Description
Viscochief® EVT-10C
Viscosity Transducer
G028261A
P000272A
In order to make the information clear only foreseeable conditions have
been considered. No warnings are given, therefore, for situations
arising from unintended usage of the machine and its tools.
Contents
1 Function Description 1
1.1 Application 1
1.2 Design 1
2 Fault Finding 3
3 Maintenance 5
4 Technical Data 7
4.1 Specifications 7
4.2 Dimensions 8
5 Installation 9
6 Spare Parts 11
1818092-02
EVT-10C
2 1818092-02
1 Function Description
1.1 Application
Viscosity transducer EVT-10C is a factory
calibrated viscometer for use in fuel oil
treatment systems, to obtain correct
measurement of fuel oil viscosity.
1.2 Design
The unit consists of three parts: Housing (1),
Vibrating sensor (2) and Electronic Unit (3)
a. Version number
b. Serial number, art. number
1818092-02 1
1 Function Description EVT-10C
G024892A
Since the density as well as the viscosity of the
oil influence the transducer pin oscillating
amplitude, this is taken into account in the
VCU-160 control unit. It is therefore important
that the correct oil density is provided by the
oil supplier in order that the VCU-160 control
unit can make a correct viscosity calculation.
2 1818092-02
2 Fault Finding
Viscosity indication not as expected Deposits on the pin Clean the sensor in strong
detergent. Do not clean
mechanically.
Comparison with oil analysis not Analyse oil at two temperatures for
adequate more accurate viscosity estimation
Rapidly fluctuating signal (seconds) EVT unstably mounted Mount rigidly. It may also help to
turn the transducer 90° in housing
so that the pin oscillates in another
direction.
Flow rate through transducer too Reduce flow rate or use a bypass
high line.
Slowly fluctuating signal (minutes) Controller settings or fuel or steam Adjust P and I constants in control
system design causing bad unit
viscosity control Review the system design
No signal (0 mA) See table following for LED See following LED indications table
indications
1818092-02 3
2 Fault Finding EVT-10C
G025041A
LED Indications
H1 H2 Cause Corrective action
OFF short flash/long pause Analogue output current fault Replace transducer
OFF two short flashes/long pause Resonance frequency deviation due Take necessary
to for example: measures
- Too high viscosity
- Vibration
The indication of a faulty watchdog circuit is not predictable, but most likely H1 and H2 would be ON.
4 1818092-02
3 Maintenance
NOTE
WARNING
Burn Hazard
1818092-02 5
3 Maintenance EVT-10C
6 1818092-02
4 Technical Data
4.1 Specifications
1818092-02 7
4 Technical Data EVT-10C
4.2 Dimensions
8 1818092-02
5 Installation
NOTE
G025243A
way that no air or gas pockets can form.
Air will disturb the transducer Recommended installation to avoid air pockets and for
measurement. less heat on the electronic unit
Retrofit installation
1818092-02 9
5 Installation EVT-10C
G025251A
• If the 4 – 20 mA signal is connected to an
automation system, it should be connected
1. Shield earth connector
via a signal isolator. Max. load that can be 2. Shield
connected is 400 Ω.
NOTE
10 1818092-02
6 Spare Parts
G033981A
Item Article No Description Remarks Qty Parts included in Qty Recommended
delivery parts for 3 years
of operation
1818092-02 11