TECHNICAL DATA

Project: CAM RANH INTERNATIONAL PASSENGER


Package: BP07 – MEP INCL. FIRE FIGHTING WORK

HVAC SYSTEM

Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

1 CHILLER
Trane, Carrier, McQuay and York
Manufacturer:
International
USA, Western Europe and Japan with
Origin:
acceptable manufacture

QCVN 09:2013/BXD.
Air Conditioning and Refrigeration Institute
(ARI) Standard 550/590-latest edition.
American Society of Heating, Refrigerating,
Standards:
and Air Conditioning Engineers (ASHRAE).
American Society of Mechanical Engineers
(ASME).

Open or closed, with Hermetic single


Centrifugal machine
compressor.
Chiller Capacity 750.0 Tons
Power 400/3/50
Chiller Input Kw
Chiller Input Power
Chiller COP
Chiller
Models:
Starter/ VFD:
Refregerants: R-134a or R123
Isolation Valve:
Automatic Hot Gas Bypass:
Operation Type:
Evaporator
Chiller water flow (l/s): 101.00
Pressure drop (maximum): 6.7 (M)
Entering water temperature (oC) 12.6
Leaving water temperature (oC) 7.0
Waterbox Type
Passes
Nozzle Arrangement

Tubing

NVL Page 1 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Fouling Factor (sqm-K)/kW 0.00010


Tube Quantity
Fouling Temp Adj
Compressor
Size
Map ID
Flow Fraction
Head Fraction
Discharge Temp
Condenser
Heat rejection
Condenser water flow (l/s) 132.00
Pressure drop (maximum): 6.7 (M)
Entering water temperature (oC) 32.0
Leaving water temperature (oC) 37.0
Fouling factor 0.00025
Fouling Temp Adj
Weights
Total Rigging Weight
Total Operating Weight
Refrigerant Weight
Flow Controls
Float Valve Size
Flasc Orifice
Others
Motor
Motor Rated Load Amps
Motor OLTA
Motor LRYA
Motor LRDA
Chiller Rated Line Amps
Max Fuse/CB Amps
Min Circuit Ampacity
Control Parameters
Surge/HGBP Gvmin
Surge/HGBP Delta Tsmin
Surge Line Shape Factor
Surge/HGBP Gvmax
Surge/HGBP Delta Tsmax
Cooler Min DP
Condenser Min DP
Heat Exchangers
Condensing Temp
Cooler Wall Temp
Suction Temp
Cooler Freeze Temp
Cooler Tube Vel
Cond Tube Vel
2 AHU
2.1 AHU-G-1A
NVL Page 2 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row

NVL Page 3 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Fin Density (FPI)


Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 33079
Ent. Air DB/WB, °C 27.5/19.8
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 250.00
Sensible Clg. Cap., kW 166.90
Fluid Flow Rate, L/s 10.80
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:

NVL Page 4 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

2.2 AHU-G-2
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type

NVL Page 5 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 37915
Ent. Air DB/WB, °C 25.8/17.5
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 204.50
Sensible Clg. Cap., kW 169.60
Fluid Flow Rate, L/s 8.81
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:

NVL Page 6 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Frame Thickness:
Bracket Material:
2.3 AHU-G-1B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

NVL Page 7 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 33079
Ent. Air DB/WB, °C 27.5/19.8
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 250.00
Sensible Clg. Cap., kW 166.90
Fluid Flow Rate, L/s 10.80
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:

NVL Page 8 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.4 AHU-G-3A
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

NVL Page 9 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 34069
Ent. Air DB/WB, °C 27.4/19.7
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 249.50
Sensible Clg. Cap., kW 167.20
Fluid Flow Rate, L/s 10.75
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
NVL Page 10 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Final Pressure Drop:


Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.5 AHU-G-3B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard

NVL Page 11 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 34069
Ent. Air DB/WB, °C 27.4/19.7
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 249.50
Sensible Clg. Cap., kW 167.20
Fluid Flow Rate, L/s 10.75
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
NVL Page 12 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Aver Pressure Drop:


Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.6 AHU-G-4
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories

NVL Page 13 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 43650
Ent. Air DB/WB, °C 26.4/18.1
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 257.10
Sensible Clg. Cap., kW 200.70
Fluid Flow Rate, L/s 11.07
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:

NVL Page 14 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Bag Filter Class:


Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.7 AHU-G-5,7
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles

NVL Page 15 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 32418
Ent. Air DB/WB, °C 27/19.1
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 222.70
Sensible Clg. Cap., kW 157.70
Fluid Flow Rate, L/s 9.60
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:

NVL Page 16 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.8 AHU-G-6
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand

NVL Page 17 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Motor Voltage (V-phase-Hz)


Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 23454
Ent. Air DB/WB, °C 26.6/18.4
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 114.70
Sensible Clg. Cap., kW 109.70
Fluid Flow Rate, L/s 6.23
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:

NVL Page 18 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Calc Pressure Drop:


Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.9 AHU-G-8
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW

NVL Page 19 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 38570
Ent. Air DB/WB, °C 26.8/18.5
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 245.20
Sensible Clg. Cap., kW 184.00
Fluid Flow Rate, L/s 10.56
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
NVL Page 20 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Aver Pressure Drop:


Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.10 AHU-G-1-1A,1B,1C
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm

NVL Page 21 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 28283
Ent. Air DB/WB, °C 27.4/19.6
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 208.50
Sensible Clg. Cap., kW 140.40
Fluid Flow Rate, L/s 8.98
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
NVL Page 22 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Panel Filter Class:


Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.11 AHU-G-1-2A,2B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa

NVL Page 23 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 32900
Ent. Air DB/WB, °C 27.6/19.7
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 208.50
Sensible Clg. Cap., kW 246.30
Fluid Flow Rate, L/s 10.61
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll

NVL Page 24 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.12 AHU-G-1-3A,3B,3C
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
ACCESS DOORS/PANELS
Size (WxH) (mmxmm) 500x1500 or as high as the casings permit.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %

NVL Page 25 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Fan Outlet Velocity, m/s


External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 29086
Ent. Air DB/WB, °C 27.3/19.5
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 208.90
Sensible Clg. Cap., kW 141.50
Fluid Flow Rate, L/s 9.00
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

NVL Page 26 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.12 AHU-G-2-1A,1B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size

NVL Page 27 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 47864
Ent. Air DB/WB, °C 26.6/18.2
Lvg. Air DB/WB, °C 11.7/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 284.60
Sensible Clg. Cap., kW 220.20
Fluid Flow Rate, L/s 12.26
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

NVL Page 28 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.12 AHU-G-2-2A,2B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type

NVL Page 29 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 40968
Ent. Air DB/WB, °C 26.8/18.7
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 264.30
Sensible Clg. Cap., kW 195.00
Fluid Flow Rate, L/s 11.39
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
NVL Page 30 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.12 AHU-G-2-3A,3B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.

NVL Page 31 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 28388
Ent. Air DB/WB, °C 26.4/18
Lvg. Air DB/WB, °C 11.7/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 160.20
Sensible Clg. Cap., kW 127.50
Fluid Flow Rate, L/s 6.90
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
NVL Page 32 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.13 AHU-G-2-4A,4B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

NVL Page 33 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 36932
Ent. Air DB/WB, °C 26.5/18.2
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 224.80
Sensible Clg. Cap., kW 174.00
Fluid Flow Rate, L/s 19.37
Fluid Pressure Drop, kPa

NVL Page 34 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.14 AHU-G-2-5A,5B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers

NVL Page 35 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Having a dimension between 1000mm and


1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 43121
Ent. Air DB/WB, °C 26.7/18.6
Lvg. Air DB/WB, °C 11.8/11.1

NVL Page 36 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Ent./Lvg. Fluid Temp., °C 6.7/12.3


Total Cooling Cap., kW 273.00
Sensible Clg. Cap., kW 202.50
Fluid Flow Rate, L/s 11.75
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.15 AHU-G-2-6A,6B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others

NVL Page 37 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

All casings, housings, plenums


and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 47072

NVL Page 38 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Ent. Air DB/WB, °C 26.6/18.3


Lvg. Air DB/WB, °C 11.7/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 281.40
Sensible Clg. Cap., kW 216.70
Fluid Flow Rate, L/s 12.12
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.16 AHU-G-2-7A,7B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:

NVL Page 39 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

External Static Pressure:


Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material

NVL Page 40 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Coolant
Actual Airflow, cmh 39789
Ent. Air DB/WB, °C 26.2/17.6
Lvg. Air DB/WB, °C 11.7/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 213.30
Sensible Clg. Cap., kW 178.80
Fluid Flow Rate, L/s 9.19
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.17 AHU-G-2-8A,8B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.

NVL Page 41 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material

NVL Page 42 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Tube Material
Header Material
Coolant
Actual Airflow, cmh 34673
Ent. Air DB/WB, °C 26.3/17.7
Lvg. Air DB/WB, °C 11.8/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 192.50
Sensible Clg. Cap., kW 157.90
Fluid Flow Rate, L/s 8.29
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.17 AHU-G-2-9A,9B
Manufacturer:
Origin:

NVL Page 43 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

ARI Standard or approved equivalent


Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row
Fin Density (FPI)
Circuit

NVL Page 44 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Face Area, sqm


Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 31793
Ent. Air DB/WB, °C 26.3/17.9
Lvg. Air DB/WB, °C 11.8/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 181.20
Sensible Clg. Cap., kW 145.70
Fluid Flow Rate, L/s 7.81
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.18 AHU-G-2-10A,10B
NVL Page 45 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.

Having a dimension between 1000mm and


1500mm shall be not less than 1.6mm thick
galvanised sheet metal.
In high pressure systems
Exceed 1500mm in any dimensions shall
be not less than 2.0mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive

Sound level

COIL
Coil Type
Row

NVL Page 46 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Fin Density (FPI)


Circuit
Face Area, sqm

NVL Page 47 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

Face Velocity, m/s


Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 40541
Ent. Air DB/WB, °C 26.2/17.6
Lvg. Air DB/WB, °C 11.8/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 218.10
Sensible Clg. Cap., kW 182.40
Fluid Flow Rate, L/s 9.40
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density

The unit shall be internally insulated with


50mm thick, 32 kg/m3 density fibreglass of
CASING INSULATION
thermal conductivity not more than 0.0350
W/m°K at a mean temperature of 24°C.

AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
3 Chiller water fan coil unit

NVL Page 48 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
Manufacturer:
Origin:
ARI Standards or approved equivalent
Standards:
standards.
Others
Coil
Type: copper tube aluminium fins
FAN
Type:
speed direct drive motor 3
DRAIN PANS
Material: Galvanised sheet steel
Insulation: Minimum 15mm thick
AIR FILTERS
Type: Washable or disposable
4 VRF
Manufacturer:
Origin:
The enables safe operation From 10% to 125% of the normal capacity.

Level difference without oil traps 50m


Minimum piping distance between
the condensing unit and the most 90m
remote fan coil unit
Refrigerant non-CFC
COP
OUTDOOR CONDENSING UNIT
compressor scroll or rotary type
Galvanized steel bowdlerized and finished
casing
with baked enamel
The condenser coil copper

Non-corrosive typed and painted to match


material the proposed condensing unit
color.

INDOOR UNIT
Galvanized steel bowdlerized and finished
casing
with baked enamel
The condenser coil copper
fan centrifugal forward curve type
VRF SYSTEM PERFORMANCE
Noise Level - Fan Coil Units
Up to 3.5 KW 42 dB(A)
Up to 5.2 KW 45 dB(A)
Up to 8.8 KW 49 dB(A)
Up to 14.5 KW 52 dB(A)
Up to 23.0 KW 55 dB(A)
Noise Level - Condensing Unit
Up to 3.5 Kw 46 dB(A)
Up to 5.2 Kw 52 dB(A)
Up to 8.8 Kw 54 dB(A)
Up to 14.5 Kw 56 dB(A)
Up to 23 Kw 59 dB(A)
Up to 30 Kw 61 dB(A)

NVL Page 49 of 206 03/23/2019


Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.

NVL Page 50 of 206 03/23/2019


Date: 15/12/2016
TECHNICAL DATA SHEET
NTERNATIONAL PASSENGER TERMINAL Rev: 00
INCL. FIRE FIGHTING WORKS

HVAC SYSTEM

CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Carrier Comply

USA Comply

QCVN 09:2013/BXD.
Air Conditioning and Refrigeration
Institute (ARI) Standard 550/590-
latest edition.
American Society of Heating,
Refrigerating, and Air
Conditioning Engineers
(ASHRAE). Comply
American Society of Mechanical
Engineers (ASME).
The regulation of refrigerants to
be limited & banned in Viet nam
to 2020 (No.47/2011/TTLT-BCT-
BTNMT, dated 31 December
2011)

Open-drive compressor will not Proposed by the supplier and


Deviation
be allowed maintaining technical
750.0 Tons Comply
400/3/50.0 Comply
430.5 kW Comply
0.5741 kW/Ton Comply
6.126 Comply

19XR-6669465LEH52 Comply
Starter - Unit Mounted, Wye-Delta Comply
R-134a Comply
Installed Comply
Installed Comply
Cooling Comply

114.6 L/s Comply


65 kpa Comply
12.2 Comply
6.7 Comply
Nozzle-in-Head, 1034 kPa Comply
2 Comply
D (Nozzles on Compressor End) Comply
Super E3 (SUPE3), .635 mm,
Comply
Copper
NVL Page 51 of 206 03/23/2019
CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Proposed by the supplier and


0.00176 Deviation
maintaining technical
599 Comply
0.10 oC Comply

465 Comply
21 Comply
0.94 Comply
0.97 Comply
44.15 oC Comply

3067 Kw Comply
147.60 Comply
58.8 Kpa Comply
31.0 Comply
36.0 Comply
Proposed by the supplier and
0.00440 Deviation
maintaining technical
0.28 oC Comply

11719 Kg Comply
13316 Kg Comply
727 Kg Comply

8 Comply
31 Comply

719.0 Comply
777 Comply
1683 Comply
4864 Comply
722 Comply
1600 Comply
903 Comply

5% Comply
21.68 oC Comply
-0.06 Comply
10% Comply
30.84 Comply
20.4 kPa Comply
16.0 kPa Comply

36.58 oC Comply
6.54 oC Comply
6.41 oC Comply
0.22 oC Comply
1.75 m/s Comply
1.87 m/s Comply

NVL Page 52 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Carrier Comply
USA Comply

ARI Standard Comply

39G1825(50mm) Comply
33079.00 Comply
850 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
77.17 Comply
14.36 Comply
850.00 Comply
529.20 Comply
0.00 Comply
1379.20 Comply
1501.00 Comply
1660.00 Comply
17.87 Comply
30.00 Comply
30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 97.2
dB(A)
Comply
Sound power level inlet 89.9
dB(A)

Chilled Water Comply


6.00 Comply

NVL Page 53 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

12 FPI Comply
FL Comply
3.70 Comply
2.48 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
33079 Comply
27.5/19.8 Comply
10.9/10.9 Comply
6.7/12.3 Comply
266.00 Comply
181.00 Comply
11.30 Comply
74.00 Comply
166.00 Comply
0.00 Comply
1881.00 Comply
2000.00 Comply
2600.00 Comply
3800.00 Comply

Std-Painted GI Comply

PU Foam Comply

Panel Filter + Bag Filter Comply


33079 m3/h Comply

G3(GI Steel Frame) Comply


113 Pa Comply
182 Pa Comply
250 Pa Comply
182 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


92 Pa Comply
171 Pa Comply
250 Pa Comply
171 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

NVL Page 54 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Carrier Comply
USA Comply

ARI Standard Comply

39G2125(50mm) Comply
37915 Comply
1150 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB710TM Comply
THF Comply
80.44 Comply
13.07 Comply
1150.00 Comply
493.60 Comply
0.00 Comply
1643.60 Comply
1745.00 Comply
1508.00 Comply
22.84 Comply
30.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 94.2
dB(A)
Comply
Sound power level inlet 87.0
dB(A)

Chilled Water Comply

NVL Page 55 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

5 Comply
14 FPI Comply
FL Comply
4.27 Comply
2.47 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
37915 Comply
25.8/17.5 Comply
11.2/10.9 Comply
6.7/12.3 Comply
216.00 Comply
184.00 Comply
9.20 Comply
26.00 Comply
153.00 Comply
0.04 Comply
2204 Comply
2300 Comply
2600 Comply
4100 Comply

Std-Painted GI Comply

PU Foam Comply

Panel Filter + Bag Filter Comply


37915 m3/h Comply

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
250 Pa Comply
172 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply

NVL Page 56 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G1825(50mm) Comply
33079 Comply
600 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
75.19 Comply
14.36 Comply
600.00 Comply
529.20 Comply
0.00 Comply
1129.20 Comply
1251.00 Comply
1568.00 Comply
15.29 Comply
22.00 Comply
25.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 96.2
dB(A)
Comply
Sound power level inlet 88.9
dB(A)

NVL Page 57 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Chilled Water Comply


6.00 Comply
12 FPI Comply
FL Comply
3.70 Comply
2.48 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
33079 Comply
27.5/19.8 Comply
10.9/10.9 Comply
6.7/12.3 Comply
266.00 Comply
181.00 Comply
11.30 Comply
74.00 Comply
166.00 Comply
0.00 Comply
1873 Comply
2000 Comply
2600 Comply
3800 Comply

Std-Painted GI Comply

PU Foam Comply

Panel Filter + Bag Filter Comply


33079 m3/h Comply

G3(GI Steel Frame) Comply


113 Pa Comply
182 Pa Comply
250 Pa Comply
182 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


92 Pa Comply
171 Pa Comply
250 Pa Comply
171 Pa Comply

NVL Page 58 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Magnehelic Gage With Plastic


Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G1825(50mm) Comply
34069 m3/h Comply
650 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
74.58 Comply
14.79 Comply
650.00 Comply
482.20 Comply
0.00 Comply
1132.20 Comply
1262.00 Comply
1590.00 Comply
16.01 Comply
22.00 Comply
25.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply

NVL Page 59 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Sound power level outlet 96.2


dB(A)
Comply
Sound power level inlet 88.9
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply
3.98 Comply
2.38 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
34069.00 Comply
27.4/19.7 Comply
11.5/11.5 Comply
6.7/12.3 Comply
255.00 Comply
178.00 Comply
10.80 Comply
39.00 Comply
154.00 Comply
0.00 Comply
1931 Comply
2200 Comply
2600 Comply
3800 Comply

Std-Painted GI Comply

PU Foam Comply

Panel Filter + Bag Filter Comply


34069 m3/h Comply

G3(GI Steel Frame) Comply


78 Pa Comply
164 Pa Comply
250 Pa Comply
164 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply
Comply
F5(GI Steel Frame) Comply
57 Pa Comply
154 Pa Comply
NVL Page 60 of 206 03/23/2019
CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

250 Pa Comply
154 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2025(50mm) Comply
34069 m3/h Comply
850 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
76.29 Comply
14.79 Comply
850.00 Comply
482.20 Comply
0.00 Comply
1332.20 Comply
1462.00 Comply
1664.00 Comply
18.13 Comply
30.00 Comply
30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply

NVL Page 61 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Fixed (1.5SF) Comply


Sound power level outlet 96.2
dB(A)
Comply
Sound power level inlet 88.9
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply
3.98 Comply
2.38 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
34069.00 Comply
27.4/19.7 Comply
11.5/11.5 Comply
6.7/12.3 Comply
255.00 Comply
178.00 Comply
10.80 Comply
39.00 Comply
154.00 Comply
0.00 Comply
1939 Comply
2200 Comply
2600 Comply
3800 Comply

Std-Painted GI Comply

PU Foam Comply

Panel Filter + Bag Filter Comply


34069 m3/h Comply

G3(GI Steel Frame) Comply


78 Pa Comply
164 Pa Comply
250 Pa Comply
164 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


57 Pa Comply
NVL Page 62 of 206 03/23/2019
CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

154 Pa Comply
250 Pa Comply
154 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2230(50mm) Comply
43650 m3/h Comply
1350 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB800XM Comply
THF Comply
81.96 Comply
11.98 Comply
1350.00 Comply
444.90 Comply
0.00 Comply
1794.90 Comply
1880.00 Comply
1345.00 Comply
27.81 Comply
37.00 Comply
50.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply

NVL Page 63 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

No Comply
Fixed (1.5SF) Comply
Sound power level outlet 96.2
dB(A)
Comply
Sound power level inlet 88.9
dB(A)

Chilled Water Comply


5.00 Comply
12 FPI Comply
FL Comply
5.39 Comply
2.25 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
43650 Comply
26.4/18.1 Comply
11.4/11.1 Comply
6.7/12.3 Comply
267.00 Comply
217.00 Comply
11.40 Comply
42.00 Comply
116.00 Comply
0.04 Comply
2628 Comply
2400 Comply
3100 Comply
4300 Comply

Std-Painted GI Comply

PU Foam Comply

Panel Filter + Bag Filter Comply


34069 m3/h Comply

G3(GI Steel Frame) Comply


78 Pa Comply
164 Pa Comply
250 Pa Comply
164 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply
Comply

NVL Page 64 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

F5(GI Steel Frame) Comply


57 Pa Comply
154 Pa Comply
250 Pa Comply
154 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G1825(50mm) Comply
32418 m3/h Comply
1000 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
78.23 Comply
14.07 Comply
1000.00 Comply
518.60 Comply
0.00 Comply
1518.60 Comply
1636.00 Comply
1696.00 Comply
18.83 Comply
30.00 Comply
30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply

NVL Page 65 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 97.3
dB(A)
Comply
Sound power level inlet 90.0
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply
3.70 Comply
2.43 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
32418 Comply
27/19.1 Comply
11.5/11.4 Comply
6.7/12.3 Comply
224.00 Comply
166.00 Comply
9.50 Comply
48.00 Comply
155.00 Comply
0.01 Comply
1861 Comply
2000 Comply
2600 Comply
3800 Comply

Std-Painted GI Comply

PU Foam Comply

Panel Filter + Bag Filter Comply


32418 m3/h Comply

G3(GI Steel Frame) Comply


113 Pa Comply
182 Pa Comply
250 Pa Comply
182 Pa Comply
Factory Supplied HVF filter Comply

NVL Page 66 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

50mm Comply

F5(GI Steel Frame) Comply


92 Pa Comply
171 Pa Comply
250 Pa Comply
171 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G1622(50mm) Comply
23454 m3/h Comply
1000 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB560TM Comply
THF Comply
79.40 Comply
12.77 Comply
1000.00 Comply
479.10 Comply
0.00 Comply
1479.10 Comply
1576.00 Comply
1824.00 Comply
12.93 Comply
18.50 Comply
20.00 Comply
TECO Comply

NVL Page 67 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 93.7
dB(A)
Comply
Sound power level inlet 86.5
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply
2.71 Comply
2.40 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
23454 Comply
26.6/18.4 Comply
11.5/11.3 Comply
6.7/12.3 Comply
147.00 Comply
117.00 Comply
6.20 Comply
25.00 Comply
151.00 Comply
0.03 Comply
1472 Comply
1800 Comply
2300 Comply
3500 Comply
Comply
Std-Painted GI Comply
Comply

PU Foam Comply

Panel Filter + Bag Filter Comply


23454 m3/h Comply

G3(GI Steel Frame) Comply


78 Pa Comply
164 Pa Comply
250 Pa Comply

NVL Page 68 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

164 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


57 Pa Comply
154 Pa Comply
250 Pa Comply
154 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2125(50mm) Comply
38570 m3/h Comply
800 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB800TM Comply
THF Comply
81.95 Comply
10.59 Comply
800.00 Comply
524.00 Comply
0.00 Comply
1324.00 Comply
1390.00 Comply
1164.00 Comply
18.18 Comply
30.00 Comply

NVL Page 69 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 94.3
dB(A)
Comply
Sound power level inlet 87.1
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply
4.27 Comply
2.51 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
38570.00 Comply
26.8/18.5 Comply
11.4/11.3 Comply
6.7/12.3 Comply
247.00 Comply
196.00 Comply
10.50 Comply
33.00 Comply
160.00 Comply
0.01 Comply
2219 Comply
2300 Comply
2600 Comply
4300 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Comply
Panel Filter + Bag Filter Comply
38570 m3/h Comply

G3(GI Steel Frame) Comply


113 Pa Comply
NVL Page 70 of 206 03/23/2019
CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

182 Pa Comply
250 Pa Comply
182 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


92 Pa Comply
171 Pa Comply
250 Pa Comply
171 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G1822(50mm) Comply
28283 m3/h Comply
800 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB560TM Comply
THF Comply
74.57 Comply
15.40 Comply
800.00 Comply
503.80 Comply
0.00 Comply
1303.80 Comply
1444.00 Comply
1905.00 Comply

NVL Page 71 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

15.22 Comply
22.00 Comply
25.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet
96.9dB(A)
Comply
Sound power level inlet 89.6
dB(A)

Chilled Water Comply


6 Comply
12 FPI Comply
FL Comply
3.20 Comply
2.45 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
28283.00 Comply
27.4/19.6 Comply
11.1/11 Comply
6.7/12.3 Comply
219.00 Comply
152.00 Comply
9.30 Comply
48.00 Comply
163.00 Comply
0.02 Comply
1619 Comply
2000 Comply
2300 Comply
3600 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Panel Filter + Bag Filter Comply


28283 m3/h Comply

NVL Page 72 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
250 Pa Comply
172 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G1825(50mm) Comply
32900 m3/h Comply
800 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
77.12 Comply
14.28 Comply
800.00 Comply
556.30 Comply
0.00 Comply
1356.30 Comply

NVL Page 73 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

1477.00 Comply
1648.00 Comply
17.50 Comply
30.00 Comply
30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 97.0
dB(A)
Comply
Sound power level inlet 89.7
dB(A)

Chilled Water Comply


6 Comply
14 FPI Comply
DB Comply
3.70 Comply
2.47 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
32900.00 Comply
27.6/19.7 Comply
11/11 Comply
6.7/12.3 Comply
257.00 Comply
180.00 Comply
11.00 Comply
38.00 Comply
193.00 Comply
0.00 Comply
1902 Comply
2000 Comply
2600 Comply
3800 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Comply
Panel Filter + Bag Filter Comply

NVL Page 74 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

28283 m3/h Comply

G3(GI Steel Frame) Comply


113 Pa Comply
182 Pa Comply
250 Pa Comply
182 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


92 Pa Comply
171 Pa Comply
250 Pa Comply
171 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G1824(50mm) Comply
29086 m3/h Comply
800 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
78.63 Comply

NVL Page 75 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

12.62 Comply
800.00 Comply
507.10 Comply
0.00 Comply
1307.10 Comply
1401.00 Comply
1554.00 Comply
14.40 Comply
18.50 Comply
25.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 94.5
dB(A)
Comply
Sound power level inlet 87.3
dB(A)

Chilled Water Comply


5 Comply
14 FPI Comply
FL Comply
3.53 Comply
2.29 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
29086.00 Comply
27.3/19.5 Comply
11.5/11.4 Comply
6.7/12.3 Comply
213.00 Comply
152.00 Comply
9.10 Comply
43.00 Comply
144.00 Comply
0.02 Comply
1806 Comply
2000 Comply
2500 Comply
3800 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

NVL Page 76 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

PU Foam Comply

Panel Filter + Bag Filter Comply


29086 m3/h Comply
Comply
G3(GI Steel Frame) Comply
113 Pa Comply
182 Pa Comply
250 Pa Comply
182 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


92 Pa Comply
171 Pa Comply
250 Pa Comply
171 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2230(50mm) Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB800XM Comply

NVL Page 77 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

THF Comply
81.00 Comply
13.14 Comply
1000.00 Comply
474.60 Comply
0.00 Comply
1474.60 Comply
1577.00 Comply
1296.00 Comply
25.88 Comply
37.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 97.8
dB(A)
Comply
Sound power level inlet 90.6
dB(A)

Chilled Water Comply


5.00 Comply
12 FPI Comply
FL Comply
5.39 Comply
2.47 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
47864.00 Comply
26.6/18.2 Comply
11.7/11.4 Comply
6.7/12.3 Comply
289.00 Comply
236.00 Comply
12.30 Comply
48.00 Comply
134.00 Comply
0.04 Comply
2575 Comply
2400 Comply
3100 Comply
4300 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

NVL Page 78 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

PU Foam Comply

Panel Filter + Bag Filter Comply


29086 m3/h Comply

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
250 Pa Comply
172 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply
Comply
F5(GI Steel Frame) Comply
66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2226(50mm) Comply
40968 m3/h Comply
1000 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply

NVL Page 79 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Kruger Comply
BDB710TM Comply
THF Comply
78.72 Comply
14.12 Comply
1000.00 Comply
497.60 Comply
0.00 Comply
1497.60 Comply
1616.00 Comply
1507.00 Comply
23.36 Comply
30.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 95.3
dB(A)
Comply
Sound power level inlet 88.0
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply
4.61 Comply
2.47 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
40968.00 Comply
26.8/18.7 Comply
11.4/11.3 Comply
6.7/12.3 Comply
271.00 Comply
208.00 Comply
11.50 Comply
38.00 Comply
157.00 Comply
0.01 Comply
2293 Comply
2400 Comply
2700 Comply
4100 Comply

Std-Painted GI Comply
NVL Page 80 of 206 03/23/2019
CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

25mm thickness, 32 kg/m3


Comply
density

PU Foam Comply

Panel Filter + Bag Filter Comply


40968 m3/h Comply

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
250 Pa Comply
172 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G1822(50mm) Comply
28388 m3/h Comply
1000 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

NVL Page 81 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
79.36 Comply
12.32 Comply
1000.00 Comply
495.40 Comply
0.00 Comply
1495.40 Comply
1585.00 Comply
1612.00 Comply
15.75 Comply
22.00 Comply
25.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 94.7
dB(A)
Comply
Sound power level inlet 87.4
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply
3.20 Comply
2.46 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
28388.00 Comply
26.4/18 Comply
11.5/11.2 Comply
6.7/12.3 Comply
168.00 Comply
140.00 Comply
7.20 Comply
26.00 Comply
154.00 Comply
0.04 Comply
1736 Comply
2000 Comply
2300 Comply
3800 Comply
NVL Page 82 of 206 03/23/2019
CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Panel Filter + Bag Filter Comply


28388 m3/h Comply

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
250 Pa Comply
172 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2125(50mm) Comply
36932 m3/h Comply
1000 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

NVL Page 83 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB710TM Comply
THF Comply
80.17 Comply
12.73 Comply
1000.00 Comply
491.70 Comply
0.00 Comply
1491.70 Comply
1588.00 Comply
1448.00 Comply
20.31 Comply
30.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 93.2
dB(A)
Comply
Sound power level inlet 85.9
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply
4.27 Comply
2.40 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
36932.00 Comply
26.5/18.2 Comply
11.3/11.1 Comply
6.7/12.3 Comply
231.00 Comply
186.00 Comply
9.80 Comply
29.00 Comply

NVL Page 84 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

151.00 Comply
0.03 Comply
2204 Comply
2300 Comply
2600 Comply
4100 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Panel Filter + Bag Filter Comply


36932 m3/h Comply

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
250 Pa Comply
172 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2230(50mm) Comply
43121 m3/h Comply
1000 Pa Comply

NVL Page 85 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB800XM Comply
THF Comply
81.74 Comply
11.84 Comply
1000.00 Comply
443.00 Comply
0.00 Comply
1443.00 Comply
1526.00 Comply
1241.00 Comply
22.36 Comply
30.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 96.2
dB(A)
Comply
Sound power level inlet 89.0
dB(A)

Chilled Water Comply


5.00 Comply
12 FPI Comply
FL Comply
5.39 Comply
2.22 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
43121.00 Comply
26.7/18.6 Comply
11.5/11.3 Comply

NVL Page 86 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

6.7/12.3 Comply
280.00 Comply
216.00 Comply
11.90 Comply
45.00 Comply
114.00 Comply
0.03 Comply
2575 Comply
2400 Comply
3100 Comply
4300 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Panel Filter + Bag Filter Comply


43121 m3/h Comply

G3(GI Steel Frame) Comply


78 Pa Comply
164 Pa Comply
250 Pa Comply
164 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


57 Pa Comply
154 Pa Comply
250 Pa Comply
154 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2230(50mm) Comply
47072 m3/h Comply
1000 Pa Comply

NVL Page 87 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB800XM Comply
THF Comply
81.16 Comply
12.92 Comply
1000.00 Comply
471.20 Comply
0.00 Comply
1471.20 Comply
1570.00 Comply
1287.00 Comply
25.29 Comply
37.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 97.5
dB(A)
Comply
Sound power level inlet 90.3
dB(A)

Chilled Water Comply


5.00 Comply
12 FPI Comply
FL Comply
5.39 Comply
2.42 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
47072.00 Comply

NVL Page 88 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

26.6/18.3 Comply
11.7/11.4 Comply
6.7/12.3 Comply
289.00 Comply
233.00 Comply
12.30 Comply
48.00 Comply
130.00 Comply
0.04 Comply
2575 Comply
2400 Comply
3100 Comply
4300 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Panel Filter + Bag Filter Comply


47072 m3/h Comply

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
172 Pa Comply
164 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

39G2226(50mm) Comply
39789 m3/h Comply

NVL Page 89 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

900 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
FDA710TM Comply
THF Comply
65.02 Comply
13.71 Comply
900.00 Comply
451.50 Comply
0.00 Comply
1351.50 Comply
1463.00 Comply
848.00 Comply
24.87 Comply
37.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 91.8
dB(A)
Comply
Sound power level inlet 84.7
dB(A)

Chilled Water Comply


5.00 Comply
12 FPI Comply
FL Comply
4.61 Comply
2.40 Comply
Alum Comply
Copper Comply
Steel Comply

NVL Page 90 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Fresh water Comply


39789.00 Comply
26.2/17.6 Comply
11.6/11.2 Comply
6.7/12.3 Comply
221.00 Comply
192.00 Comply
9.40 Comply
26.00 Comply
123.00 Comply
0.05 Comply
2236 Comply
2400 Comply
2700 Comply
4100 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Comply
Panel Filter + Bag Filter Comply
39789 m3/h Comply

G3(GI Steel Frame) Comply


78 Pa Comply
164 Pa Comply
250 Pa Comply
164 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


57 Pa Comply
154 Pa Comply
250 Pa Comply
154 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

ARI Standard Comply

NVL Page 91 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

39G2025(50mm) Comply
34673 m3/h Comply
1000 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB710TM Comply
THF Comply
80.78 Comply
11.95 Comply
1000.00 Comply
466.60 Comply
0.00 Comply
1466.60 Comply
1551.00 Comply
1408.00 Comply
18.49 Comply
30.00 Comply
30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 92.4
dB(A)
Comply
Sound power level inlet 85.1
dB(A)

Chilled Water Comply


5.00 Comply
12 FPI Comply
FL Comply
3.98 Comply
2.42 Comply
Alum Comply

NVL Page 92 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Copper Comply
Steel Comply
Fresh water Comply
34673.00 Comply
26.3/17.7 Comply
11.7/11.3 Comply
6.7/12.3 Comply
194.00 Comply
167.00 Comply
8.20 Comply
23.00 Comply
126.00 Comply
0.05 Comply
2023 Comply
2200 Comply
2600 Comply
3900 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Panel Filter + Bag Filter Comply


34673 m3/h Comply

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
250 Pa Comply
172 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

Carrier Comply
USA Comply

NVL Page 93 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

ARI Standard Comply

39G1824(50mm) Comply
31793 m3/h Comply
1000 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB630TM Comply
THF Comply
78.51 Comply
13.80 Comply
1000.00 Comply
530.00 Comply
0.00 Comply
1530.00 Comply
1643.00 Comply
1688.00 Comply
18.48 Comply
30.00 Comply
30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 96.9
dB(A)
Comply
Sound power level inlet 89.6
dB(A)

Chilled Water Comply


5.00 Comply
14 FPI Comply
FL Comply

NVL Page 94 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

3.53 Comply
2.50 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
31793.00 Comply
26.3/17.9 Comply
11.3/11.1 Comply
6.7/12.3 Comply
189.00 Comply
157.00 Comply
8.00 Comply
34.00 Comply
158.00 Comply
0.03 Comply
1814 Comply
2000 Comply
2500 Comply
3800 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Panel Filter + Bag Filter Comply


31793 m3/h Comply

G3(GI Steel Frame) Comply


123 Pa Comply
189 Pa Comply
250 Pa Comply
186 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


99 Pa Comply
174 Pa Comply
250 Pa Comply
174 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

NVL Page 95 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Carrier Comply
USA Comply

ARI Standard Comply

39G2226(50mm) Comply
40541 m3/h Comply
900 Pa Comply

Proposed by the supplier and


0.50 Deviation
maintaining technical

Proposed by the supplier and


0.50 Deviation
maintaining technical

Backward Curve Comply


Kruger Comply
BDB710TM Comply
THF Comply
78.14 Comply
13.97 Comply
900.00 Comply
467.60 Comply
0.00 Comply
1367.60 Comply
1483.00 Comply
1461.00 Comply
21.38 Comply
30.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 94.9
dB(A)
Comply
Sound power level inlet 87.7
dB(A)

Chilled Water Comply


5.00 Comply

NVL Page 96 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

12 FPI Comply
FL Comply
4.61 Comply

NVL Page 97 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

2.44 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
40541.00 Comply
26.2/17.6 Comply
11.7/11.3 Comply
6.7/12.3 Comply
224.00 Comply
195.00 Comply
9.60 Comply
27.00 Comply
127.00 Comply
0.05 Comply
2273 Comply
2400 Comply
2700 Comply
4100 Comply

Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density

PU Foam Comply

Comply
Panel Filter + Bag Filter Comply
40541 m3/h Comply

G3(GI Steel Frame) Comply


94 Pa Comply
172 Pa Comply
250 Pa Comply
172 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply

F5(GI Steel Frame) Comply


66 Pa Comply
158 Pa Comply
250 Pa Comply
158 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply

NVL Page 98 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Carrier Comply
Malaysia Comply
ARI Standards Comply

copper tube aluminium fins Comply


Comply
Centrifugal forward curved blades Comply
3 Comply

Galvanised sheet steel Comply


15mm thick Comply

Washable / Throwaway Comply

Daikin Comply
Thai Lan Comply
50% - 200% Comply
Comply
50m Comply

90m Comply

R410A Comply
3.94 Comply

scroll type Comply


Galvanized steel bowdlerized and
Comply
finished with baked enamel
copper Comply
Non-corrosive typed and painted
to match the proposed
Comply
condensing unit
color.

Galvanized steel bowdlerized and


Comply
finished with baked enamel
copper Comply
centrifugal forward curve type Comply

30 dB(A) Comply
31 dB(A) Comply
38 dB(A) Comply
45 dB(A) Comply
48 dB(A) Comply

38 dB(A) Comply
43 dB(A) Comply
50 dB(A) Comply
53 dB(A) Comply
57 dB(A) Comply
58 dB(A) Comply

NVL Page 99 of 206 03/23/2019


CONTRACTOR OFFER COMPLY/ DEVIATION REMARK

Comply

NVL Page 100 of 206 03/23/2019


BẢNG ĐÁP ỨN
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gi

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
COOLING TOWER

Manufacturer:
Origin:
Models:
Type
Thermal capacity

Energy efficiency
requirements:

Quality Assurance

Warranty

HVAC Page 101 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

Seismic Certification

Wind Certification

Corosion resistant
construction

Coil section

Cold water basin:

Casing Panels

HVAC Page 102 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

Spray water pump(s)

Water distribution
system

Fill and drift liminators

Combined inlet shields

Fan(s)

HVAC Page 103 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

Fan motor

Plenum access

Noise level

External platform with


ladder

Internal walkway for dual


air inlet

Internal platform

Motor removal system

HVAC Page 104 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

Excutions

HVAC Page 105 of 206 TECHGEL


BẢNG ĐÁP ỨNG KỸ THUẬT CỦA THIẾT BỊ VẬT TƯ
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

Poocheon, Baltimore Aircoil, Marley, Kuken or equivalent


USA, Japan, Korea

Closed Type with Plume Abatement


1170 HRT

The closed circuit cooling tower shall be warranted by the


manufacture to have capacity to cool minimum 190.6 l/s of
water from 370C to 320C at design conditions.

Coil pressure drop shall not exceed 100kPa

The performance shall be certified by the Cooling


Technology Institute in accordance with CTI Certification
Standard STD-201 or approved
equivalent type, lacking such certification, a field acceptance
test shall be conducted within the warranty period in
accordance with CTI Acceptance Test Code ATC-105, by the
Cooling Technology Institute, or other qualified independent
third party testing agency

Manufacturers' performance guarantees or performance


bonds without CTI Certification shall not be accepted

The closed circuit cooling tower(s) shall comply with the


energy efficiency requirements of ASHRAE Standard 90.1.

The closed circuit cooling tower manufacturer shall have a


Management System certified by an accredited registrar as
complying with the requirements of ISO- 9001 to ensure
consistent quality of products and services.

Unless otherwise noted, the manufacturer's standard


equipment warranty shall be for a period of not less than one
year from date of successful handing over. In addition, the
manufacturer shall warrant the rotating mechanical
equipment, including fans, fan motors, fan shafts, bearings,
sheaves and associated supports for not less than five 5
years from date of testing & commissioning. An additional two
years of warranty, for a total of seven 7 years, shall be
provided for fan motor(s) when space heaters are fieldwired at
time of initial installation.

HVAC Page 106 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

The induced draft counter flow closed circuit cooling tower


unit shall be designed, and certified in accordance with the
2015 IBC and ASCE/SEI 7-05, JCI or KARSE Certification
The unit shall be suitable for applications with Design Spectral
Acceleration at Short Period (SDS) for z/h = 1.0 up to 0.0689
g with a Component Importance Factor (lp) of 1.0 and 1.5.
The unit shall be certified by the manufacturer as maintaining
closed-circuit process fluid containment following an
earthquake

The certification shall be based on analysis and verified by


full-scale, shake table testing, and shall be reviewed and
approved by a licensed professional engineer independent of
the manufacturer. Units Comply not provided with evidence of
compliance shall not be an acceptable alternative

The closed circuit cooling tower unit shall be designed in


accordance with the 2015 IBC
and ASCE/SEI 7-05 or approved equivalent. The unit shall be
suitable for applications with a design horizontal wind
pressure up to 1.55 kN/m2. Design wind pressure shall be
calculated in accordance with Sections 6.5.15 and 6.5.15.1,
as applicable, of ASCE/SEI 7-05.

A concurrent uplift pressure equivalent to the horizontal


pressure shall be considered in the unit design. Unit
resistance shall be determined in accordance with
the material design specifications referenced in the 2015 IBC,
and shall be reviewed and approved by a licensed
professional engineer independent of the manufacturer.

Unless otherwise noted in this specification, all steel panels


and structural elements shall be constructed from heavy-
gauge, Z700 hot-dip galvanized steel, with cut edges given a
protective coat of zinc-rich compound
The heat transfer section of the closed circuit cooling tower
shall be encased with removable heavy-gauge galvanized
steel panels. The coil shall be constructed of the phosphorus -
deoxidized copper seamless tubes, be pneumatically tested
at minimum 2685 kPa. The coil shall be designed for free
drainage of fluid and shall be ASME B31.5 compliant.
Maximum allowable working pressure shall be 2171 kPa.

The coil sizing and arrangement shall be able to eliminate


forming of water plume above cooling tower during year-round
operation. This is contractor’s responsibility to ensure the
plume abatement function is integrated.

The cold water basin shall be constructed of heavy-gauge


hot-dip galvanized steel, Standard Z700.
Casing panels shall be constructed of steel matching the
structure defined in section 2.1.

HVAC Page 107 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

The closed circuit cooling tower shall include an appropriate


number of close coupled, bronze-fitted centrifugal pump and
motor assemblies equipped with mechanical seal, mounted in
the basin and piped from the suction connection to the water
distribution system.

The pump motor(s) shall be the totally enclosed fan cooled


(TEFC) type, premium efficiency suitable for 400 volts, 3
phase, and 50 hertz electrical service. The
system shall include a metering valve and bleed line to control
the bleed rate from the pump discharge to the overflow
connection.

Water shall be distributed evenly over the coil at a flow rate


sufficient to ensure complete wetting of the coil at all times.
Large diameter, non-clog, 360° plastic distribution nozzles
shall utilize a two stage diffusion pattern to provide
overlapping, umbrella spray patterns that create multiple
intersection points with adjacent nozzles.

The branches and spray nozzles shall be held in place by


snap-in rubber grommets, allowing quick removal of
individual nozzles or complete branches for cleaning or
flushing.

The fill and integral drift eliminators shall be formed from self-
extinguishing (as per ASTM-568) polyvinyl chloride (PVC)
having a flame spread rating of 5 per ASTM E84
and shall be impervious to rot, decay, fungus and biological
attack.

The fill shall be manufactured and performance tested by the


closed circuit cooling tower manufacturer to provide single
source responsibility and assure control of the final product. A
separate set of drift eliminators shall be removable in easily
handled sections for quick access to
the coil. Eliminators shall have a minimum of three changes in
air direction.

The combined inlet shields shall be UV resistant PVC,


installed on the air inlet face to minimize air resistance,
prevent water splash out, minimized sunlight exposure to
reduce the potential for algae growth in the cold water basin.

Fan(s) shall be heavy-duty, axial flow, with aluminum alloy


blades. Air shall discharge through a fan cylinder designed for
streamlined air entry and minimum fan blade tip clearance for
maximum fan efficiency.
Fan(s) and shaft(s) shall be supported by heavyduty, self-
aligning, grease-packed ball bearings with moisture-proof
seals and integral slinger rings, designed for minimum L10 life
of 80,000 hours. Fan(s) shall be drive by a one-piece, multi-
groove neoprene/polyester belt designed specifically for
evaporative cooling service. Fan and motor sheave(s) shall be
fabricated from cast aluminum.

HVAC Page 108 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

Fan motor(s) shall be totally enclosed air over (TEAO) or


Totally Enclosed Fan Cooled (TEFC), reversible, squirrel
cage, ball bearing type designed specifically for evaporative
cooling duty on 400 volt/ 50 hertz/ 3 phases electrical service.
The motor shall be furnished with special moisture protection
on windings, shafts, and bearings. Fan motors shall be
premium efficient/inverter duty type designed per NEMA
Standard MG1, Section
IV, Part 31. It shall be suitable to operate with VFD for
variable speed operation.

A large, hinged access door shall be provided on each end


wall for access to the coil, drift eliminators, and fan plenum
section. The water make-up valve, float ball, and
suction strainer shall be easily accessible. On single side air
inlet units, the access door shall open to a standard internal
walkway

To maintain the quality of the local environment, the maximum


noise level (dB(A)) measured 15 meters from the closed
circuit cooling tower operating at full fan speed shall not
exceed 65 dB(A). The contractor shall furnish necessary
sound traps/ attenuators/ baffles and water silencers if the
proposed cooling tower cannot meet above noise level
criteria. These additional components shall not compromise
the thermal
performance of cooling tower.

A pre-assembled galvanized steel platform and aluminum


ladder to grade shall be provided to access the distribution
system. The maintenance personal shall be able to inspect
the distribution system while the unit is operational. All
working surfaces shall be able to withstand 90.5 kg
concentrated load.

An internal walkway shall be provided in the plenum section to


provide for inspection and maintenance. All working surfaces
shall be able to withstand 244 g/m2 live load or 90.5 kg
concentrated load. Other components of the cooling tower,
i.e. basin and fill/drift eliminators, shall not be considered an
internal working surface.

An internal platform shall be provided in the plenum section to


provide for inspection and maintenance. All working surfaces
shall be able to withstand 90.5 kg concentrated load. Other
components of the cooling tower, i.e. basin floor and fill/drift
eliminators, shall not
be considered an internal working surface.

The unit shall be equipped with a mechanical equipment


removal davit. The motor shall be lowered from the
mechanical equipment supports down to grade. Davit shall
attach to the unit without the need for tools. If tools are
required for davit installation or removal, contractor shall
provide (1 ) davit for each motor provided.

HVAC Page 109 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

The cooling towers must be guaranteed to perform in


accordance with the conditions specified. The contractor shall
provide performance curves with appropriate correction factor
charts to substantiate the tower's duty. As only certified towers
will be considered,
the contractor shall furnish the CTI certificates of proposed
cooling towers. The contractor shall also state the amount of
water make-up required to off-set against evaporation loss,
carry-over volume and bleed under the conditions specified.

All cooling towers shall be factory tested. The contractor shall


submit the factory test certificates priority to the shipment. It
shall be installed, tested and commissioned by the cooling
tower manufacturer or their certified approved
representatives. All test records and results including other
recommendation shall be submitted to Employer for the
records. It shall be included in final O&M submission.

HVAC Page 110 of 206 TECHGEL


Date: 16/081/2017
Ỹ THUẬT CỦA THIẾT BỊ VẬT TƯ CHÍNH
Rev: 00
thoát nước - Nhà ga hành khách

VAC SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

Poocheon comply
Korea comply
4PIC-3575W
Closed Type with Plume Abatement comply
1200RT Comply

The closed circuit cooling tower shall be warranted by the


manufacture to have capacity to cool minimum 190.6 l/s of Comply
water from 370C to 320C at design conditions.

Coil pressure drop is 90kPa Comply

CTI Member Certificate


Comply
KARSE Certificat

Comply

The closed circuit cooling tower(s) shall comply with the


Comply
energy efficiency requirements of ASHRAE Standard 90.1.

The closed circuit cooling tower manufacturer shall have a


Management System certified by an accredited registrar as
Comply
complying with the requirements of ISO- 9001 to ensure
consistent quality of products and services.

Equipment warranty: 02 years


Not comply: Warranty of fans, fan motors, fan shafts,
bearings, sheaves and associated supports: 02 years

Deviation

HVAC Page 111 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
The induced draft counter flow closed circuit cooling tower
unit shall be designed, and certified in accordance with the
2015 IBC and ASCE/SEI 7-05, JCI or KARSE Certification
The unit shall be suitable for applications with Design Spectral
Acceleration at Short Period (SDS) for z/h = 1.0 up to 0.0689
g with a Component Importance Factor (lp) of 1.0 and 1.5. Comply
The unit shall be certified by the manufacturer as maintaining
closed-circuit process fluid containment following an
earthquake

The certification shall be based on analysis and verified by


full-scale, shake table testing, and shall be reviewed and
approved by a licensed professional engineer independent of
the manufacturer. Units Comply not provided with evidence of Comply
compliance shall not be an acceptable alternative

The closed circuit cooling tower unit shall be designed in


accordance with the 2015 IBC
and ASCE/SEI 7-05 or approved equivalent. The unit shall be
suitable for applications with a design horizontal wind
pressure up to 1.55 kN/m2. Design wind pressure shall be Comply
calculated in accordance with Sections 6.5.15 and 6.5.15.1,
as applicable, of ASCE/SEI 7-05.

A concurrent uplift pressure equivalent to the horizontal


pressure shall be considered in the unit design. Unit
resistance shall be determined in accordance with
the material design specifications referenced in the 2015 IBC,
and shall be reviewed and approved by a licensed
professional engineer independent of the manufacturer.

POSMAC galvanized Steel Stardard for better


corrosion resistant
Comply Better

The heat transfer section of the closed circuit cooling tower


shall be encased with removable heavy-gauge galvanized
steel panels. The coil shall be constructed of the phosphorus -
deoxidized copper seamless tubes, be pneumatically tested
at minimum 2685 kPa. The coil shall be designed for free Comply
drainage of fluid and shall be ASME B31.5 compliant.
Maximum allowable working pressure shall be 2171 kPa.

The coil sizing and arrangement shall be able to eliminate


forming of water plume above cooling tower during year-round
operation. This is contractor’s responsibility to ensure the Comply
plume abatement function is integrated.

POSMAC galvanized Steel Stardard for better


Comply Better
corrosion resistant
POSMAC galvanized Steel Stardard for better
Comply Better
corrosion resistant

HVAC Page 112 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
The closed circuit cooling tower shall include an appropriate
number of close coupled, bronze-fitted centrifugal pump and
motor assemblies equipped with mechanical seal, mounted in Comply
the basin and piped from the suction connection to the water
distribution system.

The pump motor(s) shall be the totally enclosed fan cooled


(TEFC) type, premium efficiency suitable for 400 volts, 3
phase, and 50 hertz electrical service. The
system shall include a metering valve and bleed line to control
the bleed rate from the pump discharge to the overflow
connection.

Water shall be distributed evenly over the coil at a flow rate


sufficient to ensure complete wetting of the coil at all times.
Large diameter, non-clog, 360° plastic distribution nozzles
shall utilize a two stage diffusion pattern to provide Comply
overlapping, umbrella spray patterns that create multiple
intersection points with adjacent nozzles.

The branches and spray nozzles shall be held in place by


snap-in rubber grommets, allowing quick removal of
individual nozzles or complete branches for cleaning or Comply
flushing.

The fill and integral drift eliminators shall be formed from self-
extinguishing (as per ASTM-568) polyvinyl chloride (PVC)
having a flame spread rating of 5 per ASTM E84
and shall be impervious to rot, decay, fungus and biological Comply
attack.

The fill shall be manufactured and performance tested by the


closed circuit cooling tower manufacturer to provide single
source responsibility and assure control of the final product. A
separate set of drift eliminators shall be removable in easily
handled sections for quick access to Comply
the coil. Eliminators shall have a minimum of three changes in
air direction.

The combined inlet shields shall be UV resistant PVC,


installed on the air inlet face to minimize air resistance,
prevent water splash out, minimized sunlight exposure to Comply
reduce the potential for algae growth in the cold water basin.

Fan(s) shall be heavy-duty, axial flow, with aluminum alloy


blades. Air shall discharge through a fan cylinder designed for
streamlined air entry and minimum fan blade tip clearance for Comply
maximum fan efficiency.
Fan(s) and shaft(s) shall be supported by heavyduty, self-
aligning, grease-packed ball bearings with moisture-proof
seals and integral slinger rings, designed for minimum L10 life
of 80,000 hours. Fan(s) shall be drive by a one-piece, multi-
groove neoprene/polyester belt designed specifically for Comply
evaporative cooling service. Fan and motor sheave(s) shall be
fabricated from cast aluminum.

HVAC Page 113 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Fan motor(s) shall be totally enclosed air over (TEAO) or
Totally Enclosed Fan Cooled (TEFC), reversible, squirrel
cage, ball bearing type designed specifically for evaporative
cooling duty on 400 volt/ 50 hertz/ 3 phases electrical service.
The motor shall be furnished with special moisture protection
on windings, shafts, and bearings. Fan motors shall be Comply
premium efficient/inverter duty type designed per NEMA
Standard MG1, Section
IV, Part 31. It shall be suitable to operate with VFD for
variable speed operation.

A large, hinged access door shall be provided on each end


wall for access to the coil, drift eliminators, and fan plenum
section. The water make-up valve, float ball, and suction
strainer shall be easily accessible. On single side air inlet Comply
units, the access door shall open to a standard internal
walkway

To maintain the quality of the local environment, the maximum


noise level (dB(A)) measured 15 meters from the closed
circuit cooling tower operating at full fan speed shall not
exceed 65 dB(A). The contractor shall furnish necessary
sound traps/ attenuators/ baffles and water silencers if the
proposed cooling tower cannot meet above noise level Comply
criteria. These additional components shall not compromise
the thermal
performance of cooling tower.

A pre-assembled galvanized steel platform and aluminum


ladder to grade shall be provided to access the distribution
system. The maintenance personal shall be able to inspect
the distribution system while the unit is operational. All Comply
working surfaces shall be able to withstand 90.5 kg
concentrated load.

An internal walkway shall be provided in the plenum section to


provide for inspection and maintenance. All working surfaces
shall be able to withstand 244 g/m2 live load or 90.5 kg
concentrated load. Other components of the cooling tower, Comply
i.e. basin and fill/drift eliminators, shall not be considered an
internal working surface.

An internal platform shall be provided in the plenum section to


provide for inspection and maintenance. All working surfaces
shall be able to withstand 90.5 kg concentrated load. Other
components of the cooling tower, i.e. basin floor and fill/drift Comply
eliminators, shall not
be considered an internal working surface.

The unit shall be equipped with a mechanical equipment


removal davit. The motor shall be lowered from the
mechanical equipment supports down to grade. Davit shall
attach to the unit without the need for tools. If tools are Comply
required for davit installation or removal, contractor shall
provide (1 ) davit for each motor provided.

HVAC Page 114 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
The cooling towers must be guaranteed to perform in
accordance with the conditions specified. The contractor shall
provide performance curves with appropriate correction factor
charts to substantiate the tower's duty. As only certified towers
will be considered,
the contractor shall furnish the CTI certificates of proposed Comply
cooling towers. The contractor shall also state the amount of
water make-up required to off-set against evaporation loss,
carry-over volume and bleed under the conditions specified.

All cooling towers shall be factory tested. The contractor shall


submit the factory test certificates priority to the shipment. It
shall be installed, tested and commissioned by the cooling
tower manufacturer or their certified approved
representatives. All test records and results including other Comply
recommendation shall be submitted to Employer for the
records. It shall be included in final O&M submission.

HVAC Page 115 of 206 TECHGEL


BẢNG ĐÁP ỨN
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gi

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
AHU
Manufacturer:
Origin:
Type
GENERAL
Standard

Components

HOUSING

HVAC Page 116 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
ACCESS
DOORS/PANELS

CENTRIFUGAL FANS

COOLING COILS

HVAC Page 117 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

DRAIN PANS

CASING INSULATION

AIR FILTERS

HVAC Page 118 of 206 TECHGEL


BẢNG ĐÁP ỨNG KỸ THUẬT CỦA THIẾT BỊ VẬT TƯ
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

Trane, Carrier, York or equivalent


Malaysia, Thailand
Air handling unit

All air handling units shall be certified in accordance with ARI


Standard or approved equivalent standard by an independent
testing laboratory
The air handling unit shall include, but not be limited to, the
following components:
Sheet metal housing (coated with baked enamel finish to
BS3830 or approved equivalent standard)
Fans, drives and twin motors
Variable control devices
Cooling coils
Insulation - acoustic as well as thermal
Drain pans and drain piping

Air filters
Vibration isolators and flexible connections
Supports and brackets
Local control panels and DDC control panels
Air handling unit shall have statically and dynamically
balanced extended shafts complete with pulleys
The housing shall have adequate strength and rigidity under
all operating conditions. The units shall comprise a structural
frame with panels bolted onto the structural frame, and with
neoprene rubber gaskets between frames
The casing panels shall be constructed such that they shall
comprise of two layers of galvanised metal sheet sandwiching
the insulation in-between.
All casings, housings, plenums and chambers in low and
medium pressure systems, having a dimensions between
1000mm and 1500mm, shall not be less than 1.3mm thick
galvanised sheet metal.
All casings, housings, plenums and chambers in low and
medium pressure systems which exceed 1500mm in any
dimensions shall be not less than 1.6mm thick.
All casings, housings, plenums and chambers in high
pressure systems, having a dimensions between 1000mm
and 1500mm shall be not less than 1.6mm
thick.
All casings, housings, plenums and chambers in high
pressure systems which exceed 1500mm in any dimensions
shall be not less than 2.0mm.

HVAC Page 119 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

Access doors providing entry to interior of an air-handling unit


casing shall open against air pressure and shall be secured
by two or more heavy chromium
plated bar linked to refrigerator door type catches with internal
and external handles. Adequate stiffenings in metal partitions
shall be provided for securing
hinges. Gaskets around doors shall be refrigerator type and
shall be mechanically secured in position. Such access doors
shall be 500mm wide and 1500mm high or as high as the
casings permit.

Fans shall be double width, double inlet, multi-blade


centrifugal type. In units furnished with multiple fans, an
adjustable outlet damper shall be installed on each fan to
ensure stable operation of the parallel fans.
Fans for constant air volume system air handling units shall
have forward curved fan blades
All fans shall be furnished with forward curved impellers. In
units furnished with multiple fans, an adjustable outlet damper
shall be installed on each fan to ensure stable operation of
the parallel fans.
The fan section shall be manufactured of heavy gauge steel
angle members securely bolted and braced with galvanised
steel panels which shall be easily removable. Fan wheels and
scrolls shall be of galvanised steel.
Each fan shall be driven from a Vee-belt drive rated at not
less than 150% of actual full load capacity and having a
minimum of two belts.
Drives shall include steel sheaves sized to produce the fan
speed required to deliver the specified air quantity. Perforated
metal or 3 mm x 12 mm wire mesh belt guard to protect belts
and pulleys shall be provided with accessible facilities for belt
adjustment.
Fan shafts shall be keyed to the mating pulleys. Bearings
shall be self-aligned ball type selected with a nominal life
factory of 300,000 hours and shall be grease lubricated and
equipped with grease escape valve to permit replacement of
lubricant without dismantling the bearing housing.

Provision of 40mm diameter holes in belt guard, opposite


each fan and motor axle, for insertion of a tachometer shall be
made. The tachometer, to be
supplied by the contractor, must be capable of reading all the
fan speeds of each AHU
Fans shall be statically and dynamically balanced and fan
shafts shall not pass through their first critical speed in
achieving the rated rpm.
The fan and motor assembly shall be mounted on a common
framework with factory supplied spring anti-vibration
mountings. The fan discharge shall be
isolated from the casing by a flexible connection.
Motor power shall be not less than 1.2 times of fan brake
horsepower (BHP) at the selection point.
Cooling coils shall be of the cartridge type mounted on
aluminium slide rails for easy removability.

HVAC Page 120 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

Cooling coils shall have performance certified in accordance


with ARI Standard or approved equivalent standard by an
independent laboratory. Spacers for
control bulb installation shall be provided between coils and
face velocity for coilds shall not exceed the velocity specified.

All cooling coils shall be arranged within the coil section in a


vertical position with the air passing horizontally through the
coil to ensure quick removal of condensate from the coil
surface. Coil headers shall be completely enclosed within the
insulated casing with connections only extended through the
cabinet.

Cooling coils shall be constructed of minimum 13mm diameter


copper tubes mechanically expanded into aluminium fins of
not more than 5.5 fins per cm. No
soldering or tinning shall be used in the bonding process. Coil
headers shall also be constructed of copper of appropriate
sizes.

The drain pans shall be made of stainless steel material


constructed to prevent water leakage and rust. The drain pans
shall be designed to slope towards the drain outlet and with a
drain connection on the bottom of the casing to eliminate
stagnation of condensate. An insulation of 25mm thickness,
32 kg/m3 external thermal insulation shall be applied to the
drain pan to prevent condensation forming on the outside and
to isolate the pan from the unit casing. Provision shall be
made to prevent carry-over of water from the drain pan by the
air stream, and also provision for any water-traps.

The unit shall be internally insulated with 50mm thick, 32


kg/m3 density fibreglass of thermal conductivity not more than
0.0350 W/m°K at a mean temperature of 24°C. The external
casing shall form a perfect vapour barrier.
In order to prevent cold tracking, 37mm deep pressed metal Z
sections buried in the insulation shall support internally 0.6mm
thick galvanised sheet steel sheathing secured with long
screws fixed through the sheathing and insulation.

For air handling units, primary filters of the disposable panel


type or the automatic roll type as specified shall be installed.

HVAC Page 121 of 206 TECHGEL


Date: 16/081/2017
Ỹ THUẬT CỦA THIẾT BỊ VẬT TƯ CHÍNH
Rev: 00
thoát nước - Nhà ga hành khách

VAC SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

York malaysia manufacturing COMPLY


Malaysia COMPLY
Air handling unit COMPLY

All air handling units shall be certified in accordance with ARI


Standard or approved equivalent standard by an independent COMPLY
testing laboratory
The air handling unit shall include, but not be limited to, the
COMPLY
following components:
Sheet metal housing (coated with baked enamel finish to
COMPLY
BS3830 or approved equivalent standard)
Motor is suitable for variable speed COMPLY
Variable control devices COMPLY
Cooling coil section w/ copper tube aluminum fin COMPLY
Insulation Thickness: 50mm, Insulation Density : 40kg/m3 COMPLY
Drainpan Connection: Left-BSPT
COMPLY
Drainpan material : Stanless steel
Including pre-filter(G3) and Bag filter(F7) COMPLY
Factory standard vibration isolator COMPLY
Supports and brackets COMPLY
Local control panels and DDC control panels COMPLY
Supply fan section w/ centrifugal fan, complete with fan pulley
COMPLY
and motor pulley
The housing shall have adequate strength and rigidity under
all operating conditions. The units shall comprise a structural
frame with panels bolted onto the structural frame, and with COMPLY
neoprene rubber gaskets between frames
The casing panels shall be constructed such that they shall
comprise of two layers of galvanised metal sheet sandwiching COMPLY
the insulation in-between.
All casings, housings, plenums and chambers in low and
medium pressure systems, having a dimensions between
1000mm and 1500mm, shall not be less than 1.3mm thick COMPLY
galvanised sheet metal.
All casings, housings, plenums and chambers in low and
medium pressure systems which exceed 1500mm in any COMPLY
dimensions shall be not less than 1.6mm thick.
All casings, housings, plenums and chambers in high
pressure systems, having a dimensions between 1000mm
and 1500mm shall be not less than 1.6mm COMPLY
thick.
All casings, housings, plenums and chambers in high
pressure systems which exceed 1500mm in any dimensions COMPLY
shall be not less than 2.0mm.

HVAC Page 122 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Access doors providing entry to interior of an air-handling unit
casing shall open against air pressure and shall be secured
by two or more heavy chromium
plated bar linked to refrigerator door type catches with internal
and external handles. Adequate stiffenings in metal partitions
shall be provided for securing COMPLY
hinges. Gaskets around doors shall be refrigerator type and
shall be mechanically secured in position. Such access doors
shall be 500mm wide and 1500mm high or as high as the
casings permit.

Supply fan section w/ centrifugal fan


Belt guard for all AHU
Motor Brand&Class: YORK Qualified IE3 COMPLY
Motor Enclosure Class: IP55
Fan Blade Type: Forward curved
COMPLY
All fans shall be furnished with forward curved impellers. In
units furnished with multiple fans, an adjustable outlet damper
shall be installed on each fan to ensure stable operation of COMPLY
the parallel fans.
The fan section shall be manufactured of heavy gauge steel
angle members securely bolted and braced with galvanised
steel panels which shall be easily removable. Fan wheels and COMPLY
scrolls shall be of galvanised steel.
Motor Drive Type: Vee Belt drive
COMPLY

Drives shall include steel sheaves sized to produce the fan


speed required to deliver the specified air quantity. Perforated
metal or 3 mm x 12 mm wire mesh belt guard to protect belts COMPLY
and pulleys shall be provided with accessible facilities for belt
adjustment.
Fan shafts shall be keyed to the mating pulleys. Bearings
shall be self-aligned ball type selected with a nominal life
factory of 300,000 hours and shall be grease lubricated and
equipped with grease escape valve to permit replacement of COMPLY
lubricant without dismantling the bearing housing.

Provision of 40mm diameter holes in belt guard, opposite


each fan and motor axle, for insertion of a tachometer shall be
made. The tachometer, to be COMPLY
supplied by the contractor, must be capable of reading all the
fan speeds of each AHU
Fans shall be statically and dynamically balanced and fan
shafts shall not pass through their first critical speed in COMPLY
achieving the rated rpm.
The fan and motor assembly shall be mounted on a common
framework with factory supplied spring anti-vibration
mountings. The fan discharge shall be COMPLY
isolated from the casing by a flexible connection.
Motor power shall be not less than 1.2 times of fan brake
COMPLY
horsepower (BHP) at the selection point.
Cooling coils shall be of the cartridge type mounted on
COMPLY
aluminium slide rails for easy removability.

HVAC Page 123 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Cooling coils shall have performance certified in accordance
with ARI Standard or approved equivalent standard by an
independent laboratory. Spacers for
control bulb installation shall be provided between coils and COMPLY
face velocity for coilds shall not exceed the velocity specified.

All cooling coils shall be arranged within the coil section in a


vertical position with the air passing horizontally through the
coil to ensure quick removal of condensate from the coil
surface. Coil headers shall be completely enclosed within the COMPLY
insulated casing with connections only extended through the
cabinet.

Cooling coils have construct 12.7mm diameter copper tubes


mechanically expanded into aluminium fins of not more than
5.5 fins per cm. No
soldering or tinning shall be used in the bonding process. Coil
headers shall also be constructed of copper of appropriate COMPLY
sizes.

The drain pans shall be made of stainless steel material


constructed to prevent water leakage and rust. The drain pans
shall be designed to slope towards the drain outlet and with a
drain connection on the bottom of the casing to eliminate
stagnation of condensate. An insulation of 25mm thickness,
32 kg/m3 external thermal insulation shall be applied to the
drain pan to prevent condensation forming on the outside and COMPLY
to isolate the pan from the unit casing. Provision shall be
made to prevent carry-over of water from the drain pan by the
air stream, and also provision for any water-traps.

Insulation Thickness: 50mm, Insulation Density : 40kg/m3

COMPLY

Including Plate Pre-Filter Class Media G3 and Bag Filter


Class Media F7 COMPLY

HVAC Page 124 of 206 TECHGEL


Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gi

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDE
MATERIALS
VARIABLE REFRIGERANT FLOW (VRF) SYSTEMS

Manufacturer:

Origin:
Type
GENERAL

OUTDOOR CONDENSING UNIT

HVAC Page 125 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDE
MATERIALS
INDOOR UNIT

CONTROLS

HVAC Page 126 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDE
MATERIALS

THERMOSTAT

AUTO RESTART FUNCTION

PRECISE ROOM TEMPERATURE CONTROL

VRF SYSTEM PERFORMANCE

HVAC Page 127 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDE
MATERIALS

HVAC Page 128 of 206 TECHGEL


TECHNICAL DATA SHEET
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

IGERANT FLOW (VRF) SYSTEMS


MITSUBISHI ELECTRIC, DAIKIN, TOSHIBA
OR APPROVED EQUIVALENT
THAILAND
VRF

The VRF system shall be equipped with controller that enables safe
operation from 1 0% to 1 25% of the normal capacity. The system shall
be suitable for applications requiring connection to a combination of
different types of fan coil units.
The VRF system shall be able to operate under a minimum piping
distance of 90m (one-way) between the condensing unit and the most
remote fan coil unit,
with 50m level difference
The equipment without
shall run on oil traps.
non-CFC refrigerant and shall be suitable for
operating on 230 volt, single phase; 50 Hz power supply (for fan coil
unit) and 41 5 volts, 3 phase, 50 Hz power supply (for condensing unit).
OUTDOOR CONDENSING UNIT
The condensing unit shall consist of individual compressor-condenser
sections and condenser fan(s) enclosed in a sturdy single weather proof
casing. All safety devices shall be included to ensure safe operation of
the unit. These shall include, but not limited to, high and low pressure
switch, fuses, crankcase heater, fusible plug, over current relay for
compressor, thermal protectors for compressor and fan motors, recycling
guard timer and oil recovery system. A liquid line drier shall be provided.

The compressor shall be external spring mounted serviceable


hermetically sealed scroll or rotary type and equipped with suction and
discharge service valves. The compressor shall be equipped with
controller capable of varying the speed linearly in relation to the cooling
load requirement. It shall be of the same manufacturer as the unit.
The condenser fan(s) shall be of the low noise propeller type directly
driven by a drip-proof permanently lubricated motor. The fan shall be
statically and dynamically balanced and shall be equipped with speed
control for automatic reduction of fan speed at low load.

The condensing unit casing shall be constructed of galvanized steel


bowdlerized and finished with baked enamel. Panel shall be easily
removable to provide access for servicing. The condenser shall be fitted
with its own electrical compartment complete with all necessary electrical
and control components.

HVAC Page 129 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

The evaporator coil shall be of the same construction as the condenser


coil. The fan coil unit casing shall be of the same construction as the
condensing unit casing. Top, bottom and sides shall be fully insulated to
prevent sweating and to muffle noise. The blower fan shall be of
centrifugal forward curve type, belt driven by a permanently lubricated
motor. The fan speed shall be variable by means of a Hi-Med-Lo switch.
The evaporator fan shall be capable of delivering the rated quantity of air
against the total external system static pressure.

The coils shall be seamless copper tubing, with aluminium plate fins
mechanically bonded to. All pipe joints shall be brazed. Coil shall be of
the same manufacturer as the unit.

The fan coil unit shall have a fabricated drip tray complete with a
drainage system incorporated. Complete condensate pumping system
with minimum
head of 10 m shall be allowed for indoor units to ensure condensate
water can be discharged to nearest floor trap or stack.

The VRF Systems shall be microprocessor controlled to achieve precise


room temperature control and minimum power consumption. The control
system shall
employ proportional-integral-differential temperature control and shall
have an accuracy of ± 0.5°C from the set point. The control wiring shall
link each condensing unit to multiple fan coil units using multiplex
ransmission system.
The control system shall be able to perform automatic self checking
function for connection error of wiring and piping. The system shall be
equipped with a self
diagnosis circuit with malfunction code message display to facilitate
maintenance service and trouble shooting.

Each refrigerant circuit shall have its own set of electrical control
assembly for operation and control. Individual compressors shall have
auto-reset protection
devices and compressor motor recycling guard timer circuits to prevent
restarting of the compressors immediately after stopping or more than
once every four (4) minutes.

Controller which varies the compressor speed according to the load shall
be
Eachprovided
fan coilfor allshall
unit condensing units.with
be provided It shall provide soft starting
a self-diagnostic of the
wired control
unit with large screen LCD display for operation. It shall be capable of
performing functions such as ON/OFF, setting of room temperature,
timer, air discharge direction, fan speed selection and self diagnosis
message display. Provision shall also be made for it to be permanently
fixed when requested by the Employer

HVAC Page 130 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

The VRF systems shall also be provided with individual control systems
for all fan coil units and outdoor condenser units either collectively or
individually. The
system shall have a provision for connection to a Programmable Logic
Control
(PLC) via interface port compatible to BACNET. The central controller
shall be able to perform the following functions:
- Simultaneous or individual ON/OFF of the fan coil units
- Temperature setting for each fan coil unit
- Air flow setting of each fan coil
- Fault indication of each fan coil

Thermostat of approved type shall be supplied and installed. In cases


where there are two compressors in the condensing unit, the thermostat
shall be capable of operating the compressors independently or
simultaneously to achieve the required cooling effect. The thermostat
shall be of the on/off type and operating range of 1 5°C - 30°with a
differential of 1 °C suitably mounted to sense the return air temperature
to cycle the compressors for temperature control. A built-in thermometer
shall be incorporated. This thermostat shall be suitable for operation on
24 volts AC.

AUTO RESTART FUNCTION


The VRF system shall come with a preset memory, which would not be
cleared by a power failure, and hence the system program need not
have to be reset
whenever power resumes
PRECISE ROOM TEMPERATURE CONTROL
The VRF system shall have an Electronic Expansion Valve system to
continuously adjust the refrigerant volume thus providing the necessary
room cooling load in respond to variation of heat load detected by the
indoor fan coil units. The system shall be capable of maintaining the set
point temperature at a virtually constant level, without temperature
variations, which are typical of conventional ON/OFF control systems.

VRF SYSTEM PERFORMANCE


Noise Level - Fan Coil Units
The maximum sound pressure level measured at 1 meter away from the
fan coil unit, with the fan running at high speed, shall not exceed the
level as shown below:
Cooling Capacity dB (A)
Up to 3.5 kW 42
Up to 5.2 Kw 45
Up to 8.8 kW 49
Up to 1 4.5 kW 52
Up to 23.0 kW 55
Noise Level - Condensing Unit
The maximum sound pressure level measured at 1 m away from the
condensing unit and 1 .5 m above ground shall not exceed the level as
shown below:
Cooling Capacity dB (A)
HVAC Page 131 of 206 TECHGEL
SPECIFICATION (FOLLOW TENDER DOCUMENT)

Up to 3.5 kW 46
Up to 5.2 kW 52
Up to 8.8 kW 54
Up to 1 4.5 kW 56
Up to 23 kW 59
Up to 30 kW 61
Washable Type Air Filters
Washable type air filters of minimum 70% arrestance tested in
accordance with ASHRAE 52-76 Gravimetric Air Filter Test shall be
provided.

HVAC Page 132 of 206 TECHGEL


Date: 16/08/2017
NICAL DATA SHEET
Rev: 00
ớc - Nhà ga hành khách

SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

TOSHIBA COMPLY

THAILAND COMPLY
VRF COMPLY
The VRF system shall be equipped with controller that
enables safe operation from 10% to 125% of the normal
capacity COMPLY

System layouts can use a maximum equivalent distance of up


COMPLY
to 235 metres.
'The equipment shall run on R410A refrigerant
Power supply for indoor unit : 1-phase 50Hz 230V COMPLY
Power supply for outdoor unit: 3 phase 50Hz 400V

Every outdoor unit incorporate three new DC twin -rotary


compressor and three inverter drive. This is unique to Toshiba

COMPLY

During operation the system determine which heat exchanger


can be used most efficiently and select the compressor to
deliver the power required. Inverter system save ennergy as COMPLY
continuous operation offers the same capacity with lower
power consumption
The condenser fan(s) shall be of the low noise propeller type
directly driven by a drip-proof permanently lubricated motor.
The fan shall be statically and dynamically balanced and shall
be equipped with speed control for automatic reduction of fan
speed at low load.
The condensing unit casing shall be constructed of
galvanized steel bowdlerized and finished with baked enamel.
Panel shall be easily removable to provide access for
servicing. The condenser shall be fitted with its own electrical COMPLY
compartment complete with all necessary electrical and
control components.

HVAC Page 133 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
The evaporator coil shall be of the same construction as the
condenser coil. The fan coil unit casing shall be of the same
construction as the condensing unit casing. Top, bottom and
sides shall be fully insulated to prevent sweating and to muffle
noise. The blower fan shall be of centrifugal forward curve
type, belt driven by a permanently lubricated motor. The fan COMPLY
speed shall be variable by means of a Hi-Med-Lo switch. The
evaporator fan shall be capable of delivering the rated
quantity of air against the total external system static
pressure.

The coils shall be seamless copper tubing, with aluminium


plate fins mechanically bonded to. All pipe joints shall be
brazed. Coil shall be of the same manufacturer as the unit. COMPLY

The fan coil unit shall have a fabricated drip tray complete
with a drainage system incorporated. Complete condensate
pumping system with minimum
head of 10 m shall be allowed for indoor units to ensure COMPLY
condensate water can be discharged to nearest floor trap or
stack.

The intelligent VRF ensure precise control over cooling on a


room by room basis, delivering consistent temperature to
even the furthest room from the unit

COMPLY

Each refrigerant circuit shall have its own set of electrical


control assembly for operation and control. Individual
compressors shall have auto-reset protection
devices and compressor motor recycling guard timer circuits COMPLY
to prevent restarting of the compressors immediately after
stopping or more than once every four (4) minutes.

COMPLY
Each fan coil unit shall be provided with a self-diagnostic
wired control unit with large screen LCD display for operation.
It shall be capable of performing functions such as ON/OFF,
setting of room temperature, timer, air discharge direction, fan
speed selection and self diagnosis message display. COMPLY
Provision shall also be made for it to be permanently fixed
when requested by the Employer

HVAC Page 134 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
The VRF systems shall also be provided with individual
control systems for all fan coil units and outdoor condenser
units either collectively or individually. The
system shall have a provision for connection to a
Programmable Logic Control
(PLC) via interface port compatible to BACNET. The central
controller shall be able to perform the following functions:
- Simultaneous or individual ON/OFF of the fan coil units COMPLY
- Temperature setting for each fan coil unit
- Air flow setting of each fan coil
- Fault indication of each fan coil

Thermostat of approved type shall be supplied and installed.


In cases where there are two compressors in the condensing
unit, the thermostat shall be capable of operating the
compressors independently or simultaneously to achieve the
required cooling effect. The thermostat shall be of the on/off
type and operating range of 1 5°C - 30°with a differential of 1
°C suitably mounted to sense the return air temperature to
cycle the compressors for temperature control. A built-in
thermometer shall be incorporated. This thermostat shall be
suitable for operation on 24 volts AC.

The VRF system shall come with a preset memory, which


would not be cleared by a power failure, and hence the
system program need not have to be reset
whenever power resumes

The VRF system shall have an Electronic Expansion Valve


system to continuously adjust the refrigerant volume thus
providing the necessary room cooling load in respond to
variation of heat load detected by the indoor fan coil units.
The system shall be capable of maintaining the set point COMPLY
temperature at a virtually constant level, without temperature
variations, which are typical of conventional ON/OFF control
systems.

Cooling Capacity COMPLY


Up to 35kW : 30/29/27 dB(A) : (High/Medium/Low) COMPLY
Up to 5.2kW : 32/29/27 dB(A) : (High/Medium/Low) COMPLY
Up to 8.8kW : 38/33/30 dB(A) : (High/Medium/Low) COMPLY
Up to 14.5kW : 46/38/33 dB(A) : (High/Medium/Low) COMPLY
N/A

Cooling Capacity
HVAC Page 135 of 206 TECHGEL
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Up to 3.5 Kw: N/A COMPLY
Up to 5.2 kW: 55/56 dB(A) COMPLY
Up to 8.8 kW: N/A COMPLY
Up to 1 4.5 kW: N/A COMPLY
Up to 23 kW: N/A COMPLY
Up to 30 kW: N/A COMPLY
Washable Type Air Filters
Washable type air filters of minimum 70% arrestance tested in
accordance with ASHRAE 52-76 Gravimetric Air Filter Test COMPLY
shall be provided.

HVAC Page 136 of 206 TECHGEL


Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gi

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
1 AXIAL FLOW FAN
Manufacturer:
Origin:
Type

HVAC Page 137 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

HVAC Page 138 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

2 CENTRIFUGAL FAN

Manufacturer:
Origin:
Type

HVAC Page 139 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

3 IN-LINE CENTRIFUGAL FAN

Manufacturer:
Origin:
Type

HVAC Page 140 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

4 PROPELLER FAN
Manufacturer:
Origin:
Type

HVAC Page 141 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

HVAC Page 142 of 206 TECHGEL


TECHNICAL DATA SHEET
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

Kruger, Wolter, Fantech OR APPROVED EQUIVALENT


Thailand, Viet nam, Malaysia
Axial flow fan
The fans to be installed in the ducted systems shall be of
axial-flow type, with aerofoil shaped blades directly coupled to
a purpose design motor fitted with ball
bearings of generous size to permit mounting of the fan in any
position through 360°. The fans shall have non-overloading
characteristics.
The aerofoil blades shall be of die-cast aluminium-silicon alloy
or PVC (Size 305 mm and smaller) and their pitch angle
adjustable in their impeller hub. The fan casing shall cover the
impeller and motor, fitted with an external terminal box and
sight port which is closed with a rubber moulding. The casing
and terminal box are to be hot dipped galvanised. External
lubricators are to be fitted where applicable.

Fans shall deliver the specified flowrates and pressures when


tested to B.S. 848 Pt. 1, 1963 or AMCA standard 210-74 or
approved equivalent standard. Sound
Power Levels shall be measured in accordance with B.S. 848
Pt 2: 1966 or AMCA standard 300 or approved equivalent
standard to within one standard deviation of 3 dB. The design
and manufacture of fans and quality control standards used
shall comply with B.S. 5750 Quality Systems or approved
equivalent standard.

Fans fitted with foot-mounted type motor on a pedestal frame


welded within the casing and with terminal box integral with
the motor carcass, thus obstructing
airflow and increasing noise level are not acceptable.

The totally enclosed, cage-induction type motor shall be rated


for continuous operation in ambient temperatures up to 40°C,
performance and rating being generally to B.S. 5000 Pt. 99:
1973 and IEC 34-1 or approved equivalent standards with
enclosure protection to IEC 34-5, IP54 or approved equivalent
standard. Insulation shall be to Class F specification of B.S.
2757 or approved equivalent standard.

HVAC Page 143 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

For smoke extract/high temperature duties, the motor shall be


rated at 250°C for two hours continuous operation. Insulation
shall be Class H and shall include special varnish
impregnation or a particular type of wire
enamel that has been shown to have superior high
temperature endurance. Single-phase motors are to be of the
Capacitor Start-and-Run type while three-phase units shall be
suitable for Direct-On-Line starting up to 4 kW and Star-Delta
starting above 4 kW.

Manufacturer recommended type anti-vibration isolators and


flexible connectors shall be provided to ensure minimal
vibration transmission to the adjacent duct sections and
structure.
All manufacturer's instructions for the installation,
commissioning, operation and maintenance of the fan and
frequency/type of lubricant to be used must be
observed. The manufacturer's installation, operation and
maintenance instructions booklet shall be furnished before
commencement of installation.

The following extra requirements shall be complied with


whenever applicable:
If a Flameproof Motor is Required
The flameproof cage-induction type motor shall comply with
type Ex d (BS 683 Part 2) or approved equivalent standard
requirements and certified to BS 229 for Groups II and III
gases (or BS 4683 Part 2, Group
IIA and IIB gases or approved equivalent standards).
Insulation shall be to Class F specification. For single phase
motor, the non-flameproof Start-and-Run capacitor unit shall
be mounted in a non hazardous area.

Power supply to the flameproof motor shall be brought in via


conduit, conduct fittings and flameproof external terminal box
compatible with the enclosure specification of the motor unit.
A hole in the fan casing for connection to a flameproof
terminal box integral with the motor carcass is not acceptable
as it obstructs airflow and creates increase noise.

Anti-spark track of formica or approved equivalent material


shall be fitted on inside of the fan casing adjacent to the tip of
the rotating blades.
If Anti-Condensation Heater is Required
Where the fan is exposed to severe moisture laden condition,
the motor carcass and terminal box cover shall be sealed
against water entry. Anti-condensation heater shall be
incorporated within the motor unit and
be energised whenever mains supply to the latter is shut off.

If Overheat Protection Thermistors are Required

HVAC Page 144 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

Where indicated, overheat protection thermistors (PTC type)


to BS 4999 Pt 72: 1972 or approved equivalent standard shall
be incorporated within the motor. In the event of motor
overheating, this shall energise
matching electronic protection relay which in turn will disrupt
mains supply to the motor. Such protection relays shall also
be supplied by the fan manufacturer.

If Power Factor Correction is Required


For motors rated above 55kW, they shall be power factor
corrected to operate at a power factor of not less than 0.85 at
half load and 0.95 at full load when rated for 380-
420V/3ph/50Hz operation. Power factor
correction capacitors shall be of the capacitor type, self
cooling, insulated and built to IP55 specification enclosure.

Kruger, Wolter, Fantech OR APPROVED EQUIVALENT


Thailand, Viet nam, Malaysia
Centrifugal fan
The fan provided shall be compatible with the air to be
handled and suitable for operations up to 35°C. Fan
performance shall be tested in accordance with BS
848 Pt 1, 1980 or approved equivalent standard.
Fan casing shall be of mild sheet steel construction, with the
scroll plate seam welded to the volute sides. Discharge shall
be flanged and bolting holes provided. Side plates shall be of
mild steel fabricated construction bolted to permit assembly to
any standard discharge angle. A venturi shaped inlet shall be
provided and an inlet spigot fitted. Inspection door shall also
be provided.

Impeller shall be manufactured from mild steel and be fitted to


the fan shaft by a taper bush, parallel key and keyway. The
blades shall be straight backward
inclined or backward curved, flanged and rivetted/plug welded
to the backplate and shroud. Impellers shall be dynamically
balanced to ISO 1940:1973 and BS 5265 Grade G6.3 or
approved equivalent standard.

Motors shall be totally enclosed, fan cooled squirrel cage


induction type (or of flameproof enclosure standard, Ex.d or
EX.e Bs 5501, Part 1 or approved
equivalent standard), single speed or 2-speed, as specified in
the Schedule of Particular Project Requirements, continuously
rated and sized to BS 4999/5000 or approved equivalent
standard.

Enclosure protection shall be to IPW44 or


IP54, dependent upon frame size or approved equivalent
standard. Winding insulation shall be to Class 'F' specification.
Class 'B' winding insulation is acceptable for fractional power
motors.

HVAC Page 145 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

Motors bearing shall be packed with a lithium based grease


suitable for a working temperature range of -40°C to +120°C,
sufficient for two years continuous running under normal
conditions. External lubrication points are to be fitted on motor
sizes above 7.5 kW.

Motor manufacturer's installation, operation and maintenance


instructions shall be submitted prior to commissioning of the
fan.
For motor-ratings above 20 kW, thermal protection devices
shall be incorporated within the motor. The thermistors shall
be imbedded in each phase of the motor windings and
connected in series before being brought out to the terminal
box. Suitable overheat protection relays shall be connected to
de-energise the motor in the event of thermal overload.

For duties below 0.75 kW, single phase motors are preferred
and shall be of the capacitor start and run design, having
power factor not less than 0.85 at full
load. For ratings from 0.75 kW and above, motors shall be
suitable for three phase operation via direct-on-line starters up
to 4kW and star-delta starters from 4 to 11 kW. For ratings of
11 kW and above, motors shall be the autotransformer type.

For indirectly driven fan units, motors selected shall have a


20% allowance for fan absorbed power up to 15 kW and a
10% allowance for absorbed power from
15 kW to 37 kW.

Installation: Motor and steel frame attached to the unit shall


be kept out of contact with fumes which may give rise to
corrosion formation. In mildly corrosive environment, metal
surfaces of motor and steel frame shall be given a protective
coating of chlorinated rubber paint. The fan unit shall be
mounted away from direct radiant heat which might cause
excessive heating of the
casing. Prior to installation, the manufacturer's installation and
commissioning instructions shall be submitted for reference.

Ancillaries: Silencers shall be provided where indicated in the


tender drawings. Anti-vibration isolators shall be of the floor
mounting type offering over 90% isolation efficiencies at the
operating speed. Non-skid ribbed pads/mats shall be attached
to the base of such isolators. Flexible connectors of suitable
materials
shall be used to minimise vibration and noise transmission to
adjacent equipment/duct sections and areas.

Kruger, Wolter, Fantech OR APPROVED EQUIVALENT


Thailand, Viet nam, Malaysia
In-line centrifugal fan

HVAC Page 146 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

Such fans shall be installed in ducted systems as indicated.


They shall deliver the specified flowrates and pressures when
tested to BS 848 PT 1:1963 or approved equivalent standard.
The design and manufacture of fans and the quality control
standards used shall comply with BS 5750 Quality Systems or
approved equivalent standard.

The totally enclosed, cage-induction motor shall be rated for


continuous operation in ambient temperatures up to 60°C
performance and rating generally to BS 5000 Pt 99: 1973 and
IEC 3401 or approved equivalent standards and with
enclosure protection to IP44 standard or approved equivalent
standard. Insulation material shall be to Class B specification
of BS 2757 or approved equivalent standard. The motor shall
be moisture proof.

The casing shall be manufactured from robust galvanised


steel.
The impeller shall be manufactured from galvanised steel
incorporating metal back plates.

Kruger, Wolter, Fantech OR APPROVED EQUIVALENT


Thailand, Viet nam, Malaysia
Wall mounted type

Fans shall deliver the specified flowrates and pressures when


tested to B.S. 848 Pt 1, 1963 or AMCA standard 210-74 or
approved equivalent standard. Sound
Power Levels shall be measured in accordance with B.S. 848
Pt. 2, 1966 or AMCA standard 300 or approved equivalent
standard to within one standard deviation of 3dB. The design
and manufacture of fans and quality of control standards used
shall comply with B.S. 5750, 1979 Quality Systems or
approved equivalent standard.

For wall mounting, manufacturer supplied aerodynamically


designed plastic bellmouth or steel ring mounting plate shall
be provided to ensure that the
required airflow is achieved. For mounting within duct section,
the fan should be appropriately sized for such installation and
the contractor shall ensure that the
necessary diaphragm plate shall match the duct section and
at the same time accommodate the recommended opening
required for the airflow/fan. Where
recommended by the fan manufacturer, anti-vibration mounts
should be used as integral part of the fan installation.

The impellers and motors shall be those designed as


completely integrated units delivering guaranteed
performance and electrically, in terms of power, matched to
fan duties for each size in order to achieve higher power
factors and efficiency. For motor enclosures to meet
flameproof requirements, standard flameproof, power motors
of bulkier construction and thus restricting fan performance
will not be acceptable.

HVAC Page 147 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

r construction and thus restricting fan performance will not be


acceptable. Instead fan manufacturer's own specially
designed flame-proof motor is preferred. Motors shall be of
totally enclosed, squirrel cage induction design, aluminium
construction, finned for efficient cooling and airstream rated
for continuous operation in ambient temperatures up to 40°C.
Insulation and rating shall be to BS 170 : 1962 or BS 261 3 :
1970 and I.E.C 34-1, with protection to I.E.C. 34-5 Group
IP44 minimum or approved equivalent standard.

Single phase motors shall be preferred up to approximately


0.75 kw and suitable for capacitor-start-and-run starting. For
three phase operation, motors shall be of Direct-On-Line
starting type. Where flameproof motors are required, they
shall comply with Ex.d requirements and are certified to BS
229 for groups II and III gases and for Zone 1 and 2 working
environments or approved equivalent standards. For such
duties, the start-and-run capacitors supplied with single phase
fans should be sited outside the hazardous area if the
capacitor boxes are not rated for such environment.

Where indicated, the propeller shall be supplied with actuating


damper, which shall be counterbalanced to allow exhaust
airflow when the fan is operating.

HVAC Page 148 of 206 TECHGEL


Date: 16/08/2017
CHNICAL DATA SHEET
Rev: 00
thoát nước - Nhà ga hành khách

VAC SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

KRUGER COMPLY
Viet Nam COMPLY
Axial ducted inline COMPLY
The fans to be installed in the ducted systems
Kruger direct driven axial fan consisting of long casing with
hanger, motor and impeller. Material of casing in galvanised
steel sheet COMPLY
'Impeller consists of aluminium fan blades with manually
adjustable pitch.

Motor shall be foot-mounted, TEFC, IP55, class F insulation

COMPLY

Fans shall deliver the specified flowrates and pressures when


tested to B.S. 848 Pt. 1, 1963 or AMCA standard 210-74 or
approved equivalent standard. Sound
Power Levels shall be measured in accordance with B.S. 848
Pt 2: 1966 or AMCA standard 300 or approved equivalent
standard to within one standard deviation of 3 dB. The design
and manufacture of fans and quality control standards used COMPLY
shall comply with B.S. 5750 Quality Systems or approved
equivalent standard.

Fans fitted with foot-mounted type motor on a pedestal frame


welded within the casing and with terminal box integral with
the motor carcass, thus obstructing COMPLY
airflow and increasing noise level are not acceptable.

The totally enclosed, cage-induction type motor shall be rated


for continuous operation in ambient temperatures up to 40°C,
performance and rating being generally to B.S. 5000 Pt. 99:
1973 and IEC 34-1 or approved equivalent standards with
enclosure protection to IEC 34-5, IP54 or approved equivalent
COMPLY
standard. Insulation shall be to Class F specification of B.S.
2757 or approved equivalent standard.

HVAC Page 149 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
For smoke extract/high temperature duties, the motor shall be
rated at 250°C for two hours continuous operation. Insulation
shall be Class H and shall include special varnish
impregnation or a particular type of wire
enamel that has been shown to have superior high
temperature endurance. Single-phase motors are to be of the
Capacitor Start-and-Run type while three-phase units shall be COMPLY
suitable for Direct-On-Line starting up to 4 kW and Star-Delta
starting above 4 kW.

Manufacturer recommended type anti-vibration isolators and


flexible connectors shall be provided to ensure minimal
vibration transmission to the adjacent duct sections and COMPLY
structure.
All manufacturer's instructions for the installation,
commissioning, operation and maintenance of the fan and
frequency/type of lubricant to be used must be
observed. The manufacturer's installation, operation and COMPLY
maintenance instructions booklet shall be furnished before
commencement of installation.

If a Flameproof Motor is Required


Suitable for continuous operation for 250°C for 2 hours

COMPLY

Power supply to the flameproof motor shall be brought in via


conduit, conduct fittings and flameproof external terminal box
compatible with the enclosure specification of the motor unit.
A hole in the fan casing for connection to a flameproof
terminal box integral with the motor carcass is not acceptable COMPLY
as it obstructs airflow and creates increase noise.

Anti-spark track of formica or approved equivalent material


shall be fitted on inside of the fan casing adjacent to the tip of COMPLY
the rotating blades.

Where the fan is exposed to severe moisture laden condition,


the motor carcass and terminal box cover shall be sealed
against water entry. Anti-condensation heater shall be
incorporated within the motor unit and COMPLY
be energised whenever mains supply to the latter is shut off.

HVAC Page 150 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Where indicated, overheat protection thermistors (PTC type)
to BS 4999 Pt 72: 1972 or approved equivalent standard shall
be incorporated within the motor. In the event of motor
overheating, this shall energise COMPLY
matching electronic protection relay which in turn will disrupt
mains supply to the motor. Such protection relays shall also
be supplied by the fan manufacturer.

For motors rated above 55kW, they shall be power factor


corrected to operate at a power factor of not less than 0.85 at
half load and 0.95 at full load when rated for 380-
420V/3ph/50Hz operation. Power factor COMPLY
correction capacitors shall be of the capacitor type, self
cooling, insulated and built to IP55 specification enclosure.

KRUGER COMPLY
Viet Nam COMPLY
Centrifugal fan COMPLY
Kruger belt driven single inlet backward curve centrifugal fan
consisting of motor, fanbase, belt cover, pulley
COMPLY

Material of housing in galvanised steel sheet and wheel in


mild steel with polyester powder coating. Inlet & outlet flange
shall be provided
Motor shall be foot-mounted, totally enclosed type, IP55,
class H insulation COMPLY

Impeller shall be manufactured from mild steel and be fitted to


the fan shaft by a taper bush, parallel key and keyway. The
blades shall be straight backward
inclined or backward curved, flanged and rivetted/plug welded
to the backplate and shroud. Impellers shall be dynamically
COMPLY
balanced to ISO 1940:1973 and BS 5265 Grade G6.3 or
approved equivalent standard.

Motors shall be totally enclosed, fan cooled squirrel cage


induction type (or of flameproof enclosure standard, Ex.d or
EX.e Bs 5501, Part 1 or approved
equivalent standard), single speed or 2-speed, as specified in COMPLY
the Schedule of Particular Project Requirements, continuously
rated and sized to BS 4999/5000 or approved equivalent
standard.

Enclosure protection shall be to IPW44 or


IP54, dependent upon frame size or approved equivalent
standard. Winding insulation shall be to Class 'F' specification. COMPLY
Class 'B' winding insulation is acceptable for fractional power
motors.

HVAC Page 151 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Motors bearing shall be packed with a lithium based grease
suitable for a working temperature range of -40°C to +120°C,
sufficient for two years continuous running under normal
conditions. External lubrication points are to be fitted on motor COMPLY
sizes above 7.5 kW.

Motor manufacturer's installation, operation and maintenance


instructions shall be submitted prior to commissioning of the COMPLY
fan.
For motor-ratings above 20 kW, thermal protection devices
shall be incorporated within the motor. The thermistors shall
be imbedded in each phase of the motor windings and
connected in series before being brought out to the terminal COMPLY
box. Suitable overheat protection relays shall be connected to
de-energise the motor in the event of thermal overload.

For duties below 0.75 kW, single phase motors are preferred
and shall be of the capacitor start and run design, having
power factor not less than 0.85 at full
load. For ratings from 0.75 kW and above, motors shall be
suitable for three phase operation via direct-on-line starters up COMPLY
to 4kW and star-delta starters from 4 to 11 kW. For ratings of
11 kW and above, motors shall be the autotransformer type.

For indirectly driven fan units, motors selected shall have a


20% allowance for fan absorbed power up to 15 kW and a
10% allowance for absorbed power from COMPLY
15 kW to 37 kW.

Installation: Motor and steel frame attached to the unit shall


be kept out of contact with fumes which may give rise to
corrosion formation. In mildly corrosive environment, metal
surfaces of motor and steel frame shall be given a protective
coating of chlorinated rubber paint. The fan unit shall be
mounted away from direct radiant heat which might cause
excessive heating of the COMPLY
casing. Prior to installation, the manufacturer's installation and
commissioning instructions shall be submitted for reference.

Ancillaries: Silencers shall be provided where indicated in the


tender drawings. Anti-vibration isolators shall be of the floor
mounting type offering over 90% isolation efficiencies at the
operating speed. Non-skid ribbed pads/mats shall be attached
to the base of such isolators. Flexible connectors of suitable
materials COMPLY
shall be used to minimise vibration and noise transmission to
adjacent equipment/duct sections and areas.

KRUGER COMPLY
Viet Nam COMPLY
In-line centrifugal fan COMPLY

HVAC Page 152 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Kruger direct driven in-line centrifugal fan consisting of
cabinet, motor and DIDW forward curve fan. Material of
casing in galvanised steel sheet
' COMPLY

The totally enclosed, cage-induction motor shall be rated for


continuous operation in ambient temperatures up to 60°C
performance and rating generally to BS 5000 Pt 99: 1973 and
IEC 3401 or approved equivalent standards and with
enclosure protection to IP44 standard or approved equivalent
COMPLY
standard. Insulation material shall be to Class B specification
of BS 2757 or approved equivalent standard. The motor shall
be moisture proof.

The casing shall be manufactured from robust galvanised


COMPLY
steel.
The impeller shall be manufactured from galvanised steel
COMPLY
incorporating metal back plates.

KRUGER COMPLY
Viet Nam COMPLY
Wall mounted type COMPLY

Kruger direct driven wall-mount propeller fan with induction


motor. Mounting plate and impeller made of galvanised sheet
steel with polyester paint finish

COMPLY

Motor is single phase shaded pole asynchronous induction


type with auto reset thermal overload protection device, IP44,
classB insulation

COMPLY

The impellers and motors shall be those designed as


completely integrated units delivering guaranteed
performance and electrically, in terms of power, matched to
fan duties for each size in order to achieve higher power
factors and efficiency. For motor enclosures to meet
COMPLY
flameproof requirements, standard flameproof, power motors
of bulkier construction and thus restricting fan performance
will not be acceptable.

HVAC Page 153 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
r construction and thus restricting fan performance will not be
acceptable. Instead fan manufacturer's own specially
designed flame-proof motor is preferred. Motors shall be of
totally enclosed, squirrel cage induction design, aluminium
construction, finned for efficient cooling and airstream rated
for continuous operation in ambient temperatures up to 40°C.
Insulation and rating shall be to BS 170 : 1962 or BS 261 3 : COMPLY
1970 and I.E.C 34-1, with protection to I.E.C. 34-5 Group
IP44 minimum or approved equivalent standard.

Single phase motors shall be preferred up to approximately


0.75 kw and suitable for capacitor-start-and-run starting. For
three phase operation, motors shall be of Direct-On-Line
starting type. Where flameproof motors are required, they
shall comply with Ex.d requirements and are certified to BS
229 for groups II and III gases and for Zone 1 and 2 working
environments or approved equivalent standards. For such COMPLY
duties, the start-and-run capacitors supplied with single phase
fans should be sited outside the hazardous area if the
capacitor boxes are not rated for such environment.

Where indicated, the propeller shall be supplied with actuating


damper, which shall be counterbalanced to allow exhaust
airflow when the fan is operating. COMPLY

HVAC Page 154 of 206 TECHGEL


Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gi

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
HEAT PUMPS FOR HVAC SYSTEM
Manufacturer:
Origin:
Models:
Type
REFRIGERANT
CABINET

EVAPORATOR

CONDENSER (Water-
cooled)

CENTRIFUGAL FAN

COMPRESSOR

REFRIGERANT
CIRCUIT

INSULATION

HVAC Page 155 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
Heat Pump
Characteristic

HVAC Page 156 of 206 TECHGEL


TECHNICAL DATA SHEET
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

AO SMIT, AERMEC, CALOREC, Mitsubishi


Japan, Thailand, Malaysia

AIR TO WATER HEAT PUMP


The refrigerant used shall be R-134a.
It should be weatherproof to IP54 or better. The machine
chassis shall be constructed of 14 gauge hot dipped
galvanized steel and all panels exposed to ambient conditions
shall be 20 gauge galvanized steel, plastisol coated.

It shall be constructed from rifled Copper tube, aluminium fins


and endplates, all phenolically coated to prevent corrosion
from airborne contaminates and salt.

It shall be Shell and Tube type constructed from steel (shell)


and copper (tube). They shall be extremely efficient and
specifically designed for this purpose. They shall be produced
from seamless marine grade 90/10 copper nickel and certified
to British water regulations (BS standard) for potable water.
The condenser shall be seamless construction and the
maximum working water pressure shall be 10 bar or above.

It unit shall utilize an indirect driven forward curved centrifugal


fan, driven by twin precision wedge belts. The fan motor shall
be 4 pole produced class F, IP 55.
It shall be fully compliant hermetic, high back pressure, Scroll
unit with built in overload
protection. The compressor shall be supplied with rotalock
valve for ease of servicing.

The unit shall be capable of operating in air temperatures


ranging from 5°C to 55°C and water temperature up to 68°C.
The unit shall be controlled by a thermostat with a 4°C
differential. It shall utilize R134a refrigerant and contains a
sight glass, dryer and expansion valve control.
Suction accumulators shall be sized for 100% of the unit
refrigerant capacity. The refrigerant circuit shall be protected
by high pressure and low pressure safety switch, thermal
overloads, MCBs, phase rotation protection and delay timers.
The unit shall be provided with a defrost limit thermostat
provide automatic evaporator defrosting.

All pipes shall be insulated with closed-cell Polyurethane or


equivalent of adequate thickness to prevent heat loss at
conditions of 9.5oC dry bulb and 7.6oC wet bulb.

HVAC Page 157 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

- Type: Air to Water heat pump


- Allowing temperature of heated water: Up to 68°C
- COP: Up to 5
- Material construction: IP 54 Galvanized Steel, Plastisol
coated
- Refrigerant used: R134a
- Power supply: 400V/ 3 phase/ 50 Hz
- Isolator type: Neoprene Pad
- Entering/leaving: 55/65°C
- Pressure drop: 36.5 kPa
- Compressor type: Scroll
- Fan type: Centrifugal

HVAC Page 158 of 206 TECHGEL


Date: 16/08/2017
CHNICAL DATA SHEET
Rev: 00
thoát nước - Nhà ga hành khách

VAC SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

AERMEC COMPLY
Italia COMPLY
NS1801XH°A°°°00
AIR TO WATER HEAT PUMP COMPLY
The refrigerant used shall be R-134a. COMPLY
It should be weatherproof to IP54 or better. The machine
chassis shall be constructed of 14 gauge hot dipped
galvanized steel and all panels exposed to ambient conditions COMPLY
shall be 20 gauge galvanized steel, plastisol coated.

It shall be constructed from rifled Copper tube, aluminium fins


and endplates, all phenolically coated to prevent corrosion
from airborne contaminates and salt. COMPLY

It shall be Shell and Tube type constructed from steel (shell)


and copper (tube). They shall be extremely efficient and
specifically designed for this purpose. They shall be produced
from seamless marine grade 90/10 copper nickel and certified
to British water regulations (BS standard) for potable water. COMPLY
The condenser shall be seamless construction and the
maximum working water pressure shall be 10 bar or above.

It unit shall utilize an indirect driven forward curved centrifugal


fan, driven by twin precision wedge belts. The fan motor shall COMPLY
be 4 pole produced class F, IP 55.
Compressor, volumetric, with double screw rotor in steel alloy
with ratio of 5:6 between the sections.
Semi-hermetic construction with electric motor cooling by COMPLY
means of intake gas.

The unit shall be capable of operating in air temperatures


ranging from 5°C to 55°C and water temperature up to 68°C.
The unit shall be controlled by a thermostat with a 4°C
differential. It shall utilize R134a refrigerant and contains a
sight glass, dryer and expansion valve control.
Suction accumulators shall be sized for 100% of the unit
refrigerant capacity. The refrigerant circuit shall be protected COMPLY
by high pressure and low pressure safety switch, thermal
overloads, MCBs, phase rotation protection and delay timers.
The unit shall be provided with a defrost limit thermostat
provide automatic evaporator defrosting.

All pipes shall be insulated with closed-cell Polyurethane or


equivalent of adequate thickness to prevent heat loss at
conditions of 9.5oC dry bulb and 7.6oC wet bulb. COMPLY

HVAC Page 159 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Type: Air to Water heat pump
Temperature of heated water:40/50°C as request of
equipment data
HFC-134A refrigerant.
Power supply : Three-phase + neutral power supply, 400V,
50Hz with fuses.
Compressor type: Screw COMPLY
Fan type: Axial
Max. external air temperature 48°C in cooling mode
Maximum leaving water temperature 55°C in heating mode
High efficiency, low noise screw compressors
with modulating capacity control from 25 to 100%
Electronic expansion valve as a standard

HVAC Page 160 of 206 TECHGEL


TECHNICAL DATA S
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nh

PLUMBLING AND SANITARY S

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DOCUMENT)
MATERIALS
HEAT PUMPS FOR PLUMBING
Manufacturer: A.O.Smith, AERMEC, CALOREC, MITSUBISHI
Origin: Japan, Thailand, Malaysia, England
Models:
Type Hot water heat pump
REFRIGERANT The refrigerant used shall be R-134a.
CABINET It should be weatherproof to IP54 or better. The machine
chassis shall be constructed of 14 gauge hot dipped
galvanized steel and all panels exposed to ambient
conditions shall be 20 gauge galvanized steel, plastisol
coated.

EVAPORATOR It shall be constructed from rifled Copper tube, aluminium


fins and endplates, all phenolically coated to prevent
corrosion from airborne contaminates and salt.

DOUBLE WALL It shall be Shell and Tube type constructed from steel
CONDENSER (shell) and copper (tube). They shall be extremely efficient
COILS and specifically designed for this purpose. They shall be
produced from seamless marine grade 90/10 copper
nickel and certified to British water regulations (BS
standard) for potable water. The condenser shall be
seamless construction and the maximum working water
pressure shall be 10 bar or above.
The coils utilize a "tube-in-tube" design where potable
water flows inside a double-wall convoluted copper tube in
a counterflow direction to the refrigerant vapor flowing in
the annulus between the convoluted tubing an the smooth
outer steel tube which provides efficient heat transfer and
minimizes fouling. Double-wall vented design, the only
true double-wall vented design, separates the
refrigerant from the potable water preventing
contamination in the unlikely event of a leak
in the tubing.

CENTRIFUGAL It unit shall utilize an indirect driven forward curved


FAN centrifugal fan, driven by twin precision wedge belts. The
fan motor shall be 4 pole produced class F, IP 55.
COMPRESSOR It shall be fully compliant hermetic, high back pressure,
Scroll unit with built in overload
protection. The compressor shall be supplied with rotalock
valve for ease of servicing.

HVAC Page 161 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DOCUMENT)
MATERIALS
REFRIGERANT The unit shall be capable of operating in air temperatures
CIRCUIT ranging from 5°C to 55°C and water temperature up to
68°C. The unit shall be controlled by a thermostat with a
4°C differential. It shall utilize R134a refrigerant and
contains a sight glass, dryer and expansion valve control.
Suction accumulators shall be sized for 100% of the unit
refrigerant capacity. The refrigerant circuit shall be
protected by high pressure and low pressure safety
switch, thermal overloads, MCBs, phase rotation
protection and delay timers. The unit shall be provided
with a defrost limit thermostat provide automatic
evaporator defrosting.

INSULATION All pipes shall be insulated with closed-cell Polyurethane


or equivalent of adequate thickness to prevent heat loss
at conditions of 9.5oC dry bulb and 7.6oC wet bulb.

Heat Pump - Allowing temperature of heated water: Up to 68°C


Characteristic - COP: Up to 5
- Material construction: IP 54 Galvanized Steel, Plastisol
coated
- Refrigerant used: R134a
- Power supply: 400V/ 3 phase/ 50 Hz
- Isolator type: Neoprene Pad
- Entering/leaving: 55/65°C
- Pressure drop: 36.5 kPa
- Compressor type: Scroll
- Fan type: Centrifugal

HVAC Page 162 of 206 TECHGEL


Date: 16/08/2017
CHNICAL DATA SHEET
Rev: 0
, Cấp thoát nước - Nhà ga hành khách

LING AND SANITARY SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

CALOREX COMPLY
England COMPLY
PRO PAC-90BH ( PP-90BH)
Hot water heat pump COMPLY
The refrigerant used shall be R-134a. COMPLY
The cabinet shall be weatherproof to IP24. The machine
chassis shall be constructed of 14-gauge
'hot dipped galvanised steel and all panels exposed to
ambient conditions shall be 20-gauge steel COMPLY
'phosphate protected and plastisol coated to RAL7038
Agate Grey (fixed panels) or RAL9002 Grey

The air-cooled evaporator shall be constructed from rifled


copper tube, aluminium fins and
COMPLY
endplates, all phenolically coated to prevent corrosion
from airborne contaminants and salt.
The water-cooled condensers shall be of tube in shell type
constructed from copper (tube) and
steel (shell). WRAS approved condensers with 90/10
marine grade cupro-nickel (tube) shall be
available as an option. The condensers shall be of
seamless construction and the maximum working
water pressure shall be 10 bar

COMPLY

It unit shall utilize an indirect driven forward curved


centrifugal fan, driven by twin precision wedge belts. The COMPLY
fan motor shall be 4 pole produced class F, IP 55.
The compressor shall be a fully compliant hermetic, high
back pressure, scroll unit with built in overload protection.
COMPLY
The Pro-Pac 90 and 140 shall utilise twin scroll
compressors.

HVAC Page 163 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
The refrigeration circuit shall utilise R134a refrigerant and
contain a sight glass, drier and expansion
valve control, reversing valve and pump down valve.
Suction accumulators shall be sized for 100%
of the unit refrigerant capacity. The refrigeration circuit
shall be protected by HP, LP, thermal
overloads, MCBs, phase rotation protection and delay
timers. 'The refrigeration circuit shall be capable of
operating in air temperatures ranging from 10°C to 50°C
and water temperatures up to 68°C. Heating operation COMPLY
shall be controlled by an integral digital
water thermostat with a 4°C differential.
'BH models shall be provided with a defrost limit
thermostat to provide automatic evaporator
defrosting. BHY models shall be provided with fully
automatic reverse cycle defrost mechanism to
give operation down to -15°C air temperature

- Allowing temperature of heated water: Up to 68°C


- COP: Up to 5
- Material construction: IP 54 Galvanized Steel, Plastisol
coated
- Refrigerant used: R134a
- Power supply: 400V/ 3 phase/ 50 Hz
- Isolator type: Neoprene Pad COMPLY
- Entering/leaving: 55/65°C
- Pressure drop: 36.5 kPa
- Compressor type: Scroll
- Fan type: Centrifugal

HVAC Page 164 of 206 TECHGEL


Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gi

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
CRAC UNIT

Manufacturer:
Origin:
Models:
Type

HVAC Page 165 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

HVAC Page 166 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

HVAC Page 167 of 206 TECHGEL


TECHNICAL DATA SHEET
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

GE, Emerson, Stulz, Delta


OR APPROVED EQUIVALENT
EU, USA, India

Precision air conditioner

CABINET
The cabinet shall be of self supporting welded construction in
1mm sheet steel with base
section supports in 2mm sheet steel for maximum structural
strength with low self
weight.

EVAPORATOR COIL
The evaporator coils shall be mounted on the suction side of
the fans to provide a very
uniform air distribution with low pressure drop and low noise.
The evaporator coils shall be constructed of copper tubes and
aluminium fins and shall
be 4 rows deep, with a maximum face velocity of the air of
2.25 m/s to provide a sensible
heat ratio higher than 98% under normal conditions. An
adjustable air bypass flap shall
be mounted at the top of the coils and extend along their
entire length, to provide control
of air discharge conditions. A stainless steel condensate tray
shall be fitted under the
coil.

HERMETIC COMPRESSORS
The direct expansion refrigeration system shall have a
minimum of two (2) fully hermetic
compressors suitably sized for the specified cooling and
dehumidification. The
compressors shall be fitted with suction gas cooled motors to
provide maximum
reliability, without recourse to pump down cycle, and vibration-
free operation. They shall
be dynamically balanced, mounted on vibration isolators and
shall be fitted with high and
low pressure switches, motor protection, crankcase heaters
and rotalock service valves.

Each refrigeration circuit shall include also a liquid line filter-


dryer, sight glass, solenoid
valve and externally equalized thermostatic expansion valve
factory connected with
refrigeration copper piping.

HVAC Page 168 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

FAN SECTION
The fans shall be of the double width, double inlet centrifugal
type with statically and
dynamically balanced impellers mounted in lifetime lubricated
bearings for quiet,
vibration-free operation. Each fan shall have its own direct
coupled drive motor to
provide standby dependability.
Dehumidification shall be achieved by increasing the cooling
capacity to cause a
lowering in temperature of the cooling coil to that below the
dew point of the air passing
over the coil. Stopping one fan to achieve the
dehumidification effect will not be
accepted.

FILTER SECTION
Two-stage filtration of the re-circulated air shall be
incorporated in the unit to obtain the
required degree of cleanliness of the air in the computer
room. Pre-filters shall be of the
re-generable type and second stage filters shall be of the
deep pleated fabric type
mounted in galvanized frames (or equivalent material which
can resist corrosion) to
permit rapid disposal and replacement without the danger of
dust dispersal. Filtration
efficiency shall be 96% measured by the ASHRAE Standard
52-76 or an approved
equivalent method.
Adjustable differential pressure sensor/ switches shall be
provided across the filters to
activate general alarm to IBMS when the filter is clogged or
low air flow is occurred.
Same time, the “Low air flow” text or the alarm code shall be
displayed at CRAC unit’s
user interface unit.

ELECTRIC REHEAT
A multi-stage electric heater shall be used for reheating during
the dehumidification
cycle. The reheat coil shall be capable of maintaining the
room dry bulb temperature
during the dehumidification mode. The reheat coil shall be
sized to maintain the design
room temperature and humidity without the present of
equipments heat load in the room.

CONTROL SYSTEM
The control system shall be of the microprocessor type
consisting of an operating mode
control section and a display and alarm section. The dry bulb
temperature control
system shall be able to provide an adjustable, finite time
interval between all cooling and
heating stages so as to ensure a smooth response to room
temperature fluctuations.
Wet bulb temperature control shall be provided by top quality
humidistats operating the
dehumidification modes of the system.

HVAC Page 169 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

HVAC Page 170 of 206 TECHGEL


Date: 16/08/2017
CHNICAL DATA SHEET
Rev: 00
thoát nước - Nhà ga hành khách

VAC SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

STULZ COMPLY
Germany COMPLY
ASD 562 A
Precision air conditioner COMPLY

CABINET
The cabinet shall be of self supporting welded construction in
1mm sheet steel with base
section supports in 2mm sheet steel for maximum structural COMPLY
strength with low self
weight.

EVAPORATOR COIL
The evaporator coils shall be mounted on the suction side of
the fans to provide a very
uniform air distribution with low pressure drop and low noise.
The evaporator coils shall be constructed of copper tubes and
aluminium fins and shall
be 4 rows deep, with a maximum face velocity of the air of
2.25 m/s to provide a sensible
heat ratio higher than 98% under normal conditions. An
adjustable air bypass flap shall COMPLY
be mounted at the top of the coils and extend along their
entire length, to provide control
of air discharge conditions. A stainless steel condensate tray
shall be fitted under the
coil.

HERMETIC COMPRESSORS
The direct expansion refrigeration system shall have a
minimum of two (2) fully hermetic
compressors suitably sized for the specified cooling and
dehumidification. The
compressors shall be fitted with suction gas cooled motors to
provide maximum
reliability, without recourse to pump down cycle, and vibration-
COMPLY
free operation. They shall
be dynamically balanced, mounted on vibration isolators and
shall be fitted with high and
low pressure switches, motor protection, crankcase heaters
and rotalock service valves.

Each refrigeration circuit shall include also a liquid line filter-


dryer, sight glass, solenoid
valve and externally equalized thermostatic expansion valve COMPLY
factory connected with
refrigeration copper piping.

HVAC Page 171 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
FAN SECTION
The fans shall be of the double width, double inlet centrifugal
type with statically and
dynamically balanced impellers mounted in lifetime lubricated
bearings for quiet,
vibration-free operation. Each fan shall have its own direct
coupled drive motor to
provide standby dependability.
Dehumidification shall be achieved by increasing the cooling COMPLY
capacity to cause a
lowering in temperature of the cooling coil to that below the
dew point of the air passing
over the coil. Stopping one fan to achieve the
dehumidification effect will not be
accepted.

FILTER SECTION
Two-stage filtration of the re-circulated air shall be
incorporated in the unit to obtain the
required degree of cleanliness of the air in the computer
room. Pre-filters shall be of the
re-generable type and second stage filters shall be of the
deep pleated fabric type
mounted in galvanized frames (or equivalent material which
can resist corrosion) to
permit rapid disposal and replacement without the danger of
dust dispersal. Filtration
efficiency shall be 96% measured by the ASHRAE Standard
52-76 or an approved COMPLY
equivalent method.
Adjustable differential pressure sensor/ switches shall be
provided across the filters to
activate general alarm to IBMS when the filter is clogged or
low air flow is occurred.
Same time, the “Low air flow” text or the alarm code shall be
displayed at CRAC unit’s
user interface unit.

ELECTRIC REHEAT
A multi-stage electric heater shall be used for reheating during
the dehumidification
cycle. The reheat coil shall be capable of maintaining the
room dry bulb temperature
during the dehumidification mode. The reheat coil shall be COMPLY
sized to maintain the design
room temperature and humidity without the present of
equipments heat load in the room.

CONTROL SYSTEM
The control system shall be of the microprocessor type
consisting of an operating mode
control section and a display and alarm section. The dry bulb
temperature control
system shall be able to provide an adjustable, finite time
interval between all cooling and
heating stages so as to ensure a smooth response to room COMPLY
temperature fluctuations.
Wet bulb temperature control shall be provided by top quality
humidistats operating the
dehumidification modes of the system.

HVAC Page 172 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

HVAC Page 173 of 206 TECHGEL


Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gi

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
JET NOZZLES

Manufacturer:
Origin:
Type

MATERIALS

HVAC Page 174 of 206 TECHGEL


TECHNICAL DATA SHEET
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

Trox, Barcol, WB, Kyodo, ASLI OR APPROVED


EQUIVALENT
EU, Japan, Malaysia
Jet Nozzle

The discharge nozzle and face cover ring shall be in


aluminium and the connection element and saddle connection
shall be galvanised sheet steel. All jet nozzles shall be
provided with volume control dampers to facilitate the final air
balancing.
The surface shall be pre-treated and powder coated in white
(RAL 9010) or another RAL colour as specified and approved
the Employer.

HVAC Page 175 of 206 TECHGEL


Date: 16/08/2017
CHNICAL DATA SHEET
Rev: 00
thoát nước - Nhà ga hành khách

VAC SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

ASLI COMPLY
Malaysia COMPLY
Jet Nozzle COMPLY

The discharge nozzle and face cover ring shall be in


aluminium and the connection element and saddle connection
shall be galvanised sheet steel. All jet nozzles shall be COMPLY
provided with volume control dampers to facilitate the final air
balancing.
The surface shall be pre-treated and powder coated in white
(RAL 9010) or another RAL colour as specified and approved COMPLY
the Employer.

HVAC Page 176 of 206 TECHGEL


Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gi

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
AIR DIFFUSION EQUIPMENT
Manufacturer:
Origin:

Type

SUPPLY AIR
REGISTERS

CEILING DIFFUSERS

HVAC Page 177 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
RETURN AND
EXHAUST GRILLES

OUTSIDE AIR AND


EXHAUST AIR
LOUVRES

VOLUME CONTROL
DAMPERS

OPPOSED BLADE
VOLUME CONTROL
DAMPERS

HVAC Page 178 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
FIRE DAMPERS

LINEAR DIFFUSERS

VARIABLE AIR
VOLUME (VAV) BOX

HVAC Page 179 of 206 TECHGEL


EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS

HVAC Page 180 of 206 TECHGEL


TECHNICAL DATA SHEET
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

Trox, Barcol, WB, Kyodo, ASLI OR APPROVED


EQUIVALENT
EU, Japan, Malaysia

AIR DIFFUSER, GRILLE, LOUVER, FIRE DAMPER, VAV


VCD, OBD

All supply air registers shall be of anodised aluminium


construction of such thickness so as to provide the required
rigidity. Registers shall be of the universal type with horizontal
and vertical adjustable blades. All supply air registers shall be
fitted with opposed blade volume control dampers of
approved construction.

Each vane shall be individually adjustable, and shall be


sufficient tight fitting on its spindles so that they will not vibrate
loose. Registers shall be designed and selected so as to
conform with the sound level requirements of the space.

Unless otherwise specified, take-off to each supply air register


shall be provided with a multi-blade stream splitter damper
where supply registers are connected by branches of less
than 0.5 metre in length, and a single blade splitter damper
shall be provided in place of the multi-blade stream splitter
damper for branch more than 0.5 metre.

Square and circular ceiling diffusers shall be anodised


aluminium construction and of the louvre face type suitable for
surface mounting. The diffusers shall be
rigidly constructed, and unless otherwise specified shall have
not less than four (4) louvre vanes per 150mm. All ceiling
diffusers mounted on duct collars shall be provided with
opposed blade volume control dampers to Employer's
approval.

The ceiling diffusers shall be of the type with integral conical


or pyramidal transfor-mations expanding from the diffuser
neck to the diffuser face so that supply air from the duct will
expand inside the transformations before it diffuses out
through the louvre vanes.
Unless otherwise stated, ceiling diffusers mounted directly on
the underside of ductwork shall be provided with a multi-blade
stream splitter damper. The stream splitter damper shall be
constructed as specified hereinafter in this section.

HVAC Page 181 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

All return and exhaust grilles shall be of anodised aluminium


construction and of the fixed front blade type unless otherwise
indicated. All return and exhaust
grilles shall be fitted with opposed blade volume control
dampers unless otherwise indicated in the drawings. Volume
Control dampers of approved construction shall be fitted.

All return and exhaust grilles shall be constructed of metal of


sufficient thickness to ensure sufficient rigidity of grilles.

Fresh and exhaust air ducts and openings shall be supplied


and installed with louvres of approved manufacture, unless
such louvres are specifically indicated as not required.

Louvres blades shall be horizontal and constructed of


galvanised steel or extruded aluminium set in a rigid frame.
Blades shall be set of approximately 50mm apart at an angle
of 30° to horizontal.

All fresh and exhaust louvres and openings shall be fixed with
12mm mesh matt black painted galvanised insect screen on
the inside.
Steel louvres shall be sprayed painted with two generous
layers of zinc chromate non-civic primers while aluminium
louvres shall be anodised. These louvres shall be finished
with two layers of clear methacrylate semi-matt natural
finish of colour to be nominated by the Employer.
All outside air louvres shall have insect screens, air filters and
adjustable volume control dampers. All exhaust air louvres
shall have insect screens.
Volume control dampers shall be of the opposed blade type.
The contractor shall take special care to ensure that all
dampers are free from vibration and rattles under all operating
conditions.
All damper units located behind air diffusers, registers and
grilles shall be painted matt black.

All opposed blade dampers shall be of proprietary make or of


approved local make. Dampers shall be of steel frame
construction or extruded aluminium with pressed opposed
operating blades.

The damper unit shall be complete with soft rubber sponge


gaskets of not less than 6mm thickness for connection to
ductwork and grilles.
Damper adjustment mechanism shall be of approved type and
shall be of rigid construction with no slack when opening or
closing of the damper. The adjustment mechanism shall be
concealed and shall require the use of a screw driver to make
the necessary adjustment. A simple lever type adjustment is
not acceptable.

HVAC Page 182 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

The blade(s) shall have self aligning sintered bronze bearings


actuating or pivoting on stainless steel stubs shafts. Any
interconnecting linkages required for louvred type dampers
shall have brass self aligning linkage brackets and dampers
shall be held open by one or more fusible links which shall
fuse at 60°C.

Linear diffusers connected to plenum boxes shall be of the


low resistant slot diffuser, high induction ratio type.
All linear diffusers shall be complete with an insulated plenum
box for connection to flexible duct.

Performance of the diffusers shall be based on tests


according to ASHRAE Standard 36-72 and ADC Standard
1062R4 or approved equivalent standards.
The diffuser sections shall be equipped with spring steel
security clips to prevent spread of ceiling grid and
misalignment of the diffusers.
Sufficient appurtenances such as mounting brackets,
adjustable hangers and diffuser alignment pieces shall be
provided to support the units sufficiently. All diffuser supports
shall be independent of the suspended ceiling supports.

All linear diffusers which show signs of rust or damage on


delivery to site shall be rejected.
Box Construction
The VAV box shall be of pressure independent type complete
with factory mounted DDC control, protective shroud to
enclose the control components, builtin flow sensor, air
regulation damper, discharge sound attenuator, a rectangular
flanged outlet or multiple outlet adaptor, volume setting dials
and an access panel. The box shall be factory assembled,
calibrated and tested.

The controller shall be networked to BMS for AHU airflow


control and for centralized monitoring, adjustment and control.
The electrical supply comprising of cable, truncking/conduit,
transformer etc to the VAV box motorised damper and DDC
controller shall be provided by the contractor. The supply for
the DDC controller shall not be looped together with other
devices.
The casing shall be of at least 22 gauge thick galvanized steel
and fully insulated inside and surface coated to prevent
erosion. The discharge sound attentuator
shall be of same construction as casing regarding material
and insulation. The internal and external insulation shall be
accordance with PWD Standard Specification (M&E) 2/92.

HVAC Page 183 of 206 TECHGEL


SPECIFICATION (FOLLOW TENDER DOCUMENT)

The air regulation damper shall be of heavy gauge metal


construction, with its shaft rotating in stainless steel self-
lubricating bearings. The damper shall close
against a neoprene seal to prevent air leakage during shut-
off. In the fully closed position, air leakage through the closed
damper shall not exceed 2% of the rated
airflow at 750 Pa inlet static pressure. The access panel shall
be of the quick opening type to give easy and quick access to
the volume regulator.

One thermostat shall be provided for each box. The


thermostat shall be capable of site recalibration and maintain
the desired room temperature within + 1 oC. An
external occupancy switch shall be provided for VAV box(es)
installed in the non open-plan areas to force the controller into
Unoccupied Mode to set the damper for minimum flow.

Integral step down transformer shall be provided for each box


to provide proper power supply for the control
system/components.
The tubing for the cross flow shall be hidden as to prevent
loose connection or improper connection during site
installation. Access door shall be provided.
The flow sensor shall either be pressure differential type or
electronic hot wire type. The sensor shall measure the actual
flowrate to an accuracy of + 15%.

The static pressure drop across the box shall not exceed 35
Pa at the design flow rate. The sound power level in each
octave band 2 through 6 (ie at centre frequency 125 Hz, 250
Hz, 500 Hz, 1000 Hz, 2000 Hz) when measure at 125 Pa
static pressure across the terminal unit shall not exceed:
- casing radiated sound - 40 dB(A)
- discharge sound - 40 dB(A)

VAV Box Performance Test


All VAV boxes shall be calibrated, tested and certified to
satisfy the following requirements before delivery to site:
- Air Flow Accuracy
Within + 15% of the set airflow to establish the accuracy of
the controller after it was calibrated to the characteristic of the
flow sensor.
- Pressure Independent Test
At minimum and maximum design airflow, the controller shall
maintain same flow accuracy at 3 different static pressure
settings.
- Leakage Test
Within + 2% of rated airflow when overriding the box to fully
closed damper position.
- Damper Actuator Functional Test
Actuator shall rotate at clockwise and anti-clockwise
directions in the load testing on the actuator handle to
simulate an actual static pressure acting on the damper.

HVAC Page 184 of 206 TECHGEL


Date: 16/08/2017
CHNICAL DATA SHEET
Rev: 00
thoát nước - Nhà ga hành khách

VAC SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

ASLI COMPLY
Malaysia COMPLY

AIR DIFFUSER, GRILLE, LOUVER, FIRE DAMPER, VAV


COMPLY
VCD, OBD

All supply air registers shall be of anodised aluminium


construction of such thickness so as to provide the required
rigidity. Registers shall be of the universal type with horizontal
and vertical adjustable blades. All supply air registers shall be COMPLY
fitted with opposed blade volume control dampers of
approved construction.

Each vane shall be individually adjustable, and shall be


sufficient tight fitting on its spindles so that they will not vibrate
loose. Registers shall be designed and selected so as to COMPLY
conform with the sound level requirements of the space.

Unless otherwise specified, take-off to each supply air register


shall be provided with a multi-blade stream splitter damper
where supply registers are connected by branches of less
than 0.5 metre in length, and a single blade splitter damper COMPLY
shall be provided in place of the multi-blade stream splitter
damper for branch more than 0.5 metre.

ASLI DB is a type of diffuser with multiple square


cones which provide excellent 4 ways directional
discharge pattern. Each cone is one piece dieformed
construction with seamless surface and
COMPLY
no corner joints. This consistent air flw pattern
produce rapid mixing, excellent and stable room air
distribution. DB is the most popular square ceiling
diffuser and suitable for rapid cooling usage

Frame : 1.0mm aluminum.


Blade : 1.0mm aluminum.
Support Bar : 1.5mm galvanized steel. COMPLY

White powder coated, oven baked


as standard.
Others available upon request. COMPLY

HVAC Page 185 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
All return and exhaust grilles shall be of anodised aluminium
construction and of the fixed front blade type unless otherwise
indicated. All return and exhaust
grilles shall be fitted with opposed blade volume control COMPLY
dampers unless otherwise indicated in the drawings. Volume
Control dampers of approved construction shall be fitted.

All return and exhaust grilles shall be constructed of metal of


sufficient thickness to ensure sufficient rigidity of grilles. COMPLY

Fresh and exhaust air ducts and openings shall be supplied


and installed with louvres of approved manufacture, unless
such louvres are specifically indicated as not required. COMPLY

ASLI RM series is an architectural exterior decoration


louver with the aero-dynamics blade design.
RM weather louver type return air grille is an architectural
exterior decoration
'Used commonly in outdoor air application, i.e. fresh air &
COMPLY
exhaust air where
rain-proof is a concern. It is also used in door as return air
application both
mounted on ceiling and wall

All fresh and exhaust louvres and openings shall be fixed with
12mm mesh matt black painted galvanised insect screen on COMPLY
the inside.
Baked white powder coated as standard.
Other available upon request.
COMPLY

All outside air louvres shall have insect screens, air filters and
adjustable volume control dampers. All exhaust air louvres
shall have insect screens.
HD-T is primary designed for manual balancing
application in ventilation systems for volume flw and
pressure control. The galvanized steel locking quadrant
arm (HD-T) or the OM arm linkage (HD-T OM) is mounted COMPLY
on the shaft for manual operation

G1-T Blacl powder coated, oven baked as standard


Maximum dimension is 500mm x 500mm. Damper size bigger
than
this will come in sections. COMPLY
Gear operated, can be set at fully open, half open & fully
close

The damper unit shall be complete with soft rubber sponge


gaskets of not less than 6mm thickness for connection to COMPLY
ductwork and grilles.
Damper adjustment mechanism shall be of approved type and
shall be of rigid construction with no slack when opening or
closing of the damper. The adjustment mechanism shall be
concealed and shall require the use of a screw driver to make COMPLY
the necessary adjustment. A simple lever type adjustment is
not acceptable.

HVAC Page 186 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Fire Dampers have been
developed to provide the versatility required for today’s
complex and sophisticated fie protection and safety
building system. There are two types of fie dampers:
Fire damper with fusible link (FSD60) and motorized fie
COMPLY
damper (MFSD60). During fie, the FSD60 provides the quick
closure respone by means of tentioned
spiral spring mounted at the side when the fusible link fuses
at 74°C (165°F)

Linear diffusers connected to plenum boxes shall be of the


COMPLY
low resistant slot diffuser, high induction ratio type.
ASLI SLLS series is a type of diffuser combine
a high air change rate capacity with maximum
flxibility in air pattern and volume control. It offers COMPLY
unobtrusive good looks together with functional
effiiency.
Performance of the diffusers shall be based on tests
according to ASHRAE Standard 36-72 and ADC Standard COMPLY
1062R4 or approved equivalent standards.
The diffuser sections shall be equipped with spring steel
security clips to prevent spread of ceiling grid and COMPLY
misalignment of the diffusers.
Sufficient appurtenances such as mounting brackets,
adjustable hangers and diffuser alignment pieces shall be
provided to support the units sufficiently. All diffuser supports COMPLY
shall be independent of the suspended ceiling supports.

All linear diffusers which show signs of rust or damage on


COMPLY
delivery to site shall be rejected.
Box Construction
The VAV box shall be of pressure independent type complete
with factory mounted DDC control, protective shroud to
enclose the control components, builtin flow sensor, air
regulation damper, discharge sound attenuator, a rectangular COMPLY
flanged outlet or multiple outlet adaptor, volume setting dials
and an access panel. The box shall be factory assembled,
calibrated and tested.

The controller shall be networked to BMS for AHU airflow


control and for centralized monitoring, adjustment and control.
The electrical supply comprising of cable, truncking/conduit,
transformer etc to the VAV box motorised damper and DDC COMPLY
controller shall be provided by the contractor. The supply for
the DDC controller shall not be looped together with other
devices.
The casing shall be of at least 22 gauge thick galvanized steel
and fully insulated inside and surface coated to prevent
erosion. The discharge sound attentuator
shall be of same construction as casing regarding material COMPLY
and insulation. The internal and external insulation shall be
accordance with PWD Standard Specification (M&E) 2/92.

HVAC Page 187 of 206 TECHGEL


COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
The air regulation damper shall be of heavy gauge metal
construction, with its shaft rotating in stainless steel self-
lubricating bearings. The damper shall close
against a neoprene seal to prevent air leakage during shut-
off. In the fully closed position, air leakage through the closed COMPLY
damper shall not exceed 2% of the rated
airflow at 750 Pa inlet static pressure. The access panel shall
be of the quick opening type to give easy and quick access to
the volume regulator.

One thermostat shall be provided for each box. The


thermostat shall be capable of site recalibration and maintain
the desired room temperature within + 1 oC. An
external occupancy switch shall be provided for VAV box(es) COMPLY
installed in the non open-plan areas to force the controller into
Unoccupied Mode to set the damper for minimum flow.

Integral step down transformer shall be provided for each box


to provide proper power supply for the control
system/components.
The tubing for the cross flow shall be hidden as to prevent
loose connection or improper connection during site
COMPLY
installation. Access door shall be provided.
The flow sensor shall either be pressure differential type or
electronic hot wire type. The sensor shall measure the actual
flowrate to an accuracy of + 15%.

The static pressure drop across the box shall not exceed 35
Pa at the design flow rate. The sound power level in each
octave band 2 through 6 (ie at centre frequency 125 Hz, 250
Hz, 500 Hz, 1000 Hz, 2000 Hz) when measure at 125 Pa
static pressure across the terminal unit shall not exceed: COMPLY
- casing radiated sound - 40 dB(A)
- discharge sound - 40 dB(A)

VAV Box Performance Test


All VAV boxes shall be calibrated, tested and certified to
satisfy the following requirements before delivery to site:
- Air Flow Accuracy
Within + 15% of the set airflow to establish the accuracy of
the controller after it was calibrated to the characteristic of the
flow sensor.
- Pressure Independent Test
At minimum and maximum design airflow, the controller shall
maintain same flow accuracy at 3 different static pressure
settings. COMPLY
- Leakage Test
Within + 2% of rated airflow when overriding the box to fully
closed damper position.
- Damper Actuator Functional Test
Actuator shall rotate at clockwise and anti-clockwise
directions in the load testing on the actuator handle to
simulate an actual static pressure acting on the damper.

HVAC Page 188 of 206 TECHGEL


BẢNG ĐÁP ỨNG KỸ THUẬT CỦA
Dự án: Cảng Hàng Không Quảng Ninh
Gói thầu: Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà g

HVAC SYSTEM

EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DOCUMENT)
MATERIALS
1 ELECTRICAL
Power supply

Terminal panel

Anti-Condensation
Heaters

Subsidiary switchboards
and control panels
Wall mounted control
panel

Operator control console

Radio frequency
interference (RFI)

Motors
Motor starters
Motor isolators

Power factor correction

AC frequency controlled
drivers (FCD)

Operating Condition
BẢNG ĐÁP ỨNG KỸ THUẬT CỦA THIẾT BỊ VẬT TƯ CHÍNH
ng Hàng Không Quảng Ninh
Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách

HVAC SYSTEM

SPECIFICATION (FOLLOW TENDER DOCUMENT)

- Power supply of 400V/3 Ph/50 Hz 4 wire system


underground cables or top entry cables to the air-conditioning
cubicle switchboard.
- The Contractor shall incorporate an adequately rated TP&N
circuit breaker and cable end box in the cubicle switchboard.
- Where more than one incoming supply (ie. where normal
and emergency supply) to the main airconditioning
switchboard, an adequately rated 4 pole circuit breaker shall
be provided instead.

- Power supply of 400V/3 Ph/50Hz terminating in TP&N


isolators shall be provided by the Contractor for all AHU
rooms, fan rooms etc.
- Power supply of 230V/1 Ph/50Hz terminating in SP & N
isolators or power sockets shall also be provided by the
Contractor for all ventilation fans, fan coil units, etc within 3 m
of the equipment.

An isolated terminal panel within the main airconditioning


switchboard for interface connection to other system eg
Building Management System.
- The switchboards shall be fitted with heating devices
suitable for operation at 230 Volt AC single phase of sufficient
capacity to raise the internal ambient temperature by 5°C.
- The electrical apparatus so protected shall be designed so
that the maximum permitted rise in temperature is not
exceeded if the heaters are energised while the apparatus is
in operation.
- Heater 'ON' indicating lamps shall be provided and they shall
be correctly connected to give true indication at all times.
- A suitable terminal box and control switch shall be provided
and mounted in an accessible position for each switchboard.

Each subsidiary switchboard and control panel shall be self-


contained, wall mounted, or floor-mounted, metal clad, cubical
type with flush hinged doors for front access. Doors shall be
provided with car type lockable handles.

- Subsidiary switchboards and control panels shall generally


be constructed, fitted and tested as specified.
- The fault rating of the panel shall not be less than the
prospective fault level available through a short circuit at the
panel itself.
Subsidiary switchboard and control panels for outdoor
installation shall be suitably weatherproofed.
A control panel housing the motor starters and protection
apparatus, motor operation control and indicating devices,
etc, shall be supplied and installed for the system. The control
panel shall be totally enclosed metal-clad wall mounted front
access type and installed in the plantroom.

The control panel shall be fabricated of minimum 1.30mm


thick sheet steel pressed and rolled to shape having all joints
neatly welded and finished flush. Door shall be hinged type
with concealed hinges and secured by captive knurled thumb
screws.
The control panel shall be provided with the following :
- Circuit breakers of correct rating for short-circuit protection.
- Thermal overload relays for overcurrent protection.
- All the control and indicating devices as shown in the
drawings accompanying this Specification.

The contractor is required to ensure that all indicating lights


on the control panel are properly labelled.
All control wires must be numbered for easy troubleshooting
and identification.
- Operator control console shall be constructed from 2.60mm
thick sheet steel complete with suitable doors that allow easy
access to all equipment installed therein.
- The control console shall be finished smooth with two coats
of primer and two coats of semi-glossy synthetic enamel to
colour No 631 of BS 381C or approved equivalent standard.
- Operator control console shall have a vertical white PVC
graphic panel complete with ON/OFF indicating lights for all
main airconditioning equipment ie chillers, chilled water
pumps, condenser water pumps and cooling towers.

In cases where a computer terminal is required, a network link


to the Building Management System shall be provided to
enable the proper operation from within the chiller control
room.
Electrical equipment or systems involving sudden changes, or
interruption or low frequency or of direct electric currents such
as thermostatically controlled devices, contactors,
commutators shall be fitted with radio and television
interference suppression components suitable to meet the
levels specified in BS 800 'Limits of Radio Interference' or
approved equivalent standard.

- All motors shall be Energy Efficient (High Efficiency) type


with minimum guaranteed motor efficiency of 84% or more in
accordance with NEMA MG1 -12.53a or approved equivalent
standard and tested as per IEEE 112 Method B or approved
equivalent method.
+ Motors from 2 to 10 kW rating the minimum efficiency shall
be 85%.
+ Motors rating of more than 10 kW the minimum efficiency
shall be 90%.
- Motors of 0.75kW rating and above shall be wound for 400
Volts, 3 phase, 50Hz supply.
- Motors of less than 0.75kW rating may be wound for 230
Volts, 1 phase, 50Hz supply.
- All motors shall be wound for continuous duty of not less
than 12 hours.

- All motors shall be sized to not less than 20% higher than
the power absorbed (brake horsepower) of the associated
equipment.
Motors shall be NEMA Design B Standard or approved
equivalent standard. The testing for efficiency shall be
performed in compliance with NEMA MG1 -12.53a or
approved equivalent standard which specified dynamometer
testing per IEEE U2 method B or approved equivalent
standard .

All motors shall be totally enclosed fan cooled type. Motor


fans shall be antistatic, polypropylene, corrosion resistant and
bi-directional. Motor bearings shall be of ball or roller or
sleeve type as applicable and amply sized to perform
the duties required.

All motors shall have cast iron frame and end-shield


construction for 182T and 449T frame. Steel frame and
aluminium end-shield construction shall be acceptable for
143T to 145T frame. Motor terminal box shall be diagonally
split and rotatable. The terminal boxes shall be suitable for
reception of cables or screwed conduits entry as required.

All motors shall have full class F non-hydroscopic insulation


system with multiple dipped and baked varnish treatment.

The maximum motor sound pressure level shall not exceed


85 dBA.
For all standby equipment, motors shall be equipped with
heaters. The heaters shall be connected up to ensure that
when the motor is on, the heater is switched off and vice
versa.
The labelling of efficiency on the nameplate shall be in
compliance with NEMA MG1 -12.53b or approved equivalent
standard, the full load guaranteed efficiency shall also be on
the nameplate.
Motor starters shall be constructed for intermittent duty in
accordance with BS 587 or approved equivalent standard and
equipped with overload, single-phasing and under-voltage
protection. Where remote control is required, starters shall be
of contactor type with coils wound for 230 Volt 50 cycle
operation. Heaters shall generally be located in the bottom of
the cubicle, with the thermostat at the top. The heater terminal
at the motor and starter shall be clearly labelled:
"CAUTION - MOTOR HEATER - ALIVE WHEN MOTOR
STOPPED"

Starters shall be of the following types unless otherwise


indicated on the Tender Drawings:
* Up to 4 kW motors - Direct-on-line
* 4 kW to 11 kW motors - Star/delta type
* 11 kW motors or above - Auto-transformer type.
Auto-transformer starters shall limit the motor starting current
to 1.6 times the normal full-load current.
Both star/delta and auto-transformer starters shall be of the
close transition types. The auto-transformer starters shall be
provided with tappings suitable for connection to 40% - 75%
of line voltage in steps of 5%. All motor starters shall be tested
to BS 587 or approved equivalent standard.

All starters shall be automatic type complete with


START/STOP push-buttons auxiliary contacts as required,
MANUAL/OFF/AUTO selector switch and provision for remote
controls as required. All motors shall be connected through
suitable fuses or MCCB in addition to starters.

The supply to each motor shall be controlled by means of an


efficient cut off switch placed in such a position as to be easily
handled by the person in charge of the motor, and connected
such that the power supply can be cut-off from the motor and
from the regulating switch, resistances or other devices
connected to it.

Motors arranged for remote control shall be provided with a


similar cut-off switch placed in such a position as to be easily
handled by the person in charge of the motor, and connected
such that the power supply can be cut-off from the motor and
from the regulating switch, resistances or other devices
connected to it.

All isolating switches, fuse switches and switch fuses shall be


500 Volts, metal clad, conforming with the provisions of BS
861 or approved equivalent standard.
Power factor correction capacitors shall be provided as
required to correct the power factor of all motors over 1.5kW
in size to 0.85 lagging, or better, at all loads.
The capacitors shall be installed adjacent to the motors and
complete with the necessary protection fuses, discharge
resistors and all wiring and connections.
50Hz 400/230V three phase four wire AC Frequency
Controlled drives (shall be called FCD hereinafter)
The FCD shall operate in conjunction with mechanical system
components including chilled water pumps and AHU fans. The
FCD shall be able to operate the standard AC induction motor
of the pumps and fans from a minimum of 10% to 100% of the
rated speed
The FCD shall be of high efficiency, low maintenance and
adjustable frequency and voltage type using the principle of
Pulse Width Modulation design. The FCD shall be suitable for
automatic control in response to 4 to 20 mA or 0 to 10V input
signal, the output frequency of 0 to 50 Hz shall be in
proportion to this signal range

The FCD shall be capable of withstanding any combination of


the following environmental conditions in which it must
operate without causing electrical/mechanical damage of
degradation of performance
- Ambient temperature : up to 40 C
- Relative Humidity : up to 90%
- Surge suppressor : built-in protection against lightning
surges introduced on the primary source.
The FCD shall have built-in air blower unit so that the FCD
can be forced air cooled to operate within the above rated
environmental conditions. The FCD shall be housed in
respective motor starter panel. Appropriate air inlet and
exhaust shall be provided to ensure adequate ventilation for
proper operation.

The FCD shall consist of the following major components:


- rectifier
- inverter
- control and display panel
- RFI filter to curve G or N of VDE0875 or equivalent.
The FCD shall be equipped with Auto/OFF/Manuals switch for
selection of control mode. During manual mode operation, the
FCD shall be used to provide variable speed motor controls to
the pumps and fans connected with the capability of soft start
(to restrict current during acceleration) and soft stop (to
restrict over voltage during deceleration). During automatic
mode operation, the FCD shall have the capability of soft
start, soft stop and automatically adjust its speed based on
external control signal to provide the load required by the
system. The FCD shall have facility for local setting of
frequency manually in the event of automatic control signal
failure.

The FCD shall be designed to perform and work well with the
motor without causing overheating and damage to either the
controller or the motor. The tenderer shall ensure the
matching of the FCD to the motor. In addition, the FCD shall
have adjustable starting torque boost to suit the required
starting torque of the load. The overall efficiency of the
combined FCD and the matched-motor shall be not less than
85% at full load and 100% rated speed of the motor.

The FCD shall have the following electrical characteristics:


- Input power - Voltage: 400/230V ± 10%
Frequency : 50Hz ± 5%
Power Factor : 0.85 - 0.95 full load
- Output power - Voltage :400/230V, 3 phase,
4 wire system
Frequency : adjustable from 10% -
Regulation 100% of rated speed
Overload : 150% of full load for ratings 60 seconds, 200% for
0.5 seconds with inverse time characteristics
Efficiency : 90% minimum from 50% to 100% rated speed
Power factor : 0.9 minimum from 50% to 100% rated speed

The FCD shall have RS485 interfaced built-in allowing the


invertor to be used in conjunction with external control system
within a multi-drop LAN configuration. This interface shall
enable the various parameter settings of FCD to be input via
BMS control. In addition the FCD shall have the capability to
retain these settings within non-volatile EEPROM memory.
The parameters shall include but not limit to;
acceleration/deceleration time setting, frequency setting,
multi-speed setting automatic restored after instantaneous
power failure etc.
The FCD shall make available the following output signals for
the external controller in addition to a summary alarm voltage
free contact:
- inverter running
- inverter overload alarm
- analog signal output reflecting the actual inverter frequency
output.

The display panel shall incorporate indication of output


frequency, FCD status indications, fault diagnostics indicators,
audible alarm and indication for any
abnormalities eg overload shutdown, grounded DC lms,
rectifier failure, inverter failure etc. The panel shall also
incorporate alarm reset button mode selector switch, facility to
set frequency acceleration time etc manually.

The FCD shall include DC Link Filter or Harmonic Filter to


suppress the Total Harmonic Distortion of maximum 5 % in
the mains by limiting the level of ripple in the DC link.
Date: 19/08/2017
UẬT CỦA THIẾT BỊ VẬT TƯ CHÍNH
Rev: 00
nước - Nhà ga hành khách

C SYSTEM

COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION

- Power supply of 400V/3 Ph/50 Hz 4 wire system Comply


underground cables or top entry cables to the air-conditioning
cubicle switchboard.
- The Contractor shall incorporate an adequately rated TP&N
circuit breaker and cable end box in the cubicle switchboard.
- Where more than one incoming supply (ie. where normal
and emergency supply) to the main airconditioning
switchboard, an adequately rated 4 pole circuit breaker shall
be provided instead.

- Power supply of 400V/3 Ph/50Hz terminating in TP&N Comply


isolators shall be provided by the Contractor for all AHU
rooms, fan rooms etc.
- Power supply of 230V/1 Ph/50Hz terminating in SP & N
isolators or power sockets shall also be provided by the
Contractor for all ventilation fans, fan coil units, etc within 3 m
of the equipment.

An isolated terminal panel within the main airconditioning Comply


switchboard for interface connection to other system eg
Building Management System.
- The switchboards shall be fitted with heating devices Comply
suitable for operation at 230 Volt AC single phase of sufficient
capacity to raise the internal ambient temperature by 5°C.
- The electrical apparatus so protected shall be designed so
that the maximum permitted rise in temperature is not
exceeded if the heaters are energised while the apparatus is
in operation.
- Heater 'ON' indicating lamps shall be provided and they shall
be correctly connected to give true indication at all times.
- A suitable terminal box and control switch shall be provided
and mounted in an accessible position for each switchboard.

Each subsidiary switchboard and control panel shall be self- Comply


contained, wall mounted, or floor-mounted, metal clad, cubical
type with flush hinged doors for front access. Doors shall be
provided with car type lockable handles.

- Subsidiary switchboards and control panels shall generally Comply


be constructed, fitted and tested as specified.
- The fault rating of the panel shall not be less than the
prospective fault level available through a short circuit at the
panel itself.
Subsidiary switchboard and control panels for outdoor Comply
installation shall be suitably weatherproofed.
A control panel housing the motor starters and protection Comply
apparatus, motor operation control and indicating devices,
etc, shall be supplied and installed for the system. The control
panel shall be totally enclosed metal-clad wall mounted front
access type and installed in the plantroom.

The control panel shall be fabricated of minimum 1.30mm Comply


thick sheet steel pressed and rolled to shape having all joints
neatly welded and finished flush. Door shall be hinged type
with concealed hinges and secured by captive knurled thumb
screws.
The control panel shall be provided with the following : Comply
- Circuit breakers of correct rating for short-circuit protection.
- Thermal overload relays for overcurrent protection.
- All the control and indicating devices as shown in the
drawings accompanying this Specification.

The contractor is required to ensure that all indicating lights Comply


on the control panel are properly labelled.
All control wires must be numbered for easy troubleshooting Comply
and identification.
- Operator control console shall be constructed from 2.60mm Comply
thick sheet steel complete with suitable doors that allow easy
access to all equipment installed therein.
- The control console shall be finished smooth with two coats
of primer and two coats of semi-glossy synthetic enamel to
colour No 631 of BS 381C or approved equivalent standard.
- Operator control console shall have a vertical white PVC
graphic panel complete with ON/OFF indicating lights for all
main airconditioning equipment ie chillers, chilled water
pumps, condenser water pumps and cooling towers.

In cases where a computer terminal is required, a network link Comply


to the Building Management System shall be provided to
enable the proper operation from within the chiller control
room.
Electrical equipment or systems involving sudden changes, or Comply
interruption or low frequency or of direct electric currents such
as thermostatically controlled devices, contactors,
commutators shall be fitted with radio and television
interference suppression components suitable to meet the
levels specified in BS 800 'Limits of Radio Interference' or
approved equivalent standard.

- All motors shall be Energy Efficient (High Efficiency) type Comply


with minimum guaranteed motor efficiency of 84% or more in
accordance with NEMA MG1 -12.53a or approved equivalent
standard and tested as per IEEE 112 Method B or approved
equivalent method.
+ Motors from 2 to 10 kW rating the minimum efficiency shall
be 85%.
+ Motors rating of more than 10 kW the minimum efficiency
shall be 90%.
- Motors of 0.75kW rating and above shall be wound for 400 Comply
Volts, 3 phase, 50Hz supply.
- Motors of less than 0.75kW rating may be wound for 230
Volts, 1 phase, 50Hz supply.
- All motors shall be wound for continuous duty of not less
than 12 hours.

- All motors shall be sized to not less than 20% higher than Comply
the power absorbed (brake horsepower) of the associated
equipment.
Motors shall be NEMA Design B Standard or approved Comply
equivalent standard. The testing for efficiency shall be
performed in compliance with NEMA MG1 -12.53a or
approved equivalent standard which specified dynamometer
testing per IEEE U2 method B or approved equivalent
standard .

All motors shall be totally enclosed fan cooled type. Motor Comply
fans shall be antistatic, polypropylene, corrosion resistant and
bi-directional. Motor bearings shall be of ball or roller or
sleeve type as applicable and amply sized to perform
the duties required.

All motors shall have cast iron frame and end-shield Comply
construction for 182T and 449T frame. Steel frame and
aluminium end-shield construction shall be acceptable for
143T to 145T frame. Motor terminal box shall be diagonally
split and rotatable. The terminal boxes shall be suitable for
reception of cables or screwed conduits entry as required.

All motors shall have full class F non-hydroscopic insulation Comply


system with multiple dipped and baked varnish treatment.

The maximum motor sound pressure level shall not exceed Comply
85 dBA.
For all standby equipment, motors shall be equipped with Comply
heaters. The heaters shall be connected up to ensure that
when the motor is on, the heater is switched off and vice
versa.
The labelling of efficiency on the nameplate shall be in Comply
compliance with NEMA MG1 -12.53b or approved equivalent
standard, the full load guaranteed efficiency shall also be on
the nameplate.
Motor starters shall be constructed for intermittent duty in Comply
accordance with BS 587 or approved equivalent standard and
equipped with overload, single-phasing and under-voltage
protection. Where remote control is required, starters shall be
of contactor type with coils wound for 230 Volt 50 cycle
operation. Heaters shall generally be located in the bottom of
the cubicle, with the thermostat at the top. The heater terminal
at the motor and starter shall be clearly labelled:
"CAUTION - MOTOR HEATER - ALIVE WHEN MOTOR
STOPPED"

Starters shall be of the following types unless otherwise Better


indicated on the Tender Drawings:
* Up to 4 kW motors - Direct-on-line
* 4 kW to 1 1 kW motors - Star/delta type
* 11 kW motors or above - VSD type.
Auto-transformer starters shall limit the motor starting current Comply
to 1.6 times the normal full-load current.
Both star/delta and auto-transformer starters shall be of the Comply
close transition types. The auto-transformer starters shall be
provided with tappings suitable for connection to 40% - 75%
of line voltage in steps of 5%. All motor starters shall be tested
to BS 587 or approved equivalent standard.

All starters shall be automatic type complete with Comply


START/STOP push-buttons auxiliary contacts as required,
MANUAL/OFF/AUTO selector switch and provision for remote
controls as required. All motors shall be connected through
suitable fuses or MCCB in addition to starters.

The supply to each motor shall be controlled by means of an Comply


efficient cut off switch placed in such a position as to be easily
handled by the person in charge of the motor, and connected
such that the power supply can be cut-off from the motor and
from the regulating switch, resistances or other devices
connected to it.

Motors arranged for remote control shall be provided with a Comply


similar cut-off switch placed in such a position as to be easily
handled by the person in charge of the motor, and connected
such that the power supply can be cut-off from the motor and
from the regulating switch, resistances or other devices
connected to it.

All isolating switches, fuse switches and switch fuses shall be Comply
500 Volts, metal clad, conforming with the provisions of BS
861 or approved equivalent standard.
Power factor correction capacitors shall be provided as Comply
required to correct the power factor of all motors over 1.5kW
in size to 0.85 lagging, or better, at all loads.
The capacitors shall be installed adjacent to the motors and Comply
complete with the necessary protection fuses, discharge
resistors and all wiring and connections.
50Hz 400/230V three phase four wire AC Frequency Comply
Controlled drives (shall be called FCD hereinafter)
The FCD shall operate in conjunction with mechanical system Comply
components including chilled water pumps and AHU fans. The
FCD shall be able to operate the standard AC induction motor
of the pumps and fans from a minimum of 10% to 100% of the
rated speed
The FCD shall be of high efficiency, low maintenance and Comply
adjustable frequency and voltage type using the principle of
Pulse Width Modulation design. The FCD shall be suitable for
automatic control in response to 4 to 20 mA or 0 to 10V input
signal, the output frequency of 0 to 50 Hz shall be in
proportion to this signal range

The FCD shall be capable of withstanding any combination of Comply


the following environmental conditions in which it must
operate without causing electrical/mechanical damage of
degradation of performance
- Ambient temperature : up to 40 C
- Relative Humidity : up to 90%
- Surge suppressor : built-in protection against lightning
surges introduced on the primary source.
The FCD shall have built-in air blower unit so that the FCD Comply
can be forced air cooled to operate within the above rated
environmental conditions. The FCD shall be housed in
respective motor starter panel. Appropriate air inlet and
exhaust shall be provided to ensure adequate ventilation for
proper operation.

The FCD shall consist of the following major components: Comply


- rectifier
- inverter
- control and display panel
- RFI filter to curve G or N of VDE0875 or equivalent.
The FCD shall be equipped with Auto/OFF/Manuals switch for Comply
selection of control mode. During manual mode operation, the
FCD shall be used to provide variable speed motor controls to
the pumps and fans connected with the capability of soft start
(to restrict current during acceleration) and soft stop (to
restrict over voltage during deceleration). During automatic
mode operation, the FCD shall have the capability of soft
start, soft stop and automatically adjust its speed based on
external control signal to provide the load required by the
system. The FCD shall have facility for local setting of
frequency manually in the event of automatic control signal
failure.

The FCD shall be designed to perform and work well with the Comply
motor without causing overheating and damage to either the
controller or the motor. The tenderer shall ensure the
matching of the FCD to the motor. In addition, the FCD shall
have adjustable starting torque boost to suit the required
starting torque of the load. The overall efficiency of the
combined FCD and the matched-motor shall be not less than
85% at full load and 100% rated speed of the motor.

The FCD shall have the following electrical characteristics: Comply


- Input power - Voltage: 400/230V ± 10%
Frequency : 50Hz ± 5%
Power Factor : 0.85 - 0.95 full load
- Output power - Voltage :400/230V, 3 phase,
4 wire system
Frequency : adjustable from 10% -
Regulation 100% of rated speed
Overload : 150% of full load for ratings 60 seconds, 200% for
0.5 seconds with inverse time characteristics
Efficiency : 90% minimum from 50% to 100% rated speed
Power factor : 0.9 minimum from 50% to 100% rated speed

The FCD shall have RS485 interfaced built-in allowing the Comply
invertor to be used in conjunction with external control system
within a multi-drop LAN configuration. This interface shall
enable the various parameter settings of FCD to be input via
BMS control. In addition the FCD shall have the capability to
retain these settings within non-volatile EEPROM memory.
The parameters shall include but not limit to;
acceleration/deceleration time setting, frequency setting,
multi-speed setting automatic restored after instantaneous
power failure etc.
The FCD shall make available the following output signals for Comply
the external controller in addition to a summary alarm voltage
free contact:
- inverter running
- inverter overload alarm
- analog signal output reflecting the actual inverter frequency
output.

The display panel shall incorporate indication of output Comply


frequency, FCD status indications, fault diagnostics indicators,
audible alarm and indication for any
abnormalities eg overload shutdown, grounded DC lms,
rectifier failure, inverter failure etc. The panel shall also
incorporate alarm reset button mode selector switch, facility to
set frequency acceleration time etc manually.

The FCD shall include DC Link Filter or Harmonic Filter to Comply


suppress the Total Harmonic Distortion of maximum 5 % in
the mains by limiting the level of ripple in the DC link.