MCS - LCB_II
List of Installation Parameters
GDA 21240 D1 - D3
Software Version: GAA 30082 BAC
Document Revision:
24 - May - 93 GAA 30082 AAA J. Schulte - Original Document
03 - Dec - 93 GAA 30082 AAB A.Gerwing
- OTIS 2000 features add.
29 - Apr - 94 GAA 30082 AAC M. Hnida
- Triplex parameter added
02 - Jun - 94 GAA 30082 AAD M. Hnida
- Secure Access revised
16 - Jun - 94 GAA 30082 AAE J. Schulte
- BSM mode added
17 - Jan - 95 GAA 30082 BAA J. Schulte
- MCS220M, LSVF-W, ELD,
REM III added
06 - Jun - 95 GAA 30082 BAB A. Gerwing - not distributed
27 - Jun - 95 GAA 30082 BAC A.Gerwing - CPC-TYP, N+2,
ELD-MSG, ELD-DOOR
0 (1) 31
2 BOTTOM 0 Bottom position:
0 (1) 30
3 CFT-P 255 Cafeteria Position:
0 (1) 31
> 31 Disabled
4 OPERAT 1 Operation FCL/DCL/SAPB:
0 FCL
1 DCL
2 SAPB
5 EN-BSM 0 Enable BSM mode (for DCL: both Up- and Down Hall Calls at lobby):
0 Disabled
1 Enabled
6 CONFIG 0 General configuration:
0 ETO
1 NAO
7 PI 4 Type of serial Position Indicator:
0 7/16 Segment
1 Multil.
2 Australian Dot Matrix
3 Australian Dot Matrix with CUDL/CDDL
4 OTIS 2000: LCD and ELD
8 ELD-fOPG 20 front door movement time: opening
0 (0.1) 10.0 s
0 = automatic (not yet implem.)
9 ELD-fCLG 20 front door movement time: closing
0 (0.1) 10.0 s
0 = automatic (not yet implem.)
10 ELD-rOPG 20 rear door movement time: opening
0 (0.1) 10.0 s
0 = automatic (not yet implem.)
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 (1) 19
0 SwiGer, 1 SwiFRA, 2 SwiIta, 3 Fra, 4 Italy,
5 UK, 6 Spain, 7 Nether, 8 Ger, 9 Aus,
10 Sweden, 11 Luxem, 12 Belg, 13 Por, 14 Egy,
15 Denmar, 16 SthAfr, 17 Finlnd, 18 Ara, 19 Kuw
13 ELD-Sym1 0 Enable Non-Smoking symbol:
0 Disabled
1 symbol is displayed
R) 14 ELD-DOOR 0 select type of door display:
0 Disabled
1 Enabled
17 LR-T 20 FAN (LR) time:
0 (1) 255 s
18 EN-HLC 0 Enable Hall Lanterns on car calls:
0 Disabled
1 HLC
2 HL also during closing
3 HLC and during door closing
19 HDL-TY 0 Hall Direction Lantern Type of OTIS 2000 Hall Button Box:
0 Direction Indicator
1 Hall Lantern
20 HL-SET 0 Hall Lantern/Gong Setup:
0 Disabled
1 Enabled (short or medium run)
23 DZCNT 1 Use DZ for SL counting (for Short Run):
0 Disabled
1 Enabled
24 EN-DZI 0 Enable DZI (Door Zone Indicator):
0 Disabled
1 Enabled (only if no Door ByPass)
25 ERO-TYP 0 Define ERO type
R) 0 without limit
1 with limit at terminal landings (same as TCI-limit)
R) 2 ERO-input disabled (for LCB_II version D2)
26 C-CHK 0 Enable C-Circuit Check:
0 Disabled
1 Enabled
27 MD/AES 0 select use of MD input (P7:9, only MCS220M):
0 not connected
R) 1 MD: DCS-input for Multi Door (manual plus autom. landing
doors)
R) 2 AES: ES-input if RSS or ESB is used
R) 28 CPC-TYP 0 select use of CPC outputs:
0 (1) 31
> 31 Disabled
2 ARD-T 0 Set Delay for ARD (Automayic Return Device) mode:
0 (10) 2550 s
3 L-PARK 0 Lobby Park Option:
0 Disabled
1 Enabled
4 CTL/PKS 0 Select CTL or PKS switch:
0 (1) 31
> 31 Disabled
6 PKS-TY 0 Parking Shutoff Type:
0 ETO
1 NAO
2 ETO with door open after shutdown
7 PKS-T 0 Parking Shutoff Time:
0 (1) 255 s
8 PKS-DO 0 PKS default door:
0 Normal HB-operation
1 Rear HB as Separate Riser
10 DCP-T 50 Time until DCP-mode (delayed car protection):
25 (1) 255 s
11 CTL-DO 0 CTL default door (car to any landing):
0 Disabled
>0 Number of calls to trigger ANS
14 ATT 0 ATT (Attendant Service) type:
0 Start on CCB
1 Start on DCB
2 Start on ISD/ISU
3 NAO (USA)
16 CTL-TY 0 Select Car To Landing Type:
0 ETO
1 NAO
17 SPEECH 0 Speech Mode:
0 No limit
1 (1) 255 Number of allowed door reopenings
19 DS-CCB 0 Disable CCs behind moving car:
1 (1)3
2 CNL 1 Cars parking in Lobby:
1 (1)3
3 MIT-ST 0 MIT (Moderate incomming traffic) Startdelay:
0 (1)255 s
4 MIT-T 0 MIT Time-Out:
0 (1)255 s
5 MIT-VD 0 MIT Variable Interval Dispatch:
0 (1)255 s
6 DUPK-P 255 Dual Up Peak Border Position:
0 (1)31
> 31 Disabled
7 DUPK-G 0 Dual Up Peak Group:
0 (1)255 s
9 EN-UCB 0 Enable Up Call Bypass:
0 Disabled
1 Enabled
10 TFS-P 255 Transfer Floor Position:
0 (1)31
> 31 Disabled
11 PARK-1 255 Park Clock Position 1:
0 (1)31
> 31 Disabled
12 PARK-2 255 Park Clock Position 2:
0 (1)31
> 31 Disabled
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 (1) 31
> 31 Disabled
15 PARK-5 255 Park Clock Position 5:
0 (1) 31
> 31 Disabled
16 PARK-6 255 Park Clock Position 6:
0 (1) 31
> 31 Disabled
17 PARK-7 255 Park Clock Position 7:
0 (1) 31
> 31 Disabled
18 PARK-8 255 Park Clock Position 8:
0 (1) 31
> 31 Disabled
19 EN-ZBS 0 Enable separate basement zone:
0 (0.1) 25.5 s
3 2AT 5 2A Time:
0 (0.1) 25.5 s
4 DDP 32 DDP Time (fast run):
0 (1) 45 s
5 3P 32 3P Time (slow run):
0 (1) 45 s
6 SPEED 100 Speed (fast run mode):
25
40
63
100
160
175
250 cm/s
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
European and Transcontinental Vintage : 01 / 8
Operations Software Data
PRODUCT Page : 10 / 25
MCS - LCB_II
ADMINISTRATION
List of Installation Parameters Date : 27-Jun-1995
0 (1) 254 s
255 wait forever
9 HY-TYP 0 Hydro Drive Type for Hydro:
0 Star - Delta
1 Soft
2 Direct
10 L-T 10 Set Star/Soft Time for Hydro:
0 (0.1) 25.5 s
11 UX-D 20 Set Star/Delta gap / add. Soft Time (L+UX) for Hydro:
0 (0.1) 1 s
13 EN-PLS 1 Enable PLS1 (Oil-Max-Pressure Limit Switch) for Hydro:
0 Disabled
1 Enabled
14 EN-OTS 1 Enable OTS (Oil-Over Temperature Switch) for Hydro:
0 Disabled
1 Enabled
15 ACD/UXT 0 Select ACD (Anti Creeping Device) or UXT output for Hydro:
0, 255 Disabled
1 (1) 254 s
17 P-ON-D 10 Set Power On delay for LSVF-W
8 (1) 20 s
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0(1) 4
20 EN-BCD 1 Enable Brake Current Detection:
0 Disabled
1 Enabled
21 BON-D 10 Delay of BCD (after lifted brake)
0(0.1) 10 s
22 BFLT-T 15 Max. fault time of BCD
0(0.1) 10 s
23 BOFF-D 15 Delay of BCD (after fallen brake)
0(0.1) 10 s
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 FLH
1 9550T & ACG
2 9550T & TLD / DO_2000 (DC-relay)
3 OVL / MRDS
4 OVL & ACG
5 DO_2000 (DO-relay)
6 MCG
7 Kiekert / MLI & ACG
8 Kiekert / MLI & TLD/CLD
2 EN-DDO 0 Enable DDO (double door operation):
0 Disabled
1 Enabled
3 MIXDOR 0 Mixed Dooroperators:
0 Disabled
1 Enabled
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 (1) 255 s
10 EN-CK 0 Enable Cancel Doortime with CCB:
0 Disabled
1 Enabled
11 DW-DLY 10 Debouncing Time of Door Contact DW:
0 (0.1) 25.5 s
12 DO-BEL 0 Open Door Bell Timer:
0 (0.1) 25.5 s
13 MIN-C 20 Min Doortime Car:
0 (0.1) 25.5 s
14 MAX-C 40 Max Doortime Car:
0 (0.1) 25.5 s
15 MIN-H 40 Min Doortime Hall:
0 (0.1) 25.5 s
16 MAX-H 60 Max Doortime Hall:
0 (0.1) 25.5 s
17 DOR-T 0 Door reverse time:
0 (0.004) 1 s
18 RDOR-T 0 Rear door reverse time:
0 (0.004) 1 s
19 DTC-T 20 Door Close Protection Time:
10 (1) 255 s
20 DTO-T 20 Door Open Protection Time:
10 (1) 255 s
21 LOB-NT 40 Lobby Door Time:
0 (0.1) 25.5 s
22 CFT-NT 40 Cafeteria Door Time:
0 (0.1) 25.5 s
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 (1) 255 s
25 WCO-T 0 Wild Car Door Time:
0 (0.1) 25.5 s
26 SHO-T 0 Shabat Door Time:
0 (0.1) 25.5 s
27 SHO-LT 0 Shabat Lobby Door Time:
0 (0.1) 25.5 s
28 DAR-T 60 MPD/Hydro Door Open Time:
0 (1) 255 s
29 DXT-T 0 DXT Time (extended door time):
0 (0.1) 25.5 s
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
1 DZ-TYP 0 DZ coding:
0 DZ = 1LV
1 DZ = 1LV and 2LV
2 POSY operation (if neither RLV nor ADO)
to stop: DZ = 1LV and 2LV
after stop: DZ = 1LV or 2LV
2 DZ-DLY 0 Delay for DZ:
0(0.004) 1 s (LV-MOD = 0)
3 LV-U-D 12 Delay for DZ, 1LV/2LV (in up direction):
0(0.004) 1 s (LV-MOD = 1, 2, 4)
4 LV-D-D 12 Delay for DZ, 1LV/2LV (in down direction):
0(0.004) 1 s (LV-MOD = 1, 2, 4)
5 T-BASE 0 Timebase for IPU-D, IPD-D, 1LS-D and 2LS-D:
0 0.1 s
1 0.004 s
6 IPU-D 0 Delay for IPU:
0 Disabled
1 Enabled
11 RLV-TY 0 RLV - Type:
0 RLV Relevelling
1 DRLV Delayed Relevelling (using DIS1)
12 RL-CNT 3 Limit of RLV steps:
0(1) 255
13 RL-DIS 255 Set RLV time up (DIS lost):
0(0.1) 25.5 s
14 RL-UIS 255 Set RLV time down (UIS lost):
0(0.1) 25.5 s
0(0.004) 1 s (hydraulic drive)
15 RL-U-D 0 Set RLV delay up:
0(0.004) 1 s
16 RL-D-D 0 Set RLV delay down:
0(0.004) 1 s
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 (0.004) 1 s
3 BI-T 0 Class C2: time-out for Bolts In:
0 (0.004) 1 s
4 BO-T 0 Class C2: time-out for Bolts Out:
0 (0.004) 1 s
5 MVU-T 0 Class C2: time-out for Move Up:
0 (0.004) 1 s
6 MVD-T 0 Class C2: time-out for Move Down:
0 (0.004) 1 s
7 PLS4-T 0 Class C2: time-out for PLS4:
0 (0.004) 1 s
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0(1) 31
> 31 Disabled
2 EFO-DC 0 EFO with doors closed:
0 Disabled
1(1) 255 s DC time
3 EFO-DO 0 EFO default door:
0 No override possible
1 XEFO input overrides EFO after arrival at return landing
2 After EFS no EFO is permitted if EFO or AEFO are still active
3 Functions 1 + 2 together
0 (1) 31
> 31 Disabled
7 EFS-TY 0 Type of EFS (Emergency Fireman Service) (if EFK (ASL) connected):
0 EFO
1 EFS 1 (Aut.)
2 EFS 2 (Man.)
3 ANSI (USA)
4 British Standard
5 Swiss Standard
6 Australia
R) 7 New Zealand
8 EFS 2 (Man. with ESK)
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 Disable backup
1 Enable backup
11 HDWPOS 0 Hardware position reference:
0 Disabled
1 One contact per floor
2 Binary coded contacts
3 Signal at every odd floor
12 EPO-P 255 EPO (emergency power operation) Position:
0 Disabled
1 (1) 255 s
14 EPO-DO 0 EPO default door:
0 California
1 New Zealand
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 Disabled
1 (1) 255 s
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 Disabled
1 In up direction only
2 In down direction only
3 In both directions
5 In up direction only, if ISTS active
6 In down direction only, if ISTS active
7 In both directions, if ISTS active
2 IST-P 255 Intermittent Stop Position:
0 (1) 31
>31 Disabled
3 EN-CRO 0 Enable CRO (card reader operation):
0 Disabled
1 Single contact reader
2 Australian Card Key sec type 2
3 Australian Card Key sec type 1
4 Multi contact reader
4 GCBTYP 0 General Control of Buttons type:
0 disabled
1 GCB_1
2 GCB_2
5 RIOT-P 255 RIOT Operation Position:
0 (1) 31
>31 Disabled
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 (1) 6
>6 Disabled
8 SAC-D2 255 Secure Access digit 2:
0 (1) 6
>6 Disabled
9 SAC-D3 255 Secure Access digit 3:
0 (1) 6
>6 Disabled
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
0 (1) 31
> 31 Disabled
2 TDELAY 255 Test Delay for automatic test run:
0 (1) 255 s
3 NoAdrChk 0 Disable safety check: address of TCI, 1LS and 2LS regarding to Std-IO-List
0 (1) 255 s
6 DEBUG1 0 Debug Parameter 1:
0 (1) 255 s
7 EN-1CL 0 Enable Init_1CL: default position (Mot_VLV.):
0 Disabled
1 Enabled
8 EN-EVT 0 Enable storage of 10 events into E2PROM:
0 Disabled
1 Enabled
9 EN-CRT 0 Enable contract handling: Operate up to 32 openings:
0 Disabled
1 Enabled
FIELD COMPONENT MANUAL 4 - AA 3
OTIS No. : GCA 21240 D VIIIa
J PARK-2, 7 TPOS1, 23
J-T, 11 PARK-3, 8 TPOS2, 23
PARK-4, 8 T-BASE, 15
PARK-5, 8
L PARK-6, 8
LDR, 12 U
PARK-7, 8
LOBBY, 2 PARK-8, 8 UXT-D, 10
LOB-NT, 13 PI, 2 UX-D, 10
LR-T, 3 PKS-DO, 5
LVD-5D, 17 PKS-P, 5 W
LVU-5D, 17 PKS-T, 5 WCO-T, 14
LV-D-D, 15 PKS-TY, 5
LV-MOD, 15 PLS4-T, 17
LV-U-D, 15 P-OFF-D, 10 1
L-PARK, 5 P-ON-D, 10 1AT, 9
L-T, 10 1LS-D, 16
R
M RDOR-T, 13 2
MAX-C, 13 REAR, 12 2AT, 9
MAX-H, 13 RIOT-P, 21 2LS-D, 16
MD/AES, 4 RLV-TY, 16
MIN-C, 13 RL-CNT, 16
MIN-H, 13 3
RL-DIS, 16
MIT-ST, 7 RL-D-D, 16 3P, 9
MIT-T, 7 RL-UIS, 16
MIT-VD, 7 RL-U-D, 16
MIXDOR, 12
MOT-T, 7
MPD-T, 10 S
MVD-T, 17 SACTYP, 22
MVU-T, 17 SAC-D1, 22
SAC-D2, 22
SAC-D3, 22
N SEL-CMR, 12
NDG-T, 13 SHO-LT, 14
NoAdrChk, 23 SHO-T, 14
NoDW_Chk, 23 SPB-NT, 14
SPEECH, 6
O SPEED, 9
OPERAT, 2
T
P TDELAY, 23
TFS-P, 7
PARK-1, 7
TOP, 2