Sei sulla pagina 1di 4

I-210+c ®

SmartMeter
Itron’s residential smart metering solution features a communications module that is integrated into the GE
I-210+c electricity meter. The I-210+c SmartMeter communicates over an existing cellular network with the
Itron Transaction Management System™ (TMS) or other C12.21 head-end systems and complies with ANSI
C12.19 protocols for data storage and transmission.

The I-210+c SmartMeter is a single-phase shed overall load at the premise without each interval are also transmitted to TMS,
electronic watt-hour meter for use in regards to specific appliance. This 200- which interprets them and logs appropriate
residential and light commercial service Amp switch may be used to throttle load messages (e.g. time adjustments).
locations. The I-210+c’s key features at the premise to a specific maximum
Real-Time Interval Reads
include Time of Use, Demand and Load threshold or to perform remote disconnects
Profile, Remote Connect/Disconnect, and and reconnects. Real-time interval data acquisition enables
C12.22/ compatibility. The I-210+c meter utilities to implement Load Curtailment and
® Flexible Two-Way Data Retrieval and Real Time Pricing (RTP) programs. With
may include an optional ZigBee wireless
Scheduled Data Collection this functionality, the user can configure
component for in-premise communications
®
and an optional Badger ORION wireless Users can execute all appropriate TMS the SmartMeter module to transmit load
component for gas and water reads. functionality using user-configurable, profile data as often as every 15 minutes at
SmartMeter-controlled schedules and interval completion.
TMS-controlled schedules and as well as
FUNCTIONS & FEATURES Automated Register, Self-Read and
on an on-demand basis.
TOU Retrieval
Remote Disconnect/Reconnect Automated Interval Data/Energy The I-210+c SmartMeter module is
Usage Retrieval configured by TMS to read and transmit all
Remote connect and disconnect
functionality is supported by the I-210+c The I-210+c SmartMeter module retrieves or a subset of enabled registers, including
single-phase SmartMeter, which has a and transmits interval data for 1 energy totals, self-reads, maximum demand and
load-limiting switch that can be used to value for intervals as small as 5 minutes. time-of-use values.
Recorded events and exceptions with

SPECIFICATIONS
Demand Resets is repeated a minimum number of times the SmartMeter module, utilizing a unique
The I-210+c SmartMeter module within a specific duration. TMS can also meter-specific encryption key.
executes Demand Resets using one of configure the SmartMeter to reset the
Bi-Directional Metering
three methods: SmartModule-initiated event counter when the alert message
is transmitted. The I-210+c SmartMeter is a bi-directional
schedules, TMS-initiated schedules or
meter that supports Net Metering. Both
TMS on-demand requests. Tilt Detection received and delivered data metrics are
Real-Time Meter Event and Alarm The I-210+c SmartMeter can detect stored in the meter and can be delivered
Retrieval and report tilt events that occur when to the utility as needed to support “green-
The I-210+c SmartMeter provides the SmartMeter is moved from its credit” electricity programs for consumers
automatic real-time alarm reporting of installation position. who own renewable energy facilities or
all events defined in the ANSI C12.19 participate in vehicle-to-grid systems.
Meter Clock Synchronization
standard, including history and event
If enabled, the SmartModule automatically Over-The-Air SmartMeter Module
codes, ANSI Standard status and Firmware Upgrade
manufacturer status alarms. Additionally, adjusts the meter clock when the time
deviation falls within user-defined lower TMS users with administrator privileges can
alarms received by TMS can be
and upper deviation boundaries based on remotely upgrade the I-210+c SmartMeter
automatically routed via e-mail to a specific
a reference clock provided by TMS. If the module firmware for one or multiple
user or group of users using the TMS
deviation exceeds the upper boundary, the communication modules.
Message Routing Interface.
module reports the deviation via an alarm
Transmission Efficiency
Real-Time Power Outage and but does not correct the meter clock. If the
Restoration Alarms deviation is less than the lower boundary, In addition to support for allowing users
With built-in ultracapacitor energy the module ignores the deviation. to filter the number of meter channels
storage, the I-210+c SmartMeter module and types of diagnostics that are returned,
SmartMeter Status Display all wireless messages are converted
will transmit a real-time “last gasp”
notification when detecting an AC power The I-210+c SmartMeter supports to binary and optimally compressed
outage without requiring the use of an optional LCD status sequence to before transmission to ensure the most
less reliable batteries. The I-210+c display important SmartMeter indicators economical data processing rates. The
SmartMeter also notifies TMS when the periodically. This status sequence compression ratio can be as high as
AC power is restored and provides full includes the meter site coverage status, 50% and overall data usage can be as
configuration of these alarms based on SmartModule firmware state and any little as 5% of the total usage of other
user-defined durations. SmartModule firmware warnings/errors wireless systems.
enabling technicians to ensure proper
Service Diagnostic and Tamper Automated ID Tracking
installation of the I-210+c SmartMeters
Detection Alerts and allow field troubleshooting without any Barcode labels and important identifiers
The I-210+c SmartMeter can report power other tools. (e.g. ICC-ID / MS-ISDN) are attached to
service and wiring errors detected by the the integrated SmartMeter for tracking and
meter, including reverse polarity, cross- Automated Meter Registration troubleshooting purposes. The SmartMeter
phase and energy flow, phase voltage The SmartMeter module automatically module manufacturer and meter integrator
deviation, inactive phase current, phase transmits a registration message to scan and track all device IDs accurately.
angle displacement and current waveform TMS when the meter is installed without
On-Demand Data Reads For
distortion. In addition, the SmartMeter requiring user intervention. This message
Virtual Disconnect
can detect and report exceptions for permits TMS to create or update the meter
record with validated information, ensuring Customers can perform virtual disconnects
the following tamper events: number of
accurate and automated record entries through TMS by retrieving a final read
Demand Resets, Loss of AC power and
without user intervention. for one end-user and an initial read for
reported power outages.
a subsequent end-user. This function
TMS configures a specific filter in Secure and Encrypted Data may also be used to perform meter
the SmartMeter for each of these Transmissions “switch-outs.”
events, enabling the transmission of a
256-bit encryption is applied to all
corresponding alert only after the event
messages exchanged between TMS and
SPECIFICATIONS HARDWARE
Radio Control Module Board (RCM) 32-bit ARM processor, 8MB RAM, 4MB flash
Temperature Ranges Supplies peak power for data transmissions and all
Capacitor Storage Bank (CSB)
functions during power outages – no batteries required
» Operating: [-40°C, +85°C]
Modem communicates with head-end using HSDPA or
Modem
» Transmission (wireless): [-40°C, +85°C] EVDO and SMS services
Wireless component configurable for two-way
2.4 GHz Transceiver
communications/WPAN 802.15.4
Humidity Range Internal Antenna Flexible dual frequency antenna for the modem
» 0% to 95% non-condensing
INPUT/OUTPUT SIGNAL
Accuracy Module Power Input Voltage 120 - 240 VAC
» Meets ANSI 12.20 for accuracy Meter Serial Interface 3.3V / TTL compatible asynchronous
class 0.5%
VERSION AND COMPATIBILITY
Supported Meter Forms
Supported meter forms, classes, and types,
Without Disconnect I-210+c Meter Hardware:
equipped with battery
» Class 20: 3S, 4S I-210+c Meter Firmware: Latest fully supported
» Class 100: 1S SmartModule: I-210+c GPRS SmartMeter Module
» Class 200: 2S, 12S, 25S Itron TMS: Version 6.0 or higher for HSDPA, 7.2.1 for EVDO
» Class 320: 2S
Integration
Supported Meter Forms The SmartMeter module is a fully integrated, under-the-cover option inside the
With Disconnect
I-210+c meter. The I-210+c SmartMeter is shipped as one complete unit, ready for
» Class 100: 1S field deployment.
» Class 200: 2S, 12S, 25S

Regulatory & Industry Certifications


» FCC Part 15 Class B
» ANSI C37.90.1 – 1989: Surge Withstand
Capability (SWC)
» ANSI C12.20 (Class 0.5) – 1998
» PTCRB Certified
» Measurement Canada Certified
» Network Carrier Certified
Itron is a global technology company. We build solutions that help utilities CORPORATE HEADQUARTERS
measure, monitor and manage energy and water. Our broad product portfolio 2111 N Molter Road
includes electricity, gas, water and thermal energy measurement and control Liberty Lake, WA 99019
technology; communications systems; software; and professional services. USA
With thousands of employees supporting nearly 8,000 utilities in more than
100 countries, Itron empowers utilities to responsibly and efficiently manage Phone: 1.800.635.5461
energy and water resources. Fax: 1.509.891.3355

Join us in creating a more resourceful world; start here: www.itron.com

While Itron strives to make the content of its marketing materials as timely and accurate as possible, Itron makes no claims, promises, or guarantees about the accuracy, completeness,
or adequacy of, and expressly disclaims liability for errors and omissions in, such materials. No warranty of any kind, implied, expressed, or statutory, including but not limited to
the warranties of non-infringement of third party rights, title, merchantability, and fitness for a particular purpose, is given with respect to the content of these marketing materials.
© Copyright 2012, Itron. All rights reserved.

Potrebbero piacerti anche