HVAC SYSTEM
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
1 CHILLER
Trane, Carrier, McQuay and York
Manufacturer:
International
USA, Western Europe and Japan with
Origin:
acceptable manufacture
QCVN 09:2013/BXD.
Air Conditioning and Refrigeration Institute
(ARI) Standard 550/590-latest edition.
American Society of Heating, Refrigerating,
Standards:
and Air Conditioning Engineers (ASHRAE).
American Society of Mechanical Engineers
(ASME).
Tubing
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.2 AHU-G-2
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 37915
Ent. Air DB/WB, °C 25.8/17.5
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 204.50
Sensible Clg. Cap., kW 169.60
Fluid Flow Rate, L/s 8.81
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.3 AHU-G-1B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 33079
Ent. Air DB/WB, °C 27.5/19.8
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 250.00
Sensible Clg. Cap., kW 166.90
Fluid Flow Rate, L/s 10.80
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.4 AHU-G-3A
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 34069
Ent. Air DB/WB, °C 27.4/19.7
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 249.50
Sensible Clg. Cap., kW 167.20
Fluid Flow Rate, L/s 10.75
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
NVL Page 10 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 34069
Ent. Air DB/WB, °C 27.4/19.7
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 249.50
Sensible Clg. Cap., kW 167.20
Fluid Flow Rate, L/s 10.75
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
NVL Page 12 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
Belt Guard
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 43650
Ent. Air DB/WB, °C 26.4/18.1
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 257.10
Sensible Clg. Cap., kW 200.70
Fluid Flow Rate, L/s 11.07
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Motor Class
Motor Accessories
Belt Guard
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 32418
Ent. Air DB/WB, °C 27/19.1
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 222.70
Sensible Clg. Cap., kW 157.70
Fluid Flow Rate, L/s 9.60
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.8 AHU-G-6
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 23454
Ent. Air DB/WB, °C 26.6/18.4
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 114.70
Sensible Clg. Cap., kW 109.70
Fluid Flow Rate, L/s 6.23
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 38570
Ent. Air DB/WB, °C 26.8/18.5
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 245.20
Sensible Clg. Cap., kW 184.00
Fluid Flow Rate, L/s 10.56
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
NVL Page 20 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 28283
Ent. Air DB/WB, °C 27.4/19.6
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 208.50
Sensible Clg. Cap., kW 140.40
Fluid Flow Rate, L/s 8.98
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
NVL Page 22 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 32900
Ent. Air DB/WB, °C 27.6/19.7
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 208.50
Sensible Clg. Cap., kW 246.30
Fluid Flow Rate, L/s 10.61
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.12 AHU-G-1-3A,3B,3C
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 29086
Ent. Air DB/WB, °C 27.3/19.5
Lvg. Air DB/WB, °C 11.8/11.2
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 208.90
Sensible Clg. Cap., kW 141.50
Fluid Flow Rate, L/s 9.00
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.12 AHU-G-2-1A,1B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 47864
Ent. Air DB/WB, °C 26.6/18.2
Lvg. Air DB/WB, °C 11.7/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 284.60
Sensible Clg. Cap., kW 220.20
Fluid Flow Rate, L/s 12.26
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.12 AHU-G-2-2A,2B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 40968
Ent. Air DB/WB, °C 26.8/18.7
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 264.30
Sensible Clg. Cap., kW 195.00
Fluid Flow Rate, L/s 11.39
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
NVL Page 30 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.12 AHU-G-2-3A,3B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
CENTRIFUGAL FANS
Fan Type
Fan Supplier
Fan Size
Fan Direction
Fan Efficiency %
Fan Outlet Velocity, m/s
External Static Pressure, Pa
System Static Pressure, Pa
Other Static, Pa
Total Static Pressure, Pa
Total Pressure, Pa
Fan Speed, rpm
Shaft Power, kW
Motor Power, KW
Motor Power, hp
Motor Brand
Motor Voltage (V-phase-Hz)
Motor Poles
Motor Class
Motor Accessories
Belt Guard
Drive
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 28388
Ent. Air DB/WB, °C 26.4/18
Lvg. Air DB/WB, °C 11.7/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 160.20
Sensible Clg. Cap., kW 127.50
Fluid Flow Rate, L/s 6.90
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
NVL Page 32 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.13 AHU-G-2-4A,4B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 36932
Ent. Air DB/WB, °C 26.5/18.2
Lvg. Air DB/WB, °C 11.8/11.1
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 224.80
Sensible Clg. Cap., kW 174.00
Fluid Flow Rate, L/s 19.37
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.14 AHU-G-2-5A,5B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 43121
Ent. Air DB/WB, °C 26.7/18.6
Lvg. Air DB/WB, °C 11.8/11.1
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.15 AHU-G-2-6A,6B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 47072
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.16 AHU-G-2-7A,7B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 39789
Ent. Air DB/WB, °C 26.2/17.6
Lvg. Air DB/WB, °C 11.7/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 213.30
Sensible Clg. Cap., kW 178.80
Fluid Flow Rate, L/s 9.19
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.17 AHU-G-2-8A,8B
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
Face Area, sqm
Face Velocity, m/s
Fin Material
Tube Material
Header Material
Coolant
Actual Airflow, cmh 34673
Ent. Air DB/WB, °C 26.3/17.7
Lvg. Air DB/WB, °C 11.8/11.0
Ent./Lvg. Fluid Temp., °C 6.7/12.3
Total Cooling Cap., kW 192.50
Sensible Clg. Cap., kW 157.90
Fluid Flow Rate, L/s 8.29
Fluid Pressure Drop, kPa
Air Friction, Pa
Bypass Factor
AHU Weight(KG)
AHU Height(mm)
AHU Width(mm)
AHU Length(mm)
DRAIN PANS
Material: stainless steel
Insulation: 25mm thickness, 32 kg/m3 density
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.17 AHU-G-2-9A,9B
Manufacturer:
Origin:
Sound level
COIL
Coil Type
Row
Fin Density (FPI)
Circuit
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
2.18 AHU-G-2-10A,10B
NVL Page 45 of 206 03/23/2019
Item
EQUIPMENT/ MATERIALS SPEC. & DRAWING
No.
Manufacturer:
Origin:
ARI Standard or approved equivalent
Standards: standard by an independent testing
laboratory.
Models:
Air Volume:
External Static Pressure:
Others
All casings, housings, plenums
and chambers
Having a dimension between 1000mm and
1500mm, shall not be less than 1.3mm
In low and medium pressure thick galvanised sheet metal.
systems Exceed 1500mm in any dimensions shall
be not less than 1.6mm thick galvanised
sheet metal.
Sound level
COIL
Coil Type
Row
AIR FILTERS
Type: The disposable panel or the automatic roll
Air Volume
Panel Filter Data:
Panel Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Supplier:
Frame Thickness:
Bag Filter Data:
Bag Filter Class:
Initial Pressure Drop:
Aver Pressure Drop:
Final Pressure Drop:
Calc Pressure Drop:
Accessory:
Supplier:
Frame Thickness:
Bracket Material:
3 Chiller water fan coil unit
INDOOR UNIT
Galvanized steel bowdlerized and finished
casing
with baked enamel
The condenser coil copper
fan centrifugal forward curve type
VRF SYSTEM PERFORMANCE
Noise Level - Fan Coil Units
Up to 3.5 KW 42 dB(A)
Up to 5.2 KW 45 dB(A)
Up to 8.8 KW 49 dB(A)
Up to 14.5 KW 52 dB(A)
Up to 23.0 KW 55 dB(A)
Noise Level - Condensing Unit
Up to 3.5 Kw 46 dB(A)
Up to 5.2 Kw 52 dB(A)
Up to 8.8 Kw 54 dB(A)
Up to 14.5 Kw 56 dB(A)
Up to 23 Kw 59 dB(A)
Up to 30 Kw 61 dB(A)
HVAC SYSTEM
Carrier Comply
USA Comply
QCVN 09:2013/BXD.
Air Conditioning and Refrigeration
Institute (ARI) Standard 550/590-
latest edition.
American Society of Heating,
Refrigerating, and Air
Conditioning Engineers
(ASHRAE). Comply
American Society of Mechanical
Engineers (ASME).
The regulation of refrigerants to
be limited & banned in Viet nam
to 2020 (No.47/2011/TTLT-BCT-
BTNMT, dated 31 December
2011)
19XR-6669465LEH52 Comply
Starter - Unit Mounted, Wye-Delta Comply
R-134a Comply
Installed Comply
Installed Comply
Cooling Comply
465 Comply
21 Comply
0.94 Comply
0.97 Comply
44.15 oC Comply
3067 Kw Comply
147.60 Comply
58.8 Kpa Comply
31.0 Comply
36.0 Comply
Proposed by the supplier and
0.00440 Deviation
maintaining technical
0.28 oC Comply
11719 Kg Comply
13316 Kg Comply
727 Kg Comply
8 Comply
31 Comply
719.0 Comply
777 Comply
1683 Comply
4864 Comply
722 Comply
1600 Comply
903 Comply
5% Comply
21.68 oC Comply
-0.06 Comply
10% Comply
30.84 Comply
20.4 kPa Comply
16.0 kPa Comply
36.58 oC Comply
6.54 oC Comply
6.41 oC Comply
0.22 oC Comply
1.75 m/s Comply
1.87 m/s Comply
Carrier Comply
USA Comply
39G1825(50mm) Comply
33079.00 Comply
850 Pa Comply
12 FPI Comply
FL Comply
3.70 Comply
2.48 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
33079 Comply
27.5/19.8 Comply
10.9/10.9 Comply
6.7/12.3 Comply
266.00 Comply
181.00 Comply
11.30 Comply
74.00 Comply
166.00 Comply
0.00 Comply
1881.00 Comply
2000.00 Comply
2600.00 Comply
3800.00 Comply
Std-Painted GI Comply
PU Foam Comply
Carrier Comply
USA Comply
39G2125(50mm) Comply
37915 Comply
1150 Pa Comply
5 Comply
14 FPI Comply
FL Comply
4.27 Comply
2.47 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
37915 Comply
25.8/17.5 Comply
11.2/10.9 Comply
6.7/12.3 Comply
216.00 Comply
184.00 Comply
9.20 Comply
26.00 Comply
153.00 Comply
0.04 Comply
2204 Comply
2300 Comply
2600 Comply
4100 Comply
Std-Painted GI Comply
PU Foam Comply
25mm Comply
GI Steel Comply
Carrier Comply
USA Comply
39G1825(50mm) Comply
33079 Comply
600 Pa Comply
Std-Painted GI Comply
PU Foam Comply
Carrier Comply
USA Comply
39G1825(50mm) Comply
34069 m3/h Comply
650 Pa Comply
Std-Painted GI Comply
PU Foam Comply
250 Pa Comply
154 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply
Carrier Comply
USA Comply
39G2025(50mm) Comply
34069 m3/h Comply
850 Pa Comply
Std-Painted GI Comply
PU Foam Comply
154 Pa Comply
250 Pa Comply
154 Pa Comply
Magnehelic Gage With Plastic
Comply
Tubing
Factory Supplied Bag filter Comply
25mm Comply
GI Steel Comply
Carrier Comply
USA Comply
39G2230(50mm) Comply
43650 m3/h Comply
1350 Pa Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 96.2
dB(A)
Comply
Sound power level inlet 88.9
dB(A)
Std-Painted GI Comply
PU Foam Comply
Carrier Comply
USA Comply
39G1825(50mm) Comply
32418 m3/h Comply
1000 Pa Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 97.3
dB(A)
Comply
Sound power level inlet 90.0
dB(A)
Std-Painted GI Comply
PU Foam Comply
50mm Comply
Carrier Comply
USA Comply
39G1622(50mm) Comply
23454 m3/h Comply
1000 Pa Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 93.7
dB(A)
Comply
Sound power level inlet 86.5
dB(A)
PU Foam Comply
164 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply
Carrier Comply
USA Comply
39G2125(50mm) Comply
38570 m3/h Comply
800 Pa Comply
30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 94.3
dB(A)
Comply
Sound power level inlet 87.1
dB(A)
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Comply
Panel Filter + Bag Filter Comply
38570 m3/h Comply
182 Pa Comply
250 Pa Comply
182 Pa Comply
Factory Supplied HVF filter Comply
50mm Comply
Carrier Comply
USA Comply
39G1822(50mm) Comply
28283 m3/h Comply
800 Pa Comply
15.22 Comply
22.00 Comply
25.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet
96.9dB(A)
Comply
Sound power level inlet 89.6
dB(A)
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G1825(50mm) Comply
32900 m3/h Comply
800 Pa Comply
1477.00 Comply
1648.00 Comply
17.50 Comply
30.00 Comply
30.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 97.0
dB(A)
Comply
Sound power level inlet 89.7
dB(A)
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Comply
Panel Filter + Bag Filter Comply
Carrier Comply
USA Comply
39G1824(50mm) Comply
29086 m3/h Comply
800 Pa Comply
12.62 Comply
800.00 Comply
507.10 Comply
0.00 Comply
1307.10 Comply
1401.00 Comply
1554.00 Comply
14.40 Comply
18.50 Comply
25.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 94.5
dB(A)
Comply
Sound power level inlet 87.3
dB(A)
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G2230(50mm) Comply
THF Comply
81.00 Comply
13.14 Comply
1000.00 Comply
474.60 Comply
0.00 Comply
1474.60 Comply
1577.00 Comply
1296.00 Comply
25.88 Comply
37.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 97.8
dB(A)
Comply
Sound power level inlet 90.6
dB(A)
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G2226(50mm) Comply
40968 m3/h Comply
1000 Pa Comply
Kruger Comply
BDB710TM Comply
THF Comply
78.72 Comply
14.12 Comply
1000.00 Comply
497.60 Comply
0.00 Comply
1497.60 Comply
1616.00 Comply
1507.00 Comply
23.36 Comply
30.00 Comply
40.00 Comply
TECO Comply
400V-3Ph-50Hz Comply
4-pole Comply
F, IP55 Comply
No Comply
No Comply
Fixed (1.5SF) Comply
Sound power level outlet 95.3
dB(A)
Comply
Sound power level inlet 88.0
dB(A)
Std-Painted GI Comply
NVL Page 80 of 206 03/23/2019
CONTRACTOR OFFER COMPLY/ DEVIATION REMARK
PU Foam Comply
Carrier Comply
USA Comply
39G1822(50mm) Comply
28388 m3/h Comply
1000 Pa Comply
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G2125(50mm) Comply
36932 m3/h Comply
1000 Pa Comply
151.00 Comply
0.03 Comply
2204 Comply
2300 Comply
2600 Comply
4100 Comply
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G2230(50mm) Comply
43121 m3/h Comply
1000 Pa Comply
6.7/12.3 Comply
280.00 Comply
216.00 Comply
11.90 Comply
45.00 Comply
114.00 Comply
0.03 Comply
2575 Comply
2400 Comply
3100 Comply
4300 Comply
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G2230(50mm) Comply
47072 m3/h Comply
1000 Pa Comply
26.6/18.3 Comply
11.7/11.4 Comply
6.7/12.3 Comply
289.00 Comply
233.00 Comply
12.30 Comply
48.00 Comply
130.00 Comply
0.04 Comply
2575 Comply
2400 Comply
3100 Comply
4300 Comply
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G2226(50mm) Comply
39789 m3/h Comply
900 Pa Comply
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Comply
Panel Filter + Bag Filter Comply
39789 m3/h Comply
Carrier Comply
USA Comply
39G2025(50mm) Comply
34673 m3/h Comply
1000 Pa Comply
Copper Comply
Steel Comply
Fresh water Comply
34673.00 Comply
26.3/17.7 Comply
11.7/11.3 Comply
6.7/12.3 Comply
194.00 Comply
167.00 Comply
8.20 Comply
23.00 Comply
126.00 Comply
0.05 Comply
2023 Comply
2200 Comply
2600 Comply
3900 Comply
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G1824(50mm) Comply
31793 m3/h Comply
1000 Pa Comply
3.53 Comply
2.50 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
31793.00 Comply
26.3/17.9 Comply
11.3/11.1 Comply
6.7/12.3 Comply
189.00 Comply
157.00 Comply
8.00 Comply
34.00 Comply
158.00 Comply
0.03 Comply
1814 Comply
2000 Comply
2500 Comply
3800 Comply
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Carrier Comply
USA Comply
39G2226(50mm) Comply
40541 m3/h Comply
900 Pa Comply
12 FPI Comply
FL Comply
4.61 Comply
2.44 Comply
Alum Comply
Copper Comply
Steel Comply
Fresh water Comply
40541.00 Comply
26.2/17.6 Comply
11.7/11.3 Comply
6.7/12.3 Comply
224.00 Comply
195.00 Comply
9.60 Comply
27.00 Comply
127.00 Comply
0.05 Comply
2273 Comply
2400 Comply
2700 Comply
4100 Comply
Std-Painted GI Comply
25mm thickness, 32 kg/m3
Comply
density
PU Foam Comply
Comply
Panel Filter + Bag Filter Comply
40541 m3/h Comply
Carrier Comply
Malaysia Comply
ARI Standards Comply
Daikin Comply
Thai Lan Comply
50% - 200% Comply
Comply
50m Comply
90m Comply
R410A Comply
3.94 Comply
30 dB(A) Comply
31 dB(A) Comply
38 dB(A) Comply
45 dB(A) Comply
48 dB(A) Comply
38 dB(A) Comply
43 dB(A) Comply
50 dB(A) Comply
53 dB(A) Comply
57 dB(A) Comply
58 dB(A) Comply
Comply
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
COOLING TOWER
Manufacturer:
Origin:
Models:
Type
Thermal capacity
Energy efficiency
requirements:
Quality Assurance
Warranty
Seismic Certification
Wind Certification
Corosion resistant
construction
Coil section
Casing Panels
Water distribution
system
Fan(s)
Fan motor
Plenum access
Noise level
Internal platform
Excutions
HVAC SYSTEM
The fill and integral drift eliminators shall be formed from self-
extinguishing (as per ASTM-568) polyvinyl chloride (PVC)
having a flame spread rating of 5 per ASTM E84
and shall be impervious to rot, decay, fungus and biological
attack.
VAC SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Poocheon comply
Korea comply
4PIC-3575W
Closed Type with Plume Abatement comply
1200RT Comply
Comply
Deviation
The fill and integral drift eliminators shall be formed from self-
extinguishing (as per ASTM-568) polyvinyl chloride (PVC)
having a flame spread rating of 5 per ASTM E84
and shall be impervious to rot, decay, fungus and biological Comply
attack.
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
AHU
Manufacturer:
Origin:
Type
GENERAL
Standard
Components
HOUSING
CENTRIFUGAL FANS
COOLING COILS
DRAIN PANS
CASING INSULATION
AIR FILTERS
HVAC SYSTEM
Air filters
Vibration isolators and flexible connections
Supports and brackets
Local control panels and DDC control panels
Air handling unit shall have statically and dynamically
balanced extended shafts complete with pulleys
The housing shall have adequate strength and rigidity under
all operating conditions. The units shall comprise a structural
frame with panels bolted onto the structural frame, and with
neoprene rubber gaskets between frames
The casing panels shall be constructed such that they shall
comprise of two layers of galvanised metal sheet sandwiching
the insulation in-between.
All casings, housings, plenums and chambers in low and
medium pressure systems, having a dimensions between
1000mm and 1500mm, shall not be less than 1.3mm thick
galvanised sheet metal.
All casings, housings, plenums and chambers in low and
medium pressure systems which exceed 1500mm in any
dimensions shall be not less than 1.6mm thick.
All casings, housings, plenums and chambers in high
pressure systems, having a dimensions between 1000mm
and 1500mm shall be not less than 1.6mm
thick.
All casings, housings, plenums and chambers in high
pressure systems which exceed 1500mm in any dimensions
shall be not less than 2.0mm.
VAC SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
COMPLY
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDE
MATERIALS
VARIABLE REFRIGERANT FLOW (VRF) SYSTEMS
Manufacturer:
Origin:
Type
GENERAL
CONTROLS
THERMOSTAT
HVAC SYSTEM
The VRF system shall be equipped with controller that enables safe
operation from 1 0% to 1 25% of the normal capacity. The system shall
be suitable for applications requiring connection to a combination of
different types of fan coil units.
The VRF system shall be able to operate under a minimum piping
distance of 90m (one-way) between the condensing unit and the most
remote fan coil unit,
with 50m level difference
The equipment without
shall run on oil traps.
non-CFC refrigerant and shall be suitable for
operating on 230 volt, single phase; 50 Hz power supply (for fan coil
unit) and 41 5 volts, 3 phase, 50 Hz power supply (for condensing unit).
OUTDOOR CONDENSING UNIT
The condensing unit shall consist of individual compressor-condenser
sections and condenser fan(s) enclosed in a sturdy single weather proof
casing. All safety devices shall be included to ensure safe operation of
the unit. These shall include, but not limited to, high and low pressure
switch, fuses, crankcase heater, fusible plug, over current relay for
compressor, thermal protectors for compressor and fan motors, recycling
guard timer and oil recovery system. A liquid line drier shall be provided.
The coils shall be seamless copper tubing, with aluminium plate fins
mechanically bonded to. All pipe joints shall be brazed. Coil shall be of
the same manufacturer as the unit.
The fan coil unit shall have a fabricated drip tray complete with a
drainage system incorporated. Complete condensate pumping system
with minimum
head of 10 m shall be allowed for indoor units to ensure condensate
water can be discharged to nearest floor trap or stack.
Each refrigerant circuit shall have its own set of electrical control
assembly for operation and control. Individual compressors shall have
auto-reset protection
devices and compressor motor recycling guard timer circuits to prevent
restarting of the compressors immediately after stopping or more than
once every four (4) minutes.
Controller which varies the compressor speed according to the load shall
be
Eachprovided
fan coilfor allshall
unit condensing units.with
be provided It shall provide soft starting
a self-diagnostic of the
wired control
unit with large screen LCD display for operation. It shall be capable of
performing functions such as ON/OFF, setting of room temperature,
timer, air discharge direction, fan speed selection and self diagnosis
message display. Provision shall also be made for it to be permanently
fixed when requested by the Employer
The VRF systems shall also be provided with individual control systems
for all fan coil units and outdoor condenser units either collectively or
individually. The
system shall have a provision for connection to a Programmable Logic
Control
(PLC) via interface port compatible to BACNET. The central controller
shall be able to perform the following functions:
- Simultaneous or individual ON/OFF of the fan coil units
- Temperature setting for each fan coil unit
- Air flow setting of each fan coil
- Fault indication of each fan coil
Up to 3.5 kW 46
Up to 5.2 kW 52
Up to 8.8 kW 54
Up to 1 4.5 kW 56
Up to 23 kW 59
Up to 30 kW 61
Washable Type Air Filters
Washable type air filters of minimum 70% arrestance tested in
accordance with ASHRAE 52-76 Gravimetric Air Filter Test shall be
provided.
SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
TOSHIBA COMPLY
THAILAND COMPLY
VRF COMPLY
The VRF system shall be equipped with controller that
enables safe operation from 10% to 125% of the normal
capacity COMPLY
COMPLY
The fan coil unit shall have a fabricated drip tray complete
with a drainage system incorporated. Complete condensate
pumping system with minimum
head of 10 m shall be allowed for indoor units to ensure COMPLY
condensate water can be discharged to nearest floor trap or
stack.
COMPLY
COMPLY
Each fan coil unit shall be provided with a self-diagnostic
wired control unit with large screen LCD display for operation.
It shall be capable of performing functions such as ON/OFF,
setting of room temperature, timer, air discharge direction, fan
speed selection and self diagnosis message display. COMPLY
Provision shall also be made for it to be permanently fixed
when requested by the Employer
Cooling Capacity
HVAC Page 135 of 206 TECHGEL
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
Up to 3.5 Kw: N/A COMPLY
Up to 5.2 kW: 55/56 dB(A) COMPLY
Up to 8.8 kW: N/A COMPLY
Up to 1 4.5 kW: N/A COMPLY
Up to 23 kW: N/A COMPLY
Up to 30 kW: N/A COMPLY
Washable Type Air Filters
Washable type air filters of minimum 70% arrestance tested in
accordance with ASHRAE 52-76 Gravimetric Air Filter Test COMPLY
shall be provided.
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
1 AXIAL FLOW FAN
Manufacturer:
Origin:
Type
2 CENTRIFUGAL FAN
Manufacturer:
Origin:
Type
Manufacturer:
Origin:
Type
4 PROPELLER FAN
Manufacturer:
Origin:
Type
HVAC SYSTEM
For duties below 0.75 kW, single phase motors are preferred
and shall be of the capacitor start and run design, having
power factor not less than 0.85 at full
load. For ratings from 0.75 kW and above, motors shall be
suitable for three phase operation via direct-on-line starters up
to 4kW and star-delta starters from 4 to 11 kW. For ratings of
11 kW and above, motors shall be the autotransformer type.
VAC SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
KRUGER COMPLY
Viet Nam COMPLY
Axial ducted inline COMPLY
The fans to be installed in the ducted systems
Kruger direct driven axial fan consisting of long casing with
hanger, motor and impeller. Material of casing in galvanised
steel sheet COMPLY
'Impeller consists of aluminium fan blades with manually
adjustable pitch.
COMPLY
COMPLY
KRUGER COMPLY
Viet Nam COMPLY
Centrifugal fan COMPLY
Kruger belt driven single inlet backward curve centrifugal fan
consisting of motor, fanbase, belt cover, pulley
COMPLY
For duties below 0.75 kW, single phase motors are preferred
and shall be of the capacitor start and run design, having
power factor not less than 0.85 at full
load. For ratings from 0.75 kW and above, motors shall be
suitable for three phase operation via direct-on-line starters up COMPLY
to 4kW and star-delta starters from 4 to 11 kW. For ratings of
11 kW and above, motors shall be the autotransformer type.
KRUGER COMPLY
Viet Nam COMPLY
In-line centrifugal fan COMPLY
KRUGER COMPLY
Viet Nam COMPLY
Wall mounted type COMPLY
COMPLY
COMPLY
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
HEAT PUMPS FOR HVAC SYSTEM
Manufacturer:
Origin:
Models:
Type
REFRIGERANT
CABINET
EVAPORATOR
CONDENSER (Water-
cooled)
CENTRIFUGAL FAN
COMPRESSOR
REFRIGERANT
CIRCUIT
INSULATION
HVAC SYSTEM
VAC SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
AERMEC COMPLY
Italia COMPLY
NS1801XH°A°°°00
AIR TO WATER HEAT PUMP COMPLY
The refrigerant used shall be R-134a. COMPLY
It should be weatherproof to IP54 or better. The machine
chassis shall be constructed of 14 gauge hot dipped
galvanized steel and all panels exposed to ambient conditions COMPLY
shall be 20 gauge galvanized steel, plastisol coated.
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DOCUMENT)
MATERIALS
HEAT PUMPS FOR PLUMBING
Manufacturer: A.O.Smith, AERMEC, CALOREC, MITSUBISHI
Origin: Japan, Thailand, Malaysia, England
Models:
Type Hot water heat pump
REFRIGERANT The refrigerant used shall be R-134a.
CABINET It should be weatherproof to IP54 or better. The machine
chassis shall be constructed of 14 gauge hot dipped
galvanized steel and all panels exposed to ambient
conditions shall be 20 gauge galvanized steel, plastisol
coated.
DOUBLE WALL It shall be Shell and Tube type constructed from steel
CONDENSER (shell) and copper (tube). They shall be extremely efficient
COILS and specifically designed for this purpose. They shall be
produced from seamless marine grade 90/10 copper
nickel and certified to British water regulations (BS
standard) for potable water. The condenser shall be
seamless construction and the maximum working water
pressure shall be 10 bar or above.
The coils utilize a "tube-in-tube" design where potable
water flows inside a double-wall convoluted copper tube in
a counterflow direction to the refrigerant vapor flowing in
the annulus between the convoluted tubing an the smooth
outer steel tube which provides efficient heat transfer and
minimizes fouling. Double-wall vented design, the only
true double-wall vented design, separates the
refrigerant from the potable water preventing
contamination in the unlikely event of a leak
in the tubing.
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
CALOREX COMPLY
England COMPLY
PRO PAC-90BH ( PP-90BH)
Hot water heat pump COMPLY
The refrigerant used shall be R-134a. COMPLY
The cabinet shall be weatherproof to IP24. The machine
chassis shall be constructed of 14-gauge
'hot dipped galvanised steel and all panels exposed to
ambient conditions shall be 20-gauge steel COMPLY
'phosphate protected and plastisol coated to RAL7038
Agate Grey (fixed panels) or RAL9002 Grey
COMPLY
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
CRAC UNIT
Manufacturer:
Origin:
Models:
Type
HVAC SYSTEM
CABINET
The cabinet shall be of self supporting welded construction in
1mm sheet steel with base
section supports in 2mm sheet steel for maximum structural
strength with low self
weight.
EVAPORATOR COIL
The evaporator coils shall be mounted on the suction side of
the fans to provide a very
uniform air distribution with low pressure drop and low noise.
The evaporator coils shall be constructed of copper tubes and
aluminium fins and shall
be 4 rows deep, with a maximum face velocity of the air of
2.25 m/s to provide a sensible
heat ratio higher than 98% under normal conditions. An
adjustable air bypass flap shall
be mounted at the top of the coils and extend along their
entire length, to provide control
of air discharge conditions. A stainless steel condensate tray
shall be fitted under the
coil.
HERMETIC COMPRESSORS
The direct expansion refrigeration system shall have a
minimum of two (2) fully hermetic
compressors suitably sized for the specified cooling and
dehumidification. The
compressors shall be fitted with suction gas cooled motors to
provide maximum
reliability, without recourse to pump down cycle, and vibration-
free operation. They shall
be dynamically balanced, mounted on vibration isolators and
shall be fitted with high and
low pressure switches, motor protection, crankcase heaters
and rotalock service valves.
FAN SECTION
The fans shall be of the double width, double inlet centrifugal
type with statically and
dynamically balanced impellers mounted in lifetime lubricated
bearings for quiet,
vibration-free operation. Each fan shall have its own direct
coupled drive motor to
provide standby dependability.
Dehumidification shall be achieved by increasing the cooling
capacity to cause a
lowering in temperature of the cooling coil to that below the
dew point of the air passing
over the coil. Stopping one fan to achieve the
dehumidification effect will not be
accepted.
FILTER SECTION
Two-stage filtration of the re-circulated air shall be
incorporated in the unit to obtain the
required degree of cleanliness of the air in the computer
room. Pre-filters shall be of the
re-generable type and second stage filters shall be of the
deep pleated fabric type
mounted in galvanized frames (or equivalent material which
can resist corrosion) to
permit rapid disposal and replacement without the danger of
dust dispersal. Filtration
efficiency shall be 96% measured by the ASHRAE Standard
52-76 or an approved
equivalent method.
Adjustable differential pressure sensor/ switches shall be
provided across the filters to
activate general alarm to IBMS when the filter is clogged or
low air flow is occurred.
Same time, the “Low air flow” text or the alarm code shall be
displayed at CRAC unit’s
user interface unit.
ELECTRIC REHEAT
A multi-stage electric heater shall be used for reheating during
the dehumidification
cycle. The reheat coil shall be capable of maintaining the
room dry bulb temperature
during the dehumidification mode. The reheat coil shall be
sized to maintain the design
room temperature and humidity without the present of
equipments heat load in the room.
CONTROL SYSTEM
The control system shall be of the microprocessor type
consisting of an operating mode
control section and a display and alarm section. The dry bulb
temperature control
system shall be able to provide an adjustable, finite time
interval between all cooling and
heating stages so as to ensure a smooth response to room
temperature fluctuations.
Wet bulb temperature control shall be provided by top quality
humidistats operating the
dehumidification modes of the system.
VAC SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
STULZ COMPLY
Germany COMPLY
ASD 562 A
Precision air conditioner COMPLY
CABINET
The cabinet shall be of self supporting welded construction in
1mm sheet steel with base
section supports in 2mm sheet steel for maximum structural COMPLY
strength with low self
weight.
EVAPORATOR COIL
The evaporator coils shall be mounted on the suction side of
the fans to provide a very
uniform air distribution with low pressure drop and low noise.
The evaporator coils shall be constructed of copper tubes and
aluminium fins and shall
be 4 rows deep, with a maximum face velocity of the air of
2.25 m/s to provide a sensible
heat ratio higher than 98% under normal conditions. An
adjustable air bypass flap shall COMPLY
be mounted at the top of the coils and extend along their
entire length, to provide control
of air discharge conditions. A stainless steel condensate tray
shall be fitted under the
coil.
HERMETIC COMPRESSORS
The direct expansion refrigeration system shall have a
minimum of two (2) fully hermetic
compressors suitably sized for the specified cooling and
dehumidification. The
compressors shall be fitted with suction gas cooled motors to
provide maximum
reliability, without recourse to pump down cycle, and vibration-
COMPLY
free operation. They shall
be dynamically balanced, mounted on vibration isolators and
shall be fitted with high and
low pressure switches, motor protection, crankcase heaters
and rotalock service valves.
FILTER SECTION
Two-stage filtration of the re-circulated air shall be
incorporated in the unit to obtain the
required degree of cleanliness of the air in the computer
room. Pre-filters shall be of the
re-generable type and second stage filters shall be of the
deep pleated fabric type
mounted in galvanized frames (or equivalent material which
can resist corrosion) to
permit rapid disposal and replacement without the danger of
dust dispersal. Filtration
efficiency shall be 96% measured by the ASHRAE Standard
52-76 or an approved COMPLY
equivalent method.
Adjustable differential pressure sensor/ switches shall be
provided across the filters to
activate general alarm to IBMS when the filter is clogged or
low air flow is occurred.
Same time, the “Low air flow” text or the alarm code shall be
displayed at CRAC unit’s
user interface unit.
ELECTRIC REHEAT
A multi-stage electric heater shall be used for reheating during
the dehumidification
cycle. The reheat coil shall be capable of maintaining the
room dry bulb temperature
during the dehumidification mode. The reheat coil shall be COMPLY
sized to maintain the design
room temperature and humidity without the present of
equipments heat load in the room.
CONTROL SYSTEM
The control system shall be of the microprocessor type
consisting of an operating mode
control section and a display and alarm section. The dry bulb
temperature control
system shall be able to provide an adjustable, finite time
interval between all cooling and
heating stages so as to ensure a smooth response to room COMPLY
temperature fluctuations.
Wet bulb temperature control shall be provided by top quality
humidistats operating the
dehumidification modes of the system.
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
JET NOZZLES
Manufacturer:
Origin:
Type
MATERIALS
HVAC SYSTEM
VAC SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
ASLI COMPLY
Malaysia COMPLY
Jet Nozzle COMPLY
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DO
MATERIALS
AIR DIFFUSION EQUIPMENT
Manufacturer:
Origin:
Type
SUPPLY AIR
REGISTERS
CEILING DIFFUSERS
VOLUME CONTROL
DAMPERS
OPPOSED BLADE
VOLUME CONTROL
DAMPERS
LINEAR DIFFUSERS
VARIABLE AIR
VOLUME (VAV) BOX
HVAC SYSTEM
All fresh and exhaust louvres and openings shall be fixed with
12mm mesh matt black painted galvanised insect screen on
the inside.
Steel louvres shall be sprayed painted with two generous
layers of zinc chromate non-civic primers while aluminium
louvres shall be anodised. These louvres shall be finished
with two layers of clear methacrylate semi-matt natural
finish of colour to be nominated by the Employer.
All outside air louvres shall have insect screens, air filters and
adjustable volume control dampers. All exhaust air louvres
shall have insect screens.
Volume control dampers shall be of the opposed blade type.
The contractor shall take special care to ensure that all
dampers are free from vibration and rattles under all operating
conditions.
All damper units located behind air diffusers, registers and
grilles shall be painted matt black.
The static pressure drop across the box shall not exceed 35
Pa at the design flow rate. The sound power level in each
octave band 2 through 6 (ie at centre frequency 125 Hz, 250
Hz, 500 Hz, 1000 Hz, 2000 Hz) when measure at 125 Pa
static pressure across the terminal unit shall not exceed:
- casing radiated sound - 40 dB(A)
- discharge sound - 40 dB(A)
VAC SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
ASLI COMPLY
Malaysia COMPLY
All fresh and exhaust louvres and openings shall be fixed with
12mm mesh matt black painted galvanised insect screen on COMPLY
the inside.
Baked white powder coated as standard.
Other available upon request.
COMPLY
All outside air louvres shall have insect screens, air filters and
adjustable volume control dampers. All exhaust air louvres
shall have insect screens.
HD-T is primary designed for manual balancing
application in ventilation systems for volume flw and
pressure control. The galvanized steel locking quadrant
arm (HD-T) or the OM arm linkage (HD-T OM) is mounted COMPLY
on the shaft for manual operation
The static pressure drop across the box shall not exceed 35
Pa at the design flow rate. The sound power level in each
octave band 2 through 6 (ie at centre frequency 125 Hz, 250
Hz, 500 Hz, 1000 Hz, 2000 Hz) when measure at 125 Pa
static pressure across the terminal unit shall not exceed: COMPLY
- casing radiated sound - 40 dB(A)
- discharge sound - 40 dB(A)
HVAC SYSTEM
EQUIPMENT/
Item No. SPECIFICATION (FOLLOW TENDER DOCUMENT)
MATERIALS
1 ELECTRICAL
Power supply
Terminal panel
Anti-Condensation
Heaters
Subsidiary switchboards
and control panels
Wall mounted control
panel
Radio frequency
interference (RFI)
Motors
Motor starters
Motor isolators
AC frequency controlled
drivers (FCD)
Operating Condition
BẢNG ĐÁP ỨNG KỸ THUẬT CỦA THIẾT BỊ VẬT TƯ CHÍNH
ng Hàng Không Quảng Ninh
Thi công Hệ thống ĐHKK & Thông gió, Cấp thoát nước - Nhà ga hành khách
HVAC SYSTEM
- All motors shall be sized to not less than 20% higher than
the power absorbed (brake horsepower) of the associated
equipment.
Motors shall be NEMA Design B Standard or approved
equivalent standard. The testing for efficiency shall be
performed in compliance with NEMA MG1 -12.53a or
approved equivalent standard which specified dynamometer
testing per IEEE U2 method B or approved equivalent
standard .
The FCD shall be designed to perform and work well with the
motor without causing overheating and damage to either the
controller or the motor. The tenderer shall ensure the
matching of the FCD to the motor. In addition, the FCD shall
have adjustable starting torque boost to suit the required
starting torque of the load. The overall efficiency of the
combined FCD and the matched-motor shall be not less than
85% at full load and 100% rated speed of the motor.
C SYSTEM
COMPLY/
CONTRACTOR OFFER REMARK
DEVIATION
- All motors shall be sized to not less than 20% higher than Comply
the power absorbed (brake horsepower) of the associated
equipment.
Motors shall be NEMA Design B Standard or approved Comply
equivalent standard. The testing for efficiency shall be
performed in compliance with NEMA MG1 -12.53a or
approved equivalent standard which specified dynamometer
testing per IEEE U2 method B or approved equivalent
standard .
All motors shall be totally enclosed fan cooled type. Motor Comply
fans shall be antistatic, polypropylene, corrosion resistant and
bi-directional. Motor bearings shall be of ball or roller or
sleeve type as applicable and amply sized to perform
the duties required.
All motors shall have cast iron frame and end-shield Comply
construction for 182T and 449T frame. Steel frame and
aluminium end-shield construction shall be acceptable for
143T to 145T frame. Motor terminal box shall be diagonally
split and rotatable. The terminal boxes shall be suitable for
reception of cables or screwed conduits entry as required.
The maximum motor sound pressure level shall not exceed Comply
85 dBA.
For all standby equipment, motors shall be equipped with Comply
heaters. The heaters shall be connected up to ensure that
when the motor is on, the heater is switched off and vice
versa.
The labelling of efficiency on the nameplate shall be in Comply
compliance with NEMA MG1 -12.53b or approved equivalent
standard, the full load guaranteed efficiency shall also be on
the nameplate.
Motor starters shall be constructed for intermittent duty in Comply
accordance with BS 587 or approved equivalent standard and
equipped with overload, single-phasing and under-voltage
protection. Where remote control is required, starters shall be
of contactor type with coils wound for 230 Volt 50 cycle
operation. Heaters shall generally be located in the bottom of
the cubicle, with the thermostat at the top. The heater terminal
at the motor and starter shall be clearly labelled:
"CAUTION - MOTOR HEATER - ALIVE WHEN MOTOR
STOPPED"
All isolating switches, fuse switches and switch fuses shall be Comply
500 Volts, metal clad, conforming with the provisions of BS
861 or approved equivalent standard.
Power factor correction capacitors shall be provided as Comply
required to correct the power factor of all motors over 1.5kW
in size to 0.85 lagging, or better, at all loads.
The capacitors shall be installed adjacent to the motors and Comply
complete with the necessary protection fuses, discharge
resistors and all wiring and connections.
50Hz 400/230V three phase four wire AC Frequency Comply
Controlled drives (shall be called FCD hereinafter)
The FCD shall operate in conjunction with mechanical system Comply
components including chilled water pumps and AHU fans. The
FCD shall be able to operate the standard AC induction motor
of the pumps and fans from a minimum of 10% to 100% of the
rated speed
The FCD shall be of high efficiency, low maintenance and Comply
adjustable frequency and voltage type using the principle of
Pulse Width Modulation design. The FCD shall be suitable for
automatic control in response to 4 to 20 mA or 0 to 10V input
signal, the output frequency of 0 to 50 Hz shall be in
proportion to this signal range
The FCD shall be designed to perform and work well with the Comply
motor without causing overheating and damage to either the
controller or the motor. The tenderer shall ensure the
matching of the FCD to the motor. In addition, the FCD shall
have adjustable starting torque boost to suit the required
starting torque of the load. The overall efficiency of the
combined FCD and the matched-motor shall be not less than
85% at full load and 100% rated speed of the motor.
The FCD shall have RS485 interfaced built-in allowing the Comply
invertor to be used in conjunction with external control system
within a multi-drop LAN configuration. This interface shall
enable the various parameter settings of FCD to be input via
BMS control. In addition the FCD shall have the capability to
retain these settings within non-volatile EEPROM memory.
The parameters shall include but not limit to;
acceleration/deceleration time setting, frequency setting,
multi-speed setting automatic restored after instantaneous
power failure etc.
The FCD shall make available the following output signals for Comply
the external controller in addition to a summary alarm voltage
free contact:
- inverter running
- inverter overload alarm
- analog signal output reflecting the actual inverter frequency
output.