Sei sulla pagina 1di 14

Solar Energy 81 (2007) 1058–1071

www.elsevier.com/locate/solener

Review

A review of transparent insulation systems and the evaluation


of payback period for building applications
a,*
I.L. Wong , P.C. Eames b, R.S. Perera a

a
Centre for Sustainable Technologies, University of Ulster, Newtownabbey, Co. Antrim BT37 0QB, UK
b
Warwick Institute for Sustainable Energy and Resources, School of Engineering, University of Warwick, Coventry CV4 7AL, UK

Received 9 August 2006; received in revised form 9 April 2007; accepted 9 April 2007
Available online 14 May 2007

Communicated by: Associate Editor Jean-Louis Scartezzini

Abstract

Research and development of transparent insulation systems (TI-systems) has been ongoing for 20 years with transparent insulation
materials (TIMs) used to replace standard opaque insulation materials. TIM not only performs similar functions to opaque insulation,
reducing heat losses and controlling indoor temperatures, but allows solar transmittance of more than 50%. With a thickness of less than
20 cm, it can provide a financial return to building occupants when applied to building facades, maximising occupiable and sellable
spaces in urban areas, without compromising thermal comfort within buildings.
In this review of TI-systems for building applications, drawbacks to previous applications, cost trends, and analysis of the limitation
in information from previous studies are discussed. A major drawback in the development of TI-systems identified is the lack of cost
information; the payback periods for TI-systems used in previous renovation projects are virtually unknown. Simple payback period
calculations were undertaken based on information available from a demonstration project documented by the Solar Heating and
Cooling (SHC) Programme of the International Energy Agency (IEA) Task 20 ‘‘Solar Energy in Building Renovation’’. The calculations
indicated an encouraging 5–8-year payback period for this particular case study. It was concluded that the simple payback period
calculation may be used for feasibility studies to indicate the time required to recoup investment when installing TI-systems and to
provide initial guidance for building designers when evaluating the potential application of TI-systems in their buildings.
 2007 Elsevier Ltd. All rights reserved.

Keywords: Transparent insulation material (TIM); Transparent insulation system (TI-system); Building applications

Contents

1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ......... . ......... . ......... . 1059


2. Historical background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ......... . ......... . ......... . 1059
3. Classification of TIMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ......... . ......... . ......... . 1060
4. Materials used for TIMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ......... . ......... . ......... . 1060
5. Physical properties of TIMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ......... . ......... . ......... . 1061
5.1. Theoretical analysis of optical and thermal properties of TIMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1061
5.2. Experimental characterisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1062

*
Corresponding author. Tel.: +44 028 90368014; fax: +44 028 90368239.
E-mail addresses: ing.wong@ulster.ac.uk, xijiayu@hotmail.com (I.L. Wong), P.C.Eames@warwick.ac.uk (P.C. Eames), s.perera@ulster.ac.uk (R.S.
Perera).

0038-092X/$ - see front matter  2007 Elsevier Ltd. All rights reserved.
doi:10.1016/j.solener.2007.04.004
I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071 1059

6. Applications of TIMs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1063


6.1. Flat-plate solar collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1063
6.2. Honeycomb roof cover system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1064
6.3. Integrated collector storage for domestic hot water supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1064
6.4. Space heating and daylighting for buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1065
7. Simulations of transparent insulation systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1067
8. Barriers to the development and implementation of transparent insulation systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
8.1. Imperfection in manufactured TIMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
8.2. Low working temperatures of plastic TIMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
8.3. High investment cost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
8.4. Overheating problem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
9. Limitations in current knowledge evident from previous studies on transparent insulation applications in buildings . . . . . 1068
9.1. Potential for commercial building applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
9.2. Design guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
9.3. Suitability for new building applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
9.4. Insufficient/inadequate cost information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1069
10. Calculation of simple payback period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1069
11. Discussion and conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1070
Acknowledgement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1070
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1070

Nomenclature

g total energy transmittance (%) a solar absorptance (%)


A aspect ratio (length divided by hydraulic diame- s0 model fit parameter representing effective trans-
ter) mittance
n number of cell wall interaction for the incoming a0 model fit parameter representing effective
light beam absorption
s solar transmittance (%)
Greeks h angle of incidence ()
/ azimuth angle () K thermal conductance (W/m2 K)
q solar reflectance (%) (sae) effective transmittance–absorptance product (%)

1. Introduction Russian researchers investigated the possibility of using


low-conducting and solar absorbing walls as a thermal
Standard insulation materials reduce the transmission of insulation material. A honeycomb made of paper was
heat through conduction, convection and radiation in opa- introduced between the glass cover and absorber plate
que walls (Kaushika and Sumathy, 2003). Depending on the in a flat-plate solar collector. The studies performed in
building codes and regulations across different countries, 1929 were reported by Veinberg (1959) in his publication.
the thickness of insulation materials used is typically This inspired Francia (1961) to use glass tubes in a solar
around 25–30 cm (IEA, 1997). This results in a wall thick- collector designed to work at high absorber temperatures.
ness of up to 50 cm, which reduces the letable or occupied Subsequently a theoretical study of honeycomb structures
space of buildings for a given building foot print (Hastings, between absorber and outer glass cover of a flat-plate
2004). TI has been used to overcome this problem and add solar collector to suppress convective heat transport
value with solar energy transmittance of more than 50% and was undertaken by Hollands (1965). The earliest TIMs
thermal conductivity of less than 0.2 W/m2 K (IEA, 1997). were used as absorbers or convective suppression devices
(CSDs) in solar collectors. Until 1969, plastic honey-
2. Historical background combs with desired thermal characteristics and transpar-
ency were still not available for flat-plate solar collectors
In the context of solar energy systems, the idea of sup- (Tabor, 1969). In the 1980s, to achieve energy conserva-
pressing convective heat losses emerged long before the tion, TIMs were integrated into buildings when being
term ‘transparent insulation’ was introduced. In 1929, renovated.
1060 I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071

In the past 20 years, theoretical and experimental inves- (Fig. 1a) consist of a cover, comprising of either multiple
tigations have been undertaken to improve suppression of glazing elements or transparent plastic films parallel to
natural convection using large-celled and small-celled hon- the absorber surface. The number of cover layers can be
eycomb structures. A fluorinated ethylene propylene (FEP) increased to reduce heat loss, but resulting in an increase
large-celled honeycomb structure with 20 lm thick walls in optical reflection and solar gain reduction, thus such sys-
and 10 mm hydraulic diameter was proposed as a CSD tems fail to meet the criteria of high transmission and low
for use in flat-plate collectors, achieving a solar transmit- heat loss as required for solar collectors.
tance of 92% at a 45 incidence angle (Hollands et al., Absorber-perpendicular structures (Fig. 1b), such as,
1992). In the early 1990s, large-celled honeycomb struc- parallel slat arrays, honeycombs or capillaries, have low
tures made of highly transparent films, such as, polypropyl- optical reflection losses and reflect and transmit the incom-
ene, polycarbonate (PC) and fluorised films with U-values ing beam radiation effectively towards the absorber. This
of approximately 2 W/m2 K and working temperatures of structure is widely used in various TIM applications, par-
between 60 C and 100 C were produced and commercia- ticularly, for solar collectors, avoiding the high reflection
lised (Platzer, 2001). losses occuring in the absorber-parallel structures. The cav-
Small-celled honeycomb structures with improved opti- ity structures (Fig. 1c) combine both absorber-parallel and
cal and thermal properties (U-values of less than 1 W/ absorber-perpendicular structures, they consist of duct
m2 K) have been made of glass or plastic, with square or plates or multiple plastic films that effectively suppress con-
circular cells. They are easier to produce compared to vective heat loss while maintaining approximately the same
large-celled honeycomb structures. The Fraunhofer Insti- transmittance as a multiple film cover. Quasi-homogeneous
tute for Solar Energy System (FISES) were the main pio- structures (Fig. 1d) include TIMs made of glass fibre or
neer in this area of research using different materials to aerogel and are characterised by both scattering and
suppress heat transfer by convection and radiation (Plat- absorption of the incident radiation within the TIM. The
zer, 2001). Today, TIMs produced commercially are made structure can be as clear as a glass pane although it is
of polymethylmethacrylate (PMMA), PC (Okalux Kapil- porous, with a high density (90–95%) of approximately
larglas GmbH, Advanced Glazings Ltd., Schott, Hauptsitz 10–30 nm diameter pores distributed uniformly through-
Sto AG, and Glaswerke Arnold GmbH+ Co., KG), acrylic out the materials (Platzer, 2001; Kaushika and Sumathy,
translucent foam (Prokuwa Kunststoff GmbH) and aero- 2003).
gels (Airglass AB). Their optical and thermal performance
are both influenced by the uniformity and quality of the 4. Materials used for TIMs
cells produced.
Over the past 30 years, different types of materials, such
3. Classification of TIMs as, plastics, glass, and aerogels, have been used to produce
TIMs. The materials used for different types of TIM are
TIMs are classified into four generic types in accordance detailed in Fig. 2. Various types of plastics widely used in
with the geometrical layout of the materials, each has a the productions of small-celled capillary and honeycomb
unique pattern of solar transmission and physical behav- structures are PMMA, polyethylene (TPX), polytetrafluor-
iour, as illustrated in Fig. 1. Absorber-parallel structures ethylene (HFL), polyestercarbonate (APEC), polyether-

Absorber-parallel structures Absorber-perpendicular structures

Cavity structures Quasi-homogeneous structures


Fig. 1. Classification of transparent insulation materials (Goetzberger, 1991; Platzer, 2001; Kaushika and Sumathy, 2003): (a) absorber-parallel structures;
(b) absorber-perpendicular structures; (c) cavity structures; (d) quasi-homogeneous structures.
I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071 1061

Fig. 2. Illustration of different types of materials used for transparent insulation materials.

sulfone (PES), FEP teflon (FEPT) and PC (Platzer, 2001; 5.1. Theoretical analysis of optical and thermal properties of
Kaushika and Sumathy, 2003). Despite exhibiting Ultra- TIMs
Violet (UV) stability (Platzer, 2001), plastics do not with-
stand the high stagnation temperatures of solar collectors Theoretical analysis can be used to determine both ther-
due to their low melting temperatures of between 120 C mal and optical properties of TIMs made of different mate-
and 150 C (Rommel and Wagner, 1992; Platzer, 2001; rials with different geometrical layouts. Mathematical
Kaushika and Sumathy, 2003). models have been developed by various researchers to
Glass is an ideal substitute for plastic TIMs in solar col- assess the physical properties of different TIMs, particu-
lector applications due to its high working temperature of larly, thermal conductance, K, s(h), s, and the effective
up to 550 C (Platzer, 2001). It is able to withstand the high transmittance–absorptance product (sae) (Hollands, 1965;
stagnation temperatures of more than 250 C that can 1978; Symons, 1982; Platzer, 1987, 1992a,b,c; Arulanan-
occur in many solar collectors (Rommel and Wagner, tham and Kaushika, 1994; Kaushika and Sumathy,
1992; Platzer, 2001), however, glass is fragile due to the 2003). The earliest theoretical model was developed by
average cell thickness of 100 lm (Kaushika and Sumathy, Hollands (1965) to calculate s(h) for a square honeycomb
2003). Silica aerogel is available in both monolithic cell structure for various incidence angles, h, taking into
(MSA) and granular (GSA) forms. It has been used to fill consideration cell thickness, depth and width. The predic-
the space between double glazed collector covers or win- tions however, were not subjected to experimental verifica-
dows (Rubin and Lambert, 1983; Goetzberger, 1991; Plat- tion. A more precise model detailed in Eq. (1), derived
zer, 2001; Jensen et al., 2004). The high-embodied energy from the summation of all individual rays transmitted or
required (processing temperature of up to 250 C) has been reflected at the cell walls was used to calculate s(h)
a major obstacle in the production of this material. (Symons, 1982; Platzer, 1987, 1992a,b).
sðhÞ ¼ ½sð/Þ þ qð/Þn ¼ ½1  að/Þn ð1Þ
5. Physical properties of TIMs
where n = A Æ tan h for square honeycomb cell and n = 2A Æ
Standard thermal solar energy applications involve the tan h for circular honeycomb cell. The average number of
conversion of solar radiation into heat at the absorber. cell wall interactions for the incoming light beam, n, azimuth
The temperature of the heated surface reaches a steady angle, /, reflectance, q, and a at the cell wall were taken
state when an energy balance between the solar gain and into consideration (Symons, 1982; Platzer, 1987, 1992a,b).
thermal losses occurs. When a transparent cover, such as, Platzer (1992b) developed an approximate model, as
a glass pane, is included in the solar collector, convection detailed in Eq. (2), determining parameters required to fit
heat losses are suppressed and the temperature at which s(h) for 10 different types of honeycombs and capillaries:
an energy balance between solar gains and thermal losses
sðhÞ ¼ s0 exp½a0  tanðhÞ ð2Þ
is achieved is increased (Goetzberger, 1991). The perfor-
mance of a TI-system depends on the fraction of solar The model was based on an idealisation and conceals real
input absorbed and the portion of the heat produced. factors in the measured data, which are deviations from
These are influenced by solar transmittance, s, at the cover, the idealised model. Surface imperfections and bulk effects
absorptance, a, at the absorber, and thermal insulation of the cells are included in the calculated data, incorporated
(U-value) of the system (Goetzberger, 1991). Angular in the constants, a0, and s0, both representing the effective
dependent transmittance, s(h), and a of TIMs have been absorption and effective transmittance. The constants
investigated both theoretically and experimentally. have been used for ten different types of capillary and
1062 I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071

1.0
rectangular
0.9 hc (eq 1)

0.8 rectangular
hc (Buch)
0.7
τ(θ )

15mm PC
0.6
cp (eq 2)

0.5
60mm PC
hc (eq 2)
0.4

0.3 rectangular
0 10 20 30 40 50 60 70 80 hc (eq 1)
θ (degree)

Fig. 3. Comparison of angular dependent direct-diffuse transmittance, s(h) calculation with analytical models for rectangular honeycomb (hc) (Platzer,
1987, 1992a), rectangular honeycomb (Buch) (Buchberg et al., 1971), 15 mm polycarbonate (PC) capillary (cp) (Platzer, 1992b) and 60 mm PC honeycomb
(Platzer, 1992b).

honeycomb (Platzer, 1992b). Fig. 3 shows the values of s(h) solar wavelength range from 300 nm to 2500 nm. The exper-
for different TIMs calculated using Eqs. (1) and (2) (Platzer, imental setup and procedure adopted were described in de-
1987, 1992a,b) and that due to Buchberg et al. (1971). It was tail by Buchberg et al. (1971), Symons et al. (1982), Symons
concluded that, the values of s(h) calculated using the differ- (1982), Platzer (1987, 1992b) and Goetzberger (1991).
ent analytical models agreed well for most TIMs for smaller Fig. 4 shows the comparison of experimental measure-
incidence angles. Despite theoretical calculations that indi- ments reported by different researchers. The experimental
cate high s(h) of more than 90% for all TIMs, when h is 0, results show s(h) of more than 90% for h in the range of
this value decreases dramatically after 70. The models are 0–60, agreeing well with the calculated results. Research
however, only developed for a limited number of TIM sam- shows that errors associated with spectrometry measure-
ples (Platzer, 1992a,b). ments that affect the precision of results may be reduced
by taking more measurements (Platzer, 1992b).
5.2. Experimental characterisation To measure the heat transport and thermal conductance
within the TIMs, a hot plate apparatus that consisted of
Experiments undertaken to validate theoretical predic- 400 mm · 400 mm hot and cold copper plates, heat flux
tions of s(h) for TIMs were part of the TIM system optimisa- meters and temperature sensors was used (Goetzberger,
tion process (Symons, 1982; Platzer, 1987, 1992a,b,c; 1991; Platzer, 1992a,c). The hot plate was electrically
Goetzberger, 1991). In order to measure direct-diffuse trans- heated up to 230 C, the cold plate was thermostatically
mittance at absorber-perpendicular structures, instruments controlled in the temperature range between 5 C and
used included integrating spheres for diffuse transmittance 60 C, the total apparatus could be tilted in the angular
measurement and a rotating support disc for angular mea- range from 0 to 180. The radiative and conductive heat
surements. A pyroelectric radiometer was used to sense the transport of TIMs of up to 120 mm thickness were

1.0
FEPT square
hc
0.9 FEPT parallel
slat
FEPT V-slat
0.8
Tubular glass
τ(θ )

0.7
FEPT parallel
0.6 wall
100mm hc

0.5 100mm PC cp

0.4 100mm PC hc
0 10 20 30 40 50 60 70 80
θ (deg re e)

Fig. 4. Comparison of angular dependent transmittance, s(h) for experiments undertaken by Symons (1982) (FEPT square honeycomb (hc), parallel slat,
V-slat and tubular glass), Symons et al. (1982) (FEPT parallel wall), Platzer (1987) (100 mm honeycomb) and Platzer (1992b) (100 mm PC honeycomb and
capillary).
I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071 1063

PMMA capillaries (Platzer, 1992c) PC capillaries (Platzer, 1992c)


5.0

Heat Conductance, Λ(W/m2K)


4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
1 2 3 4 5 6 7 8 9 10 11
Thickness (cm)

Fig. 5. Experimental results of total heat conductance, K of PMMA and PC capillaries of various thicknesses.

measured. Fig. 5 shows the heat conductance, K experi- studies used plastic or glass honeycombs and capillaries
mentally determined for PMMA and PC capillaries with to replace the conventional glass pane aperture covers of
different thicknesses by Platzer (1992c). The comparisons solar collectors (Hollands, 1965; Tabor, 1969; Symons,
of experimental results and theoretical calculations showed 1984; Hollands and Iynkaran, 1985; Goetzberger, 1991;
approximately 3.6% deviation (Arulanantham and Kaush- Goetzberger et al., 1992; Nordgaard and Beckman, 1992;
ika, 1994), for h of between 0 and 55, which is acceptable. Rommel and Wagner, 1992; Ghoneim, 2005). The working
temperature of the solar collectors using TIM cover could
6. Applications of TIMs be increased from 90 C to 150 C or higher (Symons,
1984). The energy absorbed was calculated as effective
6.1. Flat-plate solar collectors transmittance–absorptance product, (sae), taking into
account both s at the cover and a at the absorber, which
Prior to the application of TIMs to building facades, lead to approximately 2% higher optical efficiency com-
optical and thermal properties of circular capillaries and pared to the product of s multiplied with a (Rommel and
square-celled honeycombs were analysed theoretically with Wagner, 1992; Symons, 1984; Platzer, 1992c). Fig. 6 shows
tests undertaken in flat-plate solar collectors in a range of prototypes of solar collectors integrated with PC honey-
scaled experiments (Platzer, 1987, 1992b,c). Numerous combs, glass capillaries (Rommel and Wagner, 1992;

a) Glass capillary flat-plate solar collector (Rommel b) Polycarbonate honeycomb flat-plate solar
and Wagner, 1992) collector (Rommel and Wagner, 1992)
8 3 2 1
13
2 1
4 3
9 5

8 6

10 7
11 12 4 5 6 7
1) low-iron glass panes; 2) 80mm or 100mm glass 1) 4mm low-iron glass pane; 2) 50mm or 100mm
capillaries; 3) 20mm air gap; 4) absorber; 5) 20mm PC honeycombs; 3) 20mm air gap; 4) selective
microporous high temperature insulation material; 6) absorber (α: 0.95 and emittance: 0.1); 5) 1.5cm
100mm mineral wool; 7) 60mm polyurethane foam; 8) microporous high temperature insulation
22mm wooden frame; 9) 20mm mineral wool; 10) material; 6) 60mm polyurethane foam; 7) 15mm
30mm foam glass; 11) wooden support frame; 12) wooden frame with aluminium weather
aluminium weather protection; 13) aluminium frame protection; 8) aluminium frame
c) Monolithic silica aerogel flat-plate solar collector d) Polycarbonate honeycomb bifacial absorber
(Nordgaard and Beckman, 1992) solar collector (Goetzberger et al., 1992)
4 5
1 4 1 2 3

2 6
3 7
5

1) stainless steel seal; 2) steel frame; 3) copper foil 1) absorber sheet (α: 0.95; emittance: 0.1); 2)
supporter; 4) 4mm low iron glass pane; 5) 20mm MSA; 24mm air gap; 3) 50mm PC honeycomb; 4) 4mm
6) copper foil; 7) copper tube low-iron glass pane; 5) semi-cylindrical mirrors

Fig. 6. Illustration of different types of transparently insulated flat-plate solar collectors.


1064 I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071

1.0 5cm PC honeycombs


(Rommel and Wagner,
0.9
1992)
0.8 5cm PC honeycombs
(Goetzberger et al.,
0.7 1992)
10cm PC honeycombs
0.6
(ταe)

(Rommel and Wagner,


0.5 1992)
10cm glass capillaries
0.4 (Rommel and Wagner,
0.3 1992)
2cm MSA (Nordgaard
0.2 and Beckman, 1992)
0.1 6cm FEPT honeycombs
0 10 20 30 40 50 60 70 80 90
(Symons, 1984)
θ (degree)

Fig. 7. Comparison of the (sae) at various h for flat-plate solar collectors developed by various authors.

Goetzberger et al., 1992) and MSA (Nordgaard and Beck- a a) Glass cover
man, 1992). b b) Honeycomb slab
c c) 4cm to 16cm air gap
Rommel and Wagner (1992) presented a solar collector, d
d) Blackened surface
comprised of a 4 mm single low-iron glass pane, a 50 mm or e
e) Concrete slab
100 mm honeycomb slab, a 20 mm air gap and an absorber f f) Indoor space
(a: 0.95; emittance: 0.1). Research showed that when the
absorber temperature was at more than 80 C, the front Fig. 8. Schematic of a honeycomb roof cover system, redrawn and
cover heat losses were reduced to 0.9 W/mK, optical effi- adopted from Kaushika et al. (1987, 1992).
ciency, (sa) of between 0.7 and 0.9 were recorded at inci-
dence angles of between 0 and 30 (Rommel and 6.2. Honeycomb roof cover system
Wagner, 1992). A significant setback to PC honeycomb
was that it did not withstand the high stagnation tempera- Kaushika et al. (1987, 1992) applied honeycombs on top
ture of 261 C achieved. Thus, glass capillaries of 8 mm of the concrete roof slab of buildings for passive space
diameter and 50 mm or 100 mm thickness were used in pref- heating in the winter season. The roof cover system illus-
erence to PC honeycombs (Rommel and Wagner, 1992). trated in Fig. 8, consisted of a cover glass, a square cell
Goetzberger et al. (1992) presented a bifacially irradi- honeycomb slab, a 4–16 cm air gap, a blackened absorber
ated flat-plate solar collector, which had 50 mm PC honey- and a concrete slab for thermal storage.
combs on both sides of an absorber sheet. A system The square cell (1.25 cm · 1.25 cm) honeycombs were
efficiency of 72% and (sae) of 64% were measured at the made of 0.076 mm thick lexan films or 1 mm thick acrylic
operating temperatures, which were close to the ambient sheets (Kaushika et al., 1987). Calculations showed that
temperatures, which ranged between 10 C and 10 C s(h) of the lexan film system was greater than 0.9, com-
(Goetzberger et al., 1992). A solar collector comprised of pared to around 0.6 for the acrylic sheet system for 0–60
FEPT honeycombs, encapsulated by a low-iron glass cover incidence angles (Kaushika et al., 1987). Positive solar
with anti-reflection coatings, which had (sae) of more than gains were calculated for more than 10 h for a typical win-
0.9, was presented by Symons (1984). It was concluded that ter day in the USA when the thickness of honeycombs was
an optimised solar collector aperture should have a 2– increased from 5 cm to 15 cm. It was concluded that the
4 mm thick low-iron glass cover, a 3–20 mm air gap below optimum thickness of the honeycomb slab for a roof cover
a TIM of thickness of between 50 mm and 100 mm and an was approximately 10–15 cm (Kaushika et al., 1992).
absorber with a of at least 0.95. Fig. 7 shows the optical
performance of flat-plate collectors integrated with various
aperture cover systems. 6.3. Integrated collector storage for domestic hot water
For flat-plate solar collectors integrated with PC honey- supply
combs, the value of (sae) decreases at greater incidence
angles, with a negative influence in the performance of Integrated collector storage systems (ICS) enhanced
the solar collectors (Rommel and Wagner, 1992). The inte- with PC honeycombs were developed to provide hot
gration of MSA into the aperture cover of a flat-plate solar water for domestic houses and reported by various
collector achieves efficiencies of more than 60% at temper- researchers (Goetzberger and Rommel, 1987; Schmidt
atures below 80 C and increased the annual energy gain by et al., 1988; Schmidt and Goetzberger, 1990; Goetzber-
41% (Nordgaard and Beckman, 1992). ger, 1991; Goetzberger et al., 1992; Rommel and Wagner,
I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071 1065

a b period (Braun et al., 1992). In 1983, a TI research pro-


a) Glazing gramme was initiated by the German government and led
b) PC honeycombs several research institutes and companies to produce and
c) Roof beam
d) Reflector market TI for application in buildings. Under the IEA
e) Absorber
c f) Stainless steel storage tank SHC Programme Task 20, TIMs have been used for build-
d g) Opaque insulation
ing renovation to improve daylighting and thermal perfor-
g f e
mance (IEA, 1997; Braun et al., 1992; Voss, 2000;
Fig. 9. Illustration showing a cross section of a collector storage system Dalenback, 1996). To date, over 5000 m2 of TI-walls have
for solar domestic hot water production, adopted from Rommel and been installed in more than 20 projects throughout Europe,
Wagner (1992). which involve mostly low-rise, uncomplicated domestic
buildings. Small-scale experiments were also conducted
by Rubin and Lambert (1983), Kaushika et al. (1987),
1992; Kaushika and Reddy, 1999). A prototype ICS Raicu et al. (2002) and Wallner et al. (2004). Table 1 details
shown in Fig. 9 was constructed and tested at the FISES various types of TI-systems presented in previous case
and consisted of a cylinder shaped stainless steel storage studies.
tank with a black absorbing surface (Rommel and Wag- A well-designed TI-wall requires a massive wall for ther-
ner, 1992). mal storage, a mechanical shading device to control exces-
The collector was mounted on a south-facing test stand, sive solar gain and a south orientation (IEA, 1997; Braun
inclined at an angle of 45, for testing under central Euro- et al., 1992; Voss, 2000). TI-glazing consists of honeycombs
pean outdoor winter climates. Water was stored inside the or monolithic silica aerogel (MSA) (Jensen et al., 2004)
tank under standard pressure conditions and the aperture sandwiched between two sets of glazing, which improves
cover was transparently insulated to reduce heat losses the potential use of daylight in the room (IEA, 1997). A
through the aperture (Rommel and Wagner, 1992). The glazing with 15 mm thick MSA has a center heat loss coef-
ICS is more economical compared to conventional domes- ficient of less than 0.7 W/m2K and transmittance of 76%
tic hot water system, due to direct integration into the (Jensen et al., 2004). Yearly solar energy gains of between
domestic water circuit, avoiding an additional circulation 100 kWh/m2 and 200 kWh/m2 and solar conversion effi-
pump and control unit. When PC honeycombs were com- ciencies of between 15% and 30% have been calculated in
bined with the thermal storage mass, the system was pre- buildings with TI-systems (Braun et al., 1992; Voss,
vented from freezing during the winter period and thus, 2000). Table 2 and Table 3 show the energy savings of
saved the cost of freeze protection. An ICS with a 2.8 m2 TI-applications in the demonstration projects.
absorber recorded an annual system efficiency of 0.4 com- A large scale TI-system was applied to the south façades
pared to less than 0.25 for a conventional flat-plate system of two blocks of five-storey university residential buildings
(Rommel and Wagner, 1992). A bifacial-absorber collector in Glasgow, UK. The system consisted of 100 mm thick,
as shown in Fig. 6d was used as part of the domestic hot 3 mm · 3 mm square size PC honeycombs, encapsulated
water system and mounted at 40 on a flat roof of a solar by an external glass layer. Positive heat gains at the south
house in Germany. The system with 13.5 m2 collector area facades were measured experimentally and it was found
supplied more than 90% of the hot water demand for four that the buildings consumed 40% less energy when com-
persons (Goetzberger et al., 1992). pared to the ‘good’ category in official UK indicators over
the winter period (Twidell et al., 1994).
6.4. Space heating and daylighting for buildings In Norway, Lien et al. (1997) applied capillaries of var-
ious thicknesses (35 mm, 100 mm and 200 mm) to the
The concept of insulating external building walls using south facades of dwelling houses, replacing standard win-
TIMs emerged more than 20 years ago. It combines the dows. The implications of TIM thickness and area on the
advantages of opaque insulation and solar collection. The energy performance of the models were studied. When a
transmission heat losses of the wall are reduced and the 5 m2 TI-glazing made of 100 mm thick capillaries was
solar radiation transmitted through the TIM is converted used, 43 kWh/m2 heating energy consumption or 16%
into useful heat at the dark painted wall surfaces (Goetz- reduction compared to a reference case was recorded.
berger, 1991). As TIM possesses both light guiding and The heating energy consumption dropped to 29 kWh/m2
solar energy transmission properties, the use of TIM in (20% reduction) when the TI-glazing area was increased
buildings makes it suitable for capture of daylight and solar to 10 m2 (Lien et al., 1997). It was concluded that the
heat at the same time, resulting in the reduction of both increase in TIM thickness contributes very little to the
lighting and space heating energy consumption for build- heating energy reduction, but increases the investment cost
ings (IEA, 1997). significantly.
The first real outdoor experiments with TI-walls were Another type of TIM, made of novel polymer films,
undertaken in 1982 by the FISES using 16 mm thick such as, cellulose triacetate (CTA) and polyethyl-
PMMA foam, where direct monthly heat gains of between eneterephthalate (PET) was applied to the south-facing faç-
1 kWh/m2 and 3 kWh/m2 were measured during the winter ade of a low-energy solar house in Austria (Wallner et al.,
1066 I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071

Table 1
Specifications of different transparent insulation systems, adopted from IEA (1997)

Table 2
Comparison of the TI-systems for building façade applications
Authors TI-systems Energy balance Remarks
Braun et al. (1992) Capillaries and honeycombs for Solar energy gains of 100–200 kWh/ The estimates of solar energy gains are
south-facing wall application m2 year; space heating demand of only applicable to a particular TI-wall
43 kWh/m2 year
Twidell et al. (1994) 1040 m2 PC honeycombs for south 40% reduction of energy use 30% financial saving; 20 years payback;
facing wall application maintenance costs not considered
Lien et al. (1997) Capillaries for south-facing TI- 20% reduction of heating energy Optimisation of the TIM thickness and
glazing consumption area was crucial
Wallner et al. (2004) Thirty square meter novel polymer Heat gain fluxes of up to 50 W/m2 in The development of TI-system with easy
film for south facing wall of a testing cold January; solar energy efficiency of site installation can be used for building
house 44% renovation

Table 3
Summary of annual heating energy demand for demonstration projects after TI-application
Types of TI-system TIM Demonstration projects Specific energy yield Heating energy References
area (floor area) demand
TI-compound with PC capillaries 53 m2 Villa Tannheim, Germany 86 kWh/m2of TI- 75 kWh/m2of heated Voss et al. (1996) and
(750 m2) façade area floor area IEA (1997)
Cast-glass elements with 4 cm 7500 m2 Salzgitter, Germany – 72 kWh/m2of heated Voss et al. (1996) and
acrylic glass capillaries (43,000 m2) floor area IEA (1997)
TI-wall with 10 cm PC honeycombs 120 m2 Sonnenaeckerweg, – 43 kWh/m2of heated IEA (1997)
Germany (400 m2) floor area
TI-wall with 10 cm acrylic 63 m2 Affolternstrasse, 160 kWh/m2of TI- 40 kWh/m2of floor IEA (1997)
capillaries Switzerland (702 m2) façade area area
TI-wall 84 m2 Niederurnen, Switzerland 141 kWh/m2of TI- – IEA (1997)
(966 m2) façade area
TI-wall 300 m2 Wurzen, Germany 161 kWh/m2of TI- – IEA (1997)
(4100 m2) façade area

2004; Wallner and Lang, 2005; Wallner et al., 2005a,b; thicknesses and cell geometries were obtained from theoret-
Wallner et al., 2006). Optimum optical and thermal prop- ical model calculations. A solar energy collection efficiency
erties from more than 80 polymer film samples of different of 44% and heat gain fluxes of up to 50 W/m2 were
I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071 1067

achieved in the experimental characterisation of the opti- HAUSSIM, a modified TRNSYS version (Type 56
mised TI-wall in a demonstration building during a cold Multi-Zone Building Model), a detailed explicit finite dif-
sunny week in January (Wallner et al., 2004). ference model and ESP-r were used to predict the thermal
performance of multi-zone building models with integrated
7. Simulations of transparent insulation systems TIMs. These programs are able to perform simulations
that include detailed airflow analysis for realistic building
Computer simulation programs exist that predict the conditions. Table 4 shows the energy performance of build-
thermal and optical implications of integrating TI-systems ings with integrated TI-systems as reported by various
on buildings before real systems are manufactured and researchers.
installed (Wilke and Schmid, 1991; Braun et al., 1992; Sick A 278 mm thick external wall system, combining TIM
and Kummer, 1992; Strachan and Johnstone, 1994; Manz and phase change material (PCM) as a thermal storage
et al., 1997; Matuska, 2000). Compared to scale-models, medium or absorber was simulated in Switzerland (Manz
it is economic both in time and finance to conduct simula- et al., 1997). The system consisted of a 80 mm thick salt
tions due to the fact that parametric changes to TIMs can hydrate PCM filled glass container, a 20 mm thick air
be readily undertaken using simulation programs, thus, gap and a 4 mm thick low-iron oxide content double-glaz-
offering guidance for design optimisation (Strachan and ing unit. The double-glazing unit was filled with 120 mm
Johnstone, 1994). Daylighting and heating performance thick PMMA capillaries with a 50 mm air gap with a roller
of buildings are strongly influenced by TIM parameters, blind installation. A total energy flux of 13.3 W/m2 and
as an excessive quantity of TIMs are not only uneconomi- system efficiency of 27% were predicted behind the TI-wall
cal, but also cause problems of overheating. in December (Manz et al., 1997). Heim (2004) performed
To date, many building simulation programs have been simulations of a TI-wall integrated with a PCM, which
extended to handle TI-applications, particularly, WAND- consisted of an external glazing, a 100 mm TIM honey-
SIM (Wilke and Schmid, 1991), TRNSYS (Sick and comb structure, a 250 mm PCM-ceramic composite with
Kummer, 1992), HAUSSIM (Braun et al., 1992), finite dif- air gaps between each layer in a triple zone building model.
ference model (Ramadan and Athienitis, 1998; Athienitis The latent heat stored inside the PCM enabled 5% more
and Ramadan, 1999) and ESP-r (Strachan and Johnstone, stable temperature on the internal surface to be obtained
1994; Matuska, 2000; Heim, 2004). Wilke and Schmid during winter (Heim, 2004).
(1991) predicted heat gains of TI-systems, as a result of The thermal performance of a 3 m · 3 m · 3 m outdoor
the reduction in artificial lighting using WANDSIM. test room with a south-facing TI-wall was predicted using
TRNSYS was used by Sick and Kummer (1992) to predict an explicit finite difference numerical simulation model in
the effects of TI-walls on building energy requirements. cold sunny days in Canada (Ramadan and Athienitis,
However, both WANDSIM and TRNSYS do not allow 1998; Athienitis and Ramadan, 1999). The TI-wall con-
the generation of detailed multi-zone building models. sisted of an exterior single glazing, lexan honeycomb slab,

Table 4
Simulation predictions for TI-systems used in building façade applications
Authors Applications Programs Predicted results
Wilke and Schmid (1991) 70% south-facing TI- WANDSIM Approximately 223.7 kWh/m2 and 231.7 kWh/m2 were predicted for
glazing and TI-wall south-facing TI-wall and TI-glazing per annum
Sick and Kummer (1992) TI-wall of an TRNSYS The difference between the measured and predicted absorber and inside
apartment wall temperatures was less than 3 C
Braun et al. (1992) TI-wall TRNSYS, The difference between the measured and predicted absorber and inside
HAUSSIM wall temperatures was less than 5 C. Minimum space heating demand
of 410 kWh/year was predicted with southeast and southwest TIM
facades
Strachan and Johnstone (1994) TI-wall for low-rise ESP-r The difference between the measured and predicted temperatures within
residential blocks the TI-wall was less than 5 C The simulation results represent the
actual building performance and can be used to investigate design
alternatives
Manz et al. (1997) Prototype TI-wall Monte Carlo Predicted temperatures and total energy flux agreed well with
integrated with PCM Simulation experimental results. Mean energy flux of 13.3 W/m2 into the room was
predicted
Ramadan and Athienitis (1998) Outdoor test room Finite Significant energy savings with no auxiliary heating on cold sunny days
and Athienitis and Ramadan with TI-wall difference under Canadian climates. TI-wall surface temperatures were less than
(1999) application model 29 C and other room surface temperatures were less than 25 C when
mean outside temperature was 15 C
Matuska (2000) TIM for trombe wall ESP-r Annual total energy gains of 110–140 kWh/m2 compared to 90 kWh/
application m2 for double low-e glazing
Heim (2004) TI-wall with PCM ESP-r Latent heat storage allows 5% more stable internal surface temperature
compare to standard material
1068 I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071

200 mm concrete wall slab, interior gypsum board with air mid, 1991; Manz et al., 1997). Mechanical shading devices
gaps between each layer. When the mean outside tempera- used to overcome the problem are susceptible to failure and
ture was 15 C, the TI-wall surface temperature was more thus, require frequent and expensive maintenance (Braun
than 33 C and approached a maximum of 40 C, when et al., 1992).
room air temperature was less than 21 C. To enhance
the transfer of solar energy stored in the concrete mass, 9. Limitations in current knowledge evident from previous
air was circulated through the TI-wall to the room with studies on transparent insulation applications in buildings
blinds shut when TI-wall surface temperature exceeded
29 C. The TI-wall room surface temperature was lowered 9.1. Potential for commercial building applications
to less than 30C with no auxiliary heating required (Ram-
adan and Athienitis, 1998; Athienitis and Ramadan, 1999). Previous studies have involved either residential, school
or industrial buildings of different geometries. Installation
8. Barriers to the development and implementation of of a TI-system is costly for private buildings but may be
transparent insulation systems more acceptable when applied to large scale commercial
building facades (IEA, 1997; Braun et al., 1992; Voss,
8.1. Imperfection in manufactured TIMs 2000; Dalenback, 1996; Platzer, 2001). Despite this, no
office buildings have been considered previously with previ-
Thin-celled plastic TIMs are imperfect and far from the ous studies limited to domestic applications. To explore the
idealisation often used in simulations due to bulk effects, potential of application in commercial buildings, compara-
such as, tilted cells, broken or irregular cell edges, inhomo- tive cost studies were proposed between TI-systems and
geneous cell sizes, diameters or thicknesses (Platzer, other commercial façade materials to enable building
1992b). High cutting temperatures result in melting at the designers to select suitable facade materials for use in
cut edges of plastic TIMs, which affects the transparency new low-energy building designs (Wong et al., 2005).
of the TIMs (Lien et al., 1997). Glass honeycombs are frag-
ile and thus not suitable for building applications (Kaush- 9.2. Design guidelines
ika and Sumathy, 2003).
Previous studies show that TIMs require excellent spec-
8.2. Low working temperatures of plastic TIMs ification (such as, ideal TIM parameters) in order to profit
from optimum solar gains and added value with minimum
Plastics must have low working temperatures, in general investment. Most demonstration projects to date have not
less than 80 C and thus do not satisfy the higher operating achieved such an ideal specifications (Voss, 2000) and thus,
temperatures requirements of solar collectors, which are in fail to provide useful guidelines for future TI-applications
general between 80 C and 250 C (Rommel and Wagner, (Wong et al., 2005). Non-ideal specification resulted due
1992; Kaushika and Sumathy, 2003). Plastic TIMs are also to the fact that it is time consuming and costly to conduct
potentially exposed to fire hazards when applied to facades optimisation studies using different TIM parameters and
of high-rise buildings (Twidell et al., 1994). thus, was not performed for previous demonstration pro-
jects. A simulation program therefore is required for use
8.3. High investment cost at the early design stage to enable a time and cost saving
parametric sensitivity analysis to be performed. Critical
High investment cost has been a barrier to commerciali- TIM parameters can be further analysed and refined in
sation of TIMs. To date, only a number of TIMs, such as, the design phase to obtain optimum performance of TI-sys-
PC and PMMA are commercially available for various tems, for particular building applications (Manz et al.,
applications with most materials still in the small-scale 1997; Lien et al., 1997).
experimental and at a premature phase for large scale
implementation (Braun et al., 1992; Platzer, 2001; Kaush- 9.3. Suitability for new building applications
ika and Sumathy, 2003). With increasing fuel costs, how-
ever, initial TIM systems costs may be a less significant The demonstration projects detailed renovation work for
consideration than life-time costs. existing buildings with the aim of improving the thermal
and/or daylighting performance (IEA, 1997; Braun et al.,
8.4. Overheating problem 1992; Voss, 2000; Dalenback, 1996). The TI-systems have
been used to replace old façade materials to reduce heating
In previous research, it was reported that problems of demand and electricity and gas consumption (Braun et al.,
overheating are significant in the summer when too much 1992; Twidell et al., 1994; Lien et al., 1997). With low fuel
solar radiation is absorbed, due to either an excessive area prices, most researchers predicted that it would be hard
of TI-systems or wall mass when applied to south-facing for TI-systems to compete unless environmental impacts
building facades (Lien et al., 1997; Athienitis and Rama- are taken into account (Braun et al., 1992; Dalenback,
dan, 1999; Ramadan and Athienitis, 1998; Wilke and Sch- 1996; Platzer, 2001). With soaring fuel prices, however, fuel
I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071 1069

savings have become more significant in recent years. It may study are available from the IEA SHC Programme, Task
be more feasible and cost effective application of TI-systems 20 (IEA, 1997). TIM was sandwiched between 7500 m2
if they are incorporated into the façades of new buildings, U-shaped cast glass elements to form a self-supporting day-
allowing the offset of capital and installation costs for other light wall that allowed penetration of daylight with good
façade materials (Wong et al., 2005). thermal insulation properties, no shading device was
installed in the system (Voss, 2000). The equivalent energy
9.4. Insufficient/inadequate cost information cost and annual energy savings have been estimated at
0.03 EUR/kWh and 72 kWh per gross floor area (m2),
The cost of TI-systems is a major concern highlighted by whereas, the investment cost of the TI-system was
most authors (Kaushika and Sumathy, 2003; Braun et al., 24 EUR/m2. The yearly maintenance and the expected
1992; Voss, 2000; Platzer, 2001), with high investment cost life-time were assumed to be 4% of the initial investment
a major disincentive to the application of TIM in the build- and 20 years, respectively (IEA, 1997). The gross floor area
ing sector. TI-system cost generally comprises the TIM and total TI-glazing areas for the industrial production hall
cost, shading device cost, mounting cost and glass cover are 43,000 m2 and 7500 m2, respectively (IEA, 1997). The
cost. The shading device used in the TI-wall system com- total energy saving (3,096,000 kWh/year or 92,880 EUR/
prises 20–30% of the total investment costs (Braun et al., year) was calculated by multiplying 72 kWh/m2year by
1992; Voss, 2000). Most TI-systems are custom designed the area, 43,000 m2, whereas, the initial investment (EUR
for specific projects and it is difficult to determine typical 180,000) was calculated by multiplying 24 EUR/m2 by
system costs as these vary with each project (Braun et al., the TI-glazing area of 7500 m2.
1992) and type of TI-system installed (Platzer, 2001). Most Initial investment & Maintenance costs
case studies have used a combination of solar renovation Payback period ¼
Expected returns per year
concepts, which makes it difficult to isolate the specific
investment required for the TI-systems (IEA, 1997; Voss, ð3Þ
2000). Specific and detailed information relating to LCC It was assumed that the initial investment (EUR 180,000)
of TI-systems installed on buildings are not yet available. was paid off either in the first year or over the system
It is important to increase the efficiency of the whole life-time, and the yearly maintenance costs (EUR 7200)
system, to deliver high quality products with reasonable over the rest of the system life-time. The annual benefit
costs (Platzer, 2001). Table 5 details the various specific of the TI-system installation to the building is given in
TI-system costs, which are between 24 EUR/m2 and terms of the total energy savings (kWh/year) and also in
1000 EUR/m2 (Braun et al., 1992; IEA, 1997). a monetary value, the total energy cost savings (EUR/
Although the current information on TI-system costs is year). The total energy cost savings and total maintenance
limited and incomplete, it is evident that mechanical shad- costs are reduced to their present value (PV) using the pres-
ing devices are a major factor contributing to expensive ent worth factor (PWF) at assumed discount rates of 10%,
system costs. Most authors therefore suggest replacement 8% and 6% (Kreider et al., 1989). In economics, money has
of mechanical shading devices with cheaper alternatives a time value and a given amount of money will be worth
to reduce system costs (Braun et al., 1992; Voss, 2000; Plat- less in the future than it is today. Thus, the relation be-
zer, 2001), however, no significantly improved low cost tween present and future cash flows is embodied in the dis-
shading devices have been found to date. count rate (Kreider et al., 1989). The PWF is used to reduce
a single payment or cash flow in the future (for examples,
10. Calculation of simple payback period maintenance costs) to present values. As shown in Table
6, 3–4-year payback periods were calculated at different
Payback period is the time taken for the total initial discount rates using Eq. (3), if the initial investment was
investment of a product to be recovered by the total accu- paid off in the first year.
mulated savings. A simple calculation of payback period In some cases, it is common to convert the initial invest-
for an industrial production hall renovated with TI-glazing ment to a uniform series of payments made over the life
in Salzgitter, Germany was assessed using Eq. (3). Design span of the system. When this occurs, it involves repayment
details and energy saving features for this particular case of a loan or mortgage for purchase of the system, with, a

Table 5
Summary of costs for a range of transparent insulation systems
Types of TI-system TIM thickness (mm) EUR/m2(year) References
Sealed TI-glazing 40 (acrylic glass capillaries) 24 (1997) IEA (1997)
Prefabricated TI-wall with absorber (with solar gain control) 80–140 400–600 (1997) IEA (1997)
TI-wall and mounting 100 51 and 51 (1991) Braun et al. (1992)
TI-compound (no solar gain control) 80, 100, 120 or 140 (PC capillaries) 220–250 (1997) IEA (1997) and Voss (2000)
Cast-glass facades (no solar gain control) 120 150–250 (1997) IEA (1997)
Transom-mullion with massive wall (with solar gain control) Variable 600–1000 (1997) IEA (1997)
1070 I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071

Table 6 schools, industrial buildings and residential houses. These


Cost parameters for TI-glazing installed in the industrial hall in Salzgitter projects failed to conform to the optimum design parame-
Assumed discount rates 10% 8% 6% ters and thus fail to allow robust design guidelines for
(a) Initial investment paid off in the first year future TI-system implementations to be developed. At
Initial investment (EUR) 180,000 180,000 180,000 present, no parametric sensitivity studies can be performed
Total maintenance costs in PV 61,296 70,402 82,584 readily in real buildings. Current cost information relating
(EUR/20 years)
Total system costs (EUR/20 years) 241,296 250,402 262,584
to TI-systems is inadequate and neither payback period nor
Total energy cost savings in PV 73,603 75,976 80,460 the LCC implications for TI-systems are available. The
(EUR/year) simple payback period calculation for a selected installa-
Payback period 3.28 years 3.30 years 3.26 years tion indicates a less than 8-year payback period, for a dis-
(b) Initial investment paid off in 20 year count rate of 10%. Research is required to develop design
Initial investment (EUR) 422,856 366,660 313,848 guidelines to enable the determination of optimum and
Total maintenance costs in PV 61,296 70,402 82,584 effective TI-system designs for implementation in office
(EUR/20 years)
buildings to be developed.
Total system costs (EUR/20 years) 484,152 437,062 396,432
Total energy cost savings in PV 61,938 68,551 76,121
(EUR/year) Acknowledgement
Payback period 7.82 years 6.38 years 5.21 years
A University of Ulster research studentship is hereby
acknowledged by the first author.
fixed or level payment is made each year to pay off the ini-
tial investment (Kreider et al., 1989). The calculation was References
repeated taking into consideration the arrangement of ser-
ies payments over the life span of the TI-glazing using a Arulanantham, M., Kaushika, N.D., 1994. Global radiation transmit-
capital recovery factor (CRF) (Kreider et al., 1989). In this tance of transparent insulation materials. Solar Energy 53 (4), 323–
case, five to eight year payback periods were calculated for 328.
Athienitis, A.K., Ramadan, H., 1999. Numerical model of a building with
different discount rates. For a TI-system with an expected transparent insulation. Solar Energy 67 (1–3), 101–109.
life of 20 years without a shading device for this installa- Braun, P.O., Geotzberger, A., Schmid, J., Stahl, W., 1992. Transparent
tion, it is clearly economically viable. Detailed studies are insulation of building facades – steps from research to commercial
required to fully assess the potential of TI-systems with applications. Solar Energy 49 (5), 413–427.
changing fuel prices and the installation cost. Buchberg, H., Lalude, O.A., Edwards, D.K., 1971. Performance charac-
teristics of rectangular honeycomb solar–thermal converters. Solar
Energy 13, 193–221.
11. Discussion and conclusions Dalenback, J.-O., 1996. Solar energy in building renovation. Energy and
Buildings 24 (1), 39–50.
Various types of TIM made of different materials have Francia, G., 1961. A new collector of solar radiant energy: theory and
experimental verification. In: Proceedings of the United Nations
been discussed; each has unique characteristics and physi- Conference on New Sources of Energy, Rome, August 21–23.
cal properties. TIMs have been used extensively for flat- Ghoneim, A.A., 2005. Performance optimisation of solar collector
plate solar collectors prior to building applications and equipped with different arrangement of square-celled honeycomb.
experiments show that a (sae) value of more than 60% International Journal of Thermal Sciences 44, 95–105.
Goetzberger, A., 1991. Transparent Insulation Technology for Solar
can be achieved at angles between 0 and 60. TIMs can
Energy Conversion, second ed. Fraunhofer Institute for Solar Energy
also be integrated into the roof or facades of buildings to Systems, Freiburg.
provide space heating to the buildings during the winter Goetzberger, A., Dengler, J., Rommel, M., Gottsche, J., Wittwer, V.,
period. Approximately 100–200 kWh/m2 year of solar 1992. A new transparently insulated, bifacially irradiated solar flat-
energy gains have been measured or predicted for various plate collector. Solar Energy 49 (5), 403–411.
buildings using different types of TI-systems. It is con- Goetzberger, A., Rommel, M., 1987. Prospects for integrated storage
collector systems in Central Europe. Solar Energy 39 (3), 211–
cluded that TI-systems with optimum design parameters 219.
(area and thickness) can provide significant solar energy Hastings, S.R., 2004. Breaking the ‘‘heating barrier’’: learning from the
gains that are required by buildings, without increasing first houses without conventional heating. Energy and Buildings 36 (4),
investment cost and leading to overheating problem. Build- 373–380.
ing simulation programs have been identified as an effective Heim, D., 2004. Whole year analysis of TIM-PCM solar thermal storage
wall. In: Proceeding of SimBuild 2004, IBPSA-USA National Con-
tool for simulating the energy performance of buildings ference Boulder, CO, August 4–6.
integrated with TI-systems. Changes to the design parame- Hollands, K.G.T., 1965. Honeycomb devices in flat plate solar collectors.
ters of a system can be easily undertaken, allowing design Solar Energy 9 (3), 159–164.
optimisation of systems to be performed. Hollands, K.G.T., Iynkaran, K., 1985. Proposal for a compound-
honeycomb collector. Solar Energy 34 (4–5), 309–316.
The potential for application of TI-systems to buildings
Hollands, K.G. T., Iynkaran, K., Ford, C., Platzer, W.J., 1992. Manu-
however has not yet been fully investigated, especially for facture, solar transmission and heat transfer characteristic of
new office and other types of commercial buildings. Previ- large-celled honeycomb transparent insulation. Solar Energy 49 (5),
ous projects involved only renovation work to existing 381–386.
I.L. Wong et al. / Solar Energy 81 (2007) 1058–1071 1071

Hollands, K.G.T., Marshall, K.N., Wedel, R.K., 1978. An approximate Schmidt, C., Goetzberger, A., 1990. Single-tube integrated collector
equation for predicting the solar transmittance of transparent honey- storage systems with transparent insulation and involute reflector.
combs. Solar Energy 21, 231–236. Solar Energy 45 (2), 93–100.
IEA, 1997. IEA Solar Heating and Cooling Programme, Task 20: Solar Schmidt, C., Goetzberger, A., Schmid, J., 1988. Test results and
Energy in Building Renovation. James and James Ltd., London. evaluation of integrated collector storage systems with transparent
Jensen, K.I., Schultz, J.M., Kristiansen, F.H., 2004. Development of insulation. Solar Energy 41 (5), 487–494.
windows based on highly insulating aerogel glazings. Journal of Non- Sick, F., Kummer, J.P., 1992. Simulation of transparently insulated
Crystalline Solids 350, 351–357. buildings. Solar Energy 49 (5), 429–434.
Kaushika, N.D., Reddy, K.S., 1999. Performance of transparently Strachan, P.A., Johnstone, C.M., 1994. Solar residence with transparent
insulated solar passive hot water systems. In: Proceedings of ISES insulation: predictions from a calibrated model. In: Proceedings North
1999 Solar World Congress, Jerusalem, Israel, July 4–9. Sun 94, Glasgow, pp. 347–353.
Kaushika, N.D., Sharma, M.S., Padmapriya, R., 1992. Solar thermal Symons, J.G., 1982. The solar transmittance of some convection
analysis of honeycomb roof cover system for energy conservation in an suppression devices for solar energy applications: An experimental
air conditioned building. Energy and Buildings 18 (1), 45–49. study. Journal of Solar Energy Engineering 104, 251–256.
Kaushika, N.D., Sharma, M.S., Sanjay, K., 1987. Honeycomb roof cover Symons, J.G., 1984. Calculation of the transmittance–absorptance prod-
system for passive solar space heating. Energy Conversion and uct for flat-plate collectors with convection suppression devices. Solar
Management 27 (1), 99–102. Energy 33 (6), 637–640.
Kaushika, N.D., Sumathy, K., 2003. Solar transparent insulation mate- Symons, J.G., Christie, E.A., Peck, M.K., 1982. Integrating sphere for
rials: a review. Renewable and Sustainable Energy Review 7 (4), 317– solar transmittance measurement of planar and nonplanar samples.
351. Applied Optics 21 (15), 2827–2832.
Kreider, J.F., Hoogendoorn, C.J., Kreith, F., 1989. Solar Design: Tabor, H., 1969. Cellular insulation (honeycombs). Solar Energy 12 (4),
Components, Systems, Economics. Hemisphere Publishing Corpora- 549–552.
tion, New York. Twidell, J.W., Johnstone, C., Zuhdy, B., Scott, A., 1994. Strathclyde
Lien, A.G., Hestnes, A.G., Aschehoug, O., 1997. The use of transparent University’s passive solar, low-energy, residences with transparent
insulation in low energy dwellings in cold climates. Solar Energy 59 (1– insulation. Solar Energy 52 (1), 85–109.
3), 27–35. Veinberg, V.B., 1959. Optics in Equipment for the Utilization of Solar
Manz, H., Egolf, P.W., Suter, P., Goetzberger, A., 1997. TIM-PCM Energy. State Publishing House of Defense Ministry, Moscow.
external wall system for solar space heating and daylighting. Solar Voss, K., 2000. Solar energy in building renovation – results and
Energy 61 (6), 369–379. experience of international demonstration buildings. Energy and
Matuska, T., 2000. A simple trombe wall: comparison of different Buildings 32 (3), 291–302.
glazings, In: Proceedings of ISES Congress EuroSun2000, Voss, K., Braun, P. O., Russ, C., 1996. Transparent insulation in building
Copenhagen. renovation: German contribution to IEA-SHCP Task 20, EuroSun’96,
Nordgaard, A., Beckman, W.A., 1992. Modelling of flat plate collectors pp. 1808–1812.
based on monolithic silica aerogel. Solar Energy 49 (5), 387–402. Wallner, G.M., Lang, R.W., Schobermayr, H., Hegedys, H., Hausner, R.,
Platzer, W.J., 1987. Solar transmittance of transparent insulation mate- 2004. Development and application demonstration of a novel polymer
rials. Solar Energy Materials 16, 275–287. film based transparent insulation wall heating system. Solar Energy
Platzer, W.J., 1992a. Calculation procedure for collectors with a honey- materials and Solar Cells 84 (1–4), 441–457.
comb cover of rectangular cross section. Solar Energy 48 (6), 381– Wallner, G.M., Lang, R.W., 2005. Aging of polymeric films for
393. transparent insulation wall applications. Solar Energy 79 (6), 603–611.
Platzer, W.J., 1992b. Directional-hemispherical solar transmittance data Wallner, G.M., Platzer, W., Lang, R.W., 2005a. Structure–property
for plastic type honeycomb structures. Solar Energy 49 (5), 359–369. correlations of polymeric films for transparent insulation wall appli-
Platzer, W.J., 1992c. Total heat transport data for plastic honeycomb-type cations. Part 1: Solar optical properties. Solar Energy 79 (6), 583–592.
structures. Solar Energy 49 (5), 351–358. Wallner, G.M., Platzer, W., Lang, R.W., 2005b. Structure–property
Platzer, W.J., 2001. Transparent insulation materials and products: a correlations of polymeric films for transparent insulation wall appli-
review. Advances in Solar Energy 14, 33–65. cations. Part 2: Infrared optical properties. Solar Energy 79 (6), 593–
Raicu, A., Wilson, H.R., Nitz, P., Platzer, W., Wittwer, V., Jahns, E., 602.
2002. Façade systems with variable solar control using thermotropic Wallner, G.M., Hausner, R., Hegedys, H., Schobermayr, H., Lang, R.W.,
polymer blends. Solar Energy 72 (1), 31–42. 2006. Application demonstration and performance of a cellulose
Ramadan, H., Athienitis, A.K., 1998. Numerical simulation of a building triacetate polymer film based transparent insulation wall heating
with one transparently insulated wall. Renewable Energy 15 (1–4), system. Solar Energy 80 (11), 1410–1416.
387–390. Wilke, W.S., Schmid, J., 1991. Modelling and simulation of elements for
Rommel, M., Wagner, A., 1992. Application of transparent insulation solar heating and daylighting. Solar Energy 46 (5), 295–304.
materials in improved flat-plate collectors and integrated collector Wong, I.L., Perera, R. S., Eames, P. C., 2005. A review of transparent
storages. Solar Energy 49 (5), 371–380. insulation systems and the evaluation of payback period for building
Rubin, M., Lambert, C.M., 1983. Transparent silica aero gel for window applications, In: Proceedings of CISBAT 2005, Lausanne, Switzerland,
insulation. Solar Energy Material 7 (4), 393–400. pp. 65–70.

Potrebbero piacerti anche