT Cable off or PT1OO damaged Checking the wiring and PT100

The pressure too high or the pressure


AIR P HIGH Check the pressure and the pressure sensor
sensor failure
Cable off, Sensor damaged or the cable
AIR P SENSOR FAULT Check the wiring and sensor transformer
connected reversed

LACK WATER Water Pressure switch damaged Check the water pressure switch

Power phase lacking or the Contactor


LACK PHASE Check the power and contactors
terminal damaged
Voltage too low, tubes blocked, bearing
Check the set data, Voltage, bearings, tubes and other
OVERLOAD wear off or other mechanical failure or
mechanical system.
wrong set data etc.
Power unbalance, contactor damaged
UNBALANCE Check the power, contactors and the motor
or the internal open of the motor
Voltage too low, tubes blocked, bearing
Check the set data, Voltage, bearings, tubes and other
BLOCK wear off or other mechanical failure or
mechanical system.
wrong set data etc.
Wrong cable connection, wrong set
SHORT CIRCUIT Checking the wiring and set the data correctly
data

WRONG PHASE SEQUENCE Reversed Phase sequence or phase off Check the wiring

Fan damaged, Contactor damaged, no


Fan stopped Check the wiring and control output
control output
Overload or Rotor locking Start time set too less than the star Reset the host starting time to be longer than star
during starting process delta time delay delta delay + load delay time
Main Contactor activate time
The emergency button loose Check the wiring
to time

04.08.2017 Operation Manual MAM - 860 V1.0 - 21 -


9 Sequence Mode Control and Network

9.1 Sequence mode control


MAM-860 controller can operate with other MAM series compressor (with communication function). 16 pcs
compressors are allowed in the net at most. The cable connection for block mode is as below….

A B A B A B A B A B

Master 1 Slave 2 Slave 3 Slave 4 Slave 16

Compressors with net communication address 0001 is master, others are slave. Any one MAM series compressors
can be set as master or slave

04.08.2017 Operation Manual MAM - 860 V1.0 - 22 -


9.2 Sequence Mode Setting

9.2.1 Set as Master:

Press or to move the cursor to “USER PARAMETER”, then press to switch to the menu
below:

P, T SET
TIMER SET
OPERATION MODE
SEQ PARA. SET

Move the cursor to the “OPERATION MODE”, then press to switch to the menu below.

RUN MODE: REMOTE


LOAD MODE: AUTO Set “COM MODE” as SEQ
COM MODE: SEQ Set “COM ADD” as 0001
COM ADD: 0001

Return to the previous menu, move the cursor to “SEQ PARA SET” press to switch to the menu below.

SEQ STATE: HOST


TURN TIME: 0099H
SEQ NUMBER: 0016
SEQ LOAD: 1,36MPa

SEQ UNLOAD: 1,36MPa


SEQ DELAY: 200s

According to user requirement, set SEQ STATE as Host, set TURN TIME, SEQ NUMBER, SEQ LOAD, SEQ
UNLOAD and SEQ DELAY according to user´s need.

Attention: After setting, controller needs to be powered off and restarts to the
settings!

04.08.2017 Operation Manual MAM - 860 V1.0 - 23 -


9.2.2 Set as Slave:

When MAM controller serves as slave, it is only necessary to set COM MODE as SEQ. Set COM ADD from 2 –
16 with sequence according to the quantity of compressors, and SEQ STATE as SLAVE.

9.3 Start, stop sequence control:


Make sure sequence cables connect correctly and the parameter of compressors in net set correctly.
Activate master, master controls the compressors in Net automatically according to the air pressure
detected. Sequence control stops at the same time when manually stop the master. So master will no longer
send command to compressor in net.

AIR T: 78°C ◊
AIR P: 0.53MPa
NORMAL STOP 0S ◊: Blinking icon indicate
C16 REMOTE
master has active seq
mode function

9.4 Sequence Communication Receiving and Sending Message:


The message received and set by RS485 can be displayed by the corresponding indication screen which is
convenient for customer to make sure if they have received and feedback data in SEQ MODE or COM MODE.
The method to switch to communication menu is as below:

Press or in main menu and select “RUN PARAMETER” and move down the cursor to communication

menu. Press to switch to the menu below:

RX: ----
TX: ----

When controller receives data, RX “—“ and “*” display alternately. When sends data, TX “—“ and “*” display
alternately. When controller is in SEQ mode or communicates with monitoring center, user can confirm the
establishment of communication through this menu.

04.08.2017 Operation Manual MAM - 860 V1.0 - 24 -


9.5 Network
MAM-860 controller supports MODBUS RTU protocol and can serve as slave when connect with other equipment
and supports 03, 06, 16 MODBUS command.
 Communication baud rate: 9600BPS
 1 start bit
 8 data bits
 1 stop bit
 even parity

04.08.2017 Operation Manual MAM - 860 V1.0 - 25 -


10 Copyright

This manual is protected by copyright and intended solely for internal use.
This manual must not be made available to third parties, duplicated in any manner or form – whether in whole or in
part – and the content must not be used and/or communicated, except for internal purposes, without the written
consent of the manufacturer. Violation of the copyright will result in legal action for damages. We reserve the right to
assert further claims.

Tolpec GmbH
Wertstrasse 44
D- 73240 Wendlingen
Telephone: +49 (0)7022 789 604-0
E-mail: contact@tolpec.com

04.08.2017 Operation Manual MAM - 860 V1.0 - 26 -