Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
0-1
January 2008
Sheet 1387
36
37
38
39
40
41
42
43
IT. Starter and Enclosed IT. S801 Soft Starter
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
13/64 Diameter
27
KO KO
2 Mounting Holes
1.97
(50.0) 28
Typical Front View Typical Side View
(Single Unit)
29
Figure 31.1-1. Type 1 Enclosures (Boxes and Covers)
30
General Purpose Type 1 Enclosed MS Starter 19/64 Diameter Lockout Hole
Application 31
MS manual single-phase starters are 5.13
(130.3) 5.88
designed to give positive, accurate, (149.4)
trouble-free overload protection to 32
single-phase motors rated up to 1 hp. 5.81
Typical applications are fans, machine (147.6) 6.72
(170.7)
tools, motors, HVAC, etc. 33
0.75
Table 31.1-1. MS Ratings (19.1) 0.81 2.63
3.63 2.91 (20.6) 0.42
(66.8)
Volts hp Poles (92.2)
3/4 Inch Pipe Top
(73.7)
3.94
(10.7)
3.50
0.44
(11.2)
34
(100.1) (88.9)
120/240 V, 277 Vac 1 1 or 2 3/4 Inch Pipe Top
120/240 Vdc 1 2
240 Vdc 1/4 1 35
32 Vdc 1/4 1 or 2 Figure 31.1-2. Watertight (Cast Aluminum) Figure 31.1-3. Hazardous Location
(Cast Aluminum)
Enclosures 36
■ Type 1: General Purpose. 1.64
■ Type 1: Flush Mounted, General (41.7)
Purpose.
1.52
(38.6)
37
■ Type 3, 4, 5: Watertight. 1.06
(26.9)
■ Type 7D: Class I, Group D Hazardous 0.78 38
Locations. 2.75 Mounting Purposes (19.8)
■ Type 9E, F, G: Class II, Groups E, F, G (69.9) (2) Holes 0.66
(16.8)
Hazardous Locations. 1.38
(35.1) 0.34
39
■ Red pilot light available for NEMA 1, (8.6)
factory installed or field installed kit. Indicating
Light 40
Typical Specifications 1.64 4.50
(41.7) 3.28 (114.3) Handle
Manual single-phase starters shall be (83.3) Guard
Eaton’s Cutler-Hammer Type MS or 41
approved equal for motors rated not 0.22 2.25
(5.6) (57.2)
greater than 1 hp. They shall be built
and tested in accordance with the 42
applicable NEMA standards.
0.31 1.53
1 Unit
The starter shall have a “quick-make, (7.9) (38.9) 43
quick-break” toggle mechanism. The
overload shall have a field adjustment Figure 31.1-4. Flush Plates
allowing up to ±10% variance in ratings
of the nominal heater value. Dimensions in Inches. Not to be used for construction purposes unless approved.
25 4.98
(126.5)
4.72 5.13
3.98 (130.3)
(118.0) 1.05 (101.1)
2.56 5.00
26 2.36
(59.9)
(26.8) 1.02
(25.5) (65.0) (127.0)
27 0.92
7.59 Off 6.00 (23.4)
9.19 8.28
(192.8) (152.4) (233.4) 10.16 (210.3)
28 0.92
(23.4)
(258.1)
Locations. (52.1)
0.63
■ Type 9: Class II, Groups E, F, G
32 Hazardous Locations.
1.25
(31.8) 1.02 0.17
(4.3)
(16.0)
2.50 (25.9)
■ Type 12: Dust-tight Industrial Use. (63.5)
33 Table 31.1-2. B100 Ratings Figure 31.1-5. Type 1 Enclosed Figure 31.1-7. Type 4 Enclosed
NEMA Maximum Horsepower
34 Size 115 200-230 460-575
7.13
Vac Vac Vac (181.1) 3.56
2-Pole, Single-Phase ac (90.4)
5.13
35 M-0 1 2 — (130.3)
2.56
M-1 2 3 — 6.03 (65.0) 5.00 0.27
(153.2) (127.0) (6.9)
M-1P(1-1/2) 3 5 —
5.13
36 3-Pole, 3-Phase ac (130.3)
8.38
(212.9)
M-0 2 3 5
12.06 8.28
M-1 3 7-1/2 10 (306.3) 9.19 (210.3)
37 10.25
4.19
(106.4)
(233.4)
9.41
Typical Specifications (260.4) (239.0)
Off On
All 3-phase manual starters and
38 single-phase starters rated above 1 hp 4.06
.406 Slot
2 Req’d
shall be Eaton’s Cutler-Hammer Type (103.1)
1.50
8.25
B100 or approved equal. They shall be (38.1)
39 built and tested in accordance with the
(209.6) 3.00
(76.2)
applicable NEMA standards.
40 The starter must feature contact 1IN–11.50 NPSK
2 Holes
7.77
(197.4) 5.97
(151.6)
operation which is “quick-make,
6.31
quick-break” and cannot be teased (160.3)
2.33
41 into a partially open condition. There 1.38
(35.1) (59.2)
4.78
must be a provision which blocks the 0.88 (121.4)
closure of the contacts while the line 0.50
6.00
(22.4)
42 terminals are exposed. Operating
(12.7)
(152.4)
handle or buttons must clearly show
by their position whether unit is ON, Figure 31.1-6. Type 7/9 Enclosed Figure 31.1-8. Type 12 Enclosed
43 OFF or TRIPPED.
10 2, 3, 4 CN35 — — 39
20 2, 3, 4, 6, 9, 12 CN35 — —
30 2, 3, 4, 5, 6, 9, 12 CN35 — —
30
30
1 – 12
2, 3, 4, 5, 6, 8, 10, 12
C30CNE
—
C30CNM
—
—
A202
40
60 2, 3, 4, 5, 6, 8, 10, 12 — — A202
60
100
2, 3, 4, 5
2, 3, 4, 5
CN35
CN35
—
—
—
—
41
100 2, 3, 4, 5, 6, 8, 10, 12 — — A202
200 2, 3, 4, 5, 6, 8, 10, 12 — — A202
200 2, 3, 4, 5 CN35 — —
42
300 2, 3, 4, 5 CN35 — —
300 2, 3 — — A202
400 2, 3 — — A202 43
22 CN35-Open (ECL03-Enclosed) Filament Lamps — Incandescent, Table 31.2-2. Ratings — CN35 ac Lighting
Contactors — Electrically Held
Infrared, Heating — 480 V maximum.
Maximum Number
Resistance Heating — Radiant Ampere Rating of Poles
23 and convection heating, furnaces
10 2, 3, 4
and ovens.
20 2, 3, 4, 6, 9, 12
Cover Control — See Enclosed 30 2, 3, 4, 5, 6, 9, 12
24 Control Product Guide PG.3.02.T.E 60 2, 3, 4 , 5
100, 200, 300 2, 3, 4, 5
Start-Stop and Hand-Off-Auto only. 400 2, 3
25 Enclosures
Listed ampere ratings are based on a maxi-
mum load voltage of 480 V for tungsten
Open, NEMA Type 1, 3R, 4/4X and 12. lamp applications and 600 V for ballast or
mercury vapor type applications.
26 Additional power poles mounted on side(s)
20 Ampere
Auxiliary Contacts of contactor.
Eaton’s Cutler-Hammer CN35 Lighting
27 Contactors include a NO maintaining
auxiliary contact mounted on right-hand G A G
C
F
side (on 10-ampere, 2- and 3-pole
28 devices, auxiliary contact occupies 4th A Top A Top Side
U Mtd. U
E
Mtd. Mtd. B
power pole position — no increase in X Aux. X Aux. Aux.
dle the switching of tungsten (incandes- are Cutler-Hammer Type CN35 or Auxiliary
ELC03, or approved equal for lighting D Contacts➃
cent filament) or ballast (fluorescent and
33 mercury arc) lamp loads as well as other loads of 10 – 300 A. They are built and
non-motor (resistive) loads. Ratings of tested in accordance with applicable Figure 31.2-2. Open Type, 20 – 30 Ampere
10 – 400 amperes, 1 – 12 poles, open NEMA standards. Sizes, 4 – 6 Poles
34 or NEMA 1, 3R, 4/4X and 12 enclosed. These contactors are designed to
withstand the large initial inrush A G F
Application Description currents of tungsten and ballast lamp C
35 loads as well as non-motor (resistive)
Loads: Top
Mtd.
Top A
Mtd. U
Top
Mtd.
Side
Mtd.
loads without contact welding. Contac- 3 Mtg. Holes Aux. Aux. X E Aux. Aux. B
Ballast Lamps — Fluorescent, for #10-32
36 tors are capable of accepting up to 8 Screws
Mercury Vapor, Sodium Vapor, Quartz auxiliary contacts — top and/or side up Auxiliary
Contacts➃
D
— 600 V maximum. to 60 amperes and side only up to 400
37 amperes. Contactors are capable of
being operated by ac or dc control. Figure 31.2-3. Open Type, 20 – 30 Ampere
Sizes, 4 – 6 Poles
See “Auxiliary Contacts” for type and
38 location of auxiliary contacts supplied.
Enclosed Box Selection Table 31.2-5. Type 3R, 4/4X, 12 Non-combination Table 31.2-6. Type 1 Combination
Table 31.2-4. Type 1 Non-combination Lighting
Lighting Contactors — Electrically Held — CN35 Lighting Contactors 22
Ampere Size (Poles) Box Shipping Ampere Size Box Shipping
Contactors — Electrically Held — CN35 No. Wt. No. Wt.
Ampere Size (Poles) Box Shipping
No. Wt.
Lbs. (kg) Lbs. (kg) 23
Lbs. (kg) Non-reversing Contactors — Electrically Held — Non-reversing (3P Only) —
without Control Power Transformers with or without Control Power Transformers
Non-reversing Contactors —
without Control Power Transformers 10 A (2P, 3P, 4P, 5P, 6P) 5 12 (5.4) 30 A A 35 (16) 24
10 A (2P, 3P, 4P) 1 5 (2.3) 10 A (9P, 10P, 12P, 20P) 7 20 (9.1) 60 A A 36 (16)
20 A (2P, 3P, 4P, 5P) 5 12 (5.4) 100 A C 65 (30)
10 A (2P, 3P, 4P, 5P, 6P) 2 7.3 (3.3)
w/top adders 20 A (6P) 5 14 (6.4) 200 A with Disconnect Switch D 110 (50) 25
10 A (9P, 10P, 12P, 20P) 3 9.5 (4.3) 20 A (9P, 10P, 12P, 20P) 7 20 (9.1) 200 A with Thermal Magnetic E 150 (68)
30 A (2P, 3P, 4P) 5 13 (5.9) Breaker
20 A (2P, 3P) 1 5.2 (2.4)
20 A (2P, 3P, 4P, 5P, 6P) 2 7.3 (3.3) 30 A (5P, 6P) 6 14 (6.4) 300 A E 160 (73) 26
w/top adders & 30 A (9P, 10P, 12P, 20P) 7 20 (9.1) 400 A E 170 (77)
6P w/o top adder
20 A (9P, 10P, 12P, 20P) 3 9 (4.1)
60 A
60 A
(2P, 3P, 4P)
(5P, 6P)
5
6
13 (5.9)
16 (7.3)
Table 31.2-7. Type 3R, 4/4X, 12 Combination 27
20 A (9P, 12P) w/top adders 3 9.3 (4.2) Lighting Contactors
60 A (9P, 10P, 12P) 7 22 (10)
30 A (2P, 3P) 1 5.3 (2.4) Ampere Size (Device) Box Shipping
30 A (2P, 3P, 4P) w/top adders 2 7.3 (3.3)
100 A (2P, 3P) 8 49 (22) No. Wt. 28
100 A (4P, 5P, 6P, 9P) 8 57 (26) Lbs. (kg)
30 A (5P, 6P) 3 9.0 (4.1)
200 A (2P, 3P) 8 110 (50) Electrically Held — Non-reversing (3P Only) —
30 A (5P, 6P) w/top adders 3 9.2 (4.2) 300 A (2P, 3P) 10 113 (51) with or without Control Power Transformers 29
30 A (9P, 10P, 12P, 20P) 3 9.5 (4.3) 400 A (2P, 3P) 10 125 57) 30 A A 35 (16)
30 A (9P, 12P) w/top adders 3 9.7 (4.4) Non-reversing Contactors — 60 A A 36 (16)
60 A (2P, 3P) 1 7 (3.2) with Control Power Transformers
100 A C 65 (30)
30
60 A (2P, 3P) w/top adders 3 9.8 (4.4) 10 A (2P, 3P, 4P, 5P, 6P) 5 16 (7.3)
200 A with Disconnect Switch D 110 (50)
60 A (4P, 5P, 6P, 9P, 10P, 12P) 3 9.5 (4.3) 10 A (9P, 10P, 12P, 20P) 7 20 (9)
60 A (4P, 5P) w/top adders 3 10 (4.5) 20 A (2P, 3P, 4P, 5P) 5 16 (7.3)
200 A E 150 (68) 31
300 A E 160 (73)
100 A (2P, 3P) 4 35 (16) 20 A (6P, 9P, 10P, 12P, 20P) 7 24 (11)
400 A E 170 (77)
100 A (4P, 5P, 6P, 9P) 4 60 (27) 30 A
30 A
(2P, 3P, 4P)
(5P, 6P)
6
6
18 (8.2)
18 (8.2)
With thermal magnetic breaker.
32
200 A (2P, 3P) 4 70 (32)
200 A (4P, 5P, 6P) 10 133 (60) 30 A (9P, 10P, 12P, 20P) 7 24 (11)
300 A (2P, 3P) 10 113 (51) 60 A (2P, 3P) 6 21 (10) 33
300 A (4P, 5P, 6P) 10 136 (62) 60 A (4P, 5P, 6P) 6 23 (10)
400 A (2P, 3P) 10 125 (57) 60 A (9P, 10P, 12P) 7 22 (10)
Non-reversing Contactors — 100 A (2P, 3P) 8 56 (25) 34
with Control Power Transformers 100 A (4P, 5P, 6P, 9P) 8 64 (29)
10 A (2P, 3P, 4P) 2 11 (5.0) 200 A (2P, 3P) 8 117 (53)
10 A (2P, 3P, 4P, 5P, 6P, 9P, 3 13.1 (5.9) 300 A (2P, 3P) 10 120 (54) 35
10P, 12P, 20P) w/top 400 A (2P, 3P) 10 132 (60)
adders
20 A (2P, 3P, 4P, 6P) 2 11 (5.0) 36
20 A (2P, 3P, 4P, 5P, 6P) w/ 3 13.1 (5.9)
top adders
20 A (9P, 10P, 12P, 20P) 3 13.5 (6.1)
37
20 A (9P, 12P) w/top adders 3 13.5 (6.1)
30 A (2P, 3P, 4P) 2 12 (5.4)
38
30 A (2P, 3P, 4P) w/top adders 3 13.1 (5.9)
30 A (5P, 6P) 2 12.5 (5.7)
30 A (5P, 6P) w/top adders 3 13.5 (6.1) 39
30 A (9P, 10P, 12P, 20P) 3 13.9 (6.3)
30 A (9P, 12P) w/top adders 3 14.1 (6.4)
60 A (2P, 3P) 2 12.8 (5.8) 40
60 A (2P, 3P) w/top adders 3 14 (6.4)
60 A (4P, 5P, 6P, 9P, 10P, 12P)
60 A (4P, 5P) w/top adders
3
3
14 (6.4)
14.2 (6.4)
41
100 A (2P, 3P) 4 39 (18)
100 A (4P, 5P, 6P, 9P) 4 67 (30) 42
200 A (2P, 3P) 10 117 (53)
200 A (4P, 5P, 6P) 10 140 (64)
300 A (2P, 3P) 10 120 (54) 43
300 A (4P, 5P, 6P) 10 143 (65)
400 A (2P, 3P) 10 132 (60) For enclosure box dimensions, refer
to Page 31.7-3.
24
25
Conversion Kits
26 Power Poles
These kits are for converting electri-
The C30CNM contactor accepts up to a cally held contactors to mechanically
maximum 6 single- or double-pole (or held units. Kits include control mod-
27 combinations) power poles. These can ule, latch, latch cover and auxiliary
be used to form up to: contacts plus installation instructions.
Electrically Held Base Contactor
28 ■ 12NO poles maximum when 6 Conversion kits are suitable for coil
The C30CNE20_0 Electrically Held double-poles are used in NO voltages of 277 volts and below.
Base Contactor contains a 2NO power positions (1 – 6) or. Table 31.2-20. Table 9. Mechanically Held
29 pole as standard and will allow the ■ 8NC poles maximum with 4 double- Module Kits
addition of power poles to build an poles in the NC position (1 – 4) and
Electrically Held Contactor up to 12 poles Coil Control Catalog
4NO poles with 2 double-poles in Volts Volts Number
30 maximum. A Mechanically Held Module the 2NO positions (5 – 6) 2-Wire
Kit can also be added to convert the
Electrically Held Contactor into a Table 31.2-19. Power Poles 24 – 277 Vac 110 – 120 Vac C320MH2WA0
31 Mechanically Held Contactor in the field. Power Catalog
200 – 277 Vac
24 Vac
C320MH2WH0
C320MH2WT0
Poles Number 12 – 24 Vdc C320MH2WT1
Table 31.2-17. Electrically Held Base Contactor
3-Wire
32 Power
Poles
Catalog
Number
Single-Pole
Double-Pole
C320PRP1
C320PRP2 24 – 277 Vac 110 – 120 Vac C320MH3WA0
200 – 277 Vac C320MH3WH0
2NO C30CNE200 24 Vac C320MH3WT0
33 When ordering, select required contactor 12 – 24 Vdc C320MH3WT1
by Catalog Number and replace the magnet
coil alpha designation in the Catalog
34 Number (...) with the proper Code Suffix
from Table 31.2-18.
39
40
41
42
43
Wiring Diagrams 32
AUTO
A2 A1
42
Remote Auxiliary
Device Contact
OFF
43
OFF/ON/AUTO or HAND/OFF/AUTO Selector Switch
2 Coil
Control Voltage
24 Voltage OFF ON
Fuse
*
3 Coil
A2 A1
OFF/ON or OFF/AUTO Selector Switch
25 4 Electronic-Module
P1 P2 P3 P4 P5 *
ON
5 OFF Fuse
26 Control OFF ON AUTO
Coil
Voltage
6 Voltage *
Remote Fuse
Device Coil
27 View A
A2 A1
HAND/OFF/AUTO or ON/OFF/AUTO Selector Switch
Electronic-Module
P1 P2 P3 P4 P5 View C
28 Not Used
Optional Pilot Devices for 3-Wire Control
C Remote ”NO“ * If Used
OFF Auxiliary
Optional A1 A2 Optional Electronic-Module
29 “N/O”
Aux.
Coil “NC”
Aux.
OFF
P1 P2 P3 P4 P5
Fuse
*
Contacts Coil Contact
Voltage ON Coil
Control Voltage
30 L
2-WIRE CONTROL Voltage OFF ON *
”NC“ Coil Fuse
Refer to View “B” for Control Connections Remote A2 A1
ON Auxiliary
Electronic-Module
31 P1 P2 P3 P4 P5
ON & OFF Pushbuttons
”NO“ Electronic-Module
L Auxiliary P1 P2 P3 P4 P5 *
32 Optional A1 A2 Optional OFF
Fuse
“N/O” Coil “NC” Coil
Aux. Aux. Control Voltage
Contacts Voltage ON *
Coil Contact
33 O Voltage OFF ON ”NC“
Auxiliary A2
Coil
A1
Fuse
C
3-WIRE CONTROL
Refer to View “C” for Control Connections OFF/ON Selector Switch with Spring Return to Center
34
Figure 31.2-6. C30CNM Wiring Diagram
35
Dimensions
36
.35 SIDE VIEW TOP VIEW END VIEW
(9.0)
2 “NO” 2 “NC”
37 Power
Pole Aux P1 P2 P3 P4 P5 Aux
ON ON ON ON ON ON
Contacts Contacts
1 “NO” 1 “NC” 3.86
38 Aux
Contact
Aux (98.0)
Contact
Optional
Power 6.50
Pole
39 (165.1)
Optional “NC” 7.39
Aux Contacts (187.6) NOTE:
40 1 Mounting dimensions remain the same
for 1 to 12 poles.
Optional “NO” 2 Line and Load terminals are interchangeable.
Aux Contacts P1 P2 P3 P4 P5
3 Up to 2NO and 2NC auxiliary contacts can be
41 added onto the base product.
4 Same power pole can be configured as
Mounting Holes NO type or NC type in pole positions 1 – 4;
Accept A1 A2 NO type only in positions 5 – 6.
#10 Screws
42 .35 (9.0) .22 (5.5) 3.75 (95.3)
3.86 (98.0) 4.18 (106.2) .59 (14.9)
8
L2
3 3 2
Control
Fig. B Maintained 2 Module
Pushbutton
1 Black M M
Enclosures 2
Off On
3
White
On Off
Red 38
Open and NEMA Types 1, 3R, 4X and 12.
C A Separate Control
39
Connect separate control
Enclosed Box Selection Table 31.2-27. Type 3R, 4/4X, 12 Table 31.2-28. Type 1 Combination Lighting
22 Table 31.2-26. Type 1 Non-combination
Non-combination Lighting Contactors — Contactors
Magnetically Latched — A202 Ampere Size Box Shipping
Lighting Contactors — Magnetically
Ampere Size (Poles) Box Shipping No. Wt.
Latched — A202
23 No. Wt. Lbs. (kg)
Ampere Size (Poles) Box No. Shipping Lbs. (kg) Magnetically Latched — Non-reversing (3P Only) —
Wt. with or without Control Power Transformers
Non-reversing Contactors —
Lbs. (kg)
24 Non-reversing Contactors—
without Control Power Transformers 30 A A 35 (16)
30 A (2P, 3P, 4P, 5P) 5 13 (5.9) 60 A A 36 (16)
without Control Power Transformers
30 A (6P, 8P, 10P, 12P) 7 21 (10) 100 A C 65 (30)
25 30 A (2P, 3P, 4P, 5P) 2 8.5 (3.9)
30 A (20P) 8 46 (21) 200 A with Disconnect Switch D 110 (50)
30 A (6P, 8P, 10P, 12P) 3 13 (5.9)
60 A (2P, 3P, 4P, 5P) 5 14 (6.4) 200 A with Thermal Mag- E 150 (68)
30 A (20P) 4 35 (16)
60 A (6P, 8P, 10P, 12P) 7 22 (10) netic Breaker
26 60 A (2P, 3P, 4P, 5P) 2 8.7 (3.9)
60 A (20P) 8 48 (22) 300 A E 140 (64)
60 A (6P, 8P, 10P, 12P) 3 13.5 (6.1)
100 A (2P, 3P, 4P, 5P) 8 50 (23) 400 A E 190 (86)
60 A (20P) 4 40 (18)
27 100 A (2P, 3P, 4P, 5P) 4 40 (18)
100 A (6P, 8P, 10P,12P) 9 58 (26)
Table 31.2-29. NEMA 3R, 4/4X, 12 Combination
100 A (20P) 10 100 (45)
100 A (6P, 8P, 10P, 12P) 9 85 (39) Lighting Contactors
200 A (2P, 3P, 4P, 5P) 8 52 (24)
28 100 A
200 A
(20P)
(2P, 3P, 4P, 5P)
9
4
100 (45)
46 (21)
200 A (20P) 10 105 (48)
Ampere Size
(Device)
Box Ship
No. Wt.
300 A (2P, 3P) 10 113 (51) Lbs.
200 A (6P, 8P, 10P, 12P) 9 95 (43)
400 A (2P, 3P) 10 125 (57)
29 200 A (20P) 9 110 (50)
Non-reversing Contactors —
Magnetically Latched — Non-Reversing (3P Only)
— with or without Control Power Transformers
300 A (2P, 3P) 10 115 (52)
with Control Power Transformers 30 A A 35
400 A (2P, 3P) 10 125 (57)
30 Non-reversing Contactors —
30 A (2P, 3P) 6 15 (6.8) 60 A
100 A
A
C
36
65
30 A (4P, 5P, 6P, 8P, 10P, 12P) 7 28 (13)
with Control Power Transformers
30 A (20P) 8 54 (25) 200 A with Disconnect Switch D 110
30 A (2P, 3P, 4P, 5P) 2 12.5 (5.7)
31 30 A (6P, 8P, 10P, 12P) 3 17 (7.7)
60 A (2P, 3P) 6 16 (7.3)
200 A with Thermal Magnetic
Breaker
E 150
37
38
39
40
41
42
43
For enclosure box dimensions, refer
to Page 31.7-3.
Combination Lighting Hammer Type ECL15 (breaker) or ECL13 These contactors shall be designed to
22
(fusible) or approved equal for loads of withstand the large initial inrush cur-
Contactors 30 – 200 A when integral short circuit rents of tungsten and ballast lamp loads
protection is required. as well as non-motor (resistive) loads
Types ECL12, ECL13, ECL14 and without contact welding. Contactors 23
These contactors are designed to shall be capable of accepting up to 8
ECL15 withstand the large initial inrush auxiliary contacts — top and/or side up
Product Description
currents of tungsten and ballast lamp to 60 amperes and side only up to 400 24
loads as well as non-motor (resistive) amperes. Contactors shall be capable
Catalog Number ECL12, ECL13, ECL14 loads without contact welding. The of being operated by ac or dc control.
and ECL15 combination lighting con- contactors are capable of being 25
tactors offer convenient installation of “magnetically held” via a magnetic Features
switching and overcurrent protection latch design utilizing a permanent
magnet. The contactor shall be oper- ■ Disconnect devices — either a 26
in a single enclosure. Combination
ated by a RUN signal and a STOP Series C circuit breaker or a fusible
lighting contactors are ideally suited
signal preventing the contactor from disconnect switch.
for industrial and commercial lighting
applications or where a lighting circuit switching to “OFF” during control ■ Handle mechanism — flange 27
may have to be disconnected for peri- circuit power failures. mounted.
odic maintenance. They may also be Electrically-held combination lighting ■ UL listed.
applied on resistance heating loads. contactors are Cutler-Hammer Type ■ UL service entrance approved for 28
ECL14 (breaker) or ECL12 (fusible) or ■ NEMA 3R outdoor enclosure.
Typical Specifications approved equal for loads of 30 – 400 A
Magnetically latched combination when integral short circuit protection
■ Extra room for modifications such 29
as a 24-hour time clock.
lighting contactors are Eaton’s Cutler- is required.
30
Catalog Number Selection
Table 31.2-30. Enclosed Lighting Contactor Catalog Numbering System 31
EC L 12 D 1 A 3 E - X 32
Design Modification Codes
L = CN35 or A202 Lighting Contactor (See PG03300001E)
33
C = C30CN Lighting Contactor
Table 31.2-31. Ratings — Latched ELC15 Table 31.2-33. Ratings — Electrically-held Table 31.2-34. ELC12 — Fusible Disconnect
22 Series C Circuit Breaker Disconnect ELC14 Series C Circuit Breaker Disconnect Switch
Continuous Circuit Breaker Continuous Circuit Breaker Continuous Fuse Clip
Amperes Ampere System Amperes Ampere System Amperes Ampere System
23 (Enclosed) Rating Voltage (Enclosed) Rating Voltage (Enclosed) Rating Voltage
34
35
36
37
38
39
40
41
42
43
NEMA Motor Starters Application Description ■ Screw type power terminals have
22
captive, backed-out self-lifting pres-
Freedom Type The Freedom to Choose the Right Product sure plates with ± screws — reduced
for the Application wiring time.
Eaton has been supplying quality ■ Accessible terminals for easy wir- 23
industrial control products for more ing. Optional fingerproof shields
than 100 years — the Freedom Series available to prevent electrical shock.
of Contactors and Starters continue in ■ Top located coil terminals conve-
24
this tradition. They offer something no nient and readily accessible. 45 mm
other electrical control line in the contactor magnet coils have three
world can — the “Freedom” to choose terminals, permitting either top or
25
contactors and starters designed to diagonal wiring — easy to replace
NEMA standards. There are many starters or contactors without
difficult choices to be made today in changing wiring layout.
26
matching electrical control to a specific ■ Encapsulated dual voltage/frequency
application, but the Cutler-Hammer
Freedom Series makes it easy.
magnet coils — permanently marked 27
with voltage, frequency and part
number. NEMA Sizes 00 – 0 have
NEMA AN16DN0AB Features non-encapsulated coils as standard. 28
NEMA Size 1
Freedom Family ■ Designed to meet or exceed NEMA,
Product Description UL and CSA.
■ A single family of contactors and 29
The “Freedom Series” starters and starters suitable for applications in Freedom NEMA
contactors listed in this catalog feature NEMA markets. Freedom NEMA contactors and starters
a compact, space-saving design, using ■ Adjustable Bimetallic Ambient are designed to NEMA standards and 30
state-of-the-art technology and the Compensated Overload relays with are extremely rugged products and
latest in high strength, impact and interchangeable heater packs — built for any application. Their long
temperature-resistant insulating available in three basic sizes, electrical/mechanical life is extended 31
materials. Starters and contactors covering applications up to 900 hp through easy maintainability.
are available in the NEMA (National — reducing the number of different
Electrical Manufacturers’ Association) contactor/overload relay combina- ■ Meet and exceed all NEMA,
UL and CSA standards.
32
style. The NEMA devices are sized tions that have to be stocked.
based on traditional NEMA ■ A full line of snap-on accessories — ■ Sized based on standard NEMA
classifications. top and side mounted auxiliary classifications. 33
contacts, solid-state and pneumatic ■ Designed and built for a variety of
timers, etc. demanding applications.
■ Straight-through wiring — line lugs ■ Easy coil change and inspectable/ 34
at top, load lugs at bottom. replaceable contacts.
■ Horizontal or vertical mounting ■ Adjustable/interchangeable heater 35
on upright panel for application packs for flexibility.
freedom. ■ Available in Open and NEMA 1, 3R,
4/4X and 12 enclosures. 36
37
38
39
40
41
42
43
42
43
43
37 ■ Operational Limits:
❑ 85% to 110% of rated voltage — ac
39
40
41
42
43
35
36
37
38
39
40
41
42
43
35
36
37
38
39
40
41
42
43
Table 31.3-7. 380 Volts, 50 Hz Starters — Maximum hp Ratings Table 31.3-12. Wire (75°C) Sizes —
Description NEMA Size AWG or kcmil — NEMA Sizes 00 – 2 22
Open and Enclosed
1 2 3 4 5 6
Catalog Terminal Wire
Maximum hp 10 25 50 75 150 300 Number Size 23
Power Terminals — Load — Cu Only
Table 31.3-8. Motor FLA Current Ranges (Stranded or Solid)
Description NEMA Size C306DN38 32A 14 – 6 AWG 24
1 1 2 3 4 5 6 C306GN38 75A 14 – 2 AWG
Minimum per NEC. Maximum wire size:
1.15 to 0.47 – 3.15 – 3.15 – 9.90 – 9.90 – 38.30 – 38.30 – Sizes 00 – 0 to 8 AWG and Sizes 1 – 2 to 2 25
1.25 S.F. 3.81 27.00 45.00 90.00 135.00 270.00 540.00 AWG.
1.0 S.F. 0.51 – 3.43 – 3.43 – 10.80 – 10.80 – 41.70 – 41.70 –
4.14 27.00 45.00 90.00 135.00 270.00 540.00 Table 31.3-13. Wire (75°C) Sizes — 26
Size 1 Lower Current Range for motor hp range 1/4 hp to 2 hp at 460 V. AWG or kcmil — NEMA Sizes 3 – 8 —
Open and Enclosed
Table 31.3-9. Maximum Horsepower Rating of Starters for 380 V, 50 Hz Application
NEMA Wire 27
IEC Size A B C D E F G H J K L M N P R S Size Size
Power Terminals — Line and Load
hp 3 5 5 10 10 15 20 25 30 40 50 60 75 100 125 150
3 #1/0 – #14 Al Cu
28
Table 31.3-10. Wire (75°C) Sizes — AWG or kcmil — NEMA Sizes 00 – 2 — Open and Enclosed 4 Open – #3/0 – #8 Cu
Enclosed – 250 kcmil – #6 Al Cu
NEMA Cu
5 750 kcmil – #2 or
29
Size Only
(2) 250 kcmil – #3/0 Al Cu
Power Terminals — Line
6 (2) 750 kcmil – #3/0 Al Cu
00 #12 – #16 Stranded, #12 – #14 Solid 7 (3) 750 kcmil – #3/0 Al Cu 30
0 #8 – #16 Stranded, #10 – #14 Solid 8 (4) 750 kcmil – #1/0 Al Cu
1 #8 – #14 Stranded or Solid
2 #3 – #14 (Upper) and/or #6 – #14 (Lower) Stranded or Solid Table 31.3-14. Control Terminals — Cu Only 31
Two compartment box lug.
(2) #12 – #16 Stranded
Table 31.3-11. Overload Relay UL/CSA Contact Ratings Control Circuit (2) #12 – #14 Solid
32
ac Volts 120 V 240 V 480 V 600 V
NC Contact B600
Make and Break Amperes 30 15 7.5 6 33
Break Amperes 3 1.5 .75 .6
Continuous Amperes 5 5 5 5
NO Contact C600
34
Make and Break Amperes 15 7.5 3.375 3
Break Amperes 1.5 .75 .375 .3 35
Continuous Amperes 2.5 2.5 2.5 2.5
dc ratings cover Freedom Series coils only.
36
37
38
39
40
41
42
43
Operations
rior life performance in any worldwide
application. All testing has been based
25 on requirements as found in NEMA
and UL standards and conducted by 1,000,000
Eaton. Actual application life may vary
26 depending on environmental condi-
Size 00
tions and application duty cycle.
Size 2
Size 3
Size 0
Size 1
Size 4
Size 5
Utilization Categories
27 100,000
9 18
27 45 90 135 270
AC-1 — Non-inductive or slightly
1 10 100 1000
inductive loads, such as resistance Break Amperes
28 furnaces and heating. NEMA AC-3 Load Life, Sizes 00 – 5, 480 V 60 Hz
100,000,000
AC-2 — Starting of slip-ring motors.
29 AC-3 — Squirrel cage motors; starting,
switching off motors during running.
10,000,000
30 AC-4 — Squirrel cage motors; starting,
plugging, inching or jogging.
Operations
Size 0
Size 1
Size 2
Size 3
Size 4
Size 5
■ Decide what utilization category
33 your application is and choose the
appropriate curve. 10,000
54 108 153 270 540 822 1620
■ Locate the intersection of the 1 10 100 1000 10,000
34 life-load curve of the appropriate
Break Amperes
NEMA AC-4 Load Life, Sizes 00 – 5, 480 V 60 Hz
contactor with the applications
operational current (Ie), as found on
35 the horizontal axis. Figure 31.3-2. AC-3 and AC-4 Utilization Categories
■ Read the estimated contact life
36 along the vertical axis in number of
operational cycles.
37
38
39
40
41
42
43
ECN 22 2 1 A A F - 23
24
Modification Codes
25
Cover Control
(Starters Only) (See PG03300001E)
Design (Contact Eaton)
N = Freedom NEMA Number of Poles
26
(Contactors Only)
Class 27
Coil Voltage and/or Control Transformers
01 = Contactors
02 = Reversing Contactors (See Tables Below)
05 = FVNR Starter, Non-combination 28
06 = Reversing, Non-combination
07 = FVNR Non-combination, with CPT Disconnect Fuse Clip Ratings
08 =
16 =
Single-Phase FVNR (Freedom Only)
Combination with Disconnect Switch
A=
B=
None
30 A/250 V R
H=
J=
200 A/250 V R
200 A/600 V R
Q=
R=
1200 A/600 V L
1600 A/600 V L
29
17 = Reversing, Combination with Disconnect Switch C= 30 A/600 V R K= 400 A/250 V R S= 2000 A/600 V L
18 = Combination with Disconnect Switch, with CPT D= 60 A/250 V R L= 400 A/600 V R T= by Description
22 = Combination with HMCP/E E= 60 A/600 V R M= 600 A/250 V R U= Engineered 30
23 = Reversing, Combination with HMCP/E F= 100 A/250 V R N= 600 A/600 V R
24 = Combination with HMCP/E with CPT G= 100 A/600 V R P= 800 A/600 V L
33 = Multispeed 2S2W Non-combination
34 = Multispeed 2S1W CT or VT Non-combination HMCP/E or Breaker Ratings 31
35 = Multispeed 2S1W CH Non-combination A= None J= 250 A U = Engineered
36 = Multispeed with Disconnect Switch, 2S2W B= 3A K= 400 A 5= 3A
37 = Multispeed with Disconnect Switch, 2S1W CT or VT C= 7A L= 600 A 6= 7A 32
38 = Multispeed with Disconnect Switch, 2S1W CH D= 15 A M= 800 A 7 = 15 A
39 = Multispeed with HMCP/E, 2S2W E= 30 A N= 1000 A 8 = 30 A
40 = Multispeed with HMCP/E, 2S1W CT or VT 9 = 50 A
41 = Multispeed with HMCP/E, 2S1W CH
F=
W=
50 A
70 A
P=
Q=
1200 A
2000 A I = 100 A
33
G= 100 A R= 3000 A
H= 150 A T= by Description
NEMA Size 34
A= Size 00
Enclosure Type
0= Size 0
1= Size 1 1= Type 1 — General Purpose 35
2= Size 2 2= Type 3R — Rainproof
3= Size 3 3= Type 4 — Watertight (Painted Steel)
4=
5=
Size 4
Size 5
4=
5=
Type 4X — Watertight (304-Grade Stainless Steel)
Type 4X — Corrosion (Nonmetallic)
36
6= Size 6 6= Type 7/9 — Bolted Hazardous Location
7= Size 7 7= Type 7/9 — Threaded Hazardous Location
8= Size 8 8= Type 12 — Dust-Tight 37
9= Size 9 9= Type 4X — 316-Grade Stainless Steel
Enclosed Box Selection Table 31.3-19. Type 3R, 4/4X, 12 Freedom Table 31.3-20. Type 1 Freedom
22 Table 31.3-18. Type 1 Freedom Contactors
Contactors Non-combination Starters
NEMA Size (Poles) Box Shipping NEMA Size Box Shipping
NEMA Size (Poles) Box Shipping No. Weight No. Wt.
23 No. Weight
Lbs. (kg)
Lbs. (kg) Lbs. (kg)
Non-reversing Contactors — Non-reversing Starters —
Non-reversing Contactors — without Control Power Transformers without Control Power Transformers
24 without Control Power Transformers
00 5 14 (6.4) 00 1 7 (3.2)
00 (2P, 3P, 4P) 1 5.25 (2.4) 00 with top adders/SSOL 2 10 (4.5)
0 (2P, 3P, 4P) 5 14 (6.4)
00 (2P, 3P, 4P) 2 7.3 (3.3) 0 1 7.1 (3.2)
1 (2P, 3P, 4P, 5P) 5 15 (6.8)
25 with top adders
2 (2P, 3P, 4P, 5P) 5 15.5 (7.0) 0 with top adders/SSOL 2 10 (4.5)
0 (2P, 3P, 4P) 1 5.25 (2.4)
3 (2P, 3P) 8 45 (20) 1 1 7.9 (3.6)
0 (2P, 3P, 4P) 2 7.3 (3.3)
26 with top adders 4 (2P, 3P) 8 56 (25) 1 – 2 with top adders/SSOL
2
3
2
11.5 (5.2)
8.5 (3.9)
0 (5P) 2 7.3 (3.3) 5 10 140 (64)
1 (2P, 3P) 1 7.9 (3.6) 6 F1E 385 (175) 3 4 35 (16)
27 1 (2P, 3P) 3 11 (5.0) 7 F1E 4 4 47 (21)
with top adders 8 F1E 5 10 139 (63)
1 (4P, 5P) 2 8.3 (3.8) 9 F1E 6 F1E 360 (163)
28 2 (2P, 3P, 4P 5P) 2 8.5 (3.9) Non-reversing Contactors — with Control Power 7 F1E
3 (2P, 3P) 4 35 (16) Transformers 8 F1E
4 (2P, 3P) 4 47 (21) 00 5 18 (8.2) 9 F1E
29 5 10 113 (51) 0 (2P, 3P, 4P) 5 18 (8.2) Non-reversing Starters —
6 F1E 325 (148) 1 (2P, 3P, 4P, 5P) 6 19 (8.6) with Control Power Transformers
30 7 F1E 2 (2P, 3P, 4P, 5P) 6 19.5 (8.9) 00 3 15 (6.8)
8 F1E 3 (2P, 3P) 8 52 (24) 0 3 15 (6.8)
9 F1E 4 (2P, 3P) 8 63 (29) 1 3 16 (7.3)
31 Non-reversing Contactors — 5 10 147 (67) 2 3 16.2 (7.4)
with Control Power Transformers 6 F1E 405 (184) 3 4 42 (19)
00 (2P, 3P, 4P) 2 12 (5.4) 7 F1E 4 4 54 (25)
32 00 (2P, 3P, 4P, 5P) 3 15 (6.8) 8 F1E 5 10 146 (66)
with top adders 9 F1E 6 F1E 385 (175)
0 (2P, 3P, 4P, 5P) 2 12 (5.4) F1E
33 0 (2P, 3P, 4P, 5P) 3 15 (6.8)
3-Pole Reversing Contactors — 7
with or without Control Power Transformers 8 F1E
with top adders
00 6 18 (8.2) 9 F1E
1 (2P, 3P) 2 12.2 (5.5)
34 1 (2P, 3P) 3 12.5 (5.7)
0 6 18 (8.2) Reversing Starters —
1 6 19 (8.6) without Control Power Transformers
with top adders
2 6 19 (8.6) 00 2 8 (3.6)
35 1 (4P, 5P)
2 (2P, 3P, 4P, 5P)
2
2
12.6 (5.7)
12.8 (5.8)
3 8 47 (21) 0 2 8 (3.6)
4 9 69 (31) 0 with top adders 3 11 (5)
3 (2P, 3P) 4 40 (18)
5 10 170 (77) 1 3 13 (5.9)
36 4 (2P, 3P) 4 52 (24)
6 F1E 495 (225) 1 with top adders 3 13.4 (6.1)
5 10 120 (54)
7 F1E 2 3 15 (6.8)
6 F1E 335 (152)
37 7 F1E 8 F1E 3 4 43 (20)
9 F2E 4 9 65 (30)
8 F1E
Consult factory. 5 10 165 (75)
9 F1E
38 3-Pole Reversing Contactors —
6 F1E 450 (204)
7 F1E
without Control Power Transformers
8 F2E
39 00 2 7.8 (3.5)
9 F2E
0 2 8 (3.6)
1 3 11 (5.0)
Reversing Starters —
with Control Power Transformers
40 2 3 12 (5.4)
00 with top adders 3 15 (6.8)
3 4 67 (30)
0 3 15 (6.8)
4 4 154 (70)
41 5 10 170 (77)
1 with top adders 3 17 (7.7)
2 3 19 (8.6)
6 F1E 425 (193)
3 4 50 (23)
42 7 F1E
4 9 72 (33)
8 F1E
5 10 172 (78)
9 F2E
6 F1E 495 (225)
43 Consult factory.
7 F1E
8 F2E
9 F2E
Consult factory.
Table 31.3-21. Type 3R, 4/4X, 12 Freedom Table 31.3-22. Type 1 Freedom Table 31.3-24. Type 3R, 4/4X, 12 Freedom
Non-combination Starters Combination Starters Combination Starters 22
NEMA Size / Box Shipping NEMA Size (Device) Box Shipping NEMA Size (Device) Box Shipping
IEC Frame No. Wt. No. Wt. No. Wt.
Lbs. (kg) Lbs. (kg) Lbs. (kg) 23
Non-reversing Starters — Non-reversing — Non-reversing — with and without Control Power
with and without Control Power Transformers Transformers
without Control Power Transformers
0 5 14.3 (6.5) 0 A 37 (17) 0 A 37 (17) 24
1 A 38 (17) 1 A 38 (17)
1 5 15.3 (6.9)
2 A 39 (18) 2 A 39 (18)
2 7 16 (7.3)
3 8 46 (21) 3 C 72 (33) 3 C 72 (33) 25
4 (HMCP) C 90 (41) 4 (HMCP) C 90 (41)
4 8 60 (27)
4 (Disconnect Switch) D 150 (68)
5 10 150 (68) 4 (Disconnect Switch) D 150 (68)
5 E 180 (82)
26
6 F1E 415 (188) 5 E 180 (82)
6 F1E 435 (197)
7 F1E 6 F1E 435 (197)
8 F1E 7 F2E 7 F2E
27
F2E 8 F2E
9 F1E 8
9 F2E
Non-reversing Starters — 9 F2E
with Control Power Transformers Reversing — Reversing — with and without Control Power 28
Transformers
0 6 18 (8.2) with and without Control Power Transformers
0 B 42 (19)
0 B 42 (19)
1
2
6
6
19 (8.6)
20 (9) 1 B 43 (20)
1 B 43 (20) 29
2 B 44 (20)
3 8 53 (24) 2 B 44 (20)
3 C 84 (38)
4 8 67 (30) 3 C 84 (38)
4 D 173 (79) 30
5 10 157 (71) 4 D 173 (79)
5 E 550 (250)
6 F1E 5 F1E
7 F1E 6 F1E 550 (250)
6 F1E
31
7 F2E
8 F1E 7 F2E
8 F2E
9 F1E 8 F2E
Reversing Starters — 9
9 32
Non-reversing — Oversized
with or without Control Power Transformers Non-reversing — Oversized
0–1–2 B 44 (20)
0 7 18.5 (8.4) 0–1–2 B 44 (20)
Consult factory.
33
1 7 19.5 (8.9) Consult factory.
2 7 21 (10)
3 8 48 (22) Table 31.3-23. Type 1 Freedom Non-reversing 34
4 9 72 (33)
Combination Starters — Narrow Enclosure
5 10 175 (79) NEMA Size Box Shipping Wt.
6 F1E 525 (238)
No. Lbs. (kg) 35
NEMA 1 Enclosed
7 F1E
0–1–2 I 35 (16)
F2E
8
NEMA 12 Enclosed 36
9 F2E
0–1–2 I 36 (16)
Consult factory.
NEMA 12 Enclosed with Safety Door Interlock
0–1–2 I 37 (17)
37
38
39
40
41
42
43
For enclosure box dimensions, refer
to Page 31.7-3.
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Power Wiring — Introduction Pilot devices must be rated for use with 24 Vdc Power Supply Selection
22 The three ac line power connections a 24 Vdc low current (3 mA dc) dry cir- The IT. Coil Controller, Overload Relay
are made to the IT. Contactor or Starter cuit to ensure reliable operation. See and Contact Block coil require 24 Vdc
inputs marked 1, 3 and 5 and L1, L2 Table 31.4-8 for recommendations. control power.
23 and L3. The three motor power con- The ON/OFF control, an E-stop main- Note: The wire used for the ± 24 Vdc power
nections are made directly to the IT. tained contact, is optional for installa- supply connections to the IT. Coil Controller
Contactor outputs or to the IT. Over-
24 load Relay outputs for the IT. Starter
tions requiring the removal of power and Overload Relay terminal blocks should
take into account voltage drop due to coil
from the control circuitry to open the
to the terminals marked 2, 4 and 6 contactor independently of the normal inrush. Use of any other voltage may result
and T1, T2 and T3. Use Class B, 75ºC in personal injury, property damage, and
25 copper wire only (or 90ºC copper wire
ON/OFF circuit. Caution must be exer-
will damage the IT. device.
cised to ensure that the E-stop contact
oversized for 75ºC operation) in accor- is not closed when the ON/OFF control
dance with the National Electrical Code Control voltage must be in the range
26 (NEC) and other local regulations as
pilot device is already closed to prevent
of 20 – 28 Vdc under all conditions.
an unintended restart.
applicable. The Cutler-Hammer control power
Wiring Cautions supplies listed in Table 31.4-1 are
27 Note: The control terminal block must be recommended.
removed before wiring the T1, T2 and T3 For reversing applications, the
leads of the B, C and D Starter Frames. “Forward” input will always override Caution: Only apply 24 Vdc to any of the
28 a “Reverse” input, if both are closed. terminals of the IT. Coil Controller or
Control Wiring — General IT. Overload control terminal block.
Caution must be exercised to prevent
All of the control connections, includ- an unintended direction change.
29 ing the contactor coil, are made to the Use of Multiple Contactors or Starters on
IT. Coil Controller or Overload Relay When using the Auto Reset, Remote One Power Supply
terminal block. For the IT. Contactor Reset or E-stop features, caution must In order to determine the proper power
30 Frames A (27 mm) to C (54 mm), a four- be exercised to prevent an unintended supply for use with multiple contactors
point terminal block is used for all non- restart from causing personal injury or or starters, the number of devices clos-
reversing applications. For reversing equipment damage. ing simultaneously, and those already
31 contactors an eight-point terminal closed, must be predetermined. A
block is used but the terminals marked Control Wiring — Contactors and Starters calculation may then be made to ensure
1, 2 and 3 are unused, except for the A remote Trip Reset contact (see the appropriateness of the power
32 A-Frame which uses a single five-point Table 31.4-8) may be used, if desired, supply selected.
terminal block and the F-Frame which to reset the IT. Starter after a trip. Caution
uses multiple five-point terminal blocks. must be exercised to ensure that the
33 ON/OFF control pilot device is not
For the IT. B- through F-Frame Starters, closed to prevent an unintended restart.
an eight-point terminal block is supplied If the Auto Reset feature is used, caution
34 for reversing and non-reversing appli- must be exercised to ensure that any
cations. The difference is the use of the restart occurs in a safe manner. A solid-
“R” terminal for the reversing starter. state alarm output is available.
35 For a non-reversing application, this
terminal is marked but unused. The Figures 31.4-13 and 31.4-14 illustrate
F-Frame Starter also uses a five-point the terminal connections for the eight-
36 terminal block. Control wiring require- point terminal connections for the B-, C-,
ments for AC-4 applications are the D-, and E-Frames. A remote Trip Reset
same as for AC-3 applications. contact (see Table 31.4-8) may be used,
37 Control wire size ranges, lug torques and
if desired, to reset the IT. Starter after a
trip. Caution must be exercised to
tool types are shown in Table 31.4-9. ensure that the Start contact is not
38 Note: The wire used for the ± 24 Vdc power closed to prevent an unintended restart.
supply connections to the IT. Coil Controller Refer to the Protective Trip and Trip
and Overload Relay terminal blocks should Reset sections for further information
39 take into account voltage drop due to coil on the Remote Reset feature. If the
inrush requirements. Refer to the applica- Auto Reset feature is used, caution
tion note on 24 Vdc Voltage Drop, available must be exercised to assure that any
online at: www.EatonElectrical.com.
40 restart occurs in a safe manner. A solid-
state alarm output is available, see the
Alarm Output section for information.
41
42
43
29
Cold Start 30
100.0 Trip Class 30
Trip Class 20
Trip Class 10
31
10.0
Lift Cover Here to Expose 32
FLA Dial and Label
Overload Cover
Hot Start
Trip Class 30
33
Trip Class 20
Trip Class 10
1.0 Ø ON Ø OFF 34
4.3 5.4
35
3.6
C 10
0.1 3.2 7.2 L 36
A 20
1 2 3 4 5 6 7 8 9 10
Multiples of FLA
2.8 S 30 37
9.0
Figure 31.4-1. IT. Overload Trip Curves FLA S
FLA Dial and Label
38
40
41
42
43
26 Technologies (IT.) Electro-Mechanical Contactors and Starters. The various choices Make and Interrupting 1.1 .55
available for non-reversing models are shown in Table 31.4-2 and their ratings in Break 1.1 .55
Table 31.4-4. For reversing models, the number of auxiliaries indicated is for each Continuous 5 5
27 of the contactors/starters in the assembly. Thermal 5 5
Table 31.4-2. Auxiliary Contact Availability — Sizes 00 – 5
Top Mounted (Maximum Auxiliaries per Contactor/Starter)
28 Contactor/Starter Size Contact Catalog
Size 00, 0 Size 1 Size 2 Size 3, 4 Size 5 Type Number
29 3 3 3 3 — 1NO EMA13
3 3 3 3 — 1NC EMA14
30 2 2 3 3 — 1NO-1NC EMA15
2 2 3 3 — 2NO EMA16
2 2 3 3 — 2NC EMA17
31 2 3 3 3 3 Logic Level EMA70
1NO-1NC
For reversers, multiply quantities by two.
32 Other combinations: Single, Dual, Single; Dual, Single, Dual; and Dual, Logic Level, Dual.
33
34
35
36
37
38
39
40
41
42
43
39
40
41
42
43
Finger Protection
23 Front IP20 IP20 IP20 IP20 IP20
At Terminals IP10 IP10 IP00 IP00 IP00
At Terminals with max. IP20 IP10 IP10 IP00 IP00
24 size wire installed
Terminals L1, L2, L3/T1, T2, T3
1 Wire per Terminal 14 – 8 AWG 14 – 4 AWG 14 – 1 AWG 6 – 250 kcmil 4 – 600 kcmil
25 (stranded or solid) (1.5 – 10 mm2) (1.5 – 16 mm2) (1.5 – 35 mm2) (16 – 120 mm2) (16 – 300 mm2)
2 Wires per Terminal 14 – 10 AWG 14 – 6 AWG 14 – 2 AWG 6 – 3/0 AWG 4 — 250 kcmil
(stranded or solid) (1.5 – 4 mm2) (1.5 – 16 mm2) (1.5 – 25 mm2) (16 – 70 mm2) (16 — 120 mm2)
26 Strip Length .45" (11 mm) .5" (12 mm) .7" (18 mm) .8" (21 mm) 1.5" (40 mm)
Torque (max.) 20 lb-in (2.2 Nm) 35 lb-in (4.0 Nm) 45 lb-in (5.0 Nm) for 250 lb-in (28 Nm) 550 lb-in (62 Nm)
for 14 – 10 AWG for 14 – 10 AWG Single 14 – 8 AWG
27 (1.5 – 6 mm2); (1.5 – 6 mm2); (1.5 – 10 mm2);
25 lb-in (2.8 Nm) for 40 lb-in (4.5 Nm) for 100 lb-in (11 Nm) for
8 AWG (10 mm2) 8 AWG (10 mm2); Single 6 – 1 AWG
45 lb-in (5.0 Nm) for (16 – 35 mm2) and
28 6 – 4 AWG
(16 mm2)
Dual Wire
Combinations
Driver 2.5 mm Hex Key 3 mm Hex Key 5/32" (4 mm) Hex Key 5/16" (8 mm) Hex Key 5/16" (8 mm) Hex Key
Operation Performance
29 Coil Voltage (nominal) 24 Vdc 24 Vdc 24 Vdc 24 Vdc 24 Vdc
Coil Operating 20 – 28 20 – 28 20 – 28 20 – 28 20 – 28
Voltage Range (Vdc)
30 Control Terminals
(- and +) 14 – 12 AWG 14 – 12 AWG 14 – 12 AWG 14 – 12 AWG 14 – 12 AWG
1 Wire per Terminal (1.5 – 2.5 mm2) (1.5 – 2.5 mm2) (1.5 – 2.5 mm2) (1.5 – 2.5 mm2) (1.5 – 2.5 mm2)
31 (- and +) 14 AWG 14 AWG 14 AWG 14 AWG 14 AWG
2 Wires per Terminal (1.5 mm2) (1.5 mm2) (1.5 mm2) (1.5 mm2) (1.5 mm2)
(P, F, R, 1, 2, 3) 22 – 12 AWG 22 – 12 AWG 22 – 12 AWG 22 – 12 AWG 22 – 12 AWG
32 1 Wire per Terminal (0.5 – 2.5 mm2) (0.5 – 2.5 mm2) (0.5 – 2.5 mm2) (0.5 – 2.5 mm2) (0.5 – 2.5 mm2)
(P, F, R, 1, 2, 3) 18 – 14 AWG 18 – 14 AWG 18 – 14 AWG 18 – 14 AWG 18 – 14 AWG
2 Wires per Terminal (0.75 – 1.5 mm2) (0.75 – 1.5 mm2) (0.75 – 1.5 mm2) (0.75 – 1.5 mm2) (0.75 – 1.5 mm2)
33 Torque (max.) 4.5 lb-in (.5 Nm) 4.5 lb-in (.5 Nm) 4.5 lb-in (.5 Nm) 4.5 lb-in (.5 Nm) 4.5 lb-in (.5 Nm)
Strip Length .25 (7 mm) .25 (7 mm) .25 (7 mm) .25 (7 mm) .25 (7 mm)
Driver .13 (3.5 mm) Flat .13 (3.5 mm) Flat .13 (3.5 mm) Flat .13 (3.5 mm) Flat .13 (3.5 mm) Flat
34 Temperature
Operating -40° to +149°F -40° to +149°F -40° to +149°F -40° to +149°F -40° to +149°F
(-40° to +65°C) (-40° to +65°C) (-40° to +65°C) (-40° to +65°C) (-40° to +65°C)
35 Storage -58° to +176°F -58° to +176°F -58° to +176°F -58° to +176°F -58° to +176°F
(-50° to +80°C) (-50° to +80°C) (-50° to +80°C) (-50° to +80°C) (-50° to +80°C)
Environmental
36 Shock/Vibration 15G/5G 15G/5G 15G/5G 15G/5G 15G/5G
Altitude 6600 Ft (2000 m) 6600 Ft (2000 m) 6600 Ft (2000 m) 6600 Ft (2000 m) 6600 Ft (2000 m)
Pull-In Time (ms) at 24 Vdc
37 Excl. Debounce Time 15 15 25 30 70 – 200
Incl. Debounce Time 75 80 88 95 120 – 250
Dropout Time (ms) at 24 Vdc
38 Excl. Debounce Time 5 5 12 15 50 – 150
Incl. Debounce Time 65 70 75 80 70 – 200
39 Use Class B 75°C copper wire only (or 90°C
copper wire sized for 75°C operation per NEC)
Note: Response time for Control Inputs = Debounce Time.
The time between operating forward and reverse must be greater than the Debounce Time.
Consult factory for higher ratings.
40 Preliminary data.
Note: At other temperatures expressed in
Table 31.4-6. 24 Vdc Power Supply Requirements at 68°F (20°C) (see Note at bottom left)
Contactor/Starter Size Sealed In Inrush
°C, for either inrush or sealed, use the 20°C
Catalog Size Wattage Amperes Wattage Amperes Duration
value from the table in the following: Number
41 Watts = W20 [1.1 – .005(T) and
(msecs)
Amperes = A20 [1.1 – .005(T)] N_11B_ _X3N 00, 0 3.7 .15 80 3.3 50
N_01B_ _ _3A 00, 0 3.2 .13 80 3.3 50
For example, inrush requirements for a D Frame
42 Starter at -25°C would be:
N_11C_ _X3N 1 4.2 .18 90 3.8 50
N_01C_ _ _3A 1 3.6 .15 90 3.8 50
Watts = 130 [1.1 – .005 (-25)] = 160 N_ _1D_ _ _3_ 2 5.0 .21 130 5.4 65
Amperes = 5.4 [1.1 – .005 (-25)] = 6.6 N_ _1E_ _ _3_ 3, 4 5.6 .23 140 5.8 85
43 N_ _1F_ _ _3_ 5 8.4 .35 200 8.3 250
N_01F_ _ _3_ 5 9.1 .38 200 8.3 250
_ indicates missing digit/character of the Catalog Number; may have multiple values.
10,000,000
00 0 1 2 3 4 5
1.0
2 33
34
Contact Life (Number of Operations)
0.1
1 2 3 4 5 6 7 8 9 10
35
1,000,000 Multiples of FLA
36
1 Trip Class 10 Cold
2 Trip Class 10 Hot
3 Trip Class 20 Cold
4 Trip Class 20 Hot 37
5 Trip Class 30 Cold
6 Trip Class 30 Hot
100,000
38
Figure 31.4-4. Class 10, 20 and 30 Trip Curves
39
10,000 40
1 9 27 45 90 135 270
6 12 18 32 40 50 65 100 125 200 250 400
Rated Operational Current (Ie) AC-3 [A] 41
Figure 31.4-3. Electrical Life — AC-3 Utilization Category
Preliminary data. 42
43
Wiring Diagrams
22
23
24
25
26
27
28
29
30
Figure 31.4-5. 2-Wire Control Non-Reversing Figure 31.4-7. 2-Wire Control Reversing Figure 31.4-9. 3-Wire Control Reversing
Contactor Terminal Connections Contactor Terminal Connections — Contactor Terminal Connections — A-Frame
31 B- to E-Frames
32
33
34
35
36
37
38
39
Figure 31.4-6. 2-Wire Control Reversing Figure 31.4-8. 3-Wire Control Non-Reversing Figure 31.4-10. 3-Wire Control Reversing
40 Contactor Terminal Connections — A-Frame Contactor Terminal Connections Contactor Terminal Connections —
B- to E-Frames
41
42
43
22
23
24
25
26
27
28
Figure 31.4-11. 2-Wire Control Non-Reversing Figure 31.4-13. 3–Wire Control Non-Reversing Figure 31.4-14. 3-Wire Control Reversing 29
Starter Terminal Connections Starter Terminal Connections — B- to E-Frames Starter Terminal Connections — B- to E-Frames
Table 31.4-8. IT. Low Energy Pilot Device Pushbutton Contact Blocks 30
Pilot Device Recommended Cutler-Hammer Contact Blocks
Circuit Catalog Circuit Catalog
Number Number 31
1NC E22B1E 2NC E30KLAE5
1NO E22B2E 1NC 10250T51E
1NO E30KLAE1 1NO 10250T53E 32
1NC E30KLAE2 1NO, 1NC 10250T1E
1NO, 1NC E30KLAE3 2NC 10250T3E
2NO E30KLAE4 2NO 10250T2E 33
Note: Contact blocks with reliability “nibs” are also suitable.
34
Table 31.4-9. IT. Control Terminal Block Wire Size, Lug Torque and Tool Size
Control Terminal Block Wiring
Contactor/ Wire Size Range (AWG) mm2 Torque Terminal Tool
35
Starter Size P, F, R, 1, 2, 3 - and + Strip Lb-in Type
Figure 31.4-12. 2-Wire Control Reversing Type Frame mm Length (N-m)
Starter Terminal Connections — B- to E-Frames 36
All All All 1 of 1 of .25 4.5 Box Lug Slotted
(22 – 12) 0.5 – 2.5 (14 – 12) 1.5 – 2.5 (7 mm) (0.5) Pressure 0.13
or
2 of
or
2 of
Type (3.5 mm) 37
(18 – 14) 0.75 – 1.5 1.5 (14)
When present. 38
39
40
41
42
43
Enclosed Box Selection Table 31.4-11. Type 3R, 4/4X, 12 IT. Contactors Table 31.4-13. Type 3R, 4/4X, 12 IT.
22 Table 31.4-10. Type 1 IT. Contactors NEMA Size Box Shipping Non-combination Starters
No. Weight NEMA Size Box Shipping
NEMA Size Box Shipping Lbs. (kg) No. Wt.
23 No. Weight
Lbs. (kg) Non-reversing without PSS Power Supply Lbs. (kg)
00, 0 5 12 (5.4) Non-reversing Non-combination Starters
Non-reversing Contactors without PSS Power Supply
00, 0 5 8 (3.6)
24 00 1 3 (1.4) 1 5 12 (5.4)
1 5 9 (4.1)
0 1 3 (1.4) 2 5 14 (6.4)
2 7 12 (5.4)
1 1 3 (1.4) 3 8 32 (15)
25 2 2 5 (2.3) 4 8 41 (19)
3
4
8
8
38 (17)
38 (17)
3 2 10 (4.5) 5 10 99 (45)
5 10 110 (50)
4 2 10 (4.5) Non-reversing with PSS Power Supply
26 5 3 32 (15) 00, 0 5 13 (5.9)
Reversing Non-combination Starters
00, 0 3 10 (4.5)
Reversing Contactors without PSS Power Supply 1 6 13 (5.9) 1 3 11 (5.0)
27 00 1 4 (1.8) 2 6 15 (6.8) 2 3 18 (8.2)
0 1 4 (1.8) 3 8 34 (15) 3 4 32 (15)
1 1 6 (2.7) 4 8 43 (20) 4 4 32 (15)
28 2 2 5 (2.3) 5 10 101 (46) 5 4 92 (42)
3 3 20 (9.1)
Reversing without PSS Power Supply
4 3 20 (9.1) Table 31.4-14. Type 1 IT. Combination Starters
29 5 3 52 (24)
00, 0 6 14 (6.4)
1 6 14 (6.4) NEMA Size Box Shipping
Non-reversing Contactors with PSS Power Supply No. Wt.
2 6 17 (7.7) Lbs. (kg)
30 00 2 4 (1.8)
3 8 40 (18) Non-reversing Combination
0 2 4 (1.8)
4 9 48 (22) 00, 0 A 35 (16)
1 2 4 (1.8)
31 2 2 6 (2.7)
5 10 125 (57) 1 A 35 (16)
3 3 12 (5.4) 2 A 36 (16)
Table 31.4-12. Type 1 IT. Non-combination
4 3 12 (5.4) 3 C 60 (27)
32 Starters
5 3 33 (15) 4 (HMCP) C 60 (27)
NEMA Size Box Shipping
Reversing Contactors with PSS Power Supply No. Weight 4 (Disconnect Switch) E 120 (54)
5 E 140 (64)
33 00 2 5 (2.3) Lbs. (kg)
Reversing Combination
0 2 5 (2.3) Non-reversing Non-combination Starters
1 2 5 (2.3) 00 2 8 (3.6) 00, 0 B 36 (16)
34 2 3 10 (4.5) 0 2 8 (3.6) 1 B 36 (16)
3 3 21 (10) 1 2 8 (3.6) 2 B 37 (17)
4 3 22 (10) 2 2 11 (5.0) 3 C 68 (31)
35 5 3 54 (25) 3 4 16 (7.3)
4 E 68 (31)
5 F1E 167 (76)
4 4 16 (7.3)
36 5 4 36 (16)
Reversing Non-combination Starters
00 3 9 (4.1)
37 0 3 9 (4.1)
1 3 9 (4.1)
38 2 3 15 (6.8)
3 4 24 (11)
4 4 24 (11)
39 5 4 65 (30)
40
41
42
43
ECT 22 1 1 A A B - A 23
24
Design Modification Codes
T = IT. — NEMA (See PG03300001E)
25
Class Solid-State
01 = Contactors Overload Range 26
02 = Reversing Contactors
05 = Non-combination — FVNR Starter
06 = Non-combination — FVR Starter Disconnect Fuse Clip
16 = Combination — Fusible FVNR Starter 27
Cover Control A= None G= 100 A/600 V
17 = Combination — Fusible FVR Starter
B= 30 A/250 V H= 200 A/250 V
22 = Combination — HMCPE FVNR Starter (Contact Eaton C= 30 A/600 V J= 200 A/600 V
23 = Combination — HMCPE FVR Starter for Options.) D= 60 A/250 V K= 400 A/250 V 28
E= 60 A/600 V L= 400 A/600 V
F= 100 A/250 V
HMCP/E or Breaker Ratings 29
NEMA Size Enclosure Type Motor Voltage/
A= Size 00 1= Type 1 — General Purpose Power Supply A= None W= 70 A
B= 3A G= 100 A/RC3
0= Size 0 2= Type 3R — Rainproof B= 230 V C= 7A X= 100 A/TC3 30
1= Size 1 3= Type 4 — Painted Steel C= 460 V D= 15 A H= 150 A
2= Size 2 4= Type 4X — Watertight D= 575 V E= 30 A J= 250 A
3= Size 3 8= Type 12 — Dust-Tight E= 200 V
4= Size 4 9= Type 4X — 316-Grade Q= 24 Vdc
F= 50 A K= 400 A 31
5= Size 5 Stainless Steel L= 380V/50 Hz
32
If CPT is selected, Power Supply to be 120 Vac – 24 Vdc.
Power supply omitted.
See Table 31.4-16, Solid-State Overload Range Codes. 33
Table 31.4-16. IT. Solid-State Overload Range Codes
FLA Range Size 34
00 0 1 2 3 4 5
.25 – .80
.59 – 1.9
A
B
A
B
A
B
—
—
—
—
—
—
—
—
35
1.4 – 4.4 C C C — — — —
2.8 – 9.0 D D D — — — —
5.0 – 16 — — F — — — —
36
6.3 – 20 — G — — — — —
8.4 – 27 — — H — — — —
10 – 32 — J — — — — — 37
14 – 45 — — — K — — —
16 – 50 — — L — — — —
28 – 90 — — — — M — — 38
31 – 100 — — — N — — —
42 – 135 — — — — — P —
63 – 200 — — — — — R —
84 – 270 — — — — — — S 39
131 – 420 — — — — — — T
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Starting Characteristics 39
700
Full Voltage Starting
700
Full Voltage Starting
700 40
Line Current, % of Full Load
400
Part Winding Starting
400
41
400
Wye-Delta Starting KVA
300 300 300
(Closed Transition)
200 Autotransformer 200 200 42
Starting on 65% Tap Full Load Current Torque
100 100 100
Full Load Current
0
Motor Speed Full Load
0
Motor Speed Full Load
0
20 40 60 80 100
43
Speed Speed Motor Speed Full Load Speed
Figure 31.5-1. Autotransformer Starting Figure 31.5-2. Wye-Delta or Part Figure 31.5-3. Solid-State Starter
Winding Starting
Description Table 31.5-3. NEMA Contactor Size (1S). The interlock (1S) closes, energiz-
22 Autotransformer type starters are
Guidelines within Autotransformer Starters ing the timing relay (TR) and contactor
Maximum NEMA Size (2S) which seal in through the interlock
the most widely used reduced-voltage hp (2S). With the (1S) and (2S) contactors
Starter Contactor
23 starter because of their efficiency and
flexibility. All power taken from the line, Run Starting
closed, the motor is connected through
the autotransformer for reduced-voltage
except transformer losses, is transmitted (1S) (2S) start. After a preset time interval, the
(3-Pole) (3-Pole)
24 to the motor to accelerate the load. Taps (TRTO) contacts time open, de-energiz-
on the transformer allow adjustment of 230 Volts, 60 Hz ing contactor (1S) and connecting the
the starting torque and inrush to meet 15 2 2 2 2 autotransformer as a reactor in series
25 the requirements of most applications. 30
50
3
4
3
4
3
4
3
4
with the motor. Interlock (1S) immedi-
The following characteristics are pro- ately energizes the run contactor (R)
100 5 5 5 5
duced by the three voltage taps: 200 6 6 6 6 which seals in through its interlock (R).
26 Table 31.5-2. Starting Characteristics
300 7 7 6
7
6 The run contacts are now closed, and
450 8 8 7 the motor is running at full voltage.
Tap Starting Torque Line Inrush 460 – 575 Volts, 60 Hz Start contactor (2S) and relay (TR) are
% Locked % Locked
27 Torque Ampere 25 2 2 2 2 de-energized when interlock (R) opens.
50 3 3 3 3
100 4 4 4 4
An overload, opening the STOP push-
50% 25% 28% button or other pilot device de-ener-
200 5 5 5 5
28 65%
80%
42%
64%
45%
67%
400 6 6 6 6 gizes the (R) contactor removing the
600 7 7 6 6 motor from the line.
Not included 50 hp and below. 900 8 8 7 7
29 Includes transformer magnetizing current. 1S is 2-pole on sizes 7 and 8. Other Types
Autotransformer starters are also
Closed transition is standard on all Operation (Refer to Schematic Diagram) available in combination and reversing
30 sizes ensuring a smooth transition Closing the START button or other types.
from reduced to full voltage. Since pilot device energizes the start contactor
the motor is never disconnected from
31 the line there is no interruption of line R 3C
current which can cause a second
100%
80%
65%
50%
0%
RVNR AUTOXFMR (3-coil) 2S 1S OL T1
inrush during transition. R 5C
3E
1C
T2
Motor
32 L1 L1 #1
100%
CKT BKR
80%
65%
50%
T3
0%
2S 1S
Duty cycle of these starters is as follows: L2
L3
L2
L3
or
SW & FU
#2
R
5E 1E
#3 3D
up to 200 hp, 15 seconds on each
100%
80%
65%
50%
0%
2S 1S
4 minutes for 1 hour, repeated after
33 2 hours. Over 200 hp, three periods
5D 1D TBX2
1S R Stopped
of 30 seconds ON, 30 seconds OFF 7 8 9 10
G
repeated after 1 hour.
34 Run
R
Description Overload Relay — (OL) (1M) which seals in through its inter-
Part-Winding starting provides conve- Two 3-pole Type B overload relays lock (1M) and energizes the timer (TR). 22
provide starting and running overcur- The (1M) contacts connect the first
nient, economical one-step acceleration half-winding of the motor across the
at reduced current where the power rent protection.
company specifies a maximum or
line. After a preset time interval, the 23
Timing Relay — (TR) timer (TRTC) contact closes energizing
limits the increments of current drawn contactor (2M). The (2M) contact con-
An electrically operated pneumatic
from the line. These starters can be
relay provides accurate, adjustable nects the second half-winding of the 24
used with nine-lead dual-voltage start-to-run transfer timing. motor across-the-line.
motors on the lower voltage and with
Opening the STOP button or other
special part-winding motors designed Other Types
pilot device de-energizes contactors
25
for any voltage. When used with dual- Part-winding Type ECN45 starters are
voltage motors, it should be estab- (1M), (2M) and timer (TR), removing
also available in combination (Type 46
the motor from the line.
lished that the torque produced by and 47), reversing and three-point 26
the first half-winding will accelerate the (primary resistor) types. Table 31.5-6. Contactor Sequence
load sufficiently so as not to produce
Operation (Refer to Schematic Diagram) Contactor Start Run
a second undesirable inrush when the 27
second half-winding is connected to the Closing the START button or other pilot 1M ● ●
line. Most motors will produce a start- device energizes the start contactor 2M — ●
ing torque equal to between 1/2 to 2/3 28
of NEMA standard values with half of
the winding energized and draw about Part Winding Select Overload Heater Packs for 50%
2/3 of normal line current inrush. L1
L2
L1
L2
CKT BKR
or
#1
#2
1M OL T1
T2
Motor
of Rated Full Load Motor Current 29
SW & FU T3
Design Features L3 L3 #3
2M OL T7
T8 30
Contactors — (1M) (2M) T9
TBX2
A 3-pole contactor (1M) connects only 7 1M 8
Stopped
96
A OL
95 96
32
half-winding of the motor for running PS 1M
On-Delay 1.5 – 15 Sec.
TR
2 7
(see table below for size). TB1 TB1
Auto
TB3 E
Description Operation (Refer to Schematic Diagram) Interlock opens, de-energizes the timer
22 Wye-Delta type starters are applied Closing the START button or other pilot (TR) opening timer (TRTC) thus energiz-
device energizes contactor (1S) whose ing contactor (2S).
extensively to industrial air condition-
contacts connect the motor in a wye
23 ing installations because they are par-
ticularly suited for starting motors connection. Interlock (1S) closes, ener-
An overload, opening the STOP button
or other pilot device de-energizes con-
driving high inertia loads with resulting gizing contactor (1M) and timer (TR). tactors (1M) and (2M), removing the
The (1M) contacts energize the motor
24 long acceleration times. They are not,
windings in a wye. After a preset time
motor from the line. (TRP) de-energizes
however, limited to this application. and locks out the control circuit if the
When six- or 12-lead delta-connected interval, timer (TRTC) contact closes duty cycle of the transition resistors
energizing contactor (2S). Interlock (2S)
25 motors are started wye-connected,
opens, dropping out contactor (1S).
is exceeded.
approximately 58% of line voltage is
applied to each winding and the motor The motor is now energized in series Wye-Delta Class ECN51 closed transi-
with the resistors. Interlock (1S) closes, tion starters are also available in com-
26 develops 33% of full-voltage starting
energizing contactor (2M), bypassing bination types and Class ECN48 open
torque and draws 33% of normal
locked-rotor current from the line. the resistors and energizing the transition non-combination and com-
delta connected motor at full voltage. bination starters.
27 When the motor is accelerated, it is
reconnected for normal data operation.
Wye-Delta
28 Design Features Closed Transition 2M T6
L1 L1 CKT BKR #1
#2 T4
L2 L2 or
Contactors — (1S) (1M) (2S) (2M) L3 L3 SW & FU #3
T5
T2B
T3B
T1B
connect motor in wye (see Table 31.5-8 Select Overload Heater Coils
30
Resistor
Resistor
Resistor
for size). for 58% of Rated Full Load
Motor Current
1M OL T1
A 3-pole contactor (1M) energizes motor T1A T2 Motor
31 leads T1-T2-T3 for both wye and delta T2A T3
connections (see Table 31.5-8 for size). T3A
1S 2M Stopped TBX2
5 5 7 8
A 3-pole contactor (2S) connects resis- G
32 tors in series with the motor windings Run
during the start-to-run transition period R
(see Table 31.5-8 for size). Stop Start On-Delay 1.5 – 15 Sec. TR
33 TB1 TB1 TB2 TB3 2
E
7
T.C.
55 1S
56 A1 A2
230 Volts, 60 Hz
37 10
25
1 YD
2 YD
1
2
1
2
1
2
1
1 Figure 31.5-6. Typical Schematic Diagram
50 3 YD 3 3 3 1
75 4 YD 4 4 4 2 Table 31.5-9. Type 1, 3R, 4/4X, 12 Freedom
38 150 5 YD 5 5 4 3 Reduced Voltage Enclosures
300 6 YD 6 6 5 4
500 7 YD 7 7 6 5 Size Type 1 Type 3R, 4X, 12
7
39 800 8 YD 8 8 6 Box
No.
Shipping
Wt.
Box
No.
Shipping
Wt.
460 – 575 Volts, 60 Hz
Lbs. (kg) Lbs. (kg)
15 1 YD 1 1 1 1
Classes 48 & 51: Wye Delta — Non-combination
40 40
75
2 YD
3 YD
2
3
2
3
2
3
1
1 Classes 49 & 52: Wye Delta — with Disconnect
150 4 YD 4 4 4 2 Classes 50 & 53: Wye Delta — with Thermal
300 5 YD 5 5 4 3 Magnetic Trip Circuit Breaker
41 700 6 YD 6 6 5 4 2YD – E 185 (84) E 225 (102)
1000 7 YD 7 7 6 5 4YD
1500 8 YD 8 8 7 6
5YD F1E 605 (275) F1E 705 (320)
42 1S is 2-pole on sizes 7 and 8. 6YD F1E 635 (288) F1E 735 (334)
6YD F2E 715 (325) F2E 830 (377)
43 7YD F2E
F2E
8YD F2E F2E
Non-combination and breaker.
Fusible. For enclosure box dimensions, refer
Consult factory. to Page 31.7-3.
43
Temperature — Operating -5ºC – 40ºC -5ºC – 40ºC -35ºC – 50ºC -25ºC – 40ºC -30ºC – 50ºC 33
(No Derating)
Current Rating (50ºC) 80% 80% 100% 100% 100%
Limited Duty Cycle (50ºC) 15-Minute Duty Cycle
(maximum 8)
16-Minute Duty Cycle
(maximum 8)
Fully Rated Fully Rated Fully Rated 34
Current Rating (60ºC) 65% 65% 10% Reduction 10% Reduction Consult Factory
Limited Duty Cycle (60ºC) 16-Minute Duty Cycle
(maximum 65)
16-Minute Duty Cycle
(maximum 65)
Consult Factory Continuous Duty Cycle
at 90%
Consult Factory
35
Temperature — Storage -5ºC – 40ºC -5ºC – 40ºC -40ºC – 80ºC -40ºC – 70ºC -50ºC – 70ºC
Altitude (meters) 2000 2000 2000 2000 2000
36
Note: Consult factory for applications outside of these parameters for additional information and sizing requirements.
37
38
39
40
41
42
43
22 Multi-Motor Operation NEMA B motor draws six times full Solid-State Reduced Voltage
load amperes for starting, and starting
The S801/S811 line can be used torque is 150% of full load torque. Starters
to control multiple motors if the
23 following conditions are met:
If the same motor were started with Enclosed Box Selection
the S801 at 300% current limit, then
■ The current rating of the S801/S811 the available torque would be: Table 31.6-4. Non-combination Solid-State
Reduced Voltage Box Dimensions
24 should be equal to or greater than
300
2
90,000 Ampere SSRV Non-combination
the total of the individual motor ------------ = --------------------- =
600 360,000 Rating
full load amperes and the S801/S811 Box No.
25 overload must be set for the
1/4 x 150% full load torque = .8 – 27 S752 6A
cumulative full load amperes 37 S801/S811 7A
of the motors. 37.5% full load torque available 50 S752 6A
26 ■ Individual motor overcurrent protec- 66 S801/S811 7A
tion is provided by other devices. Heat Generation 105 S801/S811 7A
135 S801/S811 B1
■ The motors should not be mech- Due to the voltage drop that occurs
27 anically coupled together, i.e., across a SCR, there is heat generated
180 S801/S811 C
240 S801/S811 G1
two motors on same shaft. in the unit. For sizing an enclosure 304 S801/S811 G1
■ NEC and local code requirements or box size for the soft starters, it is 360 S801/S811 G1
28 for individual motor protection important to account for this heat 420 S801/S811 10
500 S801/S811 10
and branch short circuit protection generation.
are met. 650 S801/S811 10
29 With the Torque Limiter, the heat 720 S801/S811 10
■ Motors are closely matched in total generation is equivalent to 1 watt per 850 S801/S811 10
load and size. ampere of full load current. For the 1000 S801/S811 10
30 S701 line, the heat generation is equiv- Enclosure space will also accommodate for
Frequent Starting/Stopping alent to two watts per ampere of full an IT. Power Supply, two 4-pole relays, CPT,
The number of starts and stops allow- load current. The S752/S801/S811 lines and terminal blocks. Also includes space for
31 able depends upon many factors. The use a bypass contactor so its heat
a DNA module or MOV.
Same as footnote , but CPT is not included.
most important ones are: generation is a little more complex.
Upsize to 7A enclosure to include space for a
During steady state conditions, it
32 1. Set level of the starting current limit. generates about the same amount
CPT and a full voltage bypass contactor.
of heat as an across-the-line starter Note: All Type 7 and 9, see Section 11.
2. Start time.
of the same size. During start and
33 3. Run time. stopping ramps it will generate three Table 31.6-5. Combination Solid-State
watts of heat per ampere. Reduced Voltage Box Dimensions
4. Off time before next start. Ampere SSRV Comb. with Comb. with
34 The number of starts per hour is based
EXAMPLE: A 100 hp, 480 V NEMA B Rating Fuses HMCP
motor has a full load current of 125 Box No. Box No.
on the current carrying capacity of the amperes. A typical soft start on this
SCRs. A high start/stop duty may
35 require the oversizing of a soft starter.
motor is 300% current limit for 40 .8 – 27
37
S752
S801/S811
B1
B1
A1
A1
seconds. The heat generation during
If a high number of multiple starts 50 S752 C A1
this time period is: 66 S801/S811 C A1
36 occur, the starter may trip due to the
105 S801/S811 D B1
overload protection for the motor or 125 amperes x 300% = 135 S801/S811 D C
it may trip on overtemperature of the 375 watts for 40 seconds 180 S801/S811 E E
37 soft starter. In this situation, it is advis- 240 S801/S811 F1E E
able to wait a period of 10 minutes At the end of the ramp, the bypass
304 S801/S811 F1E E
before restarting to avoid damage to contactor closes and total heat genera- 360 S801/S811 F1E E
the soft starter and motor and allow tion is reduced to much lower levels.
38 the units to cool down. The motor
420
500
S801/S811
S801/S811
F1E
F1E
E
E
manufacturer should be consulted NEMA Design C and D Motors, 650 S801/S811 F1E F1E
39 about the effect of a high number Wound Rotor Motors 720
850
S801/S811 F1E
S801/S811 F1E
F1E
F1E
of multiple starts on motor life.
These motors are used due to their 1000 S801/S811 F1E F1E
high starting torque characteristics.
40 Starting Torque When high starting currents and high
Enclosure space will also accommodate for
an IT. Power Supply, two 4-pole relays, CPT,
The reduced voltage applied to the starting torques are required, it may and terminal blocks. Also includes space for
motor results in reduced inrush cur- be necessary to order the extended a DNA module or MOV.
41 rent and a soft start. However, it ramp option and oversize the soft Enclosure may be reduced to an A1, with all
reduces the starting torque of the starter to match the application space for all items as in footnote , exclud-
motor. The relationship is as follows: requirements. Consult the factory ing relays and CPTs.
42 for application considerations.
Same as footnote , but CPT is not included.
Upsize to B1 enclosure to include space for a
Torque at reduced current
---------------------------------------------------------------------- = CPT and a full voltage bypass contactor.
Torque at full current
43 2 Note: For enclosure box dimensions,
Current at reduced voltage refer to Page 31.7-3.
--------------------------------------------------------------------------
Current at full voltage
EXAMPLE: A 100 hp, 1800 RPM, 460 V
S752 Open Soft Starters Application Description The S752 was designed with safety
22
in mind. The device features a fully
The S752 combines the soft starter motor-rated run bypass contactor.
overload, bypass contactor into one The bypass contactor is capable of
device for fast and easy installation. breaking the motor load in failed SCR 23
With its small size, it can easily fit in conditions. Short circuit protection
place of existing soft starters, wye- ratings are offered with both circuit
delta starters or across-the-line NEMA breakers and fuses. Safety is enhanced 24
and IEC starters. This feature allows with the use of green materials, 24 Vdc
easy upgrades to existing systems. control and finger safe IP20 terminals.
25
The in-line version is designed for use
with three-phase motors in a delta Features and Benefits
(three-lead) configuration. The product
■ Run bypass significantly reduces
26
is designed to be wired in the three-
phase line feeding the three motor the heat generated as compared to
non-bypass soft starters. Less heat
input leads as is done for normal
minimizes enclosure size and cool-
27
across-the-line starting.
ing requirements and maximizes the
S752 The inside-the-delta version is to be life of all devices in the enclosure.
used on 6-lead or 12-lead wye-delta
28
■ Run bypass mode greatly reduces
motors. The device is wired into the internal heating created by the
Product Description windings of the motor. A reduced power dissipation across the SCRs. 29
voltage start is achieved without the The bypass contactor directly
Eaton’s Cutler-Hammer Intelligent need to reconnect the motor in wye connects the motor to the line
Technologies (IT.) S752 Line of and delta configurations. The S752
Reduced Voltage Soft Starters is very offers enhanced performance over
and improves system efficiency 30
by reducing internal power losses.
compact, multi-functional, easy to traditional wye-delta electromechani-
install and easy to program. Designed ■ Solid-state overload protection
cal starters. provides accurate current measure- 31
to control the acceleration and deceler-
ation of three-phase motors, the The starter uses Silicon Controlled ment and trip settings. Sophisti-
device is available in configurations Rectifiers (SCRs) to ramp the voltage cated algorithms solve a series
to be applied either in the line of the to the motor, providing smooth accel- of differential equations that model 32
motor, or in the delta windings of the eration and deceleration of the load. true motor heating and cooling,
motor. The in-line device is available After the motor is started, the internal resulting in superior motor overload
for current ranges from 0.25 to 50 run bypass contactor closes, resulting protection while minimizing 33
amps. The inside-the-delta device in the motor running directly across- nuisance trips. Advanced selectable
is available for current ranges from the-line. Internal run bypass signifi- protective features safeguard the
0.44 to 78 amps. cantly reduces the heat generated motor and system against a variety 34
as compared to non-bypass starters. of system faults.
The S752 is a redesign of the popular The soft stop option allows for a ramp ■ Six SCRs control all three motor
S751 soft starter. Design enhance- stop time that is longer than the coast- phases providing smooth accelera- 35
ments include an increased current to-stop time. tion and deceleration performance.
rating, short circuit coordination
The built-in solid-state overload pro- ■ Easy to read LED displays device 36
ratings with breakers and fuses, and
tects the motor from overload condi- status and provides fault indication.
inside-the-delta control. The S752
has replaced the S751 in the Cutler- tions with sophisticated algorithms ■ Internal run bypass contactors and
Hammer product offering. that model true motor heating, result- overload protection eliminate the 37
ing in better motor protection and need for additional devices,
The S752 is designed to be a complete fewer nuisance trips. Advanced pro- thereby reducing enclosure sizes,
package combining the SCRs, bypass tective and diagnostic features reduce minimizing installation and wiring 38
contactor and overload in one, very downtime. time and reducing overall assem-
compact device. The S752 is available bly size and cost.
as a component for panel mounting, in ■ Variable ramp times and torque 39
Motor Control Centers or in Enclosed control settings provide unlimited
Control (NEMA Type 1, 3R, 4, 4X, 7/9 starting configurations, allowing for
and 12). maximum application flexibility. 40
■ Soft stop control suits applications
where an abrupt stop of the load is
not acceptable. 41
42
43
Operation 22
Voltage Ramp Start
Provides a voltage ramp to the motor 23
Ramp 31
Time (Seconds)
32
Figure 31.6-2. Starting Characteristics — Soft Stop
33
Catalog Number Selection
Table 31.6-7. S752 Open Soft Starters Catalog Numbering System 34
S 752 L 50 N 3 S
35
S = IT. Soft Starter Voltage Rating
V02 = 240 V
V06 = 600 V
36
752 = Non-combination
Soft Starter
S = Standard Soft Starter —
In-Line Control
37
Frame Size
D = Inside-the-Delta Control
L = 54 mm
38
3 = 3-Pole Device
Device Rating
01 = 1 Amp 16 = 16 Amp
N = No Options 39
02 = 2 Amp 27 = 27 Amp
04 = 4 Amp 50 = 50 Amp
09 = 9 Amp
40
Inside-the-delta version only.
41
42
43
22 Product Selection
IT. S752 Product Selection — In-Line
23 Standard Duty Ratings
Standard duty ratings are defined as those that do not exceed any of the
24 following operating conditions:
■ 25 second ramp, 2 starts per hour, 40°C ambient, 300% FLA current
■ 15 second ramp, 4 starts per hour, 40°C ambient, 300% FLA current
25
■ 10 second ramp, 6 starts per hour, 40°C ambient, 300% FLA current
■ 7.5 second ramp, 8 starts per hour, 40°C ambient, 300% FLA current
26 ■ 3.0 second ramp, 15 starts per hour, 40°C ambient, 300% FLA current
Table 31.6-8. IT. S752 Soft Starter Standard Duty Ratings — In-Line
27 Maximum FLA Current kW Rating (50 Hz) Horsepower Rating (60 Hz) Catalog
Continuous Range 230 V 380 – 400 V 440 V 200 V 230 V 460 V 575 V Number
Current
28 0.8 0.25 – 0.8 0.3 0.37 0.55 1/8 1/6 1/3 1/3 S752L01N3S
1.9 0.59 – 1.9 0.6 1.1 1.1 1/3 1/3 3/4 1 S752L02N3S
29 4.4 1.4 – 4.4 1.5 2.2 3 3/4 1 2 3 S752L04N3S
9 2.8 – 9.0 3 5.5 5.5 2 2 5 7-1/2 S752L09N3S
16 5.0 – 16 5.5 10 11 3 5 10 10 S752L16N3S
30 27 8.4 – 27 10 15 18.5 7-1/2 7-1/2 20 25 S752L27N3S
50 16 – 50 12.5 22 30 10 15 30 40 S752L50N3S
31 For applications above 40°C, derate 1% per °C.
33 ■ 25 second ramp, 2 starts per hour, 40°C ambient, 400% FLA current
■ 15 second ramp, 4 starts per hour, 40°C ambient, 400% FLA current
■ 10 second ramp, 6 starts per hour, 40°C ambient, 400% FLA current
34 ■ 7.5 second ramp, 8 starts per hour, 40°C ambient, 400% FLA current
■ 3.0 second ramp, 15 starts per hour, 40°C ambient, 400% FLA current
35 Table 31.6-9. IT. S752 Soft Starter Heavy Duty Ratings — In-Line
Maximum FLA Current kW Rating (50 Hz) Horsepower Rating (60 Hz) Catalog
Continuous Range Number
36 Current
230 V 380 – 400 V 440 V 200 V 230 V 460 V 575 V
0.8 0.25 – 0.8 0.3 0.37 0.55 1/8 1/6 1/3 1/3 S752L01N3S
37 1.9 0.59 – 1.9 0.6 1.1 1.1 1/3 1/3 3/4 1 S752L02N3S
4.4 1.4 – 4.4 1.5 2.2 3 3/4 1 2 3 S752L04N3S
9 2.8 – 9.0 3 5.5 5.5 2 2 5 7-1/2 S752L09N3S
38 16 5.0 – 16 5.5 10 11 3 5 10 10 S752L16N3S
27 8.4 – 27 10 15 18.5 5 7-1/2 15 20 S752L27N3S
39 50 16 – 50 12.5 15 20 7-1/2 10 20 25 S752L50N3S
For applications above 40°C, derate 1% per °C.
42
43
Table 31.6-10. IT. S752 Soft Starter Standard Duty Ratings — Inside-the-Delta 25
Maximum FLA Current kW Rating (50 Hz) Horsepower Rating (60 Hz) Catalog
Continuous Range 230 V 380 – 400 V 440 V 200 V 230 V 460 V 575 V Number
Current 26
1.3 0.44 – 1.3 0.18 0.37 0.55 1/4 1/3 1/2 3/4 S752L01N3D_ _ _
3.2 1.1 – 3.2 0.55 1.1 1.5 1/2 3/4 1-1/2 2 S752L02N3D_ _ _ 27
7.6 2.5 – 7.6 1.5 3 4 1-1/2 1-1/2 3 5 S752L04N3D_ _ _
15 4.9 – 15 3.7 6.5 8 3 3 7-1/2 10 S752L09N3D_ _ _
27 8.7 – 27 6.5 12.5 15 7-1/2 7-1/2 15 25 S752L16N3D_ _ _ 28
46 15 – 46 12.5 22 25 10 15 30 40 S752L27N3D_ _ _
78
28 – 86 22 37 45 25 25 60 75 S752L50N3D_ _ _ 29
For applications above 40°C, derate 1% per °C.
For Voltage Suffix, See Table 31.6-11.
32
Heavy Duty Ratings
Heavy duty ratings are defined as those that do not exceed any of the
following operating conditions: 33
■ 10 second ramp, 6 starts per hour, 40°C ambient, 400% FLA current
■ 7.5 second ramp, 8 starts per hour, 40°C ambient, 400% FLA current 34
■ 3.0 second ramp, 15 starts per hour, 40°C ambient, 400% FLA current
Table 31.6-12. IT. S752 Soft Starter Light Duty Ratings — Inside-the-Delta 35
Maximum FLA Current kW Rating (50 Hz) Horsepower Rating (60 Hz) Catalog
Continuous Range 230 V 380 – 400 V 440 V 200 V 230 V 460 V 575 V Number
Current 36
1.3 0.44 – 1.3 0.18 0.37 0.55 1/4 1/3 1/2 3/4 S752L01N3D_ _ _
3.2 1.1 – 3.2 0.55 1.1 1.5 1/2 3/4 1-1/2 2 S752L02N3D_ _ _
7.6 2.5 – 7.6 1.5 3 4 1-1/2 1-1/2 3 5 S752L04N3D_ _ _
37
15 4.9 – 15 3.7 6.5 8 3 3 7-1/2 10 S752L09N3D_ _ _
27 8.7 – 27 6.5 12.5 15 7-1/2 7-1/2 15 25 S752L16N3D_ _ _ 38
46 15 – 46 12.5 22 25 10 15 30 40 S752L27N3D_ _ _
78 28 – 86 15 25 30 15 20 40 60 S752L50N3D_ _ _
For applications above 40°C, derate 1% per °C.
39
For Voltage Suffix, See Table 31.6-13.
22 Technical Data
Table 31.6-14. S752 Open Soft Starters
Soft Starter S752 S752 S752 S752 S752 S752 S752
23 (Partial Catalog Number) L01 L02 L04 L09 L16 L27 L50
Dimensions
25 Width in Inches (mm) 2.14 (54) 2.14 (54) 2.14 (54) 2.14 (54) 2.14 (54) 2.14 (54) 2.14 (54)
Height in Inches (mm) 7.78 (198) 7.78 (198) 7.78 (198) 7.78 (198) 7.78 (198) 7.78 (198) 7.78 (198)
Depth in Inches (mm) 5.13 (130) 5.13 (130) 5.13 (130) 5.13 (130) 5.13 (130) 5.13 (130) 5.13 (130)
26 Weight in lbs. (kg) 3.5 (1.6) 3.5 (1.6) 3.5 (1.6) 3.5 (1.6) 3.5 (1.6) 3.5 (1.6) 3.5 (1.6)
Electrical Characteristics
27 Line Voltage (Vac)
Operating Frequency (Hz)
200 – 600
47 – 63
200 – 600
47 – 63
200 – 600
47 – 63
200 – 600
47 – 63
200 – 600
47 – 63
200 – 600
47 – 63
200 – 600
47 – 63
Leakage Current 15 mA ac max.
28 Min. Operating Current 100 mA
Control Voltage (24 Vdc ±10%) 21.6 – 26.4 21.6 – 26.4 21.6 – 26.4 21.6 – 26.4 21.6 – 26.4 21.6 – 26.4 21.6 – 26.4
Response Time Max. 100 mS 100 mS 100 mS 100 mS 100 mS 100 mS 100 mS
29 Control Steady State Current 200 mA 200 mA 200 mA 200 mA 200 mA 200 mA 200 mA
Inrush Current (During Bypass) 3.6A @ 50 mS 3.6A @ 50 mS 3.6A @ 50 mS 3.6A @ 50 mS 3.6A @ 50 mS 3.6A @ 50 mS 3.6A @ 50 mS
Control Wiring
30 (+ and -) 1 Wire per Terminal 14 – 12 AWG 14 – 12 AWG 14 – 12 AWG 14 – 12 AWG 14 – 12 AWG 14 – 12 AWG 14 – 12 AWG
(1.5 – 2.5 mm2) (1.5 – 2.5 mm2) (1.5 – 2.5 mm2) (1.5 – 2.5 mm2) (1.5 – 2.5 mm2) (1.5 – 2.5 mm2) (1.5 – 2.5 mm2)
22 Enclosed Soft Starter Features and Benefits draw, space savings and improved
safety, you enjoy the benefit of a
■ Longer Life of System Equipment — significant improvement in system
With the impressive list of control uptime and a reduction in system
23 and protective functions, this new downtime resulting in overall sys-
line of products is designed to sig- tem cost saving.
nificantly increase the protection ■ Time Savings — Time savings in
24 it offers to system equipment (e.g., using Intelligent Technologies Soft
motors, belts, pumps, etc.). The ben- Starters are achieved through a
efit of increased system equipment quick and easy setup procedure,
25 protection is longer life and longer user-friendly operational design,
system equipment uptime. the longer life of system equipment
■ Reduced Power Draw — Power and improved safety.
26 control features like Ramp Start, ■ Productivity — Overall, Intelligent
Current Limit Start and Jog Forward Technologies Soft Starters signifi-
Enclosed Soft Starter provide maximum flexibility in cantly improve your productivity
27 selecting start profiles, minimizing by saving you time and money. This
Product Description both mechanical and electrical is demonstrated by longer product
stress while maximizing motor life, longer runs between break-
28 24 Vdc Control — IT. Soft Starters
performance. downs and the ease of installation
superiority begins with the control
package which features 24 Vdc control ■ Improved Safety — IT. Soft Starters and operation.
29 running a Digital Signal Processor, or offer fingerproof deadfront con-
Standards and Certifications
DSP, and utilizing a low impedance struction, reducing the chance of
run circuit, all of which contribute to electrical shock. With the use of 24 Vdc ■ UL 508.
30 the IT. Soft Starter’s safety, advanced control power, pilot devices and
■ IEC 947-4-2.
functionality and compact size. relays can be operated more safely.
■ EN 60947.2.
■ System Cost Savings — With
Built-in Overload Protection — With
31 most Y-Delta starters, many of the improved reliability, longer life of ■ CE marked EMC/LV directives.
system equipment, reduced power ■ CSA – 22.2.
advanced features of IT. are functions
that must be added at the expense
32 of cost and space. The IT. Soft Starter, Schematic Diagram
for example, has built-in overload pro-
tection (overloads must be added to
33 Y-Delta starters). So IT. Soft Starters T1
01 L1 L1 T1
are more compact, easier to wire 02 L2 L2 T2
T2
Motor
and less costly than their Y-Delta
34 counterparts.
03 L3 L3 T3
T3
IT Soft Start
Reduced Power Consumption — The
35 IT. Soft Starter costs less in terms of
power consumption. An IT. Soft Starter
also reduces line brown-outs and L1 L2 L3
36 decreases overall energy usage. For Power Supply
example, an IT. Soft Starter controls 480 Vac – 24 Vdc Applying Voltages Other Than
+ + – –
peak power demand while a full- 24 Vdc to Terminals P Thru 4
37 voltage starter can apply 600 – 800% (–)
May Cause Serious Damage
to Soft-Start Control Board
FLA on start-up.
Terminal Board
38 Lower Starting Torque — System cost
–
savings are significant with an IT. Soft (+)
+
Starter versus a full voltage starter.
P
39 With an IT. Soft Starter, mechanical MX 1
1
components can have longer life or 24 V Inputs
be reduced in size because of lower 2
dc Only
Reset
40 starting torque values (250 – 500% FLA 4
3
4
current with SSRV).
13
Run
41 Fewer Mechanical Problems — 14 Internal 24 Vdc
Because an IT. Soft Starter reduces Customer 95 Auxiliary or
(+) 2 96 Contacts 120 Vac
stress on a system by eliminating the Control MX 96
jolts and violent speed variations that Device
42 full-voltage starters introduce to a pro-
+ – 98
Fault
(Diode)
cess, fewer mechanical breakdowns
43 occur, improving the quality of the
Figure 31.6-3. Wiring Diagram
product and process.
42
43
Maximum Current Capacity 37 66 105 135 180 240 304 360 420 500 650 720 850 1000
27
Dimensions in Inches (mm)
Width 2.60 (66.1) 4.38 (111.3) 7.65 (194.3) 11.04 (280.4)
28 Height
Depth
7.38 (187.4)
6.63 (168.4)
7.92 (201.2)
7.03 (178.6)
12.71 (322.8)
6.69 (169.9)
16.57 (420.9)
7.69 (195.3)
Weight in lbs. (kg) 5.80 (2.6) 10.50 (4.8) 48.00 (21.8) — with Lugs 103.00 (46.0) — with Lugs
41.00 (18.6) — 91.00 (41.4) — without Lugs
29 without Lugs
General Information
Bypass Mechanical Lifespan 10M
30 Insulating Voltage (Ui) 660 V
Ramp Time Range .5 – 180 Seconds (.5 – 360 Seconds Extended Ramp)
Resistance to Vibration 3g
31 Resistance to Shock 15g
Electrical Information
Operating Voltage 200 – 600 V
32 Operating Frequency 47 – 63 Hz
Overload Setting 30% – 100%
Trip Class 5, 10, 20 and 30
33 Cabling Capacity (IEC 947)
Number of Conductors 1 1 1 or 2 2, 4 or 6
Wire Sizes 14 – 2 14 – 4/0 2/0 to 500 kcmil 2/0 to 500 kcmil
34 Type of Connectors Box Lug Box Lug Add-on Lug Kit Add-on Lug Kit
Control Wiring (12-Pin)
Wire Sizes in AWG 22 – 14
35 Number of Conductors (Stranded) 2 (or one AWG 12)
Torque Requirements in lb-in. 3.5
Solid, Stranded or Flexible 3.31
36 Maximum Size in mm2
Control Power Requirements
Voltage Range (24 V ± 10%) 21.6 – 26.4 21.6 – 26.4
37 Steady State Current Amperes 1.0 1.4
Inrush Current Amperes 10 10
Ripple 1% 1%
38 Relays (1) Class A and C
Voltage ac — Maximum 240
Voltage dc — Maximum 120
39 Amperes — Maximum 3
Environment
Temperature — Operating -30ºC – 50ºC (No Derating) Consult Factory for Operation >50ºC
40 Temperature — Storage -50ºC – 70ºC
Altitude <2000 Meters — Consult Factory for Operation >2000 meters
Humidity <95% Non-condensing
41 Operating Position
Pollution Degree (IEC 947-1)
Any
3
Impulse Withstand Voltage 4000 V
(IEC 947-4-1)
42
43
S811 Open Soft Starters solid-state overload protects the motor Modbus. The advantage of QCPort is
22
from overload conditions with sophis- that multiple control components can
ticated algorithms that model true be connected to one Cutler-Hammer
motor heating, resulting in better gateway. The gateway concentrates
motor protection and fewer nuisance data from the devices into a single 23
trips. Advanced protective and diag- node. Configuration is simple —
nostic features reduce downtime. a single press the gateway’s Auto
Configuration button sets the system 24
A voltage ramp start or current limit up for default operation. This automat-
start is available. Kick start is available ically configures the I/O assemblies
in either starting mode. The soft stop to the QCPort system devices. The 25
option allows for a ramp stop time that data from these devices are then
is longer than the coast to stop time. assembled into a single input and
The pump control option provides a output messages. 26
smooth transition for starting and
stopping a motor and eliminating The S811 communication parameters
the “water-hammer” effect that can can be configured with the DIM or 27
damage pipes, valves and pumps. through the network using CH Studio
Product Description Component Manager. Advanced
The S811 offers an impressive array of
Eaton’s Cutler-Hammer IT. S801 advanced protective features. Not only
communication configuration settings 28
revolutionized the reduced voltage provide the system integrator with
are the protective features selectable, powerful tools to facilitate system
control marketplace with its advanced but many offer variable settings allow-
feature set and small size. In fact, ing the user to fine tune the starter to
optimization. 29
readers of an industry leading control meet specific system requirements.
publication rated Cutler-Hammer Soft Features and Benefits
Starters best in customer satisfaction The S811 has an easy to use Digital
■ The DIM (Digital Interface Module)
30
in March 2004. The new IT. S811 from Interface Module (DIM) that allows the
provides an intuitive, easy-to-use
Eaton’s electrical business offers all user to configure the device and to
human interface with powerful con- 31
the popular features of the S801, but read system parameters. The DIM
figuration capabilities to maximize
adds enhanced functionality with the includes an LCD display and keypad to
system performance.
new DIM (Digital Interface Module) scroll through the various menus. The
and communications capabilities. DIM allows the user to modify control ■ Door or device mounted DIM 32
parameters, enable or disable protec- enables users to safely configure,
The Cutler-Hammer Intelligent tions, set communication variables, commission, monitor and trouble-
Technologies (IT.) Line of S811 monitor system parameters such as shoot the system at the electrical 33
Reduced Voltage Soft Starters is line voltages and currents, and access panel without opening the enclo-
very compact, multi-functional, easy the fault queue. sure door.
to install and easy to program. ■ System operating parameters can 34
Designed to control the acceleration be monitored enterprise-wide
and deceleration of three-phase through a communications network.
motors up to 690V, the line is available ONLN SS OXFDO1 H STOP Increase uptime by providing data 35
from 11 amps through 1,000 amps. Monitoring for process management and
preventive diagnostics.
The S811 is designed to be a complete PREV NEXT ENTER
■ Run bypass mode greatly reduces 36
package combining the SCRs, bypass
contactor and overload in one, very internal heating created by the
greater power dissipation in
compact unit. The S811 is available
the SCRs. Bypass contactor directly 37
as a component for panel mounting,
in motor control centers or in enclosed connects the motor to the line and
ESC
improves system efficiency by
control (NEMA Type 1, 3R, 4, 4X, 7/9
reducing internal power losses.
38
and 12).
■ Internal solid-state overload protec-
Figure 31.6-4. Digital Interface Module (DIM)
Application Description tion provides accurate current mea- 39
The DIM can be removed from the surement and trip settings.
S811 and remote mounted. Kits are Sophisticated algorithms solve a
Designed to control the acceleration
and deceleration of three-phase available to door mount the DIM, series of differential equations that 40
enabling users to safely configure, model true motor heating and cool-
motors, the IT. S811 soft starter uses
commission, monitor and trouble- ing, resulting in superior motor
Silicon Controlled Rectifiers (SCRs) to
control the voltage to soft start and shoot the system at the electrical panel overload protection while minimiz- 41
without opening the enclosure door. ing nuisance trips. Advanced select-
soft stop the motor. After the motor is
able protective features safeguard
started, internal run bypass contactors
close, resulting in the motor running
The S811 has built-in communications the motor and system against a 42
capabilities through Cutler-Hammer variety of system faults.
directly across-the-line. The built-in
QC (Quick Connect) Port. The QCPort
enables the soft starter to be con- 43
nected to a variety of networks,
including DeviceNet™ and EtherNet/
■ Internal run bypass contactors and The S811 calculates a thermal memory Stall
22 overload protection eliminate the value. A 100% value represents the Excessive current and torque up to
need for additional devices, reducing maximum safe temperature of the locked rotor levels can occur in a stall
enclosure sizes, minimizing installa- motor. When the thermal memory condition. The condition can lead to an
23 tion and wiring time and reducing value reaches 100%, an overload trip overload trip and result in stress and
overall assembly size and cost. will occur removing power to the damage to the motor, load, mechani-
■ Wide range of overload FLA settings motor. Upon trip, the S811 stores the cal system, and the electrical distribu-
24 (31 – 100% of rated current) and a calculated motor heating value and tion system. Stall protection prevents
selectable trip class (5 – 30) offers will not allow a motor re-start until the stress and damage to a motor that has
users the flexibility to fine tune the motor has sufficiently cooled. This fea- not come up to speed, or stalled after
25 starter to match specific application ture ensures the motor will not be the soft start time. The S811 will trip to
requirements. damaged by repeated overload trip, protect the system in the event that the
■ Variable ramp times and torque con- reset and re-start cycles. motor did not get to the rated speed in
26 trol settings provide unlimited start- the defined soft start period. A current
ing configurations, allowing for The thermal memory value can be
monitored through the DIM or the greater than 200% FLA at the end of
maximum application flexibility. the soft start period will cause the
27 ■ Kick-start feature enables soft start-
communications network. The thermal
starter to trip on a stall fault.
memory value can be of great use in
ing of high friction loads.
determining an impending overload Pole Over Temperature
28 ■ Soft stop control for applications trip condition. Alarms can be imple-
where an abrupt stop of the load is High ambient temperatures, extended
mented in the process monitoring
not acceptable. ramp times and high duty cycle condi-
system warning of an impending trip
tions may cause the S811 power pole
29 ■ Pump control option with sophisti- before a trip occurs halting the pro-
conductors to reach a temperature that
cated pump algorithms on both cess. Costly system downtime can be
starting and stopping that minimize exceeds their thermal rating. The S811
avoided.
is equipped with sensors that monitor
30 the pressure surges that cause
water hammer. The pump control The trip current is adjusted to match the temperature of the power poles.
option will maximize the life of the the specific application requirements Over temperature protection occurs
pump and piping systems while by entering the motor nameplate full if the device’s thermal capacity is
31 minimizing the downtime caused by load current rating and trip class. The exceeded. The soft starter will trip in
system failure. FLA adjustment includes a 3 to 1 over temperature conditions, prevent-
adjustment range. The overload trip ing device failure.
32 ■ Six SCRs control all three motor
class is adjustable from class 5
phases, providing smooth accelera- The device pole temperature value
tion and deceleration performance. through class 30. The overload is
can be monitored through the DIM or
33 ■ Soft acceleration and deceleration ambient temperature compensated —
the communications network. This
reduces wear on belts, gears, chains, meaning its trip characteristics will not
feature can be of use in determining
clutches, shafts and bearings. vary with changes in ambient
an impending over temperature trip
34 temperature. The overload protection
■ Reduce the peak inrush current’s condition. Alarms can be implemented
stress on the power system. can be enabled, disabled, or disabled
in the process monitoring system
on start.
■ Minimize peak starting torque to warning of an impending trip before a
35 diminish mechanical system wear Short Circuit trip occurs, halting the process. Costly
and damage. The use of a short circuit protective system shutdown can be avoided.
■ 24 Vdc control module enhances device in coordination with the S811 is
36 personnel and equipment safety. required in branch motor circuits by
Phase Loss
Loss of a phase can cause a significant
■ Removable, lockable control termi- most electrical codes. Short circuit
increase in the current drawn in the
37 nal block reduces maintenance coordination ratings with both fuses
remaining two phases. Phase loss can
costs. Also provides the opportunity and Cutler-Hammer molded case cir-
for OEMs to reduce assembly and lead to motor damage before an even-
cuit breakers are available providing
test costs by utilizing pre-assembled tual overload trip occurs. Phase loss is
38 customers with design flexibility. The
wire harnesses. typically an indication of a failure in
S811 has short circuit coordination
the electrical distribution system. The
ratings as an open component, an
Protective Features S811 will detect a phase loss and trip
39 enclosed starter, and in a motor
control center.
if any phase current drops below a
All protective features can be config- preset value. The phase loss trip level
ured, enabled or disabled with the DIM Jam is adjustable from 0% to 100% of the
40 or through the communications
Excessive current and torque up to average of the other two phase levels
network. with an adjustable trip delay of 0.1 to
locked rotor levels can occur in a jam
Motor Overload condition. The condition can result in 60 seconds.
41 stress and damage to the motor, load,
The S811 includes electronic overload
protection as standard. The overload mechanical system, and the electrical
42 meets applicable requirements for a distribution system. Jam protection
motor overload protective device. The prevents the stress and damage from
overload protects the motor from over a jam during normal run. After the
43 heat conditions with the use of sophis- motor is started, a current greater than
300% FLA setting will cause the starter
ticated algorithms that model true
motor heating, resulting in superior to trip on a jam fault.
motor protection and fewer nuisance
trips.
22
Percent Thermal Memory communications network to assist in Accessories
Provides the real time calculated ther- planning maintenance resources. 30
mal memory value. The S811 calcu- different faults can be identified by the
S811.
Surge Suppressors
lates thermal memory value. A 100%
23 value represents the maximum safe A surge suppressor can mount on
Control Status either the line or load side of the IT.
temperature of the motor. When the
thermal memory value reaches 100%, The S811 provides data that repre- Soft Starter. It is designed to clip the
24 an overload trip will occur, removing sents system conditions that can be line voltage (or load side induced
power to the motor. read through the DIM or the communi- voltage).
cations network. This data identifies
25 The thermal memory value can be of the status of the system and the con-
great use in determining an impending trol commands the system is request-
overload trip condition. Alarms can be ing of the S811. This can be used for
26 implemented in the process monitor- advanced troubleshooting and
ing system warning of an impending system integration activities.
trip before a trip occurs, halting the
27 process. Costly system downtime can Breaker Status
be avoided. The S811 has provisions to read and
display circuit breaker status. Cutler-
28 DC Control Voltage Hammer communicating Cover Con-
Surge Suppressor
Monitors level of the 24 Vdc control trol or other communicating protective
voltage. Fluctuations in control voltage device is required to take advantage of
29 can cause component malfunction and this feature.
failure. System control voltage data
can be used to implement warnings, User Manual
30 alarms and system actions to low or A comprehensive user manual is avail-
high voltage conditions. able and can be downloaded free of
charge from www.EatonElectrical.com
31 Pole Temperature
by performing a document search for
Increases in pole temperature are
MN03902002E.
caused by increases in ambient tem-
32 perature, start/stop times and start
duty cycles. Changes in pole tempera- Surge Suppressor Mounted on
tures represent a change in system a 200 mm Device
33 operating conditions. Identifying
unexpected operating conditions or Table 31.6-21. Surge Suppressors
changes can prompt maintenance and Description Catalog
34 aid in process evaluation activities. Number
Operation 22
Table 31.6-26. Product Selection — Severe Duty Rating Open Soft Starters
37 Frame Max. Three-Phase Motor Catalog
Size Current Number
kW Rating (50 Hertz) hp Rating (60 Hertz)
38 230 380 – 400 440 200 V 230 V 460 V 575 V
Volt Volt Volt 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF
39 N 22
42
5.5
11
10
18.5
11
22
5
10
5
10
7-1/2
15
5
10
15
30
10
25
20
40
15
30
S811N37N3S
S811N66N3S
R 65 15 30 33 15 15 20 15 50 40 50 50 S811R10N3S
80 22 40 45 25 20 30 25 60 50 75 60 S811R13N3S
40 T 115 33 59 63 30 30 40 30 75 75 100 100 S811T18N3S
150 45 80 90 50 40 50 50 100 100 150 125 S811T24N3S
192 55 100 110 60 50 75 60 150 125 200 150 S811T30N3S
41 V 240 75 110 147 75 60 75 75 200 150 200 200 S811V36N3S
305 90 160 185 100 75 100 100 250 200 300 250 S811V42N3S
365 110 185 220 125 100 150 125 300 250 350 300 S811V50N3S
42 420
480
129
147
220
257
257
295
150
150
125
150
150
200
150
150
350
400
300
350
450
500
350
450
S811V65N3S
S811V72N3S
525 160 280 335 150 150 200 150 450 350 500 450 S811V85N3S
600 185 315 375 200 150 250 200 500 450 600 500 S811V10N3S
43
Technical Data 22
Table 31.6-27. Specifications — IT. Soft Starter
Soft Starter S811 S811 S811 S811 S811 S811 S811 S811 S811 S811 S811 S811 S811 S811
(Partial Catalog Number) N37 N66 R10 R13 T18 T24 T30 V36 V42 V50 V65 V72 V85 V10 23
Max. Current Capacity 37 66 105 135 180 240 304 360 420 500 650 720 850 1000
FLA Range 11 – 37 20 – 66 32 – 42 – 56 – 75 – 95 – 112 – 131 – 156 – 203 – 225 – 265 – 320 – 24
105 135 180 240 304 360 420 500 650 720 580 1000
Dimensions
Width in Inches (mm) 2.66 (67.6) 4.42 (112.2) 7.67 (194.8) 11.05 (280.6) 25
Height in Inches (mm) 7.38 (187.4) 7.92 (201.2) 12.71 (322.9) 16.57 (420.8)
Depth in Inches (mm) 6.48 (164.5) 6.64 (168.7) 6.39 (162.4) 7.35 (186.6)
26
Weight in lbs. (kg) 5.8 (2.6) 10.5 (4.8) 48 (21.8) with lugs 103 (46.8) with lugs
41 (18.6) without lugs 91 (41.4) without lugs
General Information 27
Bypass Mechanical Lifespan 10 M
Insulating Voltage Ui 660 V
Ramp Time Range .5 – 180 Seconds (.5 – 360 Seconds Extended Ramp) 28
Resistance to Vibration 3g
Resistance to Shock 15g 29
Electrical Information
Operating Voltage 200 – 600 V
Operating Frequency 47 – 63 Hz 30
Overload Setting 30 – 100%
Trip Class 5, 10, 20 & 30
31
Cabling Capacity (IEC 947)
Number of Conductors 1 1 1 or 2 2, 4 or 6
Wire Sizes 14 – 2 14 – 4/0 4 AWG to 500 kcmil 2/0 to 500 kcmil 32
Type of Connectors Box Lug Add-On Lug Kit
Control Wiring (12-Pin)
33
Wire Sizes in AWG 22 – 14
Number of Conductors 2
(Stranded) (or one AWG 12) 34
Torque Requirements 3.5
in lb-in
Solid, Stranded or Flexible 3.31 35
Max. Size in mm2
Control Power Requirements
Voltage Range (24 V ± 10%) 21.6 – 26.4 36
Steady State Current Amps 1.0 1.0 1.0 1.4
Inrush Current Amps 10 10 10 10
Ripple 1%
37
Relays (1) Class A and C
Voltage ac — maximum 240 38
Voltage dc — maximum 120
Amps — maximum 3
Environment
39
Temperature — Operating -30 – 50°C (No derating) Consult factory for operation > 50°C
Temperature — Storage -50 – 70°C 40
Altitude <2000 Meters — Consult factory for operation > 2000 m
Humidity <95% Non-condensing
Operating Position Any
41
Pollution degree IEC947-1 3
Impulse withstand Voltage
IEC947-4-1
6000 V 42
UR Recognized Product
43
25
Typical IT. Power Supply
26 Table 31.6-29. Specifications — IT. Power Supply
Catalog Number PSS55A PSS55B PSS55C
27 Output Specifications
Output Voltage Nominal 24 Vdc 24 Vdc 24 Vdc
Voltage Regulation ±3% ±3% ±3%
28 Steady State Wattage 55W 55W 55W
Outrush Wattage 240W 240W 240W
Outrush Hold Up Time (mS) 180 mS 180 mS 180 mS
29 Output Current 2.3 A 2.3 A 2.3 A
Maximum Capacitive Load 10,000 µF 10,000 µF 10,000 µF
30 Hold Up Time (mS) 120 mS 120 mS 120 mS
Overload Protection Overcurrent shutdown Overcurrent shutdown Overcurrent shutdown
with automatic restart with automatic restart with automatic restart
31 Input Specifications
Input Voltage Nominal 115 Vac 230 Vac 360 – 480 Vac
Voltage Range ±15% ±15% ±15%
32 Input Frequency 47 – 63 Hz 47 – 63 Hz 47 – 63 Hz
Input Current .9A .53A .13A
Input Protection
33 Inrush Current 15 A 30 A 15 A
Overvoltage 390 Vac 390 Vac 550 Vac
Fused Yes Yes Yes
34 Switching Frequency 100 kHz 100 kHz 100 kHz
Efficiency (At Maximum Load) 80% 80% 85%
35 Maximum Ripple ±1% ±1% ±1%
Operating Specifications
Dielectric Strength Input to Output 3 k Vac 3 k Vac 3 k Vac
36 Dielectric Strength Input/Output to DIN Rail 3 k Vac 3 k Vac 3 k Vac
Dielectric Strength Input to Ground 1.5 k Vac 1.5 k Vac 1.5 k Vac
37 Dielectric Strength Output to Ground 200 Vac 200 Vac 200 Vac
Temperature: Operating 0°C – 50°C 0°C – 50°C 0°C – 50°C
Storage -40°C – 85°C -40°C – 85°C -40°C – 85°C
38 Altitude <2000 meters, 20 to 85% RH <2000 meters, 20 to 85% RH <2000 meters, 20 to 85% RH
Operating Humidity Non-condensing Non-condensing Non-condensing
Vibration 3g 3g 3g
39 RFI Specification Class A Class A Class A
Degree of Protection (IEC529) IP20 IP20 IP20
40 Insulation Stripping Length
Wire Size Primary 20 – 12 AWG 21 – 12 AWG 22 – 12 AWG
Clamp Screw Tightening Torque in lb-in (Nm) 4.38 (.5) 4.38 (.5) 4.38 (.5)
41 Wire Size Secondary 20 – 12 AWG 20 – 12 AWG 20 – 12 AWG
Clamp Screw Tightening Torque in lb-in (Nm) 4.38 (.5) 4.38 (.5) 4.38 (.5)
Output Connections 2 2 1
42 Insulation Stripping Length in Inches (mm) .35-inch (8.9 mm) .39-inch (9.9 mm) .43-inch (10.9 mm)
Mounting Method Panel Mount Panel Mount Panel Mount
DIN Rail Mounting Kit 1.4-inch (35.1 mm) PSSDIN PSSDIN PSSDIN
43 Dimensions and Standards
Mechanical Dimensions in Inches (mm) 2.09 x 3.90 x 5.60 (53 x 98 x 142) 2.09 x 3.90 x 5.60 (53 x 98 x 142) 2.30 x 4.20 x 6.80 (59 x 107 x 172)
Approximate Weight in lbs. (kg) 1.1 (.48) 1.1 (.48) 1.2 (.53)
Certifications/Standards cULus, IEC cULus, IEC cULus, IEC
Type 1 (Conforms to IP40) — for Indoor Use Cover-mounted pilot device holes are 27
provided and covered with hole plugs.
Suitable for most applications where
unusual service conditions do not
exist and where a measure of protec- 28
tion from accidental contact with
enclosed equipment is required.
Designed to meet tests for rod entry 29
and rust resistance. Enclosure is sheet
steel, treated to resist corrosion.
Depending on the size, knockouts are 30
provided on the top, bottom and
sometimes on the side.
31
32
33
Type 4X
42
43
1 40
41 3R 52
4 65
4X 65
42 12 62
43
Table 31.7-4. Non-combination Solid-State Reduced Voltage Box Table 31.7-5. Combination Solid-State Reduced Voltage Box Dimensions
37
Dimensions Ampere SSRV Comb. Comb. Ampere SSRV Comb. Comb.
Ampere SSRV
Rating
Non-
combination
Ampere SSRV
Rating
Non-
combination
Rating with with
Fuses HMCP
Rating with with
Fuses HMCP 38
Box No. Box No. Box Box Box Box
No. No. No. No.
.8 – 27 S752 6A 304 S801/S811 G1 39
37 S801/S811 7A 360 S801/S811 G1 .8 – 27 S752 B1 A1 304 S801/S811 F1E E
50 S752 6A 420 S801/S811 10 37 S801/S811 B1 A1 360 S801/S811 F1E E
A1
66 S801/S811 7A 500 S801/S811 10 50
66
S752
S801/S811
C
C A1
420
500
S801/S811
S801/S811
F1E
F1E
E
E
40
105 S801/S811 7A 650 S801/S811 10
135 S801/S811 B1 105 S801/S811 D B1 650 S801/S811 F1E F1E
720 S801/S811 10 135 S801/S811 D C
180 S801/S811 C 720 S801/S811 F1E F1E
240 S801/S811 G1
850 S801/S811 10 180 S801/S811 E E 850 S801/S811 F1E F1E 41
1000 S801/S811 10 240 S801/S811 F1E E 1000 S801/S811 F1E F1E
Enclosure space will also accommodate for an IT. Power Supply, two
4-pole relays, CPT, and terminal blocks. Also includes space for a DNA Enclosure space will also accommodate for an IT. Power Supply, two 4-
pole relays, CPT, and terminal blocks. Also includes space for a DNA
42
module or MOV.
module or MOV.
Same as footnote , but CPT is not included. Upsize to 7A enclosure to Enclosure may be reduced to an A1, with all space for all items as in
include space for a CPT and a full voltage bypass contactor.
footnote , excluding relays and CPTs. 43
Note: All Type 7 and 9, see Section 11. Same as footnote , but CPT is not included. Upsize to B1 enclosure to
include space for a CPT and a full voltage bypass contactor.
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Application The enclosure and wireway cover plates A dust- and weather-resistant enclo-
Eaton’s Cutler-Hammer Multi-Pak Group
come in ASA-70 light gray enamel. An sure to house the Type 1 enclosure is 22
identification card retainer is mounted also available.
Control is designed to save time, space, on each compartment door.
and expense in installing motor control 23
devices — whether for residential,
commercial, or industrial buildings.
The modular assembly allows versatile, 24
on-the-job arrangement of Sizes 1
through 4 combination starters with
ambient compensated relays, incoming 25
or feeder circuit breakers or fusible dis-
connect switches, pushbuttons, control
transformers, timers, relays, and fuses. 26
The enclosures and separate, pre-wired
modules are field-stocked and can be
ordered individually, permitting field 27
tailoring to suit the application.
Advantages 28
■ Enclosures and pre-wired equipment
modules are individually available
from stock. Each shipping carton Multi-Pak Four Compartment Enclosure Showing Variety of Possible 29
contains complete mounting and Equipment Module Combinations Available
installation instructions.
■ Cuts installation time by 25 percent.
30
The pre-wired modules can be
installed easily, using only a
screwdriver, at the job site.
31
■ Saves space over individually
mounted control. 32
■ Can be wall or rack mounted.
■ Has flexible panel space for auxil-
iary control items. Barriers can 33
be removed to provide oversized
compartments.
■ Eliminates square duct or cable 34
entrance box.
■ Simplifies wiring. Typical Six Compartment Multi-Pak After Assembly 35
■ Permits quick, easy additions and
rearrangements. The Multi-Pak enclosure adapts easily Hinging of the front doors provides
to installation requirements. Multiple for easy access to each module. The
■ UL listed — E69852, Guide NITW. units can be arranged to suit the space doors are also gasketed with a fire-
36
available — horizontally on a single retardant material. Knockouts are pro-
Enclosure Features line or two-high. Knockouts are pro- vided on the doors for the mounting
The Type 1 enclosures are partitioned vided at the top, bottom and sides of of pushbuttons and indicating lights.
37
into either four or six compartments, the enclosures for conduit connection.
to hold combination starter modules, Conduit can be installed and cables
incoming or feeder circuit breakers, fus- pulled as dictated by the construction
38
ible switches, or other auxiliary devices. schedule. Combination starter modules
The barriers can be removed to provide and incoming or feeder devices can be
oversized spaces. Each enclosure holds installed days, months or years later.
39
up to four Size 1 or 2 full-voltage, non-
reversing combination starter modules; In addition to the barrier compartments,
up to two Size 3 or 4 starter modules, the enclosure contains two wiring 40
or a combination of both size ranges. troughs. The top section is a wireway
fitted with three power terminal straps,
The compartments have hinged doors, each having terminals for extension 41
interlocked to prevent opening when the to adjoining enclosures and to all four
breaker switch is in the ON position. The compartments. The incoming line and
disconnect operating mechanism can be extension terminals are suitable for 42
padlocked in the OFF position. either copper or aluminum conductors,
from No. 6 to 350 kcmil. At the bottom
of the enclosure is another wiring 43
trough for interconnecting wiring
and outgoing cables.
22 Combination Starter Modules Outgoing Conduits May Be All Supply Feed Thru Nipples
at Top, All at Bottom or Mixed
Eaton’s Cutler-Hammer Starter modules
consist of a Class A200 magnetic line-
23 starter, prewired with a motor circuit pro-
tector or a fusible DS disconnect switch on
a panel. Full-voltage non-reversing and 26
24 reversing, combination starters are avail- Incoming Line
at Top or Side
able. An external reset button is mounted (Either End)
on the starter module door. With its versa-
25 tile, modular design, the Multi-Pak starter H-Units at 32 Inches (812.8 mm) Each
permits a variety of motor control group- Outgoing Conduits May Be All Supply Feed Thru Nipples One Compartment Used to
ings. One module can contain many at Top, All at Bottom or Mixed Feed Supply to Bottom
26 different arrangements of devices, such
as combination linestarter with control
transformers, and/or relays, or two feeder
27 circuit breakers, or fusible switches.
Incoming Line
The contactor design comprises a at Top or Side
glass polyester case with silver-cad- (Either End)
28 mium oxide alloy contacts, straight- 52
through wiring, out-front terminals,
molded coils, stainless steel kickout
29 springs, U-type magnet, and a shock
absorber baseplate.
30 The circuit breakers, equipped with
adjustable magnetic trip elements,
protect against short circuits. Standard
31 3-pole, inverse-time, and ambient 1, 2 or 3 Units at 32 Inches (812.8 mm) Each
compensated thermal overload relays
protect against overload.
Figure 31.8-1. Wiring Arrangements
32 Fusible switches are equipped to
accept either 250- or 600-volt Class H,
K, and R cartridges fuses, with capaci- 6.38 (8) Knockouts on
33 ties as listed by Underwriters Labora- 3.00
(162.1) 2-3/4 Centers (Top 8 Bottom) 3.00 Note: For Six
tories for overcurrent protection. (76.2) (76.2) Compartment
3.38 Enclosure
Add 16 Inches
34 ON-OFF operating mechanisms are mold-
ed from an ABS fire-resistant material.
7.00 6.13
(177.8) (155.7)
(85.9)
to Width.
8.50 0.63
(215.9) (16.0)
Components of each module have
35 individual printed labels identifying size,
(8) 1/2, 3/4, 1 Inch Knockouts
2.00
32.00
voltage, ampere rating, etc. The labels (812.8)
(50.8) 3.38
2.00 28.00
also contain a schematic drawing refer- (50.8) (711.2) (85.9)
36 ence number covering the wiring of the 3.00
5.50
component contained in the module. (139.7)
(76.2)
43 for 4 or 6 module units are available. Eaton Corporation. NEMA is the registered trademark
and service mark of the National Electrical Manufactur-
These enclosures are 34.00 inches ers Association. UL is a federally registered trademark
(863.6 mm) or 50.00 inches (1270.0 mm) of Underwriters Laboratories Inc. CSA is a registered
wide, 31.00 inches (787.4 mm) high, trademark of the Canadian Standards Association.
Modbus is a registered trademark of Modicon, a divi-
and 11.75 inches (298.5 mm) deep. sion of Schneider Electric Industries SA.