Sei sulla pagina 1di 4

Data Sheet

s Fire Safety Products

Sinorix® Engineered Fire Suppression Systems


Abort Station, Manual Release Station & Main / Reserve Selector Switch
Models AW-1, MH-501 and CPY- MRS
ARCHITECT AND ENGINEER SPECIFICATIONS

Abort Station
(AW-1) Manual Release Main / Reserve Selector
Station Switch
Momentary contact
(MH-501) (CPY- MRS)
‘Dead-Man’ switch
Double action with positive motion
Large mushroom button
Fail / Safe reset Allows immediate activation of a
Manually prevents Sinorix TM connected reserve system
system discharge Latch action until reset Provides uninterrupted protection
UL Listed, UL Listed; after system discharge
CSFM (#7165-0067:35:0035) CSFM (#7165-0067:35) & NYC Fire
Approved {for use with System 3TM} Department Approved

Product Overviews
Abort Station
The Sinorix Abort Station (Model AW-1) is Model AW-1 consists of a momentary contact
designed for use with Siemens Industry, Inc. – switch with a large red “mushroom” head for ease
Fire Safety detection systems, which are listed of operation, and is mounted on a steel plate.
and approved for release of Sinorix Engineered Screw-type terminals are provided for connection
Fire-Suppression Systems. to the agent-release circuit. The entire assembly
mounts on a standard 2-1/2" (6.4 cm.) deep, two-
Model AW-1 employs a momentary, normally gang electrical box.
closed contact ‘dead-man-type,’ push-button
switch, which – while held in – prevents The Abort Station (Model AW-1) is UL Listed
discharge of the clean agent. for use with fire-suppression systems.
Note: For Canadian applications, Model AW-3B,
Upon release of the push button, the Sinorix whose faceplate is only available in blue, is
Engineered Fire-Suppression System will follow used as the Abort Station.
the sequence of events as programmed in the
releasing panel, ultimately resulting in the release
of the Sinorix agent.

[Abort Station, Pull Station & Main / Reserve Selector Switch] Sinorix® 6632
s Industry, Inc.
Building Technologies Division
Product Overviews (continued)
Manual Release Station Main / Reserve Selector Switch
The Manual Release Station (Model MH-501) is The Main / Reserve Selector Switch is a means
a double-action station that contains one (1) for transferring the electrical supply from the
normally open contact. Model MH-501 is main cylinder to the reserve cylinder. The
intended for use with Siemens – Fire Safety switch is mounted on a steel cover plate.
low-voltage systems, but has a rating of Screw-type terminals are provided. The entire
120VAC for connection to other systems. assembly is capable of being mounted on a
The Model MH-501 Manual Releasing Station is standard, 2-1/2" (6.4 cm.) deep, two-gang
constructed of durable, molded polycarbonate electrical box.
material, matte-finished in red with raised
lettering in white.
The housing incorporates a ‘push-in’ tab, which Details for Ordering
must be initially operated, permitting access to Model
Part
Description Rating
the ‘pull-down’ lever. When operated, the lever Number
Abort Station
– in turn – locks in position after releasing a AW-1 500-822500 Momentary Contact,
1 Amp
115VAC / VDC
spring-loaded contact switch. Single Pole N.C.
CPY-MRS 500-697964BG Main Reserve Selector Switch N/A
Restoring the system to Normal can only be MH-501 500-622543 Manual Release Station 120VAC
accomplished by opening the cover of the
hinged housing with the reset key, and then
closing and locking the cover. In Canada, order:
Model MH-501 is constructed with a molded Part
Model Description
housing, fitted with a ‘pull-down’ lever and a Number
‘push-in’ tab. Abort Station, Blue
AW-3B 500-637038 Momentary Contact, Single Pole N.C.
Since the Manual Release Station is ‘dual- ( ULC Pending)
action’ type, it is necessary to initially operate Weatherproof Abort Station, Blue
AW-3B-WP 500-637039 Momentary Contact, Single Pole N.C.
the ‘push-in’ tab to provide access to the ‘pull- ( ULC Pending)
down’ lever. When operated, the ‘pull-down’ MSM-RB 500-637035 Manual Release Station, Yellow
lever locks in position after releasing a spring- Weatherproof
MSM-RB-WP 500-637036
loaded contact switch to engage actuation of Manual Release Station, Yellow
the release circuit.
The body of the control is hinged to a back-
plate assembly to which it is locked with a
socket-head screw. Resetting the control after
operation shall require opening the control
momentarily, and then locking the body to the
back plate. Provision is made for surface or
semi-flush mounting to conduit boxes.
Note: For Canadian applications, Model MSM-RB,
whose faceplate is only available in yellow,
is used as the Manual Release Station.

s Industry, Inc.
Building Technologies Division
Mounting Diagrams
Main / Reserve Selector Switch

Cylinder Valve Cylinder Valve


Assembly Assembly

Manual Release Station

s Industry, Inc.
Building Technologies Division
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 1577 North Service Road
s Industry, Inc. Florham Park, NJ 07932 East Oakville, Ontario April 2014
Building Technologies Division Tel: (973) 593-2600 (SII-FS) L6H 0H6 / Canada Supersedes sheet dated 6/11
FAX: (908) 547-6877 Printed in U.S.A. Tel: [905] 465-8000 (Rev. 5)

URL: www.usa.Siemens.com/Fire URL: www.Siemens.C A