SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.

SEDA AYACUCHO

[[ 2. ]] ANALISIS

ANALISIS SISMICO ESTATICO DE RESERVORIO RECTANGULAR CABRAPATA ACI 350.3 - 06

2.1.1 Geometria del tanque

2.1.2 Dimencionamiento

3
Volumen a almacenar 2000

Tirante del líquido 4.0

Se aconseja que la relacion sea mayor o igual a 1.5, para que los brazos de palanca de las masas impulsivas y
convectivas sean menores y así disminuir los esfuerzos por el sismo

2.1.3 Tanque

Ancho del depósito interior

= 12.5 12.50
10
Longitud del depósito interior

= 40 40.00

Altura de la pared del depósito 4.6

Ancho del lapared en la parte superior 0.3 0.25

Ancho del lapared en la parte superior 0.016 0.3 0.07 - 0.10

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

if 0.016 > 0.1 ||


||
0.016 ||
else ||
||
0.1 ||

= 0.64 0.6

0.12 = 0.552 0.45

Espesor promedio de la pader del depósito


+
= 0.35
2
Espesor de la tapa 0.0

2.1.4 Datos sismicos del sitio

Factor de zona

0.30

Factor de suelo

1.2

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Factor de importacia

1.25

Factor de modificacion de respuesta

2.75 1.0

2.1.5 Propiedades del material del tanque

Peso volumétrico del concreto ɣ 2400 3

Resistencia a la comprensión del concreto 210 2

Esfuerzo a la fluencia del acero de refuerzo 4200 2

Peso volumetrico del líquido ɣ 1000 3

2.1.6 Cargas de diseño

Carga viva actuante en la tapa 0 Carga por granizo en la tapa 0


2 2

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Masa especifico del liquido Masa especifica del concreto de peso normal
ɣ 2 ɣ 2
ρ = 102.041 4
ρ = 244.898 4
9.8 2
9.8 2

Modulo de elasticidad de concreto

2
15100 = 2.188 10 5 2

2.2 Calculo de los pesos actuantes

peso del liquido

ɣ = 2000000

Peso de la pared y tapa

2 ɣ + = 312597.6 direccion E-O

2 ɣ + = 100077.6 direccion N-S

ɣ =0

+ = 412675.2

Peso de la componente impulsiva

para la direccion E-O para la direccion N-S

tanh 0.866 tanh 0.866


= 230946.868 = 732466.45
0.866 0.866

Coeficiente de la masa efectiva (relación entre la masa dinamica equivalente del recipiente, a su masa total real

para la direccion E-O para la direccion N-S

2 2
ε 0.0151 - 0.1908 + 1.021 = 0.623 ε 0.0151 - 0.1908 + 1.021 = 0.572

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Peso efectivo del depósito

ε +ε = 252013.802

Peso impulsivo total

para la direccion E-O para la direccion N-S

+ + = 482960.67 + + = 984480.252

Peso de la componente convectiva

para la direccion E-O

0.264 tanh 3.16227 = 1616162.495

para la direccion N-S

0.264 tanh 3.16227 = 1264820.072

2.3 Punto de aplicacion de las fuezas

Excluyendo la presion del suelo

direccion E-O impulsiva direccion N-S impulsiva


|| ||
if < 1.333 || if < 1.333 ||
|| ||
|| ||
0.5 - 0.09375 || 0.5 - 0.09375 ||
|| ||
else || else ||
|| ||
0.375 || 0.375 ||

= 1.5 = 1.5

direccion E-O convectiva direccion N-S convectiva

cosh 3.16227 -1 cosh 3.16227 -1


1- 1-
3.16227 sinh 3.16227 3.16227 sinh 3.16227

= 2.017 = 2.155

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Incluyendo la presion del suelo

direccion E-O impulsiva direccion N-S impulsiva

|| ||
if < 0.75 || if < 0.75 ||
|| ||
0.45 || 0.45 ||
|| ||
else || else ||
|| ||
0.866 || 0.866 ||
1 || 1 ||
- || - ||
8 || 8 ||
2 tanh 0.866 2 tanh 0.866
| |
|| ||

= 16.82 = 4.961

direccion E-O convectiva direccion N-S convectiva

cosh 3.16227 - 2.01 cosh 3.16227 - 2.01


1- 1-
3.16227 sinh 3.16227 3.16227 sinh 3.16227

= 41.751 = 5.499

2.4 Propiedad dinamica del tanque

Periodo impulsivo direccion E-O Periodo impulsivo direccion N-S

Masa impulsiva del agua por unidad de ancho de muro Masa impulsiva del agua por unidad de ancho de muro

2 2
ρ = 942.64 2
ρ = 934.268 2
2 2

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Masa impulsiva de tanque por unidad de ancho de muro Masa impulsiva de tanque por unidad de ancho de muro
2 2
ρ = 394.286 ρ = 394.286
2 2

Masa total por unidad de ancho de muro Masa total por unidad de ancho de muro
2 2
+ = 1336.926 2
+ = 1328.554 2

0.5 = 2.3 0.5 = 2.3

+ +
= 1.736 = 1.737
+ +

Rigidez estructural a la fexion ancho unitario Rigidez estructural a la fexion ancho unitario

2 3 2 3

= 448.363 2
= 447.213 2
4 4

Frecuencia natural de la masa impulsiva Frecuencia natural de la masa impulsiva

2 1 2 1
= 57.911 = 58.019

Periodo natural de la masa impulsiva Periodo natural de la masa impulsiva


2 2
= 0.108 = 0.108

Periodo convectivo direccion E-O Periodo convectivo direccion N-S

2 2
λ 3.16 9.8 2
tanh 3.16 λ 3.16 9.8 2
tanh 3.16
1 1
2 2
λ = 3.078 λ = 4.871

Frecuencia naturade la masa impulsiva Frecuencia naturade la masa impulsiva


λ 1 λ 1
2
= 0.487 2
= 1.378

Periodo natural de la masa convectiva Periodo natural de la masa convectiva


2 2
= 12.911 = 4.56

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Espectro de respuesta

= 0.3

2.5 = 0.75 1.25 = 0.375

1.10 1.50

= 0.825 = 0.563

2 2
= 0.55 = 0.375
3 3

0.2 = 0.136 = 0.682

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Factores de ampliacion espectral

direccion E-O impulsiva direccion E-O impulsiva

if | | = 0.55 if | | = 0.55
|| ||
|| ||
else || else ||
|| ||
|| ||
|| ||
|| ||

direccion E-O conectiva direccion E-O conectiva

1.6 || 1.6 ||
if | | = 0.102 if | | = 0.289
|| ||
1.5 || 1.5 ||
|| ||
|| ||
|| ||
else || else ||
0.4 || 0.4 ||
6 || 6 ||
|| ||

2.5 Distribucion de presiones dinamicas por linealizacion equivalente

Fuerza producida por la masa impulsiva

para la direccion E-O para la direccion N-S

= 20785.218 = 65921.98

Fuerza producida por la masa convectiva

para la direccion E-O para la direccion N-S

= 74352.868 = 164749.604

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Presión dinámica impulsiva unitaria

para la direccion E-O

0.5 4 -6 - 6 - 12

2
= 4546.766

= 113.669 2

para la direccion N-S

0.5 4 -6 - 6 - 12

2
= 14420.433

= 1153.635 2

Presión dinámica conectiva unitaria

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

para la direccion E-O

0.5 4 -6 - 6 - 12

2
= 9064.057

= 226.601 2

para la direccion N-S

0.5 4 -6 - 6 - 12

2
= 15810.904

= 1264.872 2

Fuerza de inercia unitaria

para la direccion E-O

ε ɣ = 1883.952

= 47.099 2

para la direccion N-S

ε ɣ = 540.739

= 43.259 2

Presión hidrodinamica por efecto de la aceleracion vertical


2
3
= 0.109

ɣ - = 4000 2

= 436.364 2

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

2.6 Presion hidrodinamica del agua total

para la direccion E-O


2 2 2
2
+ + + = 20692.328

= 517.308 2

para la direccion N-S

2 2 2
2
+ + + = 22440.442

= 1795.235 2

figura fuezas dinamicas en el tanque

2.7 Presion estatica del agua y suelo total

ɣ = 4000 2

figura Presion del agua y presion del suelo

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

2.8 Determinacion de las cargas de diseño de muro

Determinacion de fuerza horizontales producto del empuje

para la direccion E-O, L= 40.0m

1.4 = 5600 ( - )
2

1.2 + = 5317.308 ( - 350)


2

como se puede verificar solo se trabajara para las carga hidroestatica

carga hidroestatica

1 = 11200
2

para la direccion N-S, B= 12.50m

1.4 = 5600 ( - )
2

1.2 + = 6595.235 ( - 350)


2

carga hidroestatica

1.2 = 4800 2

carga hidrodinamica

= 1795.235 2

1.2 + = 6595.235 2
Fuerzas estaricas Fuerzas dinamicas Fuerzas diseño

(6595.235 - 2146.737) 1 + 2146.737 1 = 13834.491


2 2
2 2

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Determinacion de fuerzas verticales

para la direccion E-O, L= 40.0m


Peso del Conc. Pantalla = 2.760 Tn
Peso del Conc. Zapata = 4.752 Tn
Peso del Conc. Pantalla = 1.104 Tn
Peso del Suelo = 0.000 Tn
Peso del agua = 7.400 Tn
P. de reserv. Lleno(∑Fv) = 16.02 Tn

1.4 16.2 1000 = 22680

para la direccion N-S, B= 12.50m


Peso del Conc. Pantalla = 2.760 Tn
Peso del Conc. Zapata = 3.312 Tn
Peso del Conc. Pantalla = 1.104 Tn
Peso del Suelo = 0.000 Tn
Peso del agua = 7.400 Tn
P. de reserv. Lleno(∑Fv) = 14.58 Tn

1.4 14.58 1000 = 20412

Determinacion de momentos producto de las fuerzas horizontales

para la direccion E-O, L= 40.0m

1 = 14933.333
2 3
para la direccion N-S, B= 12.50m

(6595.235 - 2146.737) 1 + 2146.737 1 = 23218.9


2 2
2 3 2 2
Determinacion de momentos producto de las fuerzas verticales

para la direccion E-O, L= 40.0m


Palanca en pantalla = 1.125 m Mo por muro = 3.11 Tn-m
Palanca en Zapata = 1.550 m Mo por zapata = 7.37 Tn-m
Palanca en pantalla = 1.133 m Mo por zapata = 1.25 Tn-m
Palanca en Suelo = 2.600 m Mo por suelo = 0.00 Tn-m
Palanca del agua = 0.925 m Mo por agua = 6.85 Tn-m
Mo por resitente de reserv lleno (∑Mr) = 18.57 Tn-m

1.4 18.57 1000 = 25998

para la direccion N-S, B= 12.50m


Palanca en pantalla = 1.975 m Mo por muro = 5.45 Tn-m
Palanca en Zapata = 1.050 m Mo por zapata = 3.48 Tn-m
Palanca en pantalla = 1.917 m Mo por zapata = 2.12 Tn-m
Palanca en Suelo = 0.00 m Mo por suelo = 0.00 Tn-m
Palanca del agua = 0.925 m Mo por agua = 6.85 Tn-m
Mo por resitente de reserv lleno (∑Mr) = 17.89 Tn-m
1.4 17.89 1000 = 25046

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

2.9 Determinacion de Coeficiente de Seguridad al Deslizamiento C.S.D (1.2-1.5)

para la direccion E-O, L= 40.0m


||
if 1.2 ||
|| = 2.025 = “Estable”
||
“Estable” ||
else ||
|
“Falla por deslizamiento” |
|

Correcion para que cumpla como minimo 1.2 1.5

||
if 1.2 ||=0
||
||
0 ||
else ||
||
1.2 - ||
|
||

para la direccion N-S, B= 12.50m

||
if 1.2 ||
|| = 1.475 = “Estable”
||
“Estable” ||
else ||
|
“Falla por deslizamiento” |
|

Correcion para que cumpla como minimo 1.2 1.5

||
if 1.2 ||=0
||
||
0 ||
else ||
||
1.2 - ||
|
||

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

2.10 Determinacion de Coeficiente de Seguridad al Volteo C.S.V (1.5 - 2.0)

para la direccion E-O, L= 40.0m

||
if 1.5 ||
||
||
“Estable” || = 1.741 = “Estable”
else ||
|
“Falla por Volteo ” |
|

Correcion para que cumpla como minimo 1.5 2.0

||
if 1.5 ||=0
||
||
0 ||
else ||
||
1.5 - ||
|
||

para la direccion N-S, B= 12.50m

||
if 1.5 ||
|| = 1.079 = “falla por Volteo ”
||
“Estable ” ||
else ||
|
“falla por Volteo ” |
|

Correcion para que cumpla como minimo 1.5 2.0

||
if 1.5 | | = 9782.35
||
||
0 ||
else ||
||
1.5 - ||
|
||

Acontinuacion de debera diseñar un muro que resista un momento de M = 9782.35 kg.m y asi
evitar la falla por volteo
ING. JUAN HECTOR OSORIO CLEMENTE.
RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

DISEÑO DE MURO DIRECCION X-X LADO MENOR


Project
Author : ---------------
Date : 07/03/2019
Settings
USA - Safety factor
Materials and standards
Concrete structures : ACI 318-11
Wall analysis
Active earth pressure calculation : Coulomb
Passive earth pressure calculation : Mazindrani (Rankin)
Earthquake analysis : Mononobe-Okabe
Shape of earth wedge : Calculate as skew
Base key : The base key is considered as inclined footing bottom
Verification methodology : Safety factors (ASD)
Safety factors
Permanent design situation
Safety factor for overturning : SFo = 1.50 [–]
Safety factor for sliding resistance : SFs = 1.50 [–]
Safety factor for bearing capacity : SFb = 2.00 [–]
Material of structure
Unit weight g = 24.00 kN/m3
Analysis of concrete structures carried out according to the standard ACI 318-11.

Concrete : Concrete ACI


Compressive strength fc' = 21.00 MPa
Tensile-bending strength fr = 2.85 MPa
Longitudinal steel : A616/60
Tensile strength fy = 420.00 MPa
Geometry of structure
Coordinate Depth
No.
X [m] Z [m]
1 0.00 0.00
2 0.00 4.00
3 0.00 4.60
4 0.00 5.30
5 -1.00 5.30
6 -1.00 4.60
7 -1.80 4.60
8 -1.80 4.00
9 -1.30 4.00
10 -0.30 0.00
The origin [0,0] is located at the most upper right point of the wall.
Wall section area = 4.98 m2.

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Name : Geometry Stage : 1


0.30

4.00 4.00:1
4.60
5.30

0.50

0.60
1.30

1.00
1.80

Basic soil parameters


jef cef g gsu d
No. Name Pattern
[°] [kPa] [kN/m3] [kN/m3] [°]

1 agua 80.00 1.00 0.10 0.00 80.00

All soils are considered as cohesionless for at rest pressure analysis.

Soil parameters
agua
Unit weight : g = 0.10 kN/m3
Stress-state : effective
Angle of internal friction : jef = 80.00 °
Cohesion of soil : cef = 1.00 kPa
Angle of friction struc.-soil : d = 80.00 °
Soil : cohesionless
Saturated unit weight : gsat = 0.10 kN/m3

Geological profile and assigned soils


Layer
No. Assigned soil Pattern
[m]

1 5.30 agua

2 - agua

Terrain profile
Terrain behind the structure is flat.

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Water influence
Ground water table is located below the structure.

Resistance on front face of the structure


Resistance on front face of the structure is not considered.

Applied forces acting on the structure


Force Fx Fz M x z
No. Name Action
new modification [kN/m] [kN/m] [kNm/m] [m] [m]
Force
1 YES permanent 0.00 0.00 -98.00 0.00 3.00
No. 1
Name : Applied forces Stage : 1
+x

00
4.60 -98.
5.30

+z

1.80

Settings of the stage of construction


Design situation : permanent
The wall is free to move. Active earth pressure is therefore assumed.

Verification No. 1 (Stage of construction 1)


Active pressure behind the structure - partial results
Layer Thickness a jd cd g dd Ka Comment
No. [m] [°] [°] [kPa] [kN/m3] [°]
1 4.00 0.00 80.00 1.00 0.10 80.00 0.030
2 0.60 0.00 80.00 1.00 0.10 80.00 0.030
3 0.70 0.00 80.00 1.00 0.10 80.00 0.030
Active pressure distribution behind the structure (without surcharge)
Layer Start [m] sZ sW Pressure Hor. comp. Vert. comp.
No. End [m] [kPa] [kPa] [kPa] [kPa] [kPa]
0.00 0.00 0.00 0.00 0.00 0.00
1
4.00 0.40 0.00 0.00 0.00 0.00

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Layer Start [m] sZ sW Pressure Hor. comp. Vert. comp.


No. End [m] [kPa] [kPa] [kPa] [kPa] [kPa]
4.00 0.40 0.00 0.00 0.00 0.00
2
4.60 0.46 0.00 0.00 0.00 0.00
4.60 0.46 0.00 0.00 0.00 0.00
3
5.30 0.53 0.00 0.00 0.00 0.00
Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -1.42 119.52 1.24 1.000
Active pressure 0.00 -4.60 0.00 1.80 1.000
Force No. 1 0.00 -1.60 0.00 1.80 1.000
Verification of complete wall
Check for overturning stability
Resisting moment Mres = 148.69 kNm/m
Overturning moment Movr = 98.00 kNm/m

Safety factor = 1.52 > 1.50


Wall for overturning is SATISFACTORY

Check for slip


Resisting horizontal force Hres = 632.65 kN/m
Active horizontal force Hact = -43.32 kN/m

Safety factor = 1000.00 > 1.50


Wall for slip is SATISFACTORY

Forces acting at the centre of footing bottom


Overall moment M = 56.88 kNm/m
Normal force N = 111.39 kN/m
Shear force Q = -40.37 kN/m
Overall check - WALL is SATISFACTORY

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Name : Verification Stage : 1; Analysis : 1

119.52
4.60
5.30

+x

1.80

+z

Bearing capacity of foundation soil (Stage of construction 1)


Forces acting at the centre of the footing bottom
Moment Norm. force Shear Force Eccentricity Stress
No.
[kNm/m] [kN/m] [kN/m] [m] [kPa]
1 56.88 111.39 -40.37 0.51 122.40
Name : Bearing cap. Stage : 1

4.60
5.30

1.80
40.
122

.40
122

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Dimensioning No. 1 (Stage of construction 1)


Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -1.58 76.76 0.85 1.000
Pressure at rest 0.01 -1.33 0.00 1.30 1.000
Force No. 1 0.00 -1.00 0.00 1.30 1.000
Wall check at the construction joint 4.00 m from the wall crest
Reinforcement and dimensions of the cross-section
Bar number = 4
Number of bars = 4
Reinforcement cover = 50.0 mm
Cross-section width = 1.00 m
Cross-section depth = 1.30 m
Reinforcement ratio r = 0.04 % > 0.02 % = rmin
Position of neutral axis c = 0.01 m < 0.53 m = cmax
Ultimate shear force fVn = 709.66 kN > 0.01 kN = Vu
Ultimate moment fMn = 237.00 kNm > 82.83 kNm = Mu
Cross-section is SATISFACTORY.

Name : acero vertical pantalla Stage : 1; Dimensioning : 1

76.76
4.00 prof. No. 4, cover. 50.0mm
4.00
4.60
5.30
0.01

+x

1.80

+z

Dimensioning No. 2 (Stage of construction 1)


Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -1.58 76.76 0.85 1.000
Pressure at rest 0.01 -1.33 0.00 1.30 1.000

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Name Fhor App.Pt. Fvert App.Pt. Design


[kN/m] z [m] [kN/m] x [m] coefficient
Force No. 1 0.00 -1.00 0.00 1.30 1.000
Wall check at the construction joint 4.00 m from the wall crest
Reinforcement and dimensions of the cross-section
Bar number = 4
Number of bars = 2
Reinforcement cover = 50.0 mm
Cross-section width = 1.00 m
Cross-section depth = 1.30 m
Reinforcement ratio r = 0.02 % > 0.02 % = rmin
Position of neutral axis c = 0.01 m < 0.53 m = cmax
Ultimate shear force fVn = 709.66 kN > 0.01 kN = Vu
Ultimate moment fMn = 118.79 kNm > 82.83 kNm = Mu
Cross-section is SATISFACTORY.

Name : acero horizontal pantalla Stage : 1; Dimensioning : 2

76.76
2.00 prof. No. 4, cover. 50.0mm
4.00
4.60
5.30
0.01

+x

1.80

+z

Dimensioning No. 3 (Stage of construction 1)


Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -1.42 119.52 1.24 1.000
Active pressure 0.00 -4.60 0.00 1.80 1.000
Force No. 1 0.00 -1.60 0.00 1.80 1.000
Front wall jump check
Foundation thickness is greater than offset of the front wall jump. Reinforcement is not required.

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
danny SEDA AYACUCHO

Name : acero zapata debajo Stage : 1; Dimensioning : 3

119.52
4.60
5.30

2.00 prof. No. 4, cover. 50.0mm

+x

1.80
190.72

+z

Dimensioning No. 4 (Stage of construction 1)


Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -0.30 0.00 1.80 1.000
Active pressure 0.00 -4.60 0.00 1.80 1.000
Contact tractions 0.00 0.00 0.00 1.80 1.000
Back wall jump check
The cross-section is loaded by moment 0.00 kNm/m, bottom fibers are in tension.
Top reinforcement is not required, cross-section is satisfactory.

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Name : acero zapata encima Stage : 1; Dimensioning : 4

4.60
5.30

2.00 prof. No. 4, cover. 50.0mm

+x

1.80

+z

Slope stability analysis


Input data
Project
Settings
USA - Safety factor
Stability analysis
Verification methodology : Safety factors (ASD)
Safety factors
Permanent design situation
Safety factor : SFs = 1.50 [–]
Interface
Coordinates of interface points [m]
No. Interface location
x z x z x z
-13.25 -4.60 -1.80 -4.60 -1.80 -4.00
-1.30 -4.00 -0.30 0.00 0.00 0.00
15.90 0.00
1

0.00 0.00 0.00 -4.00 0.00 -4.60


0.00 -5.30 15.90 -5.30

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Coordinates of interface points [m]


No. Interface location
x z x z x z
-1.80 -4.60 -1.00 -4.60 -1.00 -5.30
0.00 -5.30

Soil parameters - effective stress state


jef cef g
No. Name Pattern
[°] [kPa] [kN/m3]

1 agua 80.00 1.00 0.10

Soil parameters - uplift


gsat gs n
No. Name Pattern
[kN/m3] [kN/m3] [–]

1 agua 0.10

Soil parameters
agua
Unit weight : g = 0.10 kN/m3
Stress-state : effective
Angle of internal friction : jef = 80.00 °
Cohesion of soil : cef = 1.00 kPa
Saturated unit weight : gsat = 0.10 kN/m3

Rigid bodies
g
No. Name Sample
[kN/m3]

1 Wall material 24.00

Assigning and surfaces


Coordinates of surface points [m] Assigned
No. Surface position
x z x z soil
-1.00 -4.60 -1.00 -5.30
Wall material
0.00 -5.30 0.00 -4.60
1 0.00 -4.00 0.00 0.00
-0.30 0.00 -1.30 -4.00
-1.80 -4.00 -1.80 -4.60

0.00 -4.00 0.00 -4.60


agua
0.00 -5.30 15.90 -5.30
2 15.90 0.00 0.00 0.00

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Coordinates of surface points [m] Assigned


No. Surface position
x z x z soil
-1.00 -5.30 -1.00 -4.60
agua
-1.80 -4.60 -13.25 -4.60
3 -13.25 -10.30 15.90 -10.30
15.90 -5.30 0.00 -5.30

Water
Water type : No water
Tensile crack
Tensile crack not inputted.
Earthquake
Earthquake not included.
Settings of the stage of construction
Design situation : permanent
Results (Stage of construction 1)
Analysis 1
Circular slip surface
Slip surface parameters
x= -6.00 [m] a1 = -50.74 [°]
Center : Angles :
z= 0.88 [m] a2 = 84.17 [°]
Radius : R= 8.66 [m]
The slip surface after optimization.
Slope stability verification (Bishop)
Sum of active forces : Fa = 79.33 kN/m
Sum of passive forces : Fp = 210.00 kN/m
Sliding moment : Ma = 686.99 kNm/m
Resisting moment : Mp = 1818.61 kNm/m
Factor of safety = 2.65 > 1.50
Slope stability ACCEPTABLE

Name : Analysis Stage - analysis : 1 - 1

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

DISEÑO DE MURO GAVION DIRECCION Y-Y LADO MAYOR


Project
Author : DANNY FRANCO ECHEVARRIA
Date : 04/03/2019
Settings
USA - Safety factor
Wall analysis
Active earth pressure calculation : Coulomb
Passive earth pressure calculation : Mazindrani (Rankin)
Earthquake analysis : Mononobe-Okabe
Shape of earth wedge : Calculate as skew
Verification methodology : Safety factors (ASD)
Safety factors
Permanent design situation
Safety factor for overturning : SFo = 1.50 [–]
Safety factor for sliding resistance : SFs = 1.50 [–]
Safety factor for bearing capacity : SFb = 2.00 [–]
Safety factor for mesh strength : SFn = 1.50 [–]
Reduction coefficients
Permanent design situation
Reduction coeff. of friction between blocks : gf = 1.50 [–]
Material of blocks - filling
g j c
No. Name
[kN/m3] [°] [kPa]
1 PIEDRA 18.00 45.00 0.00
Material of blocks - mesh
Strength Spacing of Bear.cap.
No. Name overh. vert. meshes of front joint
Rt [kN/m] b [m] Rs [kN/m]
1 PIEDRA 43.00 1.00 34.00
Geometry of structure
Width Height Offset
No. Material
b [m] h [m] a [m]
2 1.00 1.00 0.50 PIEDRA
1 1.50 1.00 - PIEDRA
Gabion slope = 0.00 °
Overall height = 2.00 m
Overall wall volume = 2.50 m3/m

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Name : Geometry Stage : 1

1.00

0.50 1.00
2.00 2

1.00

1.50
1

Soil parameters
concreto
Unit weight : g = 0.10 kN/m3
Stress-state : effective
Angle of internal friction : jef = 80.00 °
Cohesion of soil : cef = 0.00 kPa
Angle of friction struc.-soil : d = 80.00 °
Soil : cohesionless
Saturated unit weight : gsat = 24.00 kN/m3

Geological profile and assigned soils


Layer
No. Assigned soil Pattern
[m]

1 - concreto

Terrain profile
Terrain behind the structure is flat.

Water influence
Ground water table is located below the structure.
The evolution of tensile cracks is considered in the analyses. Depth of cracks is 0.01 m.

Resistance on front face of the structure


Resistance on front face of the structure is not considered.

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Applied forces acting on the structure


Force Fx Fz M x z
No. Name Action
new modification [kN/m] [kN/m] [kNm/m] [m] [m]
presion
1 YES permanent 0.00 0.00 -20.00 0.00 2.00
del agua
Name : Applied forces Stage : 1
+x

2.00 2

+z
00
-20.
1

Settings of the stage of construction


Design situation : permanent

Verification No. 1
Active pressure behind the structure - partial results
Layer Thickness a jd cd g dd Ka Comment
No. [m] [°] [°] [kPa] [kN/m3] [°]
1 1.00 0.00 80.00 0.00 0.10 80.00 0.030
2 1.00 0.00 80.00 0.00 0.10 80.00 0.030
Active pressure distribution behind the structure (without surcharge)
Layer Start [m] sZ sW Pressure Hor. comp. Vert. comp.
No. End [m] [kPa] [kPa] [kPa] [kPa] [kPa]
0.00 0.00 0.00 0.00 0.00 0.00
1
1.00 0.10 0.00 0.00 0.00 0.00
1.00 0.10 0.00 0.00 0.00 0.00
2
2.00 0.20 0.00 0.01 0.00 0.01
Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -0.90 45.00 0.85 1.000
Active pressure 0.00 -0.67 0.01 1.50 1.000

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Name Fhor App.Pt. Fvert App.Pt. Design


[kN/m] z [m] [kN/m] x [m] coefficient
Tensile crack 0.00 -2.00 0.00 1.50 1.000
presion del agua 0.00 0.00 0.00 1.50 1.000
Verification of complete wall
Check for overturning stability
Resisting moment Mres = 38.26 kNm/m
Overturning moment Movr = 20.00 kNm/m

Safety factor = 1.91 > 1.50


Wall for overturning is SATISFACTORY

Check for slip


Resisting horizontal force Hres = 255.24 kN/m
Active horizontal force Hact = 0.00 kN/m

Safety factor = 163830.77 > 1.50


Wall for slip is SATISFACTORY

Forces acting at the centre of footing bottom


Overall moment M = 15.50 kNm/m
Normal force N = 45.01 kN/m
Shear force Q = 0.00 kN/m
Overall check - WALL is SATISFACTORY

Name : Verification Stage : 1; Analysis : 1


0.00

45.00

2.00 2
0.01

1
+x

+z

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Bearing capacity of foundation soil


Forces acting at the centre of the footing bottom
Moment Norm. force Shear Force Eccentricity Stress
No.
[kNm/m] [kN/m] [kN/m] [m] [kPa]
1 15.50 45.01 0.00 0.34 55.47
Bearing capacity of foundation soil check
Eccentricity verification
Max. eccentricity of normal force e = 344.3 mm
Maximum allowable eccentricity ealw = 495.0 mm
Eccentricity of the normal force is SATISFACTORY

Footing bottom bearing capacity verification


Max. stress at footing bottom s = 55.47 kPa
Bearing capacity of foundation soil Rd = 120.00 kPa
Safety factor = 2.16 > 2.00
Bearing capacity of foundation soil is SATISFACTORY

Overall verification - bearing capacity of found. soil is SATISFACTORY

Name : Bearing cap. Stage : 1

2.00 2

1
55.47

55.47

Dimensioning No. 1
Active pressure behind the structure - partial results
Layer Thickness a jd cd g dd Ka Comment
No. [m] [°] [°] [kPa] [kN/m3] [°]
1 1.00 0.00 80.00 0.00 0.10 80.00 0.030

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Active pressure distribution behind the structure (without surcharge)


Layer Start [m] sZ sW Pressure Hor. comp. Vert. comp.
No. End [m] [kPa] [kPa] [kPa] [kPa] [kPa]
0.00 0.00 0.00 0.00 0.00 0.00
1
1.00 0.10 0.00 0.00 0.00 0.00
Forces acting on construction
Name Fhor App.Pt. Fvert App.Pt. Design
[kN/m] z [m] [kN/m] x [m] coefficient
Weight - wall 0.00 -0.50 18.00 0.50 1.000
Active pressure 0.00 -0.33 0.00 1.00 1.000
Tensile crack 0.00 -1.00 0.00 1.00 1.000
Verification of construction joint above the block No.: 1
Check for overturning stability
Resisting moment Mres = 9.00 kNm/m
Overturning moment Movr = 0.00 kNm/m

Safety factor = 1000.00 > 1.50


Joint for overturning stability is SATISFACTORY

Check for slip


Resisting horizontal force Hres = 18.00 kN/m
Active horizontal force Hact = 0.00 kN/m

Safety factor = 1000.00 > 1.50


Joint for slip is SATISFACTORY

Forces acting at the centre of footing bottom


Overall moment M = 0.00 kNm/m
Normal force N = 18.00 kN/m
Shear force Q = 0.00 kN/m
Maximum pressure on the bottom block = 18.00 kPa
Red.Coeff. by offset of top block = 0.50
Average value of pressure on face = 4.18 kPa
Shear force transmitted by friction = 12.00 kN/m

Bearing capacity against transverse pressure:


Joint bear.capacity = 34.00 kN/m
Computed stress-state = 2.09 kN/m

Safety factor = 16.27 > 1.50


Transverse pressure check is SATISFACTORY

Joint btw. blocks check:


Mesh material bear.capacity = 43.00 kN/m
Computed stress-state = 2.09 kN/m

Safety factor = 20.57 > 1.50


Joint between blocks is SATISFACTORY

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Name : Dimensioning Stage : 1; Dimensioning : 1

18.00 0.00

0.00

2.00 2
+x

+z
1

Slope stability analysis


Input data
Project
Settings
USA - Safety factor
Stability analysis
Verification methodology : Safety factors (ASD)
Safety factors
Permanent design situation
Safety factor : SFs = 1.50 [–]
Interface
Coordinates of interface points [m]
No. Interface location
x z x z x z
-10.00 -2.00 -1.50 -2.00 -1.50 -1.00
-1.00 -1.00 -1.00 0.00 0.00 0.00
10.00 0.00
1

0.00 0.00 0.00 -1.00 0.00 -2.00


10.00 -2.00

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Coordinates of interface points [m]


No. Interface location
x z x z x z
-1.50 -2.00 0.00 -2.00

Soil parameters - effective stress state


jef cef g
No. Name Pattern
[°] [kPa] [kN/m3]

1 concreto 80.00 0.00 0.10

Soil parameters - uplift


gsat gs n
No. Name Pattern
[kN/m3] [kN/m3] [–]

1 concreto 24.00

Soil parameters
concreto
Unit weight : g = 0.10 kN/m3
Stress-state : effective
Angle of internal friction : jef = 80.00 °
Cohesion of soil : cef = 0.00 kPa
Saturated unit weight : gsat = 24.00 kN/m3

Rigid bodies
g
No. Name Sample
[kN/m3]

1 Wall material 18.00

Assigning and surfaces


Coordinates of surface points [m] Assigned
No. Surface position
x z x z soil
0.00 -2.00 0.00 -1.00
Wall material
0.00 0.00 -1.00 0.00
1 -1.00 -1.00 -1.50 -1.00
-1.50 -2.00

0.00 -1.00 0.00 -2.00


concreto
10.00 -2.00 10.00 0.00
2 0.00 0.00

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

Coordinates of surface points [m] Assigned


No. Surface position
x z x z soil
-1.50 -2.00 -10.00 -2.00
concreto
-10.00 -7.00 10.00 -7.00
3 10.00 -2.00 0.00 -2.00

Water
Water type : No water
Tensile crack
Tensile crack not inputted.
Earthquake
Earthquake not included.
Settings of the stage of construction
Design situation : permanent
Results (Stage of construction 1)
Analysis 1
Circular slip surface
Slip surface parameters
x= -4.82 [m] a1 = -46.86 [°]
Center : Angles :
z= 2.52 [m] a2 = 67.59 [°]
Radius : R= 6.61 [m]
The slip surface after optimization.
Slope stability verification (Bishop)
Sum of active forces : Fa = 28.44 kN/m
Sum of passive forces : Fp = 65.21 kN/m
Sliding moment : Ma = 188.01 kNm/m
Resisting moment : Mp = 431.03 kNm/m
Factor of safety = 2.29 > 1.50
Slope stability ACCEPTABLE

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO
PLANILLA DE METRADO
: SALDO DE OBRA N° 02 DEL PROYECTO "IMPLEMENTACIÓN DEL SISTEMA DE AGUA POTABLE, SISTEMA DE ALCANTARILLADO Y TRATAMIENTO DE AGUAS
PROYECTO
RESIDUALES DE LAS LOCALIDADES DE HUASCAHURA, MOLLEPATA Y ANEXOS, DEPARTAMENTO DE AYACUCHO"
UBICACIÓN : HUAMANGA
LUGAR : CABRAPATA
FECHA mar-18

Partida N° de MEDIDAS Parcial Total Und.


Especificaciones
N° veces Largo Ancho Altura
01 ESTRUCTURAS DE SOSTENIMIENTO EN EMBALSE

01.01 TRABAJOS PRELIMINARES


01.01.01 TRAZO Y REPLANTEO 101.60 101.60 M2
Muro Gavion 1 40.00 2.00 80.00
Muro concreto 1 12.00 1.80 21.60

01.02 MOVIMIENTO DE TIERRAS

01.02.01 EXCAVACION DE PLATAFORMA EN MATERIAL SUELTO 41.36 41.36 M3


Muro Gavion 1 40.00 1.00 0.50 20.00
Muro concreto 1 12.00 1.80 0.60 12.96
1 12.00 1.00 0.70 8.40

01.02.02 ELIMINACION DE MATERIAL EXCEDENTE D=0.50KM. 49.63 m3


Volumen de cortes en Plataforma 41.36 m3
Factor de Esponjamiento 20% 8.27 m3
Total de Material Excedente 49.63 m3

01.03 CONSTRUCCIÓN DE GAVIONES DE 2M EN 40 ML


01.03.01 EXTRACCION Y SUMINISTRO DE PIEDRA PARA CONFORMACION DE GAVIONES 160.00 160.00 m3
Gaviones Tipo A Caja (5.00m X 1.00m X 1.00m) 8.00 5.00 1.00 1.00 40.00
Gaviones Tipo CFA Caja (5.00m X 1.00m X 1.00m) 24.00 5.00 1.00 1.00 120.00

01.03.02 GAVIONES TIPO A CAJA (5.00m X 1.00m X 1.00m) 8.00 und


# por
unidad longitud
metro
1 40.00 0.20 8.00

01.03.03 GAVIONES TIPO CFA CAJA (5.00m X 1.00m X 1.00m) 24.00 und
# por
unidad longitud
metro
3 40.00 0.20 24.00

01.03.04 FLETE TERRESTRE TRANSPORTE DE GAVIONES 1.00 1.00 Glb


1 1.00

01.04 CONSTRUCCIÓN DE MURO DE CONTENCIÓN DE 4M EN 12 ML


01.04.01 SOLADO DE 2" MEZCLA 1:10 CEMENTO - HORMIGON 2.16 2.16 m3
Muro concreto 1 12.00 area 0.18 2.16

01.04.02 ENCOFRADO Y DESENCOFRADO NORMAL 123.16 123.16 m2


Muro concreto 8 1.00 3.20 25.60
1 12.00 4.00 48.00
1 12.00 4.13 49.56

01.04.03 ACERO DE REFUERZO 4200 KG/CM2 1,250.00 1,250.00 kg


PANTALLA HORIZONTAL 19 12.00 peso 3/8" 0.56 127.68
15 12.00 peso 3/8" 0.56 100.80
5 12.00 peso 3/8" 0.56 33.60
PANTALLA VERTICAL 48 5.70 peso 1/2" 1.00 273.60
40 4.60 peso 1/2" 1.00 184.00
40 1.75 peso 1/2" 1.00 70.00
ZAPATA LONGITUDINAL 60.00 2.20 peso 5/8" 1.56 205.92
60.00 2.00 peso 5/8" 1.56 187.20
ZAPATA TRANSVERSAL 5 12.00 peso 3/8" 0.56 33.60
5 12.00 peso 3/8" 0.56 33.60

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO
PLANILLA DE METRADO
: SALDO DE OBRA N° 02 DEL PROYECTO "IMPLEMENTACIÓN DEL SISTEMA DE AGUA POTABLE, SISTEMA DE ALCANTARILLADO Y TRATAMIENTO DE AGUAS
PROYECTO
RESIDUALES DE LAS LOCALIDADES DE HUASCAHURA, MOLLEPATA Y ANEXOS, DEPARTAMENTO DE AYACUCHO"
UBICACIÓN : HUAMANGA
LUGAR : CABRAPATA
FECHA mar-18

Partida N° de MEDIDAS Parcial Total Und.


Especificaciones
N° veces Largo Ancho Altura
01.04.04 CONCRETO F'C = 210 KG/CM2 59.76 59.76 m3
1 12.00 area 4.98 59.76

01.04.05 FLETE TERRESTRE TRANSPORTE DE MATERIALES 1.00 1.00 Glb


1 1.00

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO

PRESUPUESTO
: SALDO DE OBRA N° 02 DEL PROYECTO "IMPLEMENTACIÓN DEL SISTEMA DE AGUA POTABLE, SISTEMA DE
PROYECTO ALCANTARILLADO Y TRATAMIENTO DE AGUAS RESIDUALES DE LAS LOCALIDADES DE HUASCAHURA,
MOLLEPATA Y ANEXOS, DEPARTAMENTO DE AYACUCHO"
UBICACIÓN : HUAMANGA
LUGAR : CABRAPATA
FECHA 11/03/2019

Item Descripción Und. Metrado Precio (S/.) Parcial (S/.)


01 ESTRUCTURAS DE SOSTENIMIENTO EN EMBALSE 74,648.98
01.01 TRABAJOS PRELIMINARES 499.04
01.01.01 TRAZO Y REPLANTEO m2 101.60 4.91 499.04
01.02 MOVIMIENTO DE TIERRAS 4,094.28
01.02.01 EXCAVACION DE PLATAFORMA EN MATERIAL SUELTO m3 41.36 62.29 2,576.15
01.02.02 ELIMINACION DE MATERIAL EXCEDENTE DM=0.5 km m3 49.63 30.59 1,518.13
01.03 CONSTRUCCIÓN DE GAVIONES DE 2M EN 40 ML 26,579.30
01.03.01 EXTRACCION Y SUMINISTRO DE PIEDRA PARA CONFORMACION DE GAVIONES
m3 160.00 12.57 2,011.30
01.03.02 GAVIONES TIPO A CAJA (5.00MX1.00MX1.00M) und 8.00 611.50 4,892.00
01.03.03 GAVIONES TIPO CFA CAJA (5.00MX1.00MX1.00M) und 24.00 611.50 14,676.00
01.03.04 FLETE TERRESTRE TRANSPORTE DE GAVIONES glb 1.00 5,000.00 5,000.00
01.04 CONSTRUCCIÓN DE MURO DE CONTENCIÓN DE 4M EN 12 ML 43,476.36
01.04.01 SOLADO e=2" MEZCLA 1:10 CEMENTO HORMIGON m2 2.16 32.22 69.59
01.04.02 ENCOFRADO Y DESENCOFRADO NORMAL m2 123.16 47.77 5,883.30
01.04.03 ACERO DE REFUERZO fy=4,200 kg/cm2 kg 1,250.00 6.32 7,897.25
01.04.04 CONCRETO f'c=210 kg/cm2 m3 59.76 453.92 27,126.22
01.04.05 FLETE TERRESTRE TRANSPORTE DE GAVIONES glb 1.00 2,500.00 2,500.00
COSTO TOTAL 74,648.9807

ING. JUAN HECTOR OSORIO CLEMENTE.


RESPONSABLE DE OBRA
SERVICIO DE AGUA POTABLE Y ALCANTARILLADO DE AYACUCHO S.A.
SEDA AYACUCHO
Renovándose para Servir Mejor

[3] CONCLUSIONES:

 Como se ha podido comprobar la estructura en el estado actual en el que se encuentra sufre un fallo por volteo en la
dirección X – X lado menor del embalse. Esto debido a que no existe un empuje horizontal pasivo que contrarreste la carga
hidrodinámica e hidrostáticas que ejerce el agua en reposo y en movimiento. Por lo que es necesario plantear una solución
para poder estabilizar dichos muros ya que en un eventual sismo estas no soportarían cargar horizontales hidrodinámicos
produciéndose un eminente volteo de la estructura una vez producido un sismo. En ese sentido de adoptado una estructura
tipo muros de concreto reforzado de 1.80 de ancho y 4m de altura cada 3 m a lo largo de esta.

 Por motivo de seguridad se ha establecido proporcionar de la misma manera en la dirección Y-Y lado mayor, una carga de
seguridad, el cual garantice a un más la seguridad de la estructura siendo esta un componente de riesgo de falla por carga
de sismo, en este sentido sea proporcionado una estructura tipo gavión de 2 m de ancho y 2m a lo largo de esta

 Se solicita a la Supervisión del proyecto la Opinión y/o Aprobación de estas dos partidas y que esas variables que mejorara
el funcionamiento Hidráulico diseñado para estas actividades:

[4] RECOMENDACIONES:

LA APROBACION DE LAS MODIFICACIONES SOLICITADAS POR LA RESIDENCIA DE OBRA PARA AGILIZAR LOS TRABAJOS
PERTINENTES A TRAVÉS DE LA DEPENDENCIA CORRESPONDIENTE, PARA SU CONTINUIDAD DEL PROYECTO EN EJECUCIÓN A
TRAVÉS DEL SECTOR CORRESPONDIENTE.

Es todo cuanto informo a Ud. para su conocimiento:

Atentamente,

C.c.
Archivo
JHOC.