External Sensors
Additional inputs for up to five other sensors. Three 12 to
30VDC digital inputs.
Technical Specifications Communications
• Two separate channels for remote communications,
PARAMETER VALUE/MEETS local USB connection and Ethernet connection.
(compound) (measurement range)
Hydrogen (H2) 5 - 5,000 ppm • Communications protocols supported include MODBUS®,
Carbon Monoxide (CO) 2 - 50,000 ppm MODBUS/TCP, DNP3.0 and IEC®61850.
Carbon Dioxide (CO2) 20 - 50,000 ppm
• Modules available for connection via RS232, RS485,
Methane (CH4) 2 - 50,000 ppm Ethernet, PSTN modem and GSM or CDMA wireless
Acetylene (C2H2) 0.5 - 50,000 ppm modems.
Ethane (C2H6) 2 - 50,000 ppm
Ethylene (C2H4) 2 - 50,000 ppm
Technical Features
• Uses photo-acoustic spectroscopy to give highly reliable
Water (H2O) 0-100% RS (given in ppm) results. Field proven in over ninety countries worldwide.
Oxygen (O2) 100 - 50,000 ppm
Nitrogen (N2) 10 – 130,000 ppm, accuracy • Eight target gases plus moisture measured.
±15%
• Estimation of nitrogen and total gas content for free
Accuracy ± 5% or ± LDL (whichever is breathing transformers.
greater)
ENVIRONMENTAL • Full embedded processor – over two years of data at a
Temperature Range -40 to 55°C default sampling rate of one sample taken every four hours.
(-40 to 131°F)
• Non-volatile memory storage to prevent loss of data.
Oil Temperature Range -40 to 120°C
(-40 to 248°F) • Discrete sampling gives more rapid response to gas rises.
Power Supply 90 - 250 VAC; 47 - 63Hz; 150W; No ‘averaging’ of DGA results.
8A max
Operating Humidity 10 - 95% RH non-condensing Alarms
Enclosure IP55 • Two Sunlight Visible front panel LED Arrays (Red & Yellow)
and six Alarm Relay contacts, each user configurable.
Weight 78 kg (172 lbs)
Single Phase Alarm Relays NO and NC provided, 5A 250 • All alarms can be set or changed locally or remotely using
VAC, 5A 30 VDC. Kelman PERCEPTION PC Software.
Measurement Variable - 1 per hour to 1 per
Frequency day • Six alarm setting screens or scenarios are available, which
can set alarms based on the level of eight gasses, TDCG,
and moisture, and rates of change for each gas.