Sei sulla pagina 1di 12

A Reliability-Based Deformation Capacity Model for ACI 318

Compliant Special Structural Walls

Saman A. Abdullah, PhD Candidate


University of California, Los Angeles
Los Angeles, CA

John W. Wallace, Professor


University of California, Los Angeles
Los Angeles, CA

Abstract Introduction

The underlying premise of the ASCE 7 and ACI 318 In the last version of ACI 318 in 2014, extensive revisions
provisions is that special structural walls satisfying the were introduced to require more stringent detailing
provisions of ACI 318-14 §18.10.6.2 through §18.10.6.4
possess adequate drift capacity to exceed the expected drift
( )
requirements for thin, slender hw lw ≥ 2.0 walls, include a
demand determined from ASCE 7-10 analysis procedures. limit on wall slenderness (h
u )
b ≤ 16 , require a minimum
However, observations from laboratory tests and strong width of flexural compression zone (b > 12 in.) for sections
earthquakes, e.g., the 2010 Chile earthquake and the 2010 E-
Defense tests, where significant damage was noted at wall ( )
that are not tension-controlled c lw ≥ 3 8 , and require that
boundaries due to concrete crushing, rebar buckling, and more walls be detailed with Special Boundary Elements
lateral instability, have raised concerns that current design (SBE) by adding a 1.5 factor in the denominator of ACI 318-
provisions are inadequate, especially for “thin” walls, 14 Equation 18.10.6.2. These more recent changes were a
although it is not clear what attributes should be used to result of the unsatisfactory performance of many walls in the
define a “thin” wall. Recent studies have identified that 2010 Chile and 2011 New Zealand earthquakes, as well as
deformation capacity of code compliant walls is primarily a observations from recent large-scale laboratory tests
function of wall cross-section geometry, neutral axis depth, (Wallace, 2012; Wallace et al., 2012; Nagae et al., 2011;
wall shear stress demands, and configuration of boundary Lowes et al., 2012).
transverse reinforcement (i.e., use of overlapping hoops
versus a perimeter hoop with intermediate legs of crossties); Even with these more stringent requirements, the underlying
however, these parameters are not adequately considered in premise of the ACI 318-14 and ASCE 7-10 approach to
ACI 318-14. To address this issue, this study proposes a new design and detailing Special Structural Walls is that walls
reliability-based design requirement where a drift demand-to- satisfying the provisions of ACI 318-14 §18.10.6.2 through
capacity ratio (DDCR) check is performed to provide a low §18.10.6.4 possess adequate displacement capacity to exceed
probability that roof drift demands exceed roof drift capacity the expected displacement demands from ASCE 7-10
at strength loss (e.g., 10% probability of lateral strength loss analysis procedures when subjected to design-level ground
under Design Earthquake). In general, slender wall cross motions, without significant strength degradation. However,
( )
sections lw b > 15 with large neutral axis depth relative to recent research has shown that drift capacity of code-
compliant walls is impacted by parameters that are not
width of flexural compression zone ( c b > 3) and shear adequately addressed in ACI 318-14. For example, the
studies by Abdullah and Wallace (2018a) and Segura and
stresses approaching the ACI 318-14 limit (10 f 'c ) tend Wallace (2018b) showed that lateral drift capacity of walls
to be screened out for redesign to reduce the probability of with SBEs is significantly influenced by parameters, such as
collapse under MCE level shaking. width of flexural compression zone b, wall length lw, neutral
axis depth c (i.e., compression demands), wall shear demand

1
50 50 80 60 50 (a) 50 (b)

No. of Specimens
No. of Specimens
40 40 40 40
60
40 30 30
30 30
40
20 20 20 20
Vu, and configuration of boundary transverse reinforcement 20
wall provisions 20 of ACI 318 code do not adequately address
10 10
(overlapping hoops versus a single perimeter 10hoop with
10
safety concerns, nor do they ensure that walls have adequate
0 0
intermediate crossties, a detail0
allowed by ACI 0
318-14 0
drift capacity to meet the expected drift demands under DE
0

10
8

0. 9
1. 0

0.
3

0.
4
7

8
8

0
0. 9

0.
1

0
0

1-
2

4-
3

6-
5

3-
3

3.

5-
5

7-
0.

10
7

2.
4

0.
8

1.

7-

8-
0.

-3
5

-2

-4

2.

3.

9-
5-

5-
1.

5-
1-

4-

6-
3-

5-

7-

0-
7-

5-

0-
8-

0-

0.
§18.10.6.4). The findings of these studies indicated that, shaking with a reasonable
M/(Vl ) level of reliability (e.g.,
sv/db90%);

5-
9-

0.
20

2-

3-
10

30

1-

1.

2.

3.
2.
0.

1.
0.
sv/db Ash, prov./A P/(f A ) (%)
' Min. Ash, provide
sh,req: X-Dir. c g w

depending on these variables,60 drift capacity of60walls with 60 therefore, ACI 318-14
60 wall provisions should 60 be updated to
(e) 50
(f)

No. of Specimens
SBEs varies by a factor of about three, ranging between address this critical issue.
No. of Specimens

40
40
approximately 1.2% and 3.5%,40as shown in Figure 40 1. Figure 40 40 30

1 (a) presents variation of drift capacity of a dataset of 164 To address the above issue, a new reliability-based design 20
20 20
generally code-compliant walls versus a 20slenderness 20
methodology is 20proposed where a drift demand-to-capacity 10

parameter (λ b )
= lw c b 2 , whereas
0 Figure 1 (b)
0 presents 0
ratio (DDCR) 0check is performed to provide 0 a low
probability that roof drift demands exceed roof drift capacity
0

10

0. .5
0
5

0. 65
5
12 5

20 0

0. 3
15 0

0
10

-2
5

-1
0

10 0

<5

7.
5

-0
12

20

0.
0

0
15

5
30

5-
0
00
-1

0.
-2

0
<5

7.

( )

-2
2

-4
4

15
-1

-3
3

10
5-
5-

<1

1-

25
-1

7.
0-

4-
0-

5-
1-

3-
10

5-

0-

2-
15

>3
5-

15

30
10

20
7.

6
0.
results of the 121 slender walls M Vlwl /b≥ 2.0 in the dataset. 90
l /b hx/
b (mm) w at strength
c/b loss for a given
c/l hazard level (e.g., 10% probability
w
w

of lateral strength loss for the DE or MCE level shaking). In


These results have very important design implications. First,
not all code-compliant walls have the same, or nearly the general, walls with slender cross sections lw b > 15 , large ( )
same, drift capacity. Second, at Design Earthquake (DE) neutral axis depth relative to width of flexural compression
level shaking, ASCE 7-10 §12.12.1 limits allowable story
drift ratio to 0.02 for typical RC buildings in Risk Category I ( )
zone c b > 3 , shear stress demands approaching the ACI
& II that are taller than four stories and utilize structural walls 318-14 §18.10.4.4 limit of 10 f 'c , and roof drift demands
for a lateral force resisting system (LFRS). At Maximum
Considered Earthquake (MCE) level shaking, which is used approaching the maximum value allowed by ASCE 7-10 (i.e.,
to assess collapse prevention, this limit is typically taken as 0.75 × 0.02 = 0.015) tend to be screened out for redesign to
1.5 times the DE limit, or 0.03. If roof drift demand is prevent strength loss under DE level shaking and reduce the
approximated as three-quarters of peak story drift, which is a probability of collapse under MCE level shaking. This
reasonable approximation for buildings with walls, then the approach is rational and transparent and is similar to other
peak roof drift demand allowed by ASCE 7-10 is checks for moment and shear strength found in the ACI 318
approximately 0.0225 for MCE level shaking, which is about code. Finally, two design examples are presented to highlight
87% greater than the minimum wall drift capacity of 0.012 the deficiencies in the current code provisions and to
observed in Figure 1. These findings suggest that current illustrate the application of the proposed methodology.

5
vmax/÷ fc' psi £ 5 (£ 0.42 in MPa) vmax/÷ fc' psi £ 5 (£ 0.42 in MPa)
4 vmax/÷ fc' psi > 5 (> 0.42 in MPa) vmax/÷ fc' psi > 5 (> 0.42 in MPa)
Drift Capacity (%)

0
0 40 80 120 0 40 80 120
lb = lwc/b2 lb = lwc/b2
(a) Entire dataset (M/Vlw (b) M/Vlw .0 1.0)
Figure 1–Drift capacity variation of walls with special boundary elements (Abdullah and Wallace, 2018a).

5
)
Existing Design Approach (i.e., 0.03 × 0.75 = 0.0225), as can be seen in Figure 1. Walls
with these attributes are fairly common in modern wall
ACI 318-14 §18.10.6 includes two design approaches to buildings (Brown et al., 2006). Therefore, the current design
evaluate the need for SBEs at wall boundaries, a simplified provisions do not provide adequate safety margins. Next, a
displacement-based design approach (§18.10.6.2) for slender new reliability-based design approach is proposed, which has
( )
walls hw lw ≥ 2.0 and a stress-based approach (§18.10.6.3). been proposed to ACI 318-19 code to address this issue.
Since the present study focuses on a drift demand-to-capacity Proposed Approach
ratio (DDCR) approach for more slender walls with a single
critical section, the discussion that follows is limited to the A rational and transparent approach to address the
displacement-based design approach of §18.10.6.2, which deficiencies highlighted in the previous section is to introduce
(
applies to slender walls hw lw ≥ 2.0 that are effectively ) a DDCR check for Special Structural Walls, which is
continuous from a single critical section to the top of the wall. somewhat similar to demand-to-capacity checks in ACI 318
Detailed background information on the simplified code for moment and shear strengths, or drift capacity of
displacement-based design approach, which was first adopted slab-column connections (ACI 318-14 §18.14.5), to meet a
in ACI 318-99, is provided by Wallace and Orakcal (2002). specified level of reliability. The basis for the new design
Per this approach, if the maximum value of depth of neutral approach is expressed in Eq. 2:
( )
axis cmax computed for the factored axial load Pu,max and ( ) ⎛ δ ⎞ ⎛ 1.5δ u ⎞
nominal moment strength (M ) , consistent with the φd ⎜ c ⎟ ≥ ⎜ ⎟ (Eq. 2)
⎝ hw ⎠ ⎝ hw ⎠
n

direction of the design roof displacement δ u , exceeds ( )


critical depth of neutral axis ccritical ( ) computed from Eq. 1 Where δ c hw is the mean wall lateral drift capacity
(ACI 318-14 Equation 18.10.6.2), then SBEs are required at estimated from Eq. 3, a drift capacity model developed by
the wall boundary regions over a distance greater than, or Abdullah and Wallace (2018a, 2018b) with a mean of 1.0 and
equal to, the maximum of c 2 and c − 0.1lw . The 1.5 a coefficient of variation (COV) of 0.15, φ d is a
“displacement” reduction factor which can vary depending on
multiplier on δ u was added in ACI 318-14 to account for
the level of reliability required, and δ u hw is the mean roof
dispersion in the computed drift demands under DE level
drift demand estimated using ASCE 7 analysis approaches,
shaking and to produce detailing requirements more
multiplied by a 1.5 factor to convert the DE drift demands to
consistent with the ASCE 7 code intent of a low probability
MCE drift demands (ASCE 7-10 §11.4.4). This format also
of collapse for MCE level shaking.
is consistent with 1.5 multiplier used in the current ACI 318-
14 Equation 18.10.6.2 (or Eq. 1 herein).
lw
ccritical = (Eq. 1)
(
600 1.5δ u hw ) δc
(
l c
% ) = 3.85 − w 2 −
vmax
≥ 1.5% (Eq. 3)
hw 50b 10 f 'c ( psi)
If a structural wall is determined to require a SBE based on
Eq. 1, then the SBE is required to satisfy the detailing
requirements of ACI 318-14 §18.10.6.4. If these detailing Based on results of nonlinear response history analyses (NL-
requirements are satisfied, the underlying premise of the code RHA) of 28 buildings with planar structural walls (Wallace
is that the wall drift capacity exceeds the expected wall drift and Safdari, 2018), as well as results reported in the literature
demands determined from analysis when subjected to DE- (e.g., Kim 2016), Abdullah and Wallace (2018c) concluded
level ground motions, without critical strength loss. However, that the COV for roof drift demand under DE level shaking
as presented earlier, this is not always the case. In particular, generally ranges from 0.20 to 0.40. A COV of 0.30 was
adopted for the reliability analysis presented here, and the
walls with lw c b 2 > 45 and high shear stresses (e.g.,
sensitivity of the results to modest variations in the COVs
approaching the ACI 318-14 §18.10.4.4 average wall shear selected is considered later.
stress limit of 10 f 'c ( psi) ) would be expected to have a
A simple reliability analysis of Eq. 2, assuming lognormal
( )
mean roof drift capacity δ c hw less than the maximum roof distributions in roof drift demand and capacity with the
drift demand allowed by ASCE 7-10 for MCE level shaking estimated COVs on drift demand and capacity and taking φ d
= 1.0, results in a probability of strength loss of

3
approximately 10% and 50% for DE and MCE level Abdullah and Wallace (2018c) reviewed results of wall tests
demands, respectively, as shown in Figure 2. If the COVs on with λb > 40 (i.e., lower drift capacities) in a dataset of 164
roof drift demand and capacity are increased to 0.40 and 0.2,
generally code-compliant walls and observed that lateral
respectively, the probability of strength loss under DE
strength loss in these walls was abrupt and typically much
demands increases modestly from about 10% to 17%,
greater than 20%, and that axial failure was observed to occur
indicating the strength loss probabilities are not overly
sensitive to the estimated COVs. These levels of probability soon after loss of lateral strength, even for walls with
of strength loss appear to be high, given the target collapse restrained web longitudinal bars (i.e., Segura and Wallace,
2018a; Shegay et al., 2016). Although tests of well-detailed,
probabilities of ASCE 7-16 §1.3.1.3 of 10% for Risk
isolated cantilever walls show that axial failure may follow
Category I and II buildings and 5% for Risk Category III
soon after substantial lateral strength loss under continued
buildings under MCE level demands. To reduce the
lateral loading, collapse of buildings with structural walls has
probability of strength loss to 10% for MCE level demands, a
rarely been reported following earthquakes or shake table
φ d of 0.65 is required. Selection of an appropriate φ d value
tests, even for walls with substantial damage (Wallace et al.,
requires a definition for collapse, since drift capacity at 20%
2008; Nagae et al., 2015). Given these observations, use of a
strength loss, which is used by Eq. 3, is not necessarily
low probability of strength loss (i.e., 10%) for DE level
associated with building collapse, which is more commonly
shaking is suggested here as a minimum criterion for collapse
associated with loss of axial load capacity. Use of a low
probability (10%) of strength loss for MCE level demands (i.e., φ d = 1.0). This approach will screen out walls with high
likelihood of strength loss at DE level shaking for redesign,
would be a conservative estimate of collapse, since axial
failure models in the literature for columns (Elwood and which will reduce the likelihood of severe damage at hazard
Moehle, 2005) and for walls (Wallace et al., 2008), as well as levels less than DE level shaking and reduce the potential for
collapse at MCE level shaking. Future adjustment to this
ASCE 41 backbone relations, generally indicate that drift
relation could be considered once additional information
ratios at axial failure exceed those at significant strength loss.
becomes available.

Figure 2–Probabilities of strength loss under DE and MCE hazard levels.

alternative approach would be to determine the required


If Eq. 2 is not satisfied for a given wall, then the designer
would be required to revise the design for that wall. The most
minimum width of flexural compression zone bmin by ( )
likely change would be to increase the width of the flexural rearranging Eq. 2 after substituting Eq. 3:
lw c
(b )
compression zone b (i.e., wall thickness, tw), which would 2
increase the drift capacity obtained with Eq. 3 by reducing ≥ (Eq. 4)
min
⎛ vmax 1.5δ u ⎞
the slenderness parameter λb = lw c b 2 and also likely 50 ⎜ 3.85 − − ⎟
reducing the shear and drift demands by increasing the shear ⎜⎝ 10 f c' (psi) hw ⎟⎠
resisting area and effective stiffness, respectively. This may
require some iteration; however, a more convenient

4
Where 1.5 δ u hw should not be taken less than the lower The discussion and results presented here are intended to
apply to walls with rectangular, flanged, and barbell cross
limit on Eq. 3, which is 1.5%. An upper-bound width of the sectional shapes (Fig. 3(a) through (f)). For cases with a
( )
flexural compression zone bupper can be approximated using large b, e.g., where the barbell or flange of the wall is in
Eq. 4, which is based on assuming the shear stress term compression (Fig. 3(b) through (h)), drift capacity is likely to

(v max
10 f 'c ) approaches 1.0 and roof drift demand term be relatively large (due to low λb ); however, for cases with a
barbell or flange in tension, and a thin wall web in
(1.5δ u hw ) approaches 0.0225 corresponding to the compression (Fig. 3(b) and (e) through (h)), relatively large
values of c b , and thus λb , and higher shear demands are
allowable roof drift demand under MCE level shaking,
resulting in the following: likely, and thus, lower drift capacities will result. Therefore,
such cases are more critical than cases where the barbell or
flange of the wall is in compression. For cases where b varies
bupper = 0.03clw (Eq. 5) over c, or where c varies over b, a representative (e.g.,
weighted average) value of b or c should be used, as shown in
Note that, if c = 0.20lw, then Eq. 5 requires bupper of 18.6 in. Fig. 3(c), (d), (e) and (h).

(470 mm) and 28 in. (710 mm) for walls with length of 20 ft
(6096 mm) and 30 ft (9144 mm), respectively.

Fig. 3–Definition of width b ( ) ()


and length c of flexural compression zone.

5
Alternative Approaches change significantly) the lateral drift capacity. This is in part
because it is difficult to get more drift capacity out of thin
1. Stringent Detailing Requirements walls because of lateral instability problems, as highlighted
An alternative strategy that might be suggested to address the by Segura and Wallace (2018a).
deficiencies identified previously would be to require
sufficient detailing such that all walls have a roof drift 2. Limits on Wall Axial Load
capacity that exceeds a “worst-case” for a story drift demand Another approach that has been suggested is to place a limit
of 0.03 for MCE level demands (a roof level demand of on axial load ratio (Shegay et al., 2018). This is because axial
approximately 0.0225). For example, Welt et al. (2018), load has traditionally been assumed to have a significant
using results of rectangular prism tests, recommend impact on wall (and column) lateral drift (or plastic rotation)
significantly stricter detailing requirements than what is capacity. For example, in UBC 1997 §1921.6.6.3 and ASCE
currently required by ACI 318-14, such as tighter spacing of 41-13 §10.7.1.1, if axial load on a wall exceeded 0.3 Ag f 'c ,
transverse and longitudinal reinforcement, restraint of every
longitudinal bar, and an increase of the amount of transverse the lateral strength and stiffness of the wall could not be
reinforcement. Additionally, Behrouzi et al. (2017) considered. Additionally, ASCE 41-13 Tables 10-19 and 10-
recommend that the boundary element confinement pattern 20 use axial load ratio as a primary term for selecting
and horizontal spacing and lateral restraint pattern of modeling parameters and acceptance criteria for both flexure-
boundary longitudinal reinforcement should follow the and shear-controlled walls. Similar limits (0.3 or 0.35 Ag f 'c )
provisions for high axial-stress columns, specifically on wall axial load exist in other codes such as NZS 2017,
provisions of ACI 318-14 §18.7.5.2, which requires every CSA 2004, and DS 60 MINVU (Chilean Structural Standard
boundary longitudinal bars be restrained and a limit of 8 in on 2010). However, results presented by Abdullah and Wallace
the horizontal spacing of longitudinal bars. This approach
was used recently to update column detailing requirements in ( )
(2018a) revealed that axial load ratio P Ag f 'c , by itself,
ACI 318-14 §18.7.5.4 (Elwood et al., 2009); however, this has no clear correlation with wall drift capacity (correlation
approach would be overly conservative for structural walls coefficient, R = 0.08), as shown in Fig. 5. From this figure, it
where story drift demands are often considerably less than is clear that there is no significant trend between axial load
0.03, e.g., for a building with many walls. Furthermore, ratio (ranging from 0.0 to 0.35) and wall drift capacity. It is
Abdullah and Wallace (2018a) studied the impact of detailing noted that the slenderness parameter λb described earlier
variables on wall lateral drift capacity and concluded that
incorporates the impact of axial load through neutral axis
requiring more stringent detailing provisions do not
depth. Therefore, placing a limit on axial load is not
significantly improve drift capacity in many cases.
recommended.
Parameters considered included: (1) Minimum ratio of
provided-to-required (per ACI 318-14 §18.10.6.4) area of
3. Change to ASCE 7 Provisions
boundary transverse reinforcement, Ash, provided Ash,required , (2) Lastly, one might suggest that the wall provisions of ASCE 7
Ratio of vertical spacing of boundary transverse could be changed to address the issues of inadequate
reinforcement to minimum diameter of longitudinal boundary deformation capacity of walls, particularly related to reducing
reinforcement, s db , (3) Centerline distance between the seismic response coefficient ( )
R , deflection
laterally supported boundary longitudinal bars normalized by ( )
amplification factor C d , and/or the allowable story drift
maximum spacing, hx hmax , or by width of compression
zone, hx b , (4) degree of lateral restraint provided (i.e.,
(Δ a )
hx . However, this approach would also be too
conservative because it would punish all walls, even walls
support for all boundary longitudinal bars versus every other
with small λb and shear stresses which tend to possess quite
bar). For these variables, they utilized a dataset of 78 wall
tests that fully satisfied the ACI 318-14 provisions, large drift capacities, as was seen in Figure 1.
particularly those related to quantities Ash, provided , s , s db ,
For the reasons mentioned here, the above three approaches
hx , and length of confined boundary element (l ) .
be The were not considered to be effective and, thus, are not
results are presented in Fig. 4. It can be noted from this figure recommended. Next, two design examples are presented to
that changes in these parameters within ranges that are illustrate the proposed DDCR approach.
permissible or reasonable for SBEs do not influence (or

6
0 40 80 120 0 40 80 120
lwc/b2 lwc/b2

5
1.0 Ash,provided/Ash,required 1.2 1.5 s/db < 3.5
4 1.2 < Ash,provided/Ash,required 3.5 < s/db 6
Drift Capacity (%)

1
a) BE transverse reinf.: X-Dir b) Bar slenderness ratio
0
5
All bars supported 0.3 < hx/hx,max
4 Not all bars supported 0.7 < hx/hx,max
Drift Capacity (%)

1
d) Spacing of laterallysupported BE
c) Lateral support of BE longi. bars longi. bars
0
0 40 80 120 0 40 80 120
lb = lwc/b2 lb = lwc/b2
Figure 4–Impact of boundary element details on drift capacity of walls with SBEs (Abdullah and Wallace, 2018a).

Figure 5–Impact of axial load ratio on drift capacity of walls with SBEs (Abdullah and Wallace, 2018a).

7
Design Examples concrete compressive strength (f' )
c of 5 ksi and Grade 60

Description of the Buildings reinforcement with yield strength (f )


y
of 60 ksi are
In the following, two residential buildings (6-story and 10-
specified, consistent with requirements of ACI 318-14
story) located in Los Angeles, California are used to illustrate
§18.2.5 for concrete and §18.2.5 for reinforcement in
the application of the proposed design methodology, as well
structural walls. A total uniformly distributed floor dead load
as to highlight the significant deficiency in the current design
(in addition to self-weight of walls) of 150 psf and floor live
provisions of ACI 318. The building footprint is 150×75 ft.
load of 40 psf per ASCE 7-10 §4.3.1 are used as the loading
(Fig. 6), and the typical story height is 12 ft. A summary of
criteria.
seismic design parameters is provided in Table 1. Design

6@25ft (7.6m) = 150ft (45.6m)


D
3@25ft (7.6m) = 75ft (22.8m)

Tributary Area

Wall #2
Wall #1

N
B
24"x24"
Gravity column (typ.)
A

1 2 3 4 5 6 7
Figure 6–Typical plan view of the buildings.
the building.
(a) Plan view of
considered. A wall effective stiffness, Ec I eff , of 0.5Ec I g
Table 1–ASCE 7-10 seismic parameters
was assumed for the lateral analysis, consistent with ACI
Parameter Value 318-14 §6.6.3.1.2. The contribution of the gravity columns to
Building Location 34.058°N, 118.445°W the lateral strength and stiffness of the system was ignored.
The lateral analysis included the impact of accidental
Risk Category II
Importance Factor 1.0
( )
torsional moment M ta required by ASCE 7-10 §12.8.4.2.
Inclusion of accidental torsion generally resulted in an
Site Class D
increase of both roof drift and base shear demands by about
SS; SDS (g) 2.253; 1.502 15%. The ASCE 7-10 strength level load combinations (LC)
S1; SD1 (g) 0.829; 0.829 defined in §2.3.2 and §12.14.3.1 were used to compute the
ultimate force demands. Additionally, a redundancy factor
Seismic design category (SDC) E
R = Cd 5
( )
ρ of 1.3 was applied to the load combinations that include
seismic loads in accordance with ASCE 7-10 §12.3.4.2,
Redundancy factor ρ 1.3 resulting in a 30%-increase in base shear and moment
demands, and a ρ of 1.0 was used for drift calculations in
accordance with ASCE 7-10 § 12.3.4.1. It its noted that
Lateral Load Analysis
ASCE 7-10 §12.9 Modal Response Spectrum Analysis (RSA) ( )
1.2 + 0.2S DS D + 0.5L + ρQE load combination, with
was utilized to determine design lateral forces on the walls negative accidental eccentricity (i.e., moving center of mass
under DE level shaking. For the purposes of this study, only (CM) closer to the wall), produces in the largest force and
analysis and design of the LFRS in the north-south direction, drift demands.
which consists of planar RC Special Structural Walls, was

8
Detailed information for the LFRS and the analysis results MCE level shaking, respectively, for building 10A are
(maximum story and roof drifts, base moment, and base shear unacceptably high given the current target reliabilities of
demands) are summarized in Table 2 under columns A6 and ASCE 7-16 §1.3.1.3. It is important to note that the walls in
A10 for the 6-story and 10-story buildings, respectively. The both buildings (6A and 10A) satisfy the provisions of ASCE
walls were proportioned such that the maximum story drift 7-10 and ACI 318-14 for Special Structural Walls (i.e., code
demands (Δ story )
hx , computed at CM in accordance with compliant walls). These results highlight that the current code
provisions do not provide adequate safety margins, and that
ASCE 7-10 §12.8.6, were smaller than the allowable story these wall designs should not be accepted.
drift (i.e., Δ a hx = 0 .02) given in ASCE 7-10 §12.12.1 for
Revised Design
( )
DE level shaking. The DE roof drift demands δ u hx , given To reduce the probability of strength loss to an acceptable
in Table 2, were taken at the top of the wall (not at CM), level (e.g., 10% or lower for DE level shaking), either Eq. 4
consistent with wall design displacements used in ACI 318-
14 Equation 18.10.6.2. A factor of 1.5 was used to convert
( ) ( )
bmin or Eq. 5 bupper can be employed. For the given c lw
the DE roof drift demands to MCE demands, as noted
previously. Base moment, shear, and axial demands given in
(
demands, the upper bound compression zone width bupper is )
Table 2 are for a critical section at the base of the walls. 27.8 in. for the 6-story building and 30.5 in. for the 10-story
building. An alternative approach is used here, where bmin is
Walls Design determined using Eq. 4 assuming a change in wall thickness
Based on the demands from the preceding section, two
results in proportional reductions in δ u hw , v max f 'c , and
identical planar structural walls are proposed as the LFRS in
the north-south direction for each building. The walls are 24 c lw . For building 6A, revised demand values for an
ft. long and 12 in. thick for building A6 and 26 ft. long and
estimated 15% reduction are: δ u hw ≈ 1.44×0.85 = 1.22%,
18 in. thick for building A10, resulting in wall cross-section
( )
aspect ratio lw b of 24 and 17.33, respectively. Because v max f 'c ≈ 7.21×0.85 = 6.13, and c lw ≈ 0.31×0.85 =
the buildings are assigned to SDC E in accordance with 0.26.
ASCE 7-10 §11.6, the walls are required to be designed and
detailed to satisfy the provisions of ACI 318-14 §18.10 for Substituting these values in Eq. 4 results in bmin = 0.061 lw ≈
Special Structural Walls. Wall design details are shown in
18 in. for the 6-story building and, similarly, bmin = 23 in. for
Table 2 under columns 6A and 10A for the 6-story and 10-
story buildings, respectively. Since cmax > ccritical , the the 10-story building. Therefore, wall thickness values were
increased to 18 in. for the 6-story building and to 24 in. for
compression zones of the walls must be reinforced with SBE 10-story building. Using the new wall thickness values, the
details that satisfy the requirements of ACI 318-14 §18.10.6.4 analyses were rerun to determine the new force and drift
( )
over a distance of lbe,required = max c 2;c − 0.1lw . demands, as well as to determine whether Eq. 2 is satisfied
(i.e., probability of strength loss is 10% or lower for DE level
shaking). The revised design details are given in Table 2
Reliability Analysis
under columns 6B and 10B for the 6-story and 10-story
Wall roof drift capacities given in Table 2 were computed
building, respectively. As can be seen from Table 2, increase
from Eq. 3, which are defined at 20% strength degradation.
in the wall thickness for building 6A resulted in: (1) reduction
The lower bound (minimum) drift capacity from Eq. 3
governs for walls in both 6A and 10A buildings. To of δ u hw by about 17%, (2) reduction of v max f 'c by
determine the probabilities of strength loss, simple reliability about 16%, and (3) significant increase in δ c hw , because a
analyses of Eq. 2 were performed assuming lognormal
distributions in drift demand and capacity and considering portion of the drift capacity is proportional to b 2 . The new
COVs of 0.30 and 0.15 for roof drift demand and capacity, probabilities of strength loss for DE and MCE level shaking
respectively. The probabilities of strength loss under DE and have reduced to below 10% and 50%, respectively, as shown
MCE level shaking are given in Table 2. The resulting in Table 2.
values of 45% and 86% for DE and MCE level shaking,
respectively, for building 6A, and 65% and 94% for DE and

9
Table 2–Design details of the walls in each building
6-story 10-story
Building
6A 6B 10A 10B
hw × lw × t w (ft) 72×24×1.0 72×24×1.5 120×26×1.5 120×26×2.0

(
hw lw ; M base Vbase lw ) 3.0; 2.02 4.62; 2.39
lbe × b (in.) 61×12 52×18 71×18 53×24
lbe,required (in.) 60.2 41.2 69.8 50
Boundary longitudinal
45 No.11 45 No.11 42 No.14 44 No.14
reinforcement
Boundary transverse
No.4@3.75in. No.4@4.5in. No.5@4in. No.5@4.5in.
reinforcement
Ash, prov . Ash,req. ;S prov . Sreq. 1.05; 0.9 1.02; 0.8 1.00; 0.7 1.05; 0.8
Web vertical and horizontal 2layers
2 layers No.6@8in. 2 layers No.6@9in. 2 layers No.6@10in.
reinforcement No.6@8.5in.
Min φ M n (kips-ft.) 88,139 95,570 133,039 152,076

V@ Mn (A cv )
f 'c (psi) 8.3 6.0 6.0 5.1

Vn,ACI (A cv
f ' (psi) )
c
9.8 6.6 7.2 5.7

Ta ;Tu ;T1 (sec) 0.49; 0.69; 0.94 0.49; 0.69; 0.78 0.73; 1.02; 1.79 0.73; 1.02; 0.1.58
Pu1 (kips); Pu1 (A f ' )
g c 2,420; 0.14 2,649; 0.10 4,606; 0.16 5,022; 0.13

Pu2 (kips); Pu2 (A f ' )


g c 901; 0.05 991; 0.038 1,724; 0.06 1,888; 0.05

M base (kips-ft.) 85,356 92,050 132,213 146,073


Vbase (kips) 1,762 1,835 2,127 2,222

Vbase (A cv
f 'c (psi) ) 7.21 6.0 5.36 4.2

cmax ; ccritical (in.) 89; 22.2 70; 26.7 101; 20.3 81; 23

Max c lw 0.31 0.24 0.32 0.26


c b ; lw b 7.5; 24 3.89; 16 5.6; 17.33 3.38; 13

λb = l w c b 2
180 62 97 44

Max Δ story hx (%) at DE 1.92 1.56 1.93 1.70


ASCE 7-10 Δ a hx (%) 2.00 2.00 2.00 2.00
Roof δ u hw (%) at DE 1.44 1.20 1.71 1.51
Roof δ u hw (%) at MCE 1.44×1.5 = 2.16 1.20×1.5 = 1.80 1.71×1.5 = 2.56 1.51×1.5 = 2.27
δ c hw (%) (Eq. 3) 1.5 2.01 1.5 2.55
Probability of strength loss (%) at
45 (86) 6 (36) 65 (94) 6 (36)
DE (MCE)

10
Conclusions and Recommendations Abdullah S. A., Wallace J. W., 2018a, “Drift capacity of RC
structural walls with special boundary elements,” ACI
Based on the findings of this study, the following conclusions Structural Journal, accepted for publication, 33pp.
and recommendations with regards to design of structural
walls with SBEs resulted: Abdullah, S. A., and Wallace, J. W., 2018b, “Drift capacity
1. The underlying premise of the ASCE 7-10 and ACI 318- prediction of RC structural walls with special boundary
14 provisions is that special structural walls satisfying the elements,” Proceedings, 11th National Conference in
provisions of ACI 318-14 §18.10.6.2 through §18.10.6.4 Earthquake Engineering, Earthquake Engineering Research
possess adequate drift capacity to exceed the expected Institute, Los Angeles, CA.
drift demand determined from ASCE 7-10 analysis
procedures. However, results presented in this study show Abdullah S. A., Wallace J. W., 2018c, “A reliability-based
that these code provisions are insufficient to provide design methodology for RC structural walls with special
ductile, flexure-dominated response under cyclic loading, boundary elements,” ACI Structural Journal, submitted for
and, thus, do not provide adequate safety margins for wall review and possible publication, May 4, 2018, 33pp.
buildings.
2. To address the above deficiencies, a new reliability-based ASCE/SEI Standards, 2013, “Seismic Evaluation and
design methodology is proposed where a drift demand-to- Retrofit of Existing Buildings (ASCE/SEI 41-13),” American
capacity ratio (DDCR) check is performed to provide a Society of Civil Engineers, Reston, VA, 518 pp.
low probability (i.e., 10% or lower) that roof drift
demands exceed roof drift capacity at strength loss for the ASCE/SEI Standards, 2010, “Minimum Design Loads for
DE level shaking, which is a rational and transparent Buildings and Other Structures (ASCE/SEI 7-10),” American
approach and can easily be implemented in ACI 318. Society for Civil Engineers, Reston, VA, 518 pp.
(
3. In general, walls with slender cross sections lw b > 15 , ) ASCE/SEI Standards, 2016, “Minimum Design Loads for
large neutral axis depth relative to width of flexural Buildings and Other Structures (ASCE/SEI 7-16),” American
( )
compression zone c b > 3 , shear stresses approaching Society for Civil Engineers, Reston, VA, 690 pp.

( )
the ACI 318 §18.10.4.4 limit 10 f 'c (psi) , and roof Behrouzi, A., Welt, T., Lehman, D., Lowes, L., LaFave, J.,
drift demands approaching the maximum story drift and Kuchma, D., 2017, “Experimental and numerical
allowed by ASCE 7-10 are screened out for redesign. investigation of flexural concrete wall design details,”
4. Preventing strength loss under DE level shaking is Proceedings, ASCE/SEI Structures Congress, Denver,
assumed to reduce the probability of collapse under MCE Colorado.
level shaking; however, for improved performance, a
lower (or specified) probability of strength loss for MCE Brown, P., Ji, J., Sterns, A., Lehman, D. E., Lowes, Kuchma,
level shaking could be used. That is, a lower displacement D., and Zhang, J., 2006 “Investigation of the seismic
behavior and analysis of reinforced concrete walls,”
reduction factor (φ d < 1.0) could be used in Eq. 2.
Proceedings, 8th National Conference on Earthquake
5. Alternative approaches to address the noted concerns,
Engineering, San Francisco, CA.
such as requiring more strict detailing provisions than
what are currently required by ACI 318-14, placing a limit
Chilean Structural Standard, 2010, “Reinforced concrete
on axial load ratio, and/or modifying wall provisions of
design code, replacing D.S N 118 (DS 60 MINVU),” Chilean
ASCE 7, are not recommended.
Ministry of Housing and Urbanism, Diario Official, Santiago,
6. Example applications are presented to highlight current
Chile. (In Spanish)
code deficiencies and application of the proposed
approach. To assist in cases where redesign is required,
Canadian Standards Association, 2004, “Design of concrete
expressions for minimum and upper-bound width of
structures (CSA A23.3-04), Canadian Standards Association,
flexural compression zone are provided.
Mississauga, ON, Canada.
References
Elwood, K. J., Maffei, J. M., Riederer, K. A., and Telleen,
K., 2009, “Improving Column Confinement–Part 2: Proposed
ACI Committee 318, 2014, “Building Code Requirements for
New Provisions for the ACI 318 Building Code,” Concrete
Structural Concrete (ACI 318-14) and Commentary,”
International, Vol. 31, No. 12, pp. 41–48.
American Concrete Institute, Farmington Hills, MI, 519 pp.

11
Elwood, K. J. and Moehle, J. P., 2005, “Drift capacity of Wallace, J. W., and Orakcal, K., 2002, “ACI 318-99
reinforced concrete columns with light transverse provisions for seismic design of structural walls,” ACI
reinforcement,” Earthquake Spectra, Vol. 21, No. 1, pp. 71- Structural Journal, Vol. 99, No. 4, pp. 499–508.
89.
Wallace, J. W, Massone, L. M., Bonelli, P., Dragovich, J.,
Kim, S., 2016, “Reliability of structural wall shear design for Lagos, R., Luders, C., and Moehle, J., 2012, “Damage and
tall reinforced concrete core wall buildings,” Ph.D. implications for seismic design of RC structural wall
Dissertation, University of California, Los Angeles, CA, 246 buildings,” Earthquake Spectra, Vol. 28, No. S1, pp. 281–
pp. 289.

Lowes, L. N., Lehman D. E., Birely A. C., Kuchma D. A., Wallace, J. W., Elwood, K. J., and Massone, L. M., 2008,
Marley K. P., and Hart C. R., 2012, “Earthquake response of “Investigation of the axial load capacity for lightly reinforced
slender concrete planar concrete walls with modern wall piers,” Journal of Structural Engineering, Vol. 134, No.
detailing” Engineering Structures, Vol. 34, pp. 455–465. 9, pp. 1548-1557.

Nagae, T., Tahara, K., Taiso, M., Shiohara, H., Kabeyasawa, Wallace, J. W., and Safdari, A., 2018, “Design of slender
T., Kono, S., Nishiyama, M., Wallace, J. W., Ghannoum, W. reinforced concrete walls,” Proceedings, 11th National
M., Moehle, J. P., Sause, R., Keller, W., and Tuna, Z., 2011, Conference in Earthquake Engineering, Earthquake
“Design and Instrumentation of the 2010 E-Defense Four- Engineering Research Institute, Los Angeles, CA. (final
Story Reinforced Concrete and Post-Tensioned Concrete paper accepted for publication, Paper ID 1861)
Buildings,” PEER Report 2011/104, Pacific Earthquake
Engineering Research Center (PEER), Berkeley, CA, 234 pp. Welt, S., Lehman, D., and LaFave, J., 2018, “Boundary
element detailing in special concrete structural walls,” ACI
Standards New Zealand, 2017, “Concrete structures standard. Structural Journal, Vol. 115, No. 3, pp. 635-647.
Part 1: The design of concrete structures (Amendment No. 3)
(NZS 3101:2006)”, Standards New Zealand, Wellington, ICBO, 1997, Uniform Building Code, Structural Engineering
New Zealand. Provisions, Vol. 2, 1997 edition, pp. 2-161 to 2-163,
International Conference of Building Officials, Whittier,
Segura, C. L., and Wallace, W. J., 2018a, “Seismic California.
performance limitations and detailing of slender RC walls,”
ACI Structural Journal, accepted for publication (minor
revisions), Oct. 24, 2017, 29 pp.

Segura, C. L., and Wallace, W. J., 2018b, “Impact of


geometry and detailing on drift capacity of slender walls,”
ACI Structural Journal, accepted for publication (minor
revisions), Dec. 1, 2017, 32 pp.

Shegay, A. S., Motter, C. M., Elwood, K. J., Henry, R. S.,


Lehman, D. E., and Lowes, L. N., 2016, “Impact of axial
load on the seismic response of rectangular walls,” Journal of
Structural Engineering, Vol. 144, No. 8, pp. 04018124-1
04018124-14.

Uniform Building Code, 1997, “International Council of


Building Code Officials (UBC-97),” Whittier, CA.

Wallace, J. W., 2012, “Behavior, design, and modeling of


structural walls and coupling beams– lessons from recent
laboratory tests and earthquakes,” International Journal of
Concrete Structures and Materials, Vol. 6, No. 1, pp. 3–18.

12

View publication stats

Potrebbero piacerti anche